power qualkity analysis

Upload: thiyagarjan

Post on 14-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 Power Qualkity Analysis

    1/144

    1

    Advanced Power Quality

    Analysis

    Using PCs to Solve

    Harmonic Problems

    Our Circuit

    Transmission Line

    Source

    21

    5

    4

    3

  • 7/27/2019 Power Qualkity Analysis

    2/144

    2

    Our

    Transmission

    Line....

    (-X) (+X)

    50.0'

    77.5'

    98.5'

    (+Y)

    1.5'

    12.9'12.9'

    19.6' 19.6'

    LINE PHYSICAL CONFIGURATION

    TRANSMISSION LINE:

    500 kV50 miles

    (2) - "CHUKAR" - 1,780 MCM 84/19 ACSR per phase

    SS

    A

    B

    C

    Our Goal......Our goal is to modify the power system to

    reduce voltage and current distortion.

    Later we will do this by converting the

    power factor correction capacitors into tuned

    filters.

  • 7/27/2019 Power Qualkity Analysis

    3/144

  • 7/27/2019 Power Qualkity Analysis

    4/144

    4

    Define the Harmonic Source Library

    Define Transmission Lines

  • 7/27/2019 Power Qualkity Analysis

    5/144

    5

    Create Transformer Records

    text

    Create the Feeders........

  • 7/27/2019 Power Qualkity Analysis

    6/144

    6

    Create the Utility Source........

    text

    Create the Motor Contribution Source........

  • 7/27/2019 Power Qualkity Analysis

    7/144

    7

    Specify the Harmonic Sources........

    Specify the Capacitor Bank

  • 7/27/2019 Power Qualkity Analysis

    8/144

    8

    Execute Studies........

    For most cases, four studies will be executed using the power

    system configuration defined by you, typically in this

    sequence:

    1. Harmonic Load Flow.

    2. Frequency Scan for Resonance.

    3. Distortion Calculations (current and voltage).

    Harmonic Load Flow

  • 7/27/2019 Power Qualkity Analysis

    9/144

    9

    Execute the Frequency ScanFor Resonance Study........

    The impedance shown in the calculation is the

    Thevenin impedance looking into the selected bus

    to ground.

  • 7/27/2019 Power Qualkity Analysis

    10/144

  • 7/27/2019 Power Qualkity Analysis

    11/144

  • 7/27/2019 Power Qualkity Analysis

    12/144

    12

    View Graphical Output of the Voltage

    Distortion

  • 7/27/2019 Power Qualkity Analysis

    13/144

    13

    View Graphical Output of the Current

    Distortion

  • 7/27/2019 Power Qualkity Analysis

    14/144

    14

    Make System Improvements........

    The next phase of the tutorial deals with modifying the

    power system to compensate for the harmonic distortion

    that the reports and graphics indicate.

    The capacitors at Buses 4 and 5 will be tuned into

    single-tuned filters.

    Tune the Capacitor at Bus 4 into a Single-

    Tuned Filter

  • 7/27/2019 Power Qualkity Analysis

    15/144

    15

    Tune the Bus 5 Capacitor Bank into a

    Single-tuned Filter

  • 7/27/2019 Power Qualkity Analysis

    16/144

    16

    Comparing Results........

    Now that the filters have been designed and applied

    to the system, the harmonic studies must be re-

    executed to determine how the changes have affected

    the system resonance and distortion.

  • 7/27/2019 Power Qualkity Analysis

    17/144

    17

    Compare the Frequency Scan Plots at Bus 4

  • 7/27/2019 Power Qualkity Analysis

    18/144

    18

    Compare the Current Distortion Plots at

    Branches 2-3 and 3-4

  • 7/27/2019 Power Qualkity Analysis

    19/144

    19

    Compare the Voltage Distortion Plots

    at Bus 3

  • 7/27/2019 Power Qualkity Analysis

    20/144

    20

    Have a nice day!

  • 7/27/2019 Power Qualkity Analysis

    21/144

    1

    Advanced Power Quality

    Analysis

    Using PCs to Solve

    Harmonic ProblemsSection X&A

    Basic Tools and Methods ofHarmonic Analysis

    We will

    Analyze the current and voltage

    wave forms using the Fourier

    SIN or COS method

  • 7/27/2019 Power Qualkity Analysis

    22/144

    2

    Basic Tools and Methods of Harmonic Analysis.

    Harmonic Analysis Techniques Available:

    1. Symmetrical Components

    Limited to balanced 3 phase systems

    with balanced or unbalanced events

    2. Eigen Value Method

    Can be applied to four conductor,

    DC or multi-phase systems

    Basic Tools and Methods of Harmonic Analysis.

    HI_WAVE uses

    the Eigen Value

    Method.

  • 7/27/2019 Power Qualkity Analysis

    23/144

    3

    Basics of a Computer Analysis

    X. Prepare a One-Line Diagram

    X1. Define transmission line.

    X2. Define feeders.

    X3. Define capacitors and harmonic sources.

    X4. Define source and transformers.

    Basics of a Computer Analysis.

    A. Define Component Library

    A1. Define feeder library.

    A2. Define harmonic source library.

    A3. Define transmission line library.

  • 7/27/2019 Power Qualkity Analysis

    24/144

    4

    Basics of a Computer Analysis.

    B. Define System Topology

    (Branch records that connect buses)

    B1. Create the transmission lines.

    B2. Create the transformers.

