Emerson Network PowerDC PowerProduct IntroductionDC PowerProduct Introduction
Presentation Contents• DC Products
– Mini Power Systems– Small Power Systems– Medium Power Systems– Large Power Systems
19 i h S b k P S t– 19-inch Subrack Power Systems– Advanced Controller Features
2
DC ProductsMi i P S tMini Power Systems
Mini Power SystemsGIE 19” system
System Type Height Weight Rectifier Module # of rectifiers Power outputGIE4815/3A/2.55KW 2U 10 kg 850W, 3 2,6 kWGIE4815/2A/1.7KW 2U 17 kg 850W, 2 1,7 kWGIE4815/2A/1.6KW 1U 8 kg 800W, 2 1,6 kWGIE4805/2A-2 1U 6,5 kg 300W, 2 600 W
NetSure system System Type Height Weight Rectifier Module # of rectifiers Power outputActura 48201 2U 15kg 800W 3 2 4kW( can reach upActura 48201 2U 15kg 800W 3 2,4kW( can reach up
to 4,8kW)
4
GIE4815/3A/2.55KW
Rectifier: 850W, fan cooled
Performance: Dimensions: 132.5(H)x482.6(W)x350(D) mmCapacity:2.55 kW / 3 rectifiers
Configuration:Configuration: - DC distribution branch: 1*50A MCB2*20A MCB1*10A MCBBAT 1*63A MCB
5
GIE4815/2A/1.7KW
Rectifier: 850W, fan cooled
Performance: Dimensions: 88.1(H)×482.6(W)×341(D) mmCapacity: 1.7 kW / 2 rectifiers
Configuration:Configuration: - DC distribution branch: 2*20A Fuse
1*10A Fuse2*5A Fuse2 5A FuseBAT 1*50A MCB
6
GIE4815/2A/1.6KW
Rectifier: 800W, fan cooled
Performance: Dimensions: 45.6(H)×482.6(W)×325(D) mmCapacity:1.6 kW / 2 rectifiers
Configuration: - DC distribution branch:
1*10A Fuse1*20A Fuse1 20A Fuse BAT 1*20A Fuse
7
GIE4805/2A/500-2
Rectifier: 300W, fan cooled
Performance: Dimensions: 41.6(H)x482.6(W)x325(D) mm
Capacity: 600 W / 2 rectifiers
Configuration: - DC distribution branch:
2*10A FuseBAT 1*10A FuseBAT 1 10A Fuse
8
NetSure 201 A60 (formerly known as ACTURA Flex 48201)
Rectifier: 800W, fan cooled
Performance: Dimensions:Single subrack: 88.1(H)x482.6(W)x341(D) mmSingle subrack :176 2(H)x482 6(W)x341(D) mmSingle subrack :176.2(H)x482.6(W)x341(D) mmCapacity:Single subrack: 2.4 kW / 3 rectifiersDual subrack: 4.8 kW / 6 rectifiers
Configuration: - DC distribution branch: Single subrack:6 MCB( 16~63A )Dual subrack: 12 MCB( 16 63A )Dual subrack: 12 MCB( 16~63A )
9
DC ProductsS ll P S tSmall Power Systems
Small Power Systems
System Type Height Integrate BATrack
Rectifier Module # of rectifiers Power output
PS48120/1800 2m 3banks R48-1800A 4 6,96kWPS48300/1800 1.6m R48-1800A 10 17,4 kWPS48300-3B/2900 1.6m R48-2900U 6 17,4 kWActura 48420 2m 4 banks R48-1800 12 20,88 kWActura 48330 2m 4 banks R48-3200 5 16kWActura 48200 1.6m 2 banks R48-3200 3 9,6k W
11
PS48120/1800
Rectifier: R48-1800AController: M500DPerformance:Dimensions: 2000(H)×600(W)×600(D) mmCapacity:7.2 kW / 4 rectifiersSpace for 3 strings of 12V FT battery
Configuration:Single phase AC input,63A/2P × 2,
Battery 2×100A NT00 Fuse7 DC distribution branches:1×63A/1P(MCB),2×32A/1P(MCB),1×10A/1P(MCB),1×100A NT00(FUSE),1×50A NT00 (FUSE),1×6A NT00(FUSE)
12
PS48300/1800-X1
Rectifier: R48-1800AController: M500DPerformance: Dimensions: 1600(H)x600(W)x600(D) mmCapacity: 18 kW / 10 rectifiers
Configuration:Configuration:3 phase AC input, 100A/3P×2
