Page 1: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

Circuit Reliability Review

Redlands

2020

Page 2: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

2

• Southern California Edison (SCE) is an Edison International company

• One of the nation’s largest electric utilities

• More than 130 years of history

• Headquartered in Rosemead, California

• Regulated by the California Public Utilities Commission (CPUC) and the Federal Energy Regulatory Commission (FERC)

• 50,000 square miles of SCE service area across Central, Coastal, and Southern California

• 15 million residents in service territory

• 5 million customer accounts in 445 cities and communities

Who We Are

Page 3: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

Our Grid

To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system.

730,000 Transformers

119,000 Miles of Transmission and Distribution Lines

4,600 Circuits

1.5 Million Poles

50,000 Square Miles

3

Page 4: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

Strengthening and Modernizing the Grid

• Infrastructure reliability – updating underground

cables, poles, switches, and transformers

• Wildfire mitigation – hardening infrastructure,

bolstering situational awareness capabilities, and

enhancing operational practices

• Transmission – connecting renewables, installing

new substations, and updating lines

• Grid readiness – updating the grid for impacts

from new technologies

• Long-term energy policy – supporting energy

storage, electric vehicles, and renewables

SCE plans to spend more than $5B each

year to maintain, improve, and harden

its infrastructure.

SCE’s investments support safe, reliable, affordable, and clean energy for our customers

2019 Capital Investments

179 miles of underground cable replaced

502 miles of overhead conductor replaced for public safety

16.4k distribution poles replaced

4.3k transmission poles replaced

71 underground structure replacements

4

Page 5: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

PATHWAY 2045SCE’S vision to help California achieve a carbon neutral future

Carbon neutrality is achieved through deep decarbonization of

electricity, transportation and building electrification,

and the use of low-carbon fuels

Meeting California’s Climate Change Goals

5

Page 6: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

• SCE filed its second Wildfire

Mitigation Plan in February 2020

• It builds on the progress made

in 2019 to reduce the risk of fire

ignitions caused by utility

infrastructure

• SCE crews will continue to work

to install hi-tech wildfire

mitigation tools and

technologies to make

communities safer, more

resilient, and to help reduce the

number of Public Safety Power

Shutoffs (PSPS)

Addressing Wildfire Risk

6

Page 7: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

• De-energizing power lines to prevent ignitions

• Used during elevated fire conditions

• Primarily impacts circuits in high fire risk areas

• Use of multiple methods to notify people in affected areas before, during and after a de-energization event

Public Safety Power Shutoffs (PSPS)

7

4-7 DAYS AHEAD

3 DAYSAHEAD

2 DAYSAHEAD

1 DAY AHEAD POWER SHUTOFF

POWER RESTORATION

PLANNING AND MONITORING OUTAGE

*Erratic or sudden onset of conditions may impact our ability to provide advanced notice to customers.

Forecast Weather & Fire

Conditions

SCE Incident Management Team on Alert

County Operational Areas

informed of potential activation

SCE Incident Management

Team Activated

1st Notification PSPS Possible sent

to agencies and customers

2nd Notification PSPS

Possible

3rd Notification Power Shutoff

4th Notification Power Restored After Inspection

Page 8: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

Reliability Overview

8

Page 9: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

What is Reliability?

• In simplest terms:

Having dependable electricity when you need it.

• Outages:

• Maintenance outages (aka planned outages)

• Repair outages (aka unplanned outages)

• Sustained Outage = An outage lasting > 5 minutes

• Momentary Outage = An outage lasting ≤ 5 minutes

9

Major Event Day (MED) : A day in which the daily system SAIDI exceeds a threshold value. For the purposes of calculating daily system SAIDI, any interruption that spans multiple calendar days is accrued to the day on which the interruption began. Statistically, days having a daily system SAIDI greater than a threshold value are days on which the energy delivery system experienced stresses beyond that normally expected (such as severe weather).

Public Safety Power Shutoff (PSPS) : An operational protocol that SCE implements under extreme weather conditions in order to minimize the threat of wildfires and keep communities safe from potentially dangerous situations. These types of sustained outages are temporary and usually involve situations where high fire areas are experiencing adverse weather or public safety is at risk.

Page 10: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

How Do We Measure Reliability?

