GEOTECHNICAL INVESTIGATION
REPORT
PROJECT
REPORT ON GEOTECHNICAL INVESTIGATION WORK FOR PROPOSED 33 KV GRID STATION
AT NAAZ CINEMA (D) SRD
SUBMITTED BY
RAO ENGINEERING ENTERPRISES GEOTECHNICAL CONSULTANTS & LAND SURVEYORS
91-D-3, STREET NO.1, EAST MOTI BAGH , OLD ROHTAK ROAD, DELHI-110007. PHONES :011-23698806, Mob. 09310502435, 9310402435 , 9811108174, TeleFax-23691434
e-mail : [email protected] , [email protected]
PROJECT : REPORT ON GEOTECHNICAL INVESTIGATION WORK FOR
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA(D)SRD. CLIENT : BSES YAMUNA POWER LIMITED SHAKTI KIRAN BUILDING, KARKARDOOMA, DELHI. REPORT NO. : 5203 DATE : 26.02.2013
RAO ENGINEERING ENTERPRISES - - - GEOTECHNICAL REPORT
PROJECT : REPORT ON GEOTECHNICAL INVESTIGATION WORK FOR PROPOSED 33 KV GRID STATION AT NAAZ CINEMA(D) SRD
C O N T E N T S
PAGE NO.
1.0 INTRODUCTION 1 1.1 PROJECT DESCRIPTION 1 1.2 AIM OF SOIL INVESTIGATION 1-2 1.3 SCOPE OF WORK 2 2.0 INVESTIGATIONS CONDUCTED 3 2.1 INSITU TESTS 3 2.1.1 BOREHOLES 3 2.1.1.1 WATER TABLE 3 2.1.1.2 FIELD TEST RESULTS 4 2.2 LABORATORY TESTS AND RESULTS 5 3.0 OBSERVATIONS 6 4.0 DISCUSSIONS 6 4.1 TYPE & DEPTH OF FOUNDATION 7 4.2 ALLOWABLE BEARING PRESSURE 7 5.0 RECOMMENDATIONS 8 6.0 ELECTRICAL RESISTIVITY TEST RESULTS 8 7.0 CHEMICAL ATTACK 8-9 8.0 CLOSURE 9 ------ FIGURES 1-9
*****************************
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 1
1.0 INTRODUCTION
1.1 PROJECT DESCRIPTION
This soil investigation work , whose results are being presented herewith , has been carried out for proposed 33 KV Grid Station at Naaz Cinema (D) SRD.The proposed building may consists of Ground+2-3 storied. A layout plan showing the locations of our field investigation is illustrated in our report.
1.2 AIM OF SOIL INVESTIGATION Soil investigation has been conducted at the site in order to evaluate the parameters required for design of foundations. These parameters are :
(a) Type of foundation on which the
proposed super structure will be supported.
(b) Depth of foundation , and (c) Allowable bearing pressure at the
founding level.
RAO ENGINEERING ENTERPRISES -- GEOTECHNICAL REPORT - PAGE 2
To evaluate these parameters , following engineering properties of the sub - Rock strata have been studied :
(a) Core recoveries and Rock quality designation (RQD) for different core runs.
(b) Properties like Moisture content, Bulk density ,
Water absorption, Porosity, Void ratio, Crushing strength, Point load etc; which have been determined in the laboratory by conducting testing of cores obtained from rock drilling.
1.3 SCOPE OF WORK
The stipulated scope of work comprised of the following : 1. Mobilization of equipment and personnel to the
site and back. 2. Sinking 3 boreholes through soil/rock strata to
6.0 – 9.40m depth, observing ground water table levels, conducting required field and laboratory tests and their analysis.
3. Preparation and submission of technical report in triplicate.
RAO ENGINEERING ENTERPRISES -- GEOTECHNICAL REPORT - - PAGE 3 2.0 INVESTIGATIONS CONDUCTED 2.1 INSITU TESTS
Locations of field-testing points have been marked at the site as per the direction of the client. These locations have been designated as BH-1 to BH-3 in this report.