Battery 2×250A NT00 Fuse12 DC distribution branches:LLVD:100A ×5(Fuse), 63A/1P × 1(MCB)
BLVD: 63A/1P × 2, 32A/1P × 2, 10A/1P × 2(MCB)
13
PS48300-3B/2900-X1
Rectifier: R48-2900UController: M500SController: M500SPerformance: Dimensions: 1600(H)x600(W)x400(D) mmCapacity: 17.4 kW / 6 rectifiersCapacity: 17.4 kW / 6 rectifiers
Configuration:3 phase AC input, 100A/3P
Battery 2×250A NT00 Fuse12 DC distribution branches:LLVD:100A ×5(Fuse) 63A/1P × 1(MCB)LLVD:100A ×5(Fuse), 63A/1P × 1(MCB)BLVD: 63A/1P × 2, 32A/1P × 2, 10A/1P × 2(MCB)
14
PS48300-3B/2900-W6
Rectifier: R48-2900UController: M500SController: M500SPerformance: Dimensions: 800(H)x600(W)x400(D) mmCapacity: 17.4 kW / 6 rectifiersCapacity: 17.4 kW / 6 rectifiers
Configuration: 3 phase AC input, 63A/3P
Battery 2×160A NT00 Fuse17 DC distribution branches:
BLVD: 10A/1P × 4 16A/1P × 5 40A/1P × 8(MCB)BLVD: 10A/1P × 4, 16A/1P × 5, 40A/1P × 8(MCB)
15
NetSure 501 AC0 (formerly known as ACTURA Flex 48420)
Product characteristic System: NetSure 501 AC0 System: NetSure 501 AC0 Rectifier: R48-1800 Controller: M501D, M800D EMC: class B Safety: EN60950 . Dimension:
2000(H)*600(W)*600(D) mm2000(H)*600(W)*400(D) mm1800(H)*600(W)*600(D) mm
Up to 20.4kW and 720Ah in one cabinet, can be mounted against wall and with cabinets on eithermounted against wall and with cabinets on either side, configurable number of distribution/battery circuit breakers, various AC options with/without SPD and AC breakers.
16
NetSure 701 A30 (formerly known as ACTURA Optima 48200)
Product characteristicS t N tS 701 A30 System: NetSure 701 A30
Rectifier: R48-3200, R48-2900 Controller :M501D, M800D EMC: class B EMC: class B Safety: EN60950 . Dimension:
1600(H)*600(W)*600(D) mm1600(H) 600(W) 600(D) mm Low cost open frame battery rack, provides up to 9.6kw one rack together with up to 360AH of batteries. Front access and top cabling design for installation and maintenance AC input optionalinstallation and maintenance, AC input optional.
17
NetSure 701 A50 (formerly known as ACTURA Flex 48330)
Product characteristic S t N tS 701 A50 System: NetSure 701 A50 Rectifier: R48-3200, R48-2900 Controller: M501D, M800D EMC: class B EMC: class B Safety: EN60950 . Dimension:
2000(H)*600(W)*600(D) mm( ) ( ) ( )2000(H)*600(W)*400(D) mm700(H)*600(W)*600(D) mm
Provides up to 14.5kw in one rack together with up to 720AH of batteries.Front access and top cabling design for installation and maintenance, AC input optional.
18
DC ProductsM di P S tMedium Power Systems
Medium Power Systems
System Type Height Integrate BAT rack Rectifier Module # of rectifiers Power outputPS48600-3/2900 2m No R48-2900U 12 34,8kWPS48600-3B/2900 1.6m No R48-2900U 12 34,8 kW
20
PS48600-3/2900
Product characteristicS t PS48600 3/2900 System: PS48600-3/2900
Rectifier: R48-2900U Controller: M500F EMC: class A EMC: class A Safety: EN60950 . Dimension:
2000(H)*600(W)*600(D) mm2000(H) 600(W) 600(D) mm Provides up to 34.8kw in one cabinet,applicable to single or three phase AC input. Front access and top cabling design for installation and maintenance.