    B3. Create the feeders.

    B4. Create the Utility sources.

    B5. Create motor contribution sources.

    Basics of a Computer Analysis.

    C. Define System Topology

    (Loads and Devices at Buses)

    C1. Specify the source bus.

    C2. Specify the harmonic sources.

    C3. Specify the capacitor banks/filters.

  • 7/27/2019 Power Qualkity Analysis

    25/144

    5

    Basics of a Computer Analysis.

    D. Execute Studies

    D1. Execute demand load analysis (if reqd).

    D 2. Execute harmonic load flow analysis.

    D 3. Execute freq. scan for system resonance.

    D 4. Execute voltage and current dist. calcs.

    Basics of a Computer Analysis.

    E. Evaluate and Modify System

    E1. Make system improvements.

    E2. Comparing results.

  • 7/27/2019 Power Qualkity Analysis

    26/144

    6

    X1. Our Transmission Line

    Transmission Line

    Source

    21

    5

    4

    3

    X1. Our

    Transmission

    Line....

    (-X) (+X)

    50.0'

    77.5'

    98.5'

    (+Y)

    1.5'

    12.9'12.9'

    19.6' 19.6'

    LINE PHYSICAL CONFIGURATION

    TRANSMISSION LINE:

    500 kV50 miles(2) - "CHUKAR" - 1,780 MCM 84/19 ACSR per phase

    SS

    A

    B

    C

  • 7/27/2019 Power Qualkity Analysis

    27/144

    7

    Cable or Transmission Line Modeling

    In a low voltage system non-linear modeling is

    usually not required.

    Cables and lines can be modeled by Cascaded PI

    modeling or Distributed Equivalent PI modeling.

    The Distributed Equivalent PI method is used in

    HI_WAVE for increased accuracy.

    HI_WAVE allows for modeling of line charging,series compensation, and shunt compensation.

    X2. Our Feeders....Feeder from BUS 3 to 4:Feeder from BUS 3 to 5:

    250 MCM - Copper - XLP - 15 kV rated cabl1000 circuit feetin 3.5 inch non-metallic conduit

    21

    5

    4

    3

    Feeder

    Feeder

  • 7/27/2019 Power Qualkity Analysis

    28/144

    8

    X3. Our Capacitor Banks and

    Harmonic Source....

    21

    5

    4

    3HarmonicSource

    Capacitor Bank #5

    Capacitor Bank #4

    X3. Our

    Capacitor

    Banks

    and

    Harmonic

    Source....

    Capacitor Bank - BUS 5:

    Capacitor Bank - BUS 4:

    Harmonic Source:

    400 kVAR13.8 kV ratedWYE Connected

    1000 kVAR13.8 kV ratedWYE connected

    1000 HP (kVA) VFD driveMeasured CURRENT DISTORTIONper SKM "TUTORIAL"

    5th = 37.6%7th = 12.55%11th = 7.11%13th = 3.35%17th = 2.93%19th = 1.67%

  • 7/27/2019 Power Qualkity Analysis

    29/144

    9

    X4. Our Utility Source and

    Transformers....

    Z = 8%

    X/R = 10Fault Duty1000 MVA

    21

    5

    4

    3

    Source:

    500 kV1000 mVA (Avail. short ckt.)X/R = 30

    Transformer:

    500 kV Delta primary13.8 kV WYE (grounded) secondary5000/5500 kVA 0A/FAZ = 8%X/R = 10

    Our Goal......Our goal is to modify the power system to

    reduce voltage and current distortion.

    Later we will do this by converting the

    power factor correction capacitors into tuned

    filters.

    Let's go to the computer lab.

  • 7/27/2019 Power Qualkity Analysis

    30/144

    10

    About HI_WAVE.....

    Minimum System Operation requires:

    HI_WAVE 386 needs EXTENDED memory

    Free ram must be greater than 575 k

    MEM = 2 megs or greater of XMS Memory

    5 megs of hard drive to install program

    To start HI_WAVE

  • 7/27/2019 Power Qualkity Analysis

    31/144

    11

    Press F1, and the HI_WAVE Project Manager will list all of the

    available project files. Select the TUTORIAL project.

    Press F5: Execute, and the HI_WAVE Main Menu will appear

  • 7/27/2019 Power Qualkity Analysis

    32/144

    12

    Press F2: Libraries. Press Enter to access the HI_WAVE library

    A1. Define Feeder Library........Press F1: Feeder & Raceway;

    Make sure the menu data matches the menu below.

  • 7/27/2019 Power Qualkity Analysis

    33/144

    13

    Press F1: Fetch to access the cable data

    To enter the non-linear data required for this project, press F9:

    Frequency Dependent, and the window shown below will appear

  • 7/27/2019 Power Qualkity Analysis

    34/144

    14

    To view the existing model, position the marker bar over the

    250 EXISTING and press Enter

    Resistivity = 1/volume conductivity

    Relative Permeability is a relationship between

    magnetic induction and magnetic force

    Relative Permittivity is related to the dielectric

    constant

  • 7/27/2019 Power Qualkity Analysis

    35/144

    15

    Select F10:Continue and make sure the Menu data

    matches the data below

    Press Esc-Abort to return to the menu below

  • 7/27/2019 Power Qualkity Analysis

    36/144

    16

    Press Esc-Abort until you return to the menu below

    Press F5: Harmonic Sources

    A2. Define the Harmonic Source Library

    From the HI_Wave

    Libraries menu select

    F5:Harmonic Sources

  • 7/27/2019 Power Qualkity Analysis

    37/144

    17

    Press Enter then press F5: Enter/Edit Detailed Model

    Load Types

    Constant Impedance = incandescent lights

    or resistance heaters - loads that vary with

    the square of the voltage applied.