SAIDI SAIFI MAIFI CAIDI

10

Page 11: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CityList1Communities in the REDLANDS District

MENTONE

MUSCOY

REDLANDS

RIALTO

BEAUMONT

BOX SPRINGS MOUNTAIN

CALIMESA

CHERRY VALLEY

CITY OF SAN BERNARDINO

COLTON

BANNING

RIVERSIDE

SAN MANUEL BAND OF MISSION INDIANS

YUCAIPA

GRAND TERRACE

HIGHGROVE

HIGHLAND

LOMA LINDA

11

Page 12: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

*”Exclusions” are days which utilities are allowed to remove from their metrics because the outages on those days were caused by a severe acts of nature.**In the columns showing “Rank,” lower numbers indicate poorer performance.

12

Page 13: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitList1Overview of RedlandsThere are 41 circuits that serve Redlands 1

Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type Customers

ALABAMA(12KV) 1,255 MUTUAL(12KV) 1,720 - -

ANTIQUE(12KV) 351 NAVEL(12KV) 1,492 - -

ARLISS(12KV) 1,417 NIKE(12KV) 223 - -

BOULDER(12KV) 1,291 REED(12KV) 938 - -

BROOKSIDE(4.16KV) 583 RUGGLES(4.16KV) 261 - -

BRYN MAWR(12KV) 1,662 SPARLING(12KV) 1,074 - -

CAJON(4.16KV) 385 SPHINX(12KV) 1,456 - -

CASA LOMA(4.16KV) 626 SURGEON(12KV) 2,539 - -

CENTAUR(12KV) 452 SYLVAN(4.16KV) 402 - -

CHANDLER(4.16KV) 138 THOMPSEN(12KV) 287 - -

CLINIC(12KV) 756 UNICORN(12KV) 281 - -

DEARBORN(12KV) 1,339 - - -

DENTAL(12KV) 1,018 - - -

DRAGON(12KV) 341 - - -

DUROX(12KV) 689 - - -

FROST(12KV) 2,560 - - -

GRANNY SMITH(12KV) 322 - - -

HASS(12KV) 2,231 - - -

HASTINGS(4.16KV) 396 - - -

JAKE(4.16KV) 285 - - -

JASPER(12KV) 1,394 - - -

JIMS(12KV) 555 - - -

JUDSON(12KV) 2,499 - - -

KILTS(12KV) 1,844 - - -

LA POSADA(4.16KV) 500 - - -

LUGONIA(12KV) 841 - - -

MEDUSA(12KV) 211 - - -

MEMPHIS(12KV) 1,447 - - -

MINOTAUR(12KV) 595 - - -

MUSE(12KV) 1,548 - - -

Grand Total 40,204

13

Page 14: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

BarChart

SCE SYSTEMWIDE

**Data is as of 02/14/2020, data

can be slightly different due to

outage data validation process

Redlands

Reliability History of Circuits Serving Redlands (No Exclusions)

**“Exclusions” are days which

utilities are allowed to

remove from their metrics

because the outages on

those days were caused by

acts of nature.

79.466.8

86.0

117.6

134.5 139.7 136.8

178.0

0.0

50.0

100.0

150.0

200.0

2016 2017 2018 2019

SAIDI

(average

minutes of

sustained

interruptions)

0.8

0.7

1.1

1.2

1.11.2

0.9

1.0

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

SAIFI

(average

frequency of

sustained

interruptions)

1.3 1.3

1.0

1.41.6

1.8

1.4 1.4

0.0

0.5

1.0

1.5

2.0

MAIFI

(average

frequency of

momentary

interruptions)

14

Page 15: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

SAIDIChart

SAIDI = the cumulative amount of time the average customer is interrupted by “sustained” outages each year.

Causes of Repair Outages in Redlands

2019

3rd Party

24.4%

Equipment Failure

38.2%

Operation

13.0%

Other

11.1%

Vegetation /Animal

7.7%

Weather /Fire

/Earthquake

5.6%PSPS

0.0%

Contributions to SAIDI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

PSPS

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found,

PSPS Operations

e.g., urgent maintenance w/o 3-daynotice

3rd Party e.g., balloon, car hit pole, dig-in

PSPS

e.g., Public Safety Power Shutoff

15

Page 16: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

SAIFIChart

SAIFI = the number of times the average customer is interrupted by “sustained” outages each year