2 .1.1 BOREHOLES Following operations have been carried out during the progress of boreholes :
(a) Drilling through NX size core drill machine using diamond bits through rock down to termination depth of 6.0-9.40m .
(b) Measurement of Core recoveries & Rock quality designation.
(c) Collection of rock cores from the site for
laboratory testing.
2.1.1.1 WATER TABLE
In the boreholes, groundwater was not encountered to the final explored depth of 9.40m below ground surface during the time of our field investigation (February, 2013).
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 4 2.1 .1 .2 FIELD TEST RESULTS
Following Core recoveries & Rock quality designation values have been recorded at various depths in the three boreholes:
Borehole
No. Depth (m) Core
recoveries % RQD %
0.0-1.5 35 15
1.5-3.0 48 20
3.0-4.5 55 30 1
4.5-6.0 42 22
0.5-2.0 30 20
2.0-3.5 45 25
3.5-5.0 50 28 2
5.0-6.5 60 40
0.1-1.5 56 21
1.5-3.0 59 20
3.0-4.5 50 26
4.5-6.0 44 32
6.0-7.5 35 31
7.5-9.0 32 22
3
9.0-9.40 25 0
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 5
2.2 LABORATORY TESTS AND RESULTS
Following tests have been conducted on Rock samples in the laboratory :
ROCK SAMPLES
(a) Crushing strength (b) Point load strength index (c) Natural Moisture Content (d) Bulk Density (e) Water absorption. (f) Void Ratio & porosity. (g) Specific gravity
Note: The laboratory tests results conducted on rock samples are given on table no.4a.
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 6
3.0 OBSERVATIONS
Following points are observed from results obtained :
(a) The Quartzite (Rock) is encountered at the site from ground surface to the final explored depth of 9.40 m. It is moderately strong to strong in in quality & moderately weathered in nature. The core recovery ranges between 25 to 60 percent with 0 to 40 percent RQD.
(b) Bulk density values in rock strata vary from 2.68 to 2.71 gms/cc.
(d) The Crushing Strength ranges between 420.0-870.6 kg/cm².
(e) The RMR value of the rock ranges between 18-24.
4.0 DISCUSSIONS
For designing the foundation system, the following Parameters are required:
(a) Suitable type of foundation on which the proposed super – structure can be supported.
(b) Depth of these foundations, and
(c) Allowable bearing pressure at the founding level corresponding to various footing sizes.
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 7
4.1 TYPE & DEPTH OF FOUNDATION
Type of foundation to be adopted for a particular structure depends upon the loading intensity at the foundation level and the configuration of loading points. Reviewing the site stratigraphy & laboratory test results of the rock samples, we recommend that Isolated open spread foundation bearing at or below 1.5m depth below the existing ground surface resting on Rock formation may be provided at the site to support the structural load.
4.2 ALLOWABLE BEARING PRESSURE
Following criterion have been considered for evaluating the bearing capacity values:
(a) Settlement criteria
(b) Shear failure criterion
Shear failure condition as per I.S. 6403 has been considered for allowable bearing pressure computation.
Allowable settlement value of 50 mm has been considered for deducing shear strength value.
5.0 RECOMMENDATIONS
The following table presents our recommended Net allowable bearing pressures for 1-4 m wide Isolated Open Spread Foundation bearing at or below 1.5m depth below the existing ground surface on rock formation.
Foundation Embedment Depth (m)
Recommended Net Allowable Bearing Pressure(T/sq.m.)
1.5 23.0
2.0 26.0
The above values include a Safety Factor of 3.0.The total permissible settlement for the above recommended bearing pressures may range between 20-25 mm.