    Constant kVA = motors, constant wattage

    ballast's - loads that attempt to remain at

    the same kW input regardless of voltage

    applied.

    Constant Current = load whose current is

    affected by fluctuations in bus voltage

    phase angle.

  • 7/27/2019 Power Qualkity Analysis

    38/144

    18

    Modeling The Harmonic Source

    Six pulse (Classical method)

    Pros: Can model commutation reactance and phase angles.

    Cons: Cannot accurately model ripples of the wave form.

    Six pulse (Dobinson method)

    Pros: Allows ripples in the direct current to be modeled.

    Pros: Particularly accurate for 5th and 7th harmonics .

    Cons: Cannot model commutation reactance and phase angles.

    Modeling The Harmonic Source

    Six pulse (Graham-Schonholzer / G-S method)

    Pros: Models direct current and higher order

    harmonics.

    Six pulse (Rice FFT method)

    Pros: Samples the direct current wave form

    considering commutation and firing angles.

    Pros: Produces an accurate description of entirecurve in time domain.

  • 7/27/2019 Power Qualkity Analysis

    39/144

    19

    Modeling The Harmonic Source

    Twelve pulse (Classical method)

    Twelve pulse (Dobinson method)

    Twelve pulse (Graham-Schonholzer method)

    Twelve pulse (Rice FFT method)

    Twelve pulse converters are modeled as two six pulse units

    with a 30 degree phase shift.

    Modeling The Harmonic Source

    kVA field is the converter kVA nameplate rating.

    PF must be estimated since it changes with load.

    Max Order is up to your discretion.

    Alpha data field is up to your discretion (0-90)

    Lower value implies more power to the load.

    Xc usually is reactance in p.u. of the series reactor.

    L(mh) is the motor load converted to an inductance.

  • 7/27/2019 Power Qualkity Analysis

    40/144

    20

    When the data for the first screen is checked, use F2: Next Page to

    move to screen two.

    When all the data has been checked, press F1: Return with Data

    and then F1: Save to exit the screen and save the source in the

    library.

    The source name will appear on

    the left-hand side of the screen

    at the bottom of the source list

    as shown below.

  • 7/27/2019 Power Qualkity Analysis

    41/144

    21

    When the harmonic source has been created and saved, press F10:

    Exit until you return to the HI_WAVE Libraries Menu.

    A3. Define the Transmission Line Library........

    From the HI_WAVE

    Libraries Menu, select F8:

    Transmission Lines and

    the Transmission Line

    Library shown will appear.

  • 7/27/2019 Power Qualkity Analysis

    42/144

    22

    Press Enter This library allows you to enter detailed

    frequency dependent transmission line data.

    After the data has been checked, press F10: Exit to return tothe HI Wave library menu.

  • 7/27/2019 Power Qualkity Analysis

    43/144

    23

    Goto Section B

  • 7/27/2019 Power Qualkity Analysis

    44/144

    1

    Advanced Power Quality

    Analysis

    Using PCs to Solve

    Harmonic ProblemsSection B&C

    B1. Create the Transmission Line.....

    Return to the Main menu. Press F10: Exit

  • 7/27/2019 Power Qualkity Analysis

    45/144

    2

    Press F1: Branch Records to obtain the menu SIMILAR to the

    menu below. Hit F9 to turn scan on.

    text

    On the left side of the menu, highlight the record line that says

    From Bus 1 (Utility) to Bus 2 (TRX Pri). Then press Return to get

    the Menu as shown below:

  • 7/27/2019 Power Qualkity Analysis

    46/144

    3

    When all of the above data is correct, press F9: Freq. Dep. Ln.

    This will call up a list of the non-linear transmission line models in

    the transmission line library, as illustrated below.

    Position the marker bar over the Transmission Line ID name, and

    press Enter. This will automatically enter the model into the

    branch record.

  • 7/27/2019 Power Qualkity Analysis

    47/144

    4

    The name of the selected model Transmission will appear in the

    Frequency Dep. Model data field as shown in the figure below.

    This is important!

    The transmission line branch record is now complete and may be

    saved by pressing F1: Save.

    Press F10: Exit to return to the left hand portion of the screen.

    Note that the branch name is now visible in this portion of the

    screen, verifying that the branch record has been created and

    saved.

  • 7/27/2019 Power Qualkity Analysis

    48/144

    5

    B2. Create the Transformer........

    Transformer Modeling

    Program considers non-linearity caused by over

    excitation or overloading.

    Transformer connections and phase shifting are modeled.

    Phase shifting is important when more than one source

    of harmonics exists.

    Program considers impedance versus frequency using a

    Laplace transformation. This modeling is automatic.

    Consider using EXISTING vs. DESIGN when modeling

    transformers.

  • 7/27/2019 Power Qualkity Analysis

    49/144

    6

    The transformer branch record is now complete. Press F1: Save

    to save the record and F10: Exit to return to the left-hand

    window of the Branch Record Editor.

    B3. Create the Feeders........

    On the left side of the menu, highlight the record line that says FromBus 3 (TRX Sec) to Bus 4 (Filter). Then press Return to get the

    Menu as shown below.