Causes of Repair Outages in Redlands

2019

3rd Party

32.9%

Equipment Failure

38.4%

Operation

6.9%

Other

8.8%

Vegetation /Animal

8.0%

Weather /Fire

/Earthquake

5.0% PSPS

0.0%

Contributions to SAIFI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

PSPS

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found

Operationse.g., urgent maintenance w/o 3-day

notice 3rd Party

e.g., balloon, car hit pole, dig-in

PSPS

e.g., Public Safety Power Shutoff

16

Page 17: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

17

Page 18: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

18

Page 19: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

Back-up Slides

Reliability Histories of Circuits Serving Redlands

Updated through Dec 2019

19

Page 20: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CitySummary

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

79.4 0.8 1.3 66.8 0.7 1.3 86.0 1.1 1.0 54.5 0.6 0.7 18.2 0.2 0.2 30.5 0.2 0.2 14.3 0.2 0.3 117.6 1.2 1.4

3rd Party 43% 33% 26% 8% 7% 33% 20% 18% 25% 37% 37% 27% 28% 52% 36% 10% 14% 61% 4% 20% 4% 24% 33% 28%

Equipment Failure 35% 21% 25% 42% 42% 4% 42% 33% 29% 30% 35% 9% 28% 9% - 51% 56% 15% 53% 62% 29% 38% 38% 13%

Operation 9% 18% 10% 13% 16% 6% 11% 20% 7% 17% 7% 0% 3% 2% 14% 4% 5% - 29% 14% 18% 13% 7% 5%

Other 7% 20% 22% 12% 10% 28% 17% 15% 25% 3% 10% 54% 5% 4% 50% 28% 15% 13% 15% 3% 35% 11% 9% 44%

Vegetation/Animal 0% 0% 8% 12% 7% 15% 1% 1% - 1% 2% - 35% 30% - 7% 11% - - - - 8% 8% -

Weather/Fire/Earthquake 6% 8% 9% 13% 18% 14% 9% 13% 13% 12% 9% 9% 1% 3% - - - 11% 0% 0% 15% 6% 5% 10%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SCE SYSTEMWIDE 134.5 1.1 1.6 139.7 1.2 1.8 136.8 0.9 1.4 28.1 0.3 0.4 18.9 0.2 0.4 31.8 0.2 0.3 99.3 0.3 0.3 178.0 1.0 1.4

2nd Qtr 2019 3rd Qtr 2019

41 Circuits Serving Redlands -- Total Customers:

40,204

Average Reliability of 41 Circuits Serving Redlands

4th Qtr 2019 20192016 2017 2018 1st Qtr 2019

Notes:

No outages are excluded from the metrics.

Outage Causes: Other: e.g., patrolled but no cause could be foundOperations: e.g., urgent maintenance w/o 3-day notice to customers3rd Party: e.g., balloons, car hit pole, dig-inVegetation/Animal: e.g., tree branch, rodent, or bird causing short circuit across conductorsPSPS: e.g., Public Safety Power Shutoff

SAIDI (minutes) = the cumulative amount of time the average customer is interrupted by “sustained” (longer than 5 minutes) outages.

SAIFI (interruptions) = the number of times the average customer is interrupted by “sustained” outages.

MAIFI (interruptions) = the number of times the average customer is interrupted by “momentary " (lasting 5 minutes or less) outages.

20

Page 21: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory1

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

ALABAMA(12KV) - Customers: 1,255 91.0 1.0 1.9 8.8 0.0 1.0 60.8 1.0 1.0 - - - - - 1.0 2.0 0.0 - - - - 2.0 0.0 1.0

3rd Party - - - - - - 98% 100% 100% - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 100% 57% 68% - 2% 0% - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - 100% 100% 100% - - - - 100% 100% 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 43% 32% 100% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ANTIQUE(12KV) - Customers: 351 69.2 0.5 - - - - 89.3 1.0 - 124.2 2.0 - 12.4 0.1 - - - - - - - 136.6 2.1 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% - 69% 51% - 55% 53% - - - - - - - 68% 51% -

Operation 100% 100% - - - - - - - - - - 45% 47% - - - - - - - 4% 2% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - 31% 49% - - - - - - - - - - 28% 47% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ARLISS(12KV) - Customers: 1,417 41.7 0.2 - 3.3 0.1 - 176.9 1.9 0.5 45.3 1.0 - 89.1 1.5 - - - - - - - 134.4 2.5 -

3rd Party - - - - - - - - - - - - 71% 95% - - - - - - - 47% 58% -

Equipment Failure 68% 39% - 70% 85% - 40% 35% 100% 100% 100% - 29% 5% - - - - - - - 53% 42% -

Operation 32% 61% - 30% 15% - 1% 2% - - - - - - - - - - - - - - - -

Other - - - - - - 51% 54% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - 9% 9% - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