RAO ENGINEERING ENTERPRISES - GEOTECHNICAL REPORT - PAGE 8
6.0 ELECTRICAL RESISTIVITY TEST RESULTS Electrical resistivity tests were conducted as per IS: 3043-1987 at the project site. The tests were conducted using the Wenner configuration along different directions at various electrode spacings ranging from 1 to 10 m. The average apparent resistivity values are presented graphically and also tabulated on Figs. 5 to 7. The test results are also tabulated below:
Average Resistivity, ohm-m Electrode
Spacing, m ERT-1 ERT-2 ERT-3 1.0 52.6 60.2 48.2 2.0 82.9 88.7 99.5 3.0 95.3 99.5 108.6 5.0 120.5 110.5 135.7 7.0 145.7 158.5 155.7 10.0 210.8 205.3 253.6
These resistivity data are used as an indicator for potential for corrosion of buried metallic pipes and other utility lines. All buried metallic pipelines be coated adequately.
7.0 CHEMICAL ATTACK
Chemical test results on soil are presented in our report on sheet no. 8. The results indicate that the soils contain sulphate in the range of 0.10 to 0.12 percent and chlorides 0.03 to 0.04 percent. The pH value of soil is between 7.2 to 7.6 indicating slightly alkaline conditions. The groundwater at the site is not met to 9.40m depth.
IS:456-2000 recommends that precautions should be taken against chemical degradation of concrete if the sulphates content of the soils exceeds 0.2 percent or if the groundwater contains more than 300 mg per litre of sulphates (SO3).
RAO ENGINEERING ENTERPRISES -- GEOTECHNICAL REPORT - PAGE 9
Comparing the test results with the specified limits in IS 456-2000, We recommend the following measures to limit the potential for chemical attack:
(1) Concrete for Open foundations should contain a minimum cement content of 330 kg/m3 of cement.
(2) Water cement ratio in foundation concrete should
be in the range of 0.50. (3) A clear concrete cover over the reinforcement
steel of at least 50mm should be provided for all foundations.
8.0 CLOSURE
We appreciate the opportunity to perform this investigation for you and have pleasure in submitting this report. Please contact us when we can be of further service to you.
For RAO ENGINEERING ENTERPRISES
(G.R.RAO) (PUSHPENDRA KUMAR) DIRECTOR EXECUTIVE DIRECTOR
WATER TABLE
Type of Boring: Rotary
Col
our
Loss
0.00 RK-1 1-3 35 151.50 1.50 Moderately weathered 20
RK: Rock core1.50 RK-2 4-6 Moderately Strong,0.0m to 3.0m 48 203.00 1.50
Dark Brown Partial3.00 RK-3 7-10 55 304.50 1.50 24
4.50 RK-4 11-15 42 226.00 1.50 (6.00m)
Project : Proposed 33KV Grid Station at Naaz Cinema (D) SRD.
Bits
Use
d
Sym
bol
DESCRIPTION
Per
cent
Rec
over
y
Roc
k Q
ualit
y D
esig
natio
n (R
QD
) (%
)
Roc
k M
ass
Rat
ing
(RM
R)
Return Water
Dep
th (m
)
Dril
l Run
(m)
Sam
ple
No.
Sei
ral N
o. o
f Cor
es
BH.No.-1 Termination Depth - 6.0 m
TABLE NO. 1
JOB NO. 5203Not Met
Moderately Strong to Strong brown Quartzite (Rock),
Strong,3.0m to 6.0m
32 C
T D
iam
ond
Impr
egna
ted
Bit
WATER TABLE
Type of Boring: Rotary
Col
our
Loss
0.00 Fill :Light Brown Fine sand0.50 0.50 DS-1 (0.50 m)
0.50 RK-1 1-3 Moderately weathered 30 20 202.00 1.50
Moderately Strong,0.5m to 3.0m RK: Rock core2.00 RK-2 4-8 45 253.50 1.50
3.50 RK-3 9-12 50 285.00 1.50 24 Dark Brown Partial
5.00 RK-4 13-16 60 406.50 1.50 (6.50 m)
5203Not Met
Strong,3.0m to 6.5m
Dep
th (m
)
Dril
l Run
(m)
Sam
ple
No.
Sei
ral N
o. o
f Cor
es
Sym
bol
DESCRIPTION
Per
cent
Rec
over
y
Roc
k Q
ualit
y D
esig
natio
n (R
QD
) (%
)
Roc
k M
ass
Rat
ing
(RM
R)
Return Water
Moderately Strong to Strong brown Quartzite (Rock),
Project : Proposed 33KV Grid Station at Naaz Cinema (D) SRD.