21
PS48600-3B/2900
Product characteristic System: PS48600-3B/2900 Rectifier: R48-2900U Controller: M500S Controller: M500S EMC: class A Safety: EN60950 . Dimension: Dimension:
1600(H)*600(W)*400(D) mm
22
DC ProductsL P S tLarge Power Systems
Large Power Systems
NETSURE 801 AG0S / * * f fPS481600/5800 2350*600*600 270kg Rectifer cabinet 16 Nos. rectifier 1 battery unit and 2
HOD or 2 LOD or1Fuse unit
PD482000DD 2350*600*600 260kg DC distribution cabinet,bottom cabling
2000A DC 1 battery unit and 6HOD or 6 LOD or3Fuse unit
PD482000DU 2350*600*600 260kg DC distribution cabinet, topcabling
2000A DC 1 battery unit and 6HOD or 6 LOD or3Fuse unit
R48-5800 88*244*372 7,8kg Rectifer moudle 5800WM800D 88*244*161 2kg Controllerg
24
NetSure 801 AG0
System Output Capacity: 278.4 kW or 5800 A
Rectifier Cabinet Output Capacity: 92.8 kW or 1930 A
Distribution Cabinet Rating: 96 kW or 2000 ADistribution Cabinet Rating: 96 kW or 2000 A
Input Voltage: 260 – 530 VAC 50/60 Hz/3 Phase
O t t V lt 48VOutput Voltage: -48VDC
Temperature Range: -5°C to +45°C
Relative Humidity: 0% to 95%
25
Large Power Systems
• Dimension: 2350(H) x 600(W) x 600(D)Rectifier CabinetRectifier Cabinet
( ) ( ) ( )• Up to 16 pcs R48-5800 rectifiers
– Each rectifier outputs 5.8 kW– Provides up to 92.8 kW per
cabinet
• ACU (M800D) as standard equipment• Battery distribution Unit as standard
equipmentF U it LOD HOD ti l• Fuse Unit, LOD, HOD as optional config
26
NetSure 801 AG0
Distribution CabinetDistribution Cabinet• Dimension: 2350(H) x 600(W) x 600(D)
• Battery distribution Unit as standardBattery distribution Unit as standard equipment
• Fuse Unit, LOD, HOD as optional config
27
NetSure 801 CA
28
NetSure 801 CA
• Rack 1000-6• Rack 1000-6-Dimension: 2000(H) x 600(W) x 600(D)-Capacity:Up to 58KW/10 rectifier
• Rack 2000-6Dimension: 2000(H) x 600(W) x 600(D)-Dimension: 2000(H) x 600(W) x 600(D)
-Capacity:Up to 101.6KW/20 rectifier
29
NetSure 801 CA
DC Distribution Cabinet
30
DC Products19 i h S b k P S t19 inch Subrack Power Systems
19 Inch Subrack Power Systems
NetSure 501A50
NetSure 701A51NetSure 701A51
32NetSure 501AA0
NetSure 501 A50
• High power and battery density– Up to 8.5kW
• 19” , 6U sub-rack, Front Access – Can be mounted in 19 inch cabinet
• High flexibility and wide variety of ordering options– Output power, system: 1.7 – 8.5kW– Standard or advanced controller– Configurable number of distribution circuit breakers,
and sizes– Configurable number of battery circuit breakers, and
sizes– With or without Priority and Non-Priority Low VoltageWith or without Priority and Non Priority Low Voltage
Disconnect– Various AC options with/without SPD– Battery rack available
• Base on Global Building Block (Rectifier and Controller)
NetSure 501A50
– Utilizes UL approved rectifier R48-1800– Hot pluggable rectifier and controller (ACU or SCU)
• Wide operating range– Input voltage range (85-300Vac)
I t t t ( 5 t 55C)
33
– Input temperature range (-5 to +55C)
NetSure 501 A50
System Layout
Positive terminals
Battery MCBLoad MCB
Monitoring moduleAC input MCB
Rectifier Dummy plate
34
NetSure 501 AA0
• High power and battery density– Up to 17.0kW
• 19” 11U High sub-rack, Front Access – Can be mounted in 19 inch cabinet
• High flexibility and wide variety of ordering options– Output power, system: 1.7 – 17.0kW– Standard or advanced controller– Configurable number of distribution circuit breakers,
and sizes– Configurable number of battery circuit breakers, and
sizes– With or without Priority and Non-Priority Low VoltageWith or without Priority and Non Priority Low Voltage
Disconnect– Various AC options with/without SPD– Battery rack available
• Base on Global Building Block (Rectifier and Controller)
NetSure 501AA0
– Utilizes UL approved rectifier R48-1800– Hot pluggable rectifier and controller (ACU or SCU)