BOULDER(12KV) - Customers: 1,291 50.2 0.1 1.9 65.9 2.0 - 8.2 0.4 - 100.1 0.9 0.3 8.3 0.0 - 332.6 1.9 0.1 - - - 441.0 2.9 0.4

3rd Party - - - - - - 27% 90% - - - - - - - 18% 46% 100% - - - 14% 31% 26%

Equipment Failure 19% 22% - 85% 52% - 6% 2% - 99% 96% 100% - - - 0% 0% - - - - 23% 31% 74%

Operation 18% 39% 49% 15% 48% - 67% 7% - 1% 4% - - - - 3% 2% - - - - 2% 2% -

Other 17% 20% - - - - - - - - - - 100% 100% - 79% 51% - - - - 61% 35% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 46% 20% 51% - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 1 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

21

Page 22: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory2

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

BROOKSIDE(4.16KV) - Customers: 583 6.8 0.0 1.0 41.6 0.5 0.5 - - 2.0 - - - - - - - - - - - - - - -

3rd Party - - 100% - - - - - 50% - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - 100% 100% 100% - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - 50% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

BRYN MAWR(12KV) - Customers: 1,662 15.7 0.7 2.0 68.9 1.1 1.0 148.6 1.7 2.4 3.2 0.0 1.0 - - - - - - - - - 3.2 0.0 1.0

3rd Party - - 49% - - - 24% 58% 42% 40% 53% - - - - - - - - - - 40% 53% -

Equipment Failure 54% 7% - 52% 92% - 37% 6% - 60% 47% - - - - - - - - - - 60% 47% -

Operation 46% 93% 51% 42% 7% 5% - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - 100% - - - - - - - - - - - 100%

Vegetation/Animal - - - 6% 1% 95% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - 39% 36% 58% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CAJON(4.16KV) - Customers: 385 68.4 1.2 2.0 4.8 0.0 1.0 1.9 0.0 0.8 - - - - - - - - 1.0 - - - - - 1.0

3rd Party - - 50% - - - - - 100% - - - - - - - - 100% - - - - - 100%

Equipment Failure 68% 15% - - - - 51% 60% - - - - - - - - - - - - - - - -

Operation 18% 82% 50% - - - 49% 40% - - - - - - - - - - - - - - - -

Other 14% 3% - - - 100% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 100% 100% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CASA LOMA(4.16KV) - Customers: 626 - - - 527.9 4.0 5.0 42.9 0.2 3.0 - - - - - - - - - - - - - - -

3rd Party - - - - - - - - 33% - - - - - - - - - - - - - - -

Equipment Failure - - - 41% 25% - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - 33% - - - - - - - - - - - - - - -

Other - - - 45% 50% 100% 100% 100% 33% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 14% 25% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

2019

Reliability Histories for Individual Circuits Serving Redlands - 2 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019

22

Page 23: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory3

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

CENTAUR(12KV) - Customers: 452 - - 1.0 12.9 0.0 1.0 111.7 2.0 1.0 0.2 0.0 - - - - - - - 280.1 1.5 1.0 280.3 1.5 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 100% 100% - 100% 100% 100% 100% 100% - - - - - - - 40% 65% - 40% 66% -

Operation - - - - - - - - - - - - - - - - - - - - 100% - - 100%

Other - - 100% - - - - - - - - - - - - - - - 60% 35% - 60% 34% -

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CHANDLER(4.16KV) - Customers: 138 641.1 2.2 1.7 45.3 0.4 - 630.0 2.5 0.1 81.4 2.8 - - - - - - - - - - 81.4 2.8 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 92% 89% - 100% 100% - 94% 86% 100% 79% 41% - - - - - - - - - - 79% 41% -

Operation 8% 11% - - - - 6% 14% - 21% 59% - - - - - - - - - - 21% 59% -

Other - - 100% - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CLINIC(12KV) - Customers: 756 - - - - - - 81.2 1.3 - 18.4 0.9 0.1 - - - 1.8 0.0 - - - - 20.1 0.9 0.1

3rd Party - - - - - - - - - 100% 100% 100% - - - - - - - - - 91% 99% 100%

Equipment Failure - - - - - - 100% 100% - - - - - - - 100% 100% - - - - 9% 1% -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

DEARBORN(12KV) - Customers: 1,339 15.9 1.0 1.0 54.8 0.8 - 32.2 0.0 1.0 79.8 0.8 0.4 - - - 78.4 0.8 0.2 - - - 158.2 1.6 0.6