Bits
Use
d
BH.No.-2 Termination Depth-6.50 m
TABLE NO. 2
JOB NO.
32 C
T D
iam
ond
Impr
egna
ted
Bit
WATER TABLE
Type of Boring: Rotary
Col
our
Loss
0.00 Fill:Light Brown Fine sand0.10 DS-1 (0.10 m)
0.10 RK-1 1-3 Moderately weathered 56 21 201.50 1.40
Strong,0.1m to 7.5m RK: Rock core1.50 RK-2 4-7 59 203.00 1.50
3.00 RK-3 8-13 50 264.50 1.50
4.50 RK-4 14-16 44 326.00 1.50 22
6.00 RK-5 17-22 35 317.50 1.50 Dark Brown Partial
Moderately strong,7.5m to 9.40m7.50 RK-6 23-27 32 229.00 1.50 18
9.00 RK-7 28-30 25 09.40 0.40 ( 10.0m)
Sym
bol
DESCRIPTION
Per
cent
Rec
over
y
Roc
k Q
ualit
y D
esig
natio
n (R
QD
) (%
)
Roc
k M
ass
Rat
ing
(RM
R)
Return Water
5203Not Met
Dep
th (m
)
Dril
l Run
(m)
Sam
ple
No.
Sei
ral N
o. o
f Cor
es
Termination Depth-9.40 mProject : Proposed 33KV Grid Station at Naaz Cinema
(D) SRD.
Bits
Use
d
TABLE NO. 3
JOB NO.
BH.No.-3
Moderately Strong to Strong brown Quartzite (Rock),
32 C
T D
iam
ond
Impr
egna
ted
Bit
4
SYMBOLFill
Quartzite( Rock)
LEGEND
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA (D) SRD.
3D E
P T
H,
m0
SUMMARY OF BOREHOLE
1
2
4
BH-3
9.40m
56/21
59/20
Recovery/RQD
5
50/26
6
7
8
44/32
35/31
9
1.5m
3.0m
4.5m
6.0m
7.5m
32/22
BH-1
6.00m
35/15
48/20
Recovery/RQD
55/30
42/22
1.5m
3.0m
4.5m
BH-2
6.50m
30/20
45/25
Recovery/RQD
50/28
60/40
2.0m
3.5m
5.0m
10
25/09.0m
0.5m 0.1m
5
Electode ApparentSpacing,m Resistivity, Ohm-m
1.0 52.62.0 82.93.0 95.35.0 120.57.0 145.710.0 210.8
ELECTRICAL RESISTIVITY TEST NO - 1
1
10
100
1000
0 2 4 6 8 10 12 14 16Electrode Spacing , m
App
aren
t Res
istiv
ity ,O
hm-m
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA (D) SRD.
6
Electode ApparentSpacing,m Resistivity, Ohm-m
1.0 60.22.0 88.73.0 99.55.0 110.57.0 158.510.0 205.3
ELECTRICAL RESISTIVITY TEST NO - 2
1
10
100
1000
0 2 4 6 8 10 12 14 16Electrode Spacing , m
App
aren
t Res
istiv
ity ,O
hm-m
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA (D) SRD.
7
Electode ApparentSpacing,m Resistivity, Ohm-m
1.0 48.22.0 99.53.0 108.65.0 135.77.0 155.710.0 253.6
ELECTRICAL RESISTIVITY TEST NO - 3
1
10
100
1000
0 2 4 6 8 10 12 14 16Electrode Spacing , m
App
aren
t Res
istiv
ity ,O
hm-m
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA (D) SRD.
8
SOIL :
Borehole No.
pH Value
1 7.23 7.54 7.6
0.04
CHEMICAL TEST RESULTS
Depth, (m)
Sulphate Content ,%
(SO3)
Chloride Content ,%
PROPOSED 33 KV GRID STATION AT NAAZ CINEMA (D) SRD.
0.00 0.12 0.030.501.00 0.10 0.03
0.11