  • 7/27/2019 Power Qualkity Analysis

    50/144

    7

    Press F1: Save to save the record and F10: Exit to return to the

    left-hand window of the Branch Record Editor.

    On the left side of the menu, highlight the record line that says

    From Bus 3 (TRX Sec) to Bus 5 (Harm Source). Then press

    Return to get the Menu as shown below.

    text

  • 7/27/2019 Power Qualkity Analysis

    51/144

    8

    Press F1: Save to save the record and F10: Exit to return

    to the left-hand window of the Branch Record Editor.

    B4. Create the Utility Source........

    On the left side of the menu, highlight the record line that

    says From C UTILITY to 1 UTILITY. Then press

    Return to get the Menu as shown below.

    Note that the fault duty contribution record is displayed on a

    line different than the specified branch, and is identified

    with a "C" to the left of contribution type, as shown below.

    For the purposes of this tutorial, a utility fault duty will be

    defined for Bus 1, and the harmonic source at Bus 5 will bespecified as an induction motor contribution.

  • 7/27/2019 Power Qualkity Analysis

    52/144

    9

    Press F10: Exit to return to the Branch Record Editor.

    text

    B5. Create the Motor Contribution Source........

    On the left side of the menu, highlight the record line that

    says From C MOTOR to 5 HARM SOURC. Then press

    Return to get the Menu as shown below.

    Note that the fault duty contribution record is displayed on a

    line different than the specified branch, and is identified

    with a "C" to the left of contribution type, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    53/144

    10

    We define the induction motor contribution record in the same

    manner as the utility fault duty, specifying the contribution data

    as shown below. Press F10: Exit to return to the Branch RecordEditor

    Notes On Inputting Data:

    Co-generation - Do not model as a source bus, use the

    special co-generator model.

    Generators operating in parallel with the Utility may be

    defined as special bus generation load in the bus records.

  • 7/27/2019 Power Qualkity Analysis

    54/144

  • 7/27/2019 Power Qualkity Analysis

    55/144

    12

    To specify a source bus, press F7: Source Bus from the figure

    above, and the Define Source Bus Records window will appear as

    shown below.

    Specify Bus 1 as the source bus, as shown

    above. When the source bus has been

    specified, press F10: Exit to return to the

    list of bus records on the left side of the

    screen.

  • 7/27/2019 Power Qualkity Analysis

    56/144

    13

    C2. Specify the Harmonic Sources........

    To specify the harmonic source at Bus 5, position the marker barover Bus 5, and press F9: Load/Filter. The Harmonic Filter Data

    screen shown below will appear. Press Enter to access the screen.

    When the screen is accessed, a harmonic source may be selected by

    pressing F5: Harmonic Source Library; the list of sources in the

    harmonic source library will appear as shown below

  • 7/27/2019 Power Qualkity Analysis

    57/144

    14

    Position the marker bar on the Tutorial Source and press Enter to

    select it. HI_WAVE returns to the Harmonic Source/Filter Data

    screen, automatically inserting the source into the bus record. To

    verify that the source has been added to the bus record, make surethat the source name appears in the Library Source data field.

    Specify a 1000 kVA rating in the kVA data field, as illustrated

    below.

    C3. Specify the Capacitor Bank and Filter........

    While you are in this window, the capacitor bank data maybe defined. Press F6: Filter or Capacitor to access the

    Interactive Designer for Filters and Capacitor Banks

    window shown below.

  • 7/27/2019 Power Qualkity Analysis

    58/144

    15

    Enter the capacitor data for Bus 5 shown below.

    Press F6: Calculate Filter or Capacitor & Return Data;

    HI_WAVE calculates the capacitor data, inserts the data into the

    branch record, and returns control to the Harmonic Filter Datawindow, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    59/144

    16

    Press F1: Save to save the capacitor data with

    Bus 5 and return to the list of bus records on the

    left where the capacitor data for Bus 4 will now

    be specified.

    Position the marker bar over Bus 4 and press Enter to access the

    Harmonic Source/Filter Data entry window shown below. Make

    sure that Bus 4 has been selected by checking the bus record

    number in the upper left-hand portion of this window.

  • 7/27/2019 Power Qualkity Analysis

    60/144

    17

    Press F6: Filter or Capacitor to access the Filter/Capacitor design

    window. Enter the capacitor data shown below.

    When this data has been entered, press F6: Calculate Filter or

    Capacitor & Return Data. HI_WAVE will calculate the

    capacitor data, insert the data into the bus record, and return controlto the Harmonic Filter Data window, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    61/144

    18

    Bus 4 is now defined and the bus records are complete. Press F1:

    Save to save the filter data, and press F10: Exit until the

    HI_WAVE Main Menu appears. You have now configured the

    network topology for the entire tutorial project, and can begin to

    execute HI_WAVE studies to scan the system for resonance and

    harmonic distortion.

  • 7/27/2019 Power Qualkity Analysis

    62/144

    1

    Advanced Power Quality

    Analysis

    Using PCs to Solve

    Harmonic ProblemsSection D1-D2-D3

    D. Execute Studies........

    You have now configured the network

    topology for the entire tutorial project, and can

    begin to execute HI_WAVE studies to scan the

    system for resonance and harmonic distortion.