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 92% 99% - 6% 11% 100% 100% 100% 100% - - - 100% 100% 100% - - - 100% 100% 100%

Operation 100% 100% - - - - 94% 89% - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - 8% 1% - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - 100% - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 3 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

23

Page 24: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory4

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

DENTAL(12KV) - Customers: 1,018 126.3 1.1 2.0 38.2 0.1 1.9 152.1 2.9 - - - 1.0 0.7 0.0 2.3 85.3 1.0 1.8 2.7 0.0 0.9 88.7 1.0 6.0

3rd Party - - 50% 17% 9% 51% 28% 36% - - - 100% - - 100% - - - - - - - - 55%

Equipment Failure 23% 4% - 3% 1% - 1% 0% - - - - - - - 9% 4% 49% 100% 100% - 12% 5% 15%

Operation 8% 6% - - - - - - - - - - - - - - - - - - - - - -

Other 69% 89% 50% 46% 39% - 41% 29% - - - - 100% 100% - - - - - - 100% 1% 0% 15%

Vegetation/Animal - - - 34% 51% 49% - - - - - - - - - 91% 96% - - - - 87% 95% -

Weather/Fire/Earthquake 1% 0% - - - - 29% 35% - - - - - - - - - 51% - - - - - 15%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

DRAGON(12KV) - Customers: 341 - - - - - 1.0 7.8 1.0 - 0.6 0.0 - - - - - - - - - - 0.6 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - - 100% 100% - - - - - - - - - - 100% 100% -

Operation - - - - - - 100% 100% - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

DUROX(12KV) - Customers: 689 101.7 1.4 0.6 536.3 1.3 - 141.5 2.0 - 6.5 0.3 0.7 - - - - - - - - - 6.5 0.3 0.7

3rd Party 100% 100% 100% - - - 48% 49% - 100% 100% 100% - - - - - - - - - 100% 100% 100%

Equipment Failure - - - 89% 75% - 52% 51% - - - - - - - - - - - - - - - -

Operation - - - 11% 25% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

FROST(12KV) - Customers: 2,560 57.0 0.3 2.8 13.2 0.1 1.0 87.4 1.2 2.0 - - - 0.2 0.0 - 144.2 1.0 - - - - 144.4 1.0 -

3rd Party 24% 10% - 40% 16% 100% - - - - - - - - - - - - - - - - - -

Equipment Failure 63% 67% 65% 52% 74% - 17% 4% - - - - 100% 100% - 100% 100% - - - - 100% 100% -

Operation 8% 17% - 8% 10% - - - - - - - - - - - - - - - - - - -

Other - - - - - - 82% 95% 100% - - - - - - - - - - - - - - -

Vegetation/Animal 3% 5% 35% - - - 2% 1% - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 2% 0% - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 4 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

24

Page 25: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory5

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

GRANNY SMITH(12KV) - Customers: 322 293.1 3.5 3.9 370.6 4.3 2.1 348.9 2.9 2.5 231.9 2.0 1.8 55.7 0.3 0.6 6.9 0.0 - 275.8 1.8 1.0 570.3 4.2 3.4

3rd Party 95% 79% 86% 44% 41% 53% 95% 99% 100% 79% 45% - - - - - - - 7% 0% - 35% 22% -

Equipment Failure 1% 0% - - - - 5% 1% - 19% 29% - 10% 4% - 63% 30% - 93% 99% - 54% 58% -

Operation 4% 21% - 24% 38% - 0% 0% - 1% 9% - 90% 95% 100% 15% 60% - 0% 0% - 9% 13% 17%

Other - - 14% 32% 21% - - - - - - 100% 0% 1% - 22% 10% - 0% 0% 100% 0% 0% 83%

Vegetation/Animal - - - - - 47% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - 1% 16% - - - - - - - - - - 0% 8% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HASS(12KV) - Customers: 2,231 358.3 3.2 1.0 26.3 0.5 - 142.8 3.9 3.3 103.1 0.4 1.0 2.1 0.0 0.0 1.4 0.0 - 57.2 0.4 0.7 163.8 0.8 1.7

3rd Party 69% 35% - 18% 3% - - - 22% - - - 6% 2% - - - - 4% 1% - 1% 1% -

Equipment Failure 4% 2% - 38% 11% - 45% 48% 48% 1% 2% - 11% 15% - 2% 13% - - - - 1% 1% -

Operation 4% 1% - 44% 85% - 55% 52% 30% 9% 2% 1% 20% 63% 100% 98% 88% - 96% 99% 100% 40% 50% 43%