• Wide operating range– Input voltage range (85-300Vac)
I t t t ( 5 t 55C)
35
– Input temperature range (-5 to +55C)
NetSure 501 AA0
System Layout
Load MCB
Positive terminals
Positive terminalsLoad MCB
Load MCB Battery MCB
Positive terminals
AC input MCBMonitoring module
Dummy plateRectifier
36
NetSure 701 A51
• High power and battery density– Up to 16kW
• 19” 10 U High sub-rack, Front Access – Can be mounted in 19 inch cabinet
• High flexibility and wide variety of ordering options– Output power, system: 3.2 – 16kW– Standard or advanced controller– Configurable number of distribution circuit breakers,
and sizes– Configurable number of battery circuit breakers, and
sizes– With or without Priority and Non-Priority Low VoltageWith or without Priority and Non Priority Low Voltage
Disconnect– Various AC options with/without SPD– Battery rack available
• Base on Global Building Block (Rectifier and Controller)
NetSure 701A51
– Utilizes UL approved rectifier R48-3200– Hot pluggable rectifier and controller (ACU or SCU)
• Wide operating range– Input voltage range (85-290Vac)
I t t t ( 5 t 55C)
37
– Input temperature range (-5 to +55C)
NetSure 701 A51
System Layout
Positive terminals
Load MCB
Load MCB Battery MCB
Positive terminals
AC input MCB Monitoring module
Dummy plateRectifier
38
NetSure 701 A51
Battery Rack
4 L k
2 L k3 Layers rack
4 Layers rack
2 Layers rack
750mm(H)*600mm(W)*600mm(D) 1200mm(H)*600mm(W)*600mm(D) 1500mm(H)*600mm(W)*600mm(D)
39
DC ProductsAd d C t ll F tAdvanced Controller Features
ACU- Energy Saving and Rectifier Redundancy
The function maintains a configured redundancy level by switching on/off rectifiers depending on the actual load on the system. This increases the individual switched on rectifier efficiency. Periodical cycling of the switched on/off rectifiers will increase rectifiers life.
ON20%
ON20%
ON20%
ON20%
ON20%
N l F tiNormal Function
ON50%
ON50%
OFF0%
OFF20%
OFF20%
OFF0%
OFF0%
ON50%
ON50%
OFF0%
Feature Activated
41
ACU- Energy Saving and Rectifier Redundancy
++
30% 30% 30%
Load Share Average efficiency 88.5%
Working
++ Standby
Working
StandbyAverage efficiency 90%++
90%
Standby Average efficiency 90%
Energy
Saving
++Energy Saving
(T ff)
Average efficiency 92.3%
4290%
(Turn off)
ACU- Energy Saving and Rectifier Redundancy
Case Study
System with R48-2900 ModulesSystem with R48 2900 ModulesSite 1: 3 modules, Load is 12A/53.5VSite 2: 5 modules, Load is 19A /53.5V
90
6132.2
28.4Before energy saving
Unit: kWh/ Day
Site 1 Site 2
After energy saving
43
Due to use energy saving program, Site 1 saves 12%, site 2 saves 32%
ACU- PowerSplit Function
Allows extension of legacy DC power supply and battery backup.
-48V
500A 1000A
Battery Battery
LegacyNetSure 801
Msater System Slave System
44
ACU- PowerSplit Function
Low load conditionLow load condition
As long as the Slave Power output is lower than the Current Limit Set Value, Slave Power shall feed the whole load.
Normal load conditionNormal load condition
When the load of the system exceeds Slave Power’s the Current Limit Set Value, Master Power shall start to take load.
High load conditionHigh load condition
When Master Power reaches it maximum output power, system voltage will decrease as the load increases (overload situation for Master Power).
Over load conditionOver load condition
When the load is higher than the sum of the master and the slave maximum power. The master and the slave and the battery shall feed the load.
45
ACU- PowerSplit Function
46
ACU-SM support
Allows adding SM modules (supervision modules) to the M800D. There are three different SM modules• SM BAT for battery supervisiony p• SM IO for generic supervision• SM AC for mains and generator supervision
SM modules are optional add-on items
RS485NetSure 801
SM IOSM BAT SM AC
CAN
M800D
R1…
R2 RN
47