  • 7/27/2019 Power Qualkity Analysis

    63/144

    2

    For most cases, four studies will be executed using thepower system configuration defined by you, typically in this

    sequence:

    1. Demand Load Analysis.

    2. Harmonic Load Flow.

    3. Frequency Scan for Resonance.

    4. Distortion Calculations (current and voltage).

  • 7/27/2019 Power Qualkity Analysis

    64/144

    3

    In the case of the Tutorial, executing a Demand Load Analysis is

    not necessary. The reasons for executing the studies in this

    sequence will be explained during the course of the analysis

    sections.

    D1. Execute Demand Load Analysis........

    Normally, you would have specified end use load and/or

    special bus loads in a project in which case a Demand Load

    Analysis would be executed.

    Since the only loads in this project are harmonic sources, a

    Demand Load Analysis is not necessary; the Harmonic Load

    Flow Program models all harmonic source load data. Had you

    specified end use loads or special bus loads, the Demand Load

    Analysis would have been the first study executed.

  • 7/27/2019 Power Qualkity Analysis

    65/144

    4

    Demand Load Analysis

    Connected Load - Sum of:

    End Use Loads + Loads on feeders to that bus.

    Demand Load - Sum of:

    End Use Loads + Loads on feeders to that bus,

    except that diversity factors are applied at EACH bus.

    Design Load - Sum of:

    DEMAND Loads times applicable code or designer safetyfactors.

    Demand load analysis does not allow loops, only radial

    feeders.

    If all the loads are entered as special bus loads,

    there is no need to run the DLA.

    The Harmonic Load Analysis allows looped feeders.

  • 7/27/2019 Power Qualkity Analysis

    66/144

    5

    D2. Execute Harmonic Load Flow Analysis........

    From the main menu select F8: Execute Studies, and the

    Harmonic Investigation Studies screen will appear.

    Select F2: Harmonic Load Flow from this screen, and the

    report name window will be called up.

    Enter the report name as shown below.

  • 7/27/2019 Power Qualkity Analysis

    67/144

    6

    Harmonic Load Flow Study

    Does not evaluate feeder or transformer capacity.

    Automatically includes all passive elements

    including filters.

    Harmonic load flow can have looped system.

    Press F1: Continue, and enter title lines for the study as

    shown below or any text you like.

  • 7/27/2019 Power Qualkity Analysis

    68/144

    7

    After the title lines have been entered, press F1: Continue,and the HI_WAVE Load Flow Criteria screen will appear.

    In this screen, you set the criteria for the solution method, the

    system modeling requirements and the solution criteria.

    These criterion categories should be reviewed to discover the

    available options.

    For the purposes of the tutorial, enter the criteria options

    shown below.

    Press F1: Continue, and HI_WAVE will execute the

    harmonic load flow study.

  • 7/27/2019 Power Qualkity Analysis

    69/144

    8

    Review the Harmonic Load Flow Report

    After executing the harmonic load flow study, the

    program will return to the HI_WAVE Main Menu.

    To review the harmonic load flow report, select

    F7: Edit Scan Files. Enter the harmonic load

    report file name in response to the HI_WAVE

    prompt, as shown below or select F3: to view all

    available files.

    Press F1: Continue, and the report shown below will be

    displayed.

    Important Features of the Harmonic Load Flow Report

  • 7/27/2019 Power Qualkity Analysis

    70/144

    9

    P A S S I V E F I L T E R D A T A

    BUS VOLTAGE FILTER PARAMETERS FILTER LOAD

    R JWL JWC KVA PF

    ==============================================================================

    4 FILTER 13800.

    + sequ: .00 .00 190.44 1000.0 .0000

    0 sequ: .00 .00 .00

    5 HARM SOURC 13800.

    + sequ: .00 .00 476.10 400.0 .0000

    0 sequ: .00 .00 .00

    F E E D E R D A T A

    FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER DESCRIPTION

    NO NAME NO NAME /PH L-L SIZE TYPE DUCT INSUL

    ==============================================================================

    1 UTILITY 2 TRX PRI 1 500000. 50. MI

    IMPEDANCE: .0300000 + J .0900000 PER UNIT

    B/2: .004000 PER UNIT % SERIES COMP: .0

    TO SHUNT(KVAR): 200. FROM SHUNT(KVAR): 200.

    3 TRX SEC 4 FILTER 1 13800. 1000. FT 250 C N XLP

    IMPEDANCE: .0891 + J .0396 OHMS/M FEET

    3 TRX SEC 5 HARM SOURC 1 13800. 1000. FT 250 C N XLP

    IMPEDANCE: .0891 + J .0396 OHMS/M FEET STATUS: EXISTING

    ==============================================================================

    SOURCE BUS THEVENIN EQUIVALENT IMPEDANCE: 8.329 + J 249.861 OHMS

    Calculated From Largest 3-PHASE Fault Contribution

    ==============================================================================

  • 7/27/2019 Power Qualkity Analysis

    71/144

    10

    T R A N S F O R M E R D A T A

    PRIMARY RECORD VOLTS PRI * SECONDARY RECORD VOLTS SEC NOMINAL

    NO NAME L-L FLA NO NAME L-L FLA KVA

    ==============================================================================

    2 TRX PRI 500000. 6. 3 TRX SEC 13800. 209. 5000.

    IMPEDANCE: .7960 + J 7.9603 PERCENT

    B R A N C H L O A D D A T A

    =============================================================================F R O M / T O BR. CONSTANT KVA CONSTANT Z CONSTANT I FLOW

    B U S / B U S TYPE KVA %PF KVA %PF KVA %PF DIR.