Other 9% 31% - - - - 0% 0% - 1% 1% 99% 64% 20% - - - - - - - 1% 1% 57%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 14% 31% 100% - - - - - - 88% 96% - - - - - - - - - - 56% 47% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HASTINGS(4.16KV) - Customers: 396 14.4 1.0 1.0 - - - - - - 41.5 1.0 - - - - - - - - - - 41.5 1.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other 100% 100% 100% - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - 100% 100% - - - - - - - - - - 100% 100% -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

JAKE(4.16KV) - Customers: 285 239.0 2.7 2.9 282.2 2.1 - 65.9 1.0 1.0 8.4 0.0 1.0 0.1 0.0 - 2.6 0.0 - - - - 11.2 0.1 1.0

3rd Party - - 34% - - - - - 100% - - - - - - - - - - - - - - -

Equipment Failure - - - 8% 3% - - - - 20% 69% - 100% 100% - - - - - - - 17% 44% -

Operation 9% 21% - - - - - - - - - - - - - 2% 20% - - - - 0% 8% -

Other 22% 38% 35% - - - - - - - - - - - - 98% 80% - - - - 23% 32% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 69% 41% 31% 92% 97% - 100% 100% - 80% 31% 100% - - - - - - - - - 60% 16% 100%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 5 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

25

Page 26: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory6

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

JASPER(12KV) - Customers: 1,394 126.7 2.0 2.0 118.3 2.0 6.0 78.9 1.0 3.0 55.7 1.0 1.5 0.3 0.0 0.5 0.9 0.0 - 7.1 0.0 - 64.0 1.1 2.0

3rd Party 95% 50% 50% - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 50% 50% - 2% 1% 33% 100% 100% 33% - - - 79% 6% - 28% 76% - 91% 97% 24%

Operation - - - 1% 1% - - - - - - - 100% 100% 100% 21% 94% - - - - 1% 2% 26%

Other 5% 50% 50% - - 67% - - - - - 67% - - - - - - 72% 24% - 8% 1% 50%

Vegetation/Animal - - - 49% 50% 16% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 17% 98% 99% 67% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

JIMS(12KV) - Customers: 555 - - - - - - - - - - - 1.0 - - - - - - - - - - - 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - 100% - - - - - - - - - - - 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

JUDSON(12KV) - Customers: 2,499 16.6 0.1 1.0 96.9 0.3 1.9 20.9 0.1 - 66.8 1.9 1.1 103.4 1.0 - - - - 62.0 1.1 1.0 232.2 4.0 2.1

3rd Party - - 100% - - 54% - - - 32% 46% 100% - - - - - - - - - 9% 21% 54%

Equipment Failure 34% 19% - 10% 17% - 100% 100% - 68% 54% - - - - - - - 73% 92% 100% 39% 51% 46%

Operation 66% 81% - 6% 30% 46% - - - - - - - - - - - - 27% 8% - 7% 2% -

Other - - - - - - - - - - - - 4% 2% - - - - - - - 2% 0% -

Vegetation/Animal - - - 84% 53% - - - - - - - 96% 98% - - - - - - - 43% 25% -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

KILTS(12KV) - Customers: 1,844 50.9 0.9 1.0 37.5 1.2 3.0 291.7 3.6 1.0 5.0 0.0 0.5 25.7 0.2 - 2.8 0.1 - - - - 33.4 0.3 0.5

3rd Party - - - - - 33% 63% 28% 100% - - 100% - - - - - - - - - - - 100%

Equipment Failure 78% 96% - 13% 2% - 12% 3% - 92% 89% - 100% 100% - - - - - - - 90% 58% -

Operation 22% 4% - 11% 4% - 15% 42% - 8% 11% - - - - 100% 100% - - - - 10% 42% -

Other - - - - - 33% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - 100% - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 76% 94% 33% 11% 28% - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 6 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

26

Page 27: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory7

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

LA POSADA(4.16KV) - Customers: 500 195.0 0.5 - 6.9 0.0 - - - 1.0 - - - - - - - - 1.0 1.8 0.0 1.0 1.8 0.0 2.0

3rd Party - - - - - - - - 100% - - - - - - - - 100% - - 100% - - 100%

Equipment Failure 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Operation - - - 100% 100% - - - - - - - - - - - - - 100% 100% - 100% 100% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

LUGONIA(12KV) - Customers: 841 1.0 0.0 - - - 0.0 36.0 0.1 0.9 512.9 1.8 1.0 - - - - - - - - - 512.9 1.8 1.0

3rd Party - - - - - 100% - - - - - 100% - - - - - - - - - - - 100%

Equipment Failure - - - - - - 100% 100% 100% 23% 15% - - - - - - - - - - 23% 15% -

Operation 100% 100% - - - - - - - 77% 85% - - - - - - - - - - 77% 85% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MEDUSA(12KV) - Customers: 211 196.5 1.0 0.9 19.1 0.0 2.0 128.7 1.6 1.9 - - - 25.0 1.0 - 87.7 0.1 - - - - 112.7 1.1 -

3rd Party 100% 100% 100% 100% 100% 50% 100% 100% 100% - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - 100% 100% - - - - 78% 11% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - 50% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - 100% 100% - - - - - - - 22% 89% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MEMPHIS(12KV) - Customers: 1,447 250.5 3.1 3.5 26.9 0.1 0.7 2.6 0.0 2.0 61.9 1.1 1.0 11.9 0.2 1.0 31.5 0.1 1.0 7.5 1.0 - 112.7 2.4 3.0

3rd Party 66% 75% 28% - - - - - - 69% 92% - - - - 89% 52% 100% 99% 100% - 69% 86% 33%

Equipment Failure 28% 16% 43% 10% 13% - 100% 100% - 3% 1% - 6% 7% - 2% 21% - 1% 0% - 3% 2% -

Operation 7% 9% - 59% 45% 98% - - - 12% 3% - 3% 2% - 8% 26% - - - - 9% 3% -

Other - - 29% 4% 20% 2% - - 100% 16% 4% 100% 92% 91% 100% - - - - - - 19% 9% 67%

Vegetation/Animal - - - - - - - - - - - - - - - 1% 1% - - - - 0% 0% -

Weather/Fire/Earthquake - - - 27% 22% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 7 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

27

Page 28: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory8

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

MINOTAUR(12KV) - Customers: 595 2.2 0.0 - - - 1.0 0.6 0.0 - 44.3 1.0 - 3.8 0.0 1.0 45.4 0.6 0.1 - - - 93.5 1.6 1.1

3rd Party 91% 86% - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% - - - - 100% 100% - 100% 100% 100% - - - 53% 35% 6%

Operation 9% 14% - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - 100% 100% - - - 100% - - - - - - 47% 65% 94%

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MUSE(12KV) - Customers: 1,548 41.0 0.8 2.0 146.4 2.2 1.0 117.3 0.9 - 19.2 0.8 0.3 - - - 7.8 0.1 - - - - 27.0 0.8 0.3

3rd Party - - 50% 13% 6% 100% - - - 80% 96% 100% - - - - - - - - - 57% 88% 100%

Equipment Failure 71% 11% - 23% 46% - 95% 94% - - - - - - - 68% 53% - - - - 20% 4% -

Operation 29% 89% - 12% 3% - - - - - - - - - - - - - - - - - - -

Other - - 50% - - - 0% 0% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - 5% 5% - 20% 4% - - - - 32% 47% - - - - 23% 7% -

Weather/Fire/Earthquake - - - 52% 45% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MUTUAL(12KV) - Customers: 1,720 52.8 1.0 5.2 103.0 0.9 2.1 29.2 0.1 - 9.0 1.0 3.1 1.2 0.0 - 1.6 0.0 - 27.3 0.5 2.5 39.1 1.5 5.6

3rd Party - - - 54% 50% 26% - - - - - - - - - - - - - - - - - -

Equipment Failure 93% 46% 43% 0% 0% - 81% 67% - - - - - - - - - - 100% 100% 21% 70% 32% 9%

Operation 1% 2% 19% - - - 19% 33% - - - 0% - - - 100% 100% - - - - 4% 2% 0%

Other 6% 52% 38% 45% 50% 26% - - - 100% 100% 100% - - - - - - - - 40% 23% 66% 73%

Vegetation/Animal - - - - - - - - - - - - 100% 100% - - - - - - - 3% 1% -

Weather/Fire/Earthquake - - - 1% 0% 48% - - - - - - - - - - - - - - 40% - - 18%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

NAVEL(12KV) - Customers: 1,492 - - - 25.4 0.2 2.0 96.8 1.8 0.7 0.2 0.0 1.0 56.4 0.1 - - - - - - - 56.6 0.1 1.0

3rd Party - - - - - 100% - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 63% 40% - 95% 86% 100% 100% 100% - 100% 100% - - - - - - - 100% 100% -