    =============================================================================

    The Harmonic Load Flow Program reports end use load data

    under the Branch Load Data heading. Since there is no such

    data in the Tutorial project, this heading is empty.

  • 7/27/2019 Power Qualkity Analysis

    72/144

    11

    B U S S P E C I A L S T U D Y D A T A

    ==============================================================================

    * NO * NAME * KW * KVAR * LOAD/GENERATION

    ==============================================================================

    4 FILTER 0. -1000. CONSTANT Z LOAD

    5 HARM SOURC 0. -400. CONSTANT Z LOAD

    5 HARM SOURC 800. 600. CONSTANT I LOAD

    *** SOLUTION COMMENTS ***

    SOLUTION PARAMETERS

    PER UNIT DRIVING VOLTAGE : 1.0000

    BRANCH VOLTAGE CRITERIA : 4.00 %

    BUS VOLTAGE CRITERIA : 5.00 %

    EXACT(ITERATIVE) SOLUTION : YES

    TRANSFORMERS MODELED : YES

  • 7/27/2019 Power Qualkity Analysis

    73/144

    12

    BALANCED VOLTAGE DROP AND LOAD

    FLOW ANALYSIS (SPECIAL BUS LOAD

    REPORT

    VOLTAGE EFFECT ON LOADS MODELED TRANSFORMER VOLTAGE DROP MODELED

    VOLTAGE DROP CRITERIA: BRANCH = 4.00 % BUS = 5.00

    PER UNIT DRIVING VOLTAGE = 1.0000

    LOAD BUS: 1 UTILITY DESIGN VOLTAGE:500000 LOAD VOLTAGE:500590 %VD: -.1

    ------------------------- VOLTAGE ANGLE: .0 DEGREES

    LOAD TO: 2 TRX PRI FEEDER AMPS: 2 VOLTAGE DROP: -332. %VD: -.07

    PROJECTED POWER FLOW: 814. KW -1209. KVAR 1457. KVA PF: .56 LEADING

    LOSSES THRU FEEDER: 1. KW -400. KVAR 400. KVA

    LOAD FROM: **** SOURCE FEEDER AMPS: 2 VOLTAGE DROP: 0. %VD: .00

    PROJECTED POWER FLOW: 814. KW -1209. KVAR 1457. KVA PF: .56 LEADING

    LOSSES THRU FEEDER: 0. KW 0. KVAR 0. KVA

    LOAD BUS: 5 HARM SOURC DESIGN VOLTAGE: 13800 LOAD VOLTAGE: 13981 %VD: -1.3------------------------- VOLTAGE ANGLE: -.9 DEGREES

    PROJECTED SPECIAL BUS LOAD: 810. KW 197. KVAR

    LOAD FROM: 3 TRX SEC FEEDER AMPS: 34 VOLTAGE DROP: 6. %VD: .04

    PROJECTED POWER FLOW: 810. KW 197. KVAR 834. KVA PF: .97 LAGGING

    LOSSES THRU FEEDER: 0. KW 0. KVAR 0. KVA

    5 BUSES

    *** T O T A L S Y S T E M L O S S E S ***

    3. KW -378. KVAR

  • 7/27/2019 Power Qualkity Analysis

    74/144

  • 7/27/2019 Power Qualkity Analysis

    75/144

    14

    Based on the frequency scan report results, you will be able to

    decide if there is cause to execute a distortion calculation.

    If there are large resonance points at frequencies where

    harmonic sources exist at high magnitudes, then a distortion

    calculation should be executed.

    Frequency Scan

    The frequency scan requires you to define all

    harmonic sources, but is unaffected by the source

    type or magnitude of harmonics.

    The impedance shown in the calculation is the

    Thevenin impedance looking into the selected

    bus to ground.

  • 7/27/2019 Power Qualkity Analysis

    76/144

    15

    To execute a frequency scan, select F8: Execute Studies

    from the Main Menu.

    From the Harmonic Investigation Studies window, select F8:

    Frequency Scan for Resonance(386).

    Enter the file name for the Frequency Scan for Resonance

    report as shown below.

    After the report name has been entered, press F1: Continue.

  • 7/27/2019 Power Qualkity Analysis

    77/144

    16

    Enter the project title lines for the frequency scan for

    resonance study as shown below.

    After the project title lines have been entered, press

    F1: Continue.

  • 7/27/2019 Power Qualkity Analysis

    78/144

    17

    A window listing of all the buses in the power system will

    now appear. This screen allows you to select all of the buses

    that will be included in the frequency scan. To select a bus,

    position the marker bar over the desired bus using the choice

    keys and press F5:

    Select Buses for Display. Asterisk brackets will appear

    around the bus, indicating that it has been selected.

    Pressing F5 again will de-select the bus. For the purposes of

    the tutorial, select all of the buses in the power system with

    the exception of the utility source bus (Bus 1) as shown

    below.

    Notice also in this window the double arrow symbol to the

    right of bus five; this indicates the presence of a harmonic

    source at the indicated bus.

  • 7/27/2019 Power Qualkity Analysis

    79/144

    18

    Press F9: Execute after the buses have been selected, and the

    Solution Criteria for HI_WAVE Frequency Scan window

    will appear.

    This window is similar to the solution criteria window for the

    harmonic load flow study; it allows you to specify the

    scanning range and the solution criteria for the frequency

    scan.

  • 7/27/2019 Power Qualkity Analysis

    80/144

    19

    Enter the data for this screen as shown below.

    Notice that in theDefine Scanning Range window the data

    are entered manually, while in the Select the Solution Criteria

    window the choice keys are used to toggle through a list of

    options.

  • 7/27/2019 Power Qualkity Analysis

    81/144

    20

    When finished, press F1: Execute and HI_WAVE will

    execute the frequency scan for resonance analysis. When the

    analysis is complete, the program returns you to the

    HI_WAVE Main Menu.

    View the Frequency Scan Report

    To view the report results, select F7: Edit/Scan

    files from the HI_WAVE Main Menu.

    Enter the frequency scan report name as shown

    below.

  • 7/27/2019 Power Qualkity Analysis

    82/144

    21

    Press F1: Continue to view the frequency scan for resonance

    report below.

    Frequency Scan Criteria

    Text Output

  • 7/27/2019 Power Qualkity Analysis

    83/144

    22

    C R I T E R I A O F F R E Q U E N C Y

    S C A N

    FUNDAMENTAL FREQUENCY: 60.HZ

    START FREQUENCY: 60.HZ

    SCAN STEP SIZE: 20.HZ

    SCAN STEPS: 75

    EQUIVALENT IMPEDANCE REPORTED IN PER UNIT

    WITH ONE PER UNIT CURRENT

    INJECTED AT SELECTED BUSES

    BASED ON BUS NOMINAL VOLTAGE AND 100MVA POWER BASE

    BOTH AERIAL AND GROUND MODES ARE SELECTED

    NONLINEAR FREQUENCY DEPENDENT BRANCHES

    ARE SELECTED

    MOTORS ARE FROM CONTRIBUTION DATA

    SPECIAL LOADS ARE INCLUDED IN THE STUDY

  • 7/27/2019 Power Qualkity Analysis

    84/144

    23

    L E G E N D O F T E R M I N O L O G Y

    FREQUENCY SCAN: INJECTING 1 PER UNIT CURRENT ATTHE HARMONIC SOURCE LOCATIONS,

    REPORTING SYSTEM BUS VOLTAGES

    (EQUIVALENT IMPEDANCES)

    FOR A RANGE OF FREQUENCIES

    SET UP BY USER

    BUS EQUIVALENT IMPEDANCE: THE IMPEDANCE SEEN FROM THE

    USER SELECTED BUS

    DRIVING BUS: ANY BUS WITH A HARMONIC

    SOURCE

    HARMONIC SOURCE: REPLACED BY CONSTANT ONE

    PER UNIT CURRENT SOURCE

    R PU: REAL PART OF COMPLEX IMPEDANCE

    IN PER UNIT

    JX PU: IMAGINARY PART OF COMPLEX IMPEDANCE

    IN PER UNIT

    Z PU: MAGNITUDE OF IMPEDANCE

    IN PER UNIT

    P A S S I V E F I L T E R D A T A

    BUS VOLTAGE R (OHM) JXL (OHM) -JXC (OHM)==============================================================================

    4 FILTER 13800.

    POS SEQ. .00 .00 190.44

    ZERO SEQ. .00 .00 .00

    5 HARM SOURC 13800.

    POS SEQ. .00 .00 476.10

    ZERO SEQ. .00 .00 .00

  • 7/27/2019 Power Qualkity Analysis

    85/144

    24

    C O N T R I B U T I O N D A T A

    CONTRIBUTION VOLTAGE BASE

    FROM NAME TO NAME L-L MVA XD"(PU) X/R

    ==============================================================================

    UTILITY 1 UTILITY 500000. 3P-KA: 1.155 30.0

    TYPE: UTILITY 1P-KA:

    POS SEQUENCE IMPEDANCE (100 MVA BASE) .00333 + J .09994 PER UNIT

    MOTOR 5 HARM SOURC 13800. 1.000 .25000 15.0

    TYPE: IND. MOTOR KW/HP: 1000. RPM: 1800.

    POS SEQUENCE IMPEDANCE (100 MVA BASE) 1.66667 + J 25.00000 PER UNIT

    F E E D E R D A T A

    FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER DESCRIPTIONNo. NAME No. NAME /PH L-L FEET SIZE TYPE DUCT INSUL

    ==============================================================================

    1 UTILITY 2 TRX PRI 1 500000. 264000.

    IMPEDANCE: .0300000 + J .0900000 PER UNIT

    B/2: .004000 PER UNIT % SERIES COMP: 200.0

    TO SHUNT(KVAR): 200. FROM SHUNT(KVAR): 0.

    3 TRX SEC 4 FILTER 1 13800. 1000. 250 C N XLP

    POS seq Z .0891 + J .0396 OHMS/M FEET .04679 + J .02079 PU

  • 7/27/2019 Power Qualkity Analysis

    86/144

    25

    T R A N S F O R M E R D A T A

    PRIMARY SIDE VOLTS PRI * SECONDARY SIDE VOLTS SEC NOMINALNo. NAME CONN L-L FLA * No. NAME CONN L-L FLA KVA

    ==============================================================================

    2 TRX PRI D 500000. 6. 3 TRX SEC YG 13800. 209. 5000.

    POS SEQ Z .7960 + J 7.9603 PERCENT .15921 + J 1.59206 PER UNIT

    Equivalent Bus Impedance at Fundamental Frequency

    B U S E Q U I V A L E N T

    I M P E D A N C E AT 60 HZ AND ABOVE

    HI_WAVE reports equivalent bus impedance for

    all harmonic frequencies, according to user-

    defined steps, up to and including the maximum

    selected frequency. For the purposes of this

    illustration, the middle frequencies are omitted.

  • 7/27/2019 Power Qualkity Analysis

    87/144

    26

    To exit the viewing mode press F10: and the program will ask

    whether or not you want to exit. Press D(on't) and Enter in

    response to the prompt, and the program will return to the

    Main Menu.

    View the Graphical Output of the

    Frequency Scan Report

    This step of the tutorial is required so that you can decide

    whether or not distortion calculations need to be executed on

    the project.

    To view a drawing of the frequency report, from the

    HI_WAVE Main Menu select F4: Graphics Output and the

    HI_WAVE Graphing Utility window will appear. From this

    window select F1: Frequency Scan Drawings as illustratedbelow.

  • 7/27/2019 Power Qualkity Analysis

    88/144

    27

    When F1: Frequency Scan Drawings is selected, the Select

    Drawing Name window will appear. In this window, there

    will be a list of frequency scan file names. Select the SCAN

    file as shown below, and press Enter.

  • 7/27/2019 Power Qualkity Analysis

    89/144

    28

    When Enter is pressed, the buses that you selected for

    inclusion in the frequency scan calculation will appear in a

    window on the right side of the screen.

    From this window select Bus 2 for graphical output by

    positioning the marker bar over the bus name and pressing

    F1: Select Data. Arrows will appear to the right of the bus

    name to indicate that it has been selected.

  • 7/27/2019 Power Qualkity Analysis

    90/144

    29

    Next, access the Plot Data Choices data choice field and

    select H Order V Z (harmonic order versus impedance) from

    the list of provided options using the PgUp/PgDn keys.

    Press F2: Plot Selected, and HI_WAVE will generate the

    requested drawing, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    91/144

    30

    Using the same process outlined above, de-select Bus 2,

    select Buses 3, 4, and 5 for simultaneous output. The

    drawing of the combined plots is illustrated below.

  • 7/27/2019 Power Qualkity Analysis

    92/144

    31

    To save this drawing to a plot file press F9: Save Plot File.

    Pressing F10: Exit will not save the drawing into a plot file, it will

    only save the screen data.

    After pressing F9, the Save Plot File window will appear.

    Enter the output file name and plot description as shown

    below.

  • 7/27/2019 Power Qualkity Analysis

    93/144

    32

    Press F1: Continue/Save to save the plot file under

    the entered report name, and HI_WAVE will return

    to the drawing window.

    Press F10: Exit to access the HI_WAVE

    Graphing Utility window.

    Press F10: Exit to Main Menu.

  • 7/27/2019 Power Qualkity Analysis

    94/144

    1

    Advanced Power Quality

    Analysis

    Using PCs to Solve

    Harmonic ProblemsSection D4-E1-E2

    D4. Execute Voltage and Current Distortion

    Calculations........

    The distortion calculations determine the system's total

    voltage distortion at each selected bus, and the total

    current distortion at each selected branch.

    To perform the distortion calculations, from the

    HI_WAVE Main Menu select F8: Execute Studies, and

    the Harmonic Investigation Studies window will appear.

    From this window select F7: DistortionCalculations(386).

  • 7/27/2019 Power Qualkity Analysis

    95/144

    2

    HI_WAVE will prompt you to enter a report name for the

    distortion calculation. Enter the report name DIST as shown

    below. The date and time will be entered automatically by

    HI_WAVE.

  • 7/27/2019 Power Qualkity Analysis

    96/144

    3

    Press F1: Continue and the Enter Project

    Title Lines window will appear.

    Enter title lines for the distortion calculation

    report as shown below.

  • 7/27/2019 Power Qualkity Analysis

    97/144

    4

    Press F1: Continue, and a window containing a list of all the

    buses in the power system will appear. In this window you

    specify the buses to be included for graphical output in the

    voltage distortion calculation.

    To select a bus, position the marker bar over the desired bus

    record, and press F5: Select Buses For Display. When a bus

    record is selected, asterisk brackets appear around the bus name.

    Select all of the bus records except the utility bus (Bus 1) as

    shown below.

  • 7/27/2019 Power Qualkity Analysis

    98/144

    5

    When all of the buses are selected, press F9: Execute, and the

    Select Branch Flow Records screen illustrated below will appear.

  • 7/27/2019 Power Qualkity Analysis

    99/144

    6

    In this screen, you select the branches to be included in graphicaloutput of the current distortion calculation.

    To select a branch, position the marker bar over the desired branch

    and press F5: Toggle Select. When a branch is selected, asterisk

    brackets appear around the branch name, and the branch name

    appears in the Selected Records window on the right side of the

    screen.

    For the purposes of the tutorial, select ALL of the branches in the

    system for inclusion in the current distortion calculation as shown

    below.

  • 7/27/2019 Power Qualkity Analysis

    100/144

    7

    When the branches have been selected, press F9: Execute to

    access the Solution Criteria for HI_WAVE Distortion

    Calculation screen. In this screen, specify the solution

    criteria for the distortion calculation as shown below.

    Notice that in the Define the Distortion Calculation Range window,data are entered manually, while in the Select Solution Criteria

    window, data options are toggled using the