Operation - - - 37% 60% - 5% 14% - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - 100% - - - - - - - - - - - 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 8 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

28

Page 29: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory9

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

NIKE(12KV) - Customers: 223 - - - - - 1.0 42.7 0.3 3.0 - - - - - - - - - - - - - - -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% 67% - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - 33% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

REED(12KV) - Customers: 938 37.0 0.1 - 4.9 0.0 1.0 224.1 1.8 1.4 43.2 1.0 3.0 1.9 0.0 - 0.3 0.0 - 0.6 0.0 - 46.0 1.0 3.0

3rd Party - - - 100% 100% 100% - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - - - - 88% 47% 100% - - 33% 100% 100% - 44% 8% - - - - 4% 0% 33%

Operation - - - - - - 12% 53% - - - - - - - 56% 92% - - - - 0% 1% -

Other - - - - - - - - - - - 33% - - - - - - - - - - - 33%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - 100% 100% 33% - - - - - - 100% 100% - 95% 99% 33%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

RUGGLES(4.16KV) - Customers: 261 205.6 1.0 - 115.9 1.0 1.0 73.4 1.0 1.1 2.7 0.0 - 17.9 0.0 - - - - - - - 20.6 0.1 -

3rd Party 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 1% 1% - 100% 100% - 100% 100% - - - - - - - 100% 100% -

Operation - - - 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - 100% 99% 99% 100% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SPARLING(12KV) - Customers: 1,074 174.7 1.0 2.0 102.9 1.6 4.5 189.6 1.3 - - - - 3.6 0.0 - 2.1 0.0 1.0 - - 1.0 5.6 0.0 2.0

3rd Party 59% 96% 50% - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 41% 4% - 73% 95% 33% 13% 14% - - - - 100% 100% - 49% 15% - - - - 81% 73% -

Operation - - - 0% 0% - 17% 9% - - - - - - - 51% 85% - - - - 19% 27% -

Other - - 50% 23% 4% 45% 70% 77% - - - - - - - - - 100% - - 100% - - 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 3% 0% 22% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 9 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

29

Page 30: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory10SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

SPHINX(12KV) - Customers: 1,456 56.1 0.1 - 97.1 0.2 1.0 - - - 62.5 0.8 1.2 - - - 71.1 0.6 - - - - 133.6 1.5 1.2

3rd Party - - - - - - - - - 100% 100% 15% - - - - - - - - - 47% 56% 15%

Equipment Failure 90% 50% - 61% 27% - - - - - - - - - - 100% 100% - - - - 53% 44% -

Operation 10% 50% - 39% 73% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - 85% - - - - - - - - - - - 85%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SURGEON(12KV) - Customers: 2,539 20.2 0.0 - 14.8 0.0 1.0 - - - 13.4 0.6 0.4 45.8 0.9 - - - 1.0 - - - 59.2 1.6 1.4

3rd Party - - - - - 100% - - - 100% 100% 100% 100% 100% - - - 100% - - - 100% 100% 100%

Equipment Failure 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 100% 100% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SYLVAN(4.16KV) - Customers: 402 3.5 0.0 - - - - 17.6 0.0 - 1153.6 1.0 - 13.9 0.1 - 10.4 0.1 - - - - 1178.0 1.2 -

3rd Party - - - - - - - - - 100% 98% - - - - - - - - - - 98% 83% -

Equipment Failure - - - - - - 100% 100% - - - - 100% 100% - - - - - - - 1% 8% -

Operation 100% 100% - - - - - - - - - - - - - 100% 100% - - - - 1% 8% -

Other - - - - - - - - - 0% 2% - - - - - - - - - - 0% 1% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

THOMPSEN(12KV) - Customers: 287 101.7 1.6 2.5 0.1 0.0 - 107.5 0.9 0.3 - - - 110.6 0.7 - - - - - - - 110.6 0.7 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 67% - - - 100% 100% 100% - - - 100% 100% - - - - - - - 100% 100% -

Operation - - 33% 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 10 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

30

Page 31: PowerPoint Presentation · 2020-06-07 · Our Grid To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system. 730,000 Transformers 119,000

CircuitHistory11SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

UNICORN(12KV) - Customers: 281 15.7 0.1 - 5.2 0.1 1.0 154.7 1.8 - - - - - - - - - - - - - - - -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 100% 100% - - - - - - - - - - - - - - - -

Operation 100% 100% - 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - 100% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Redlands - 11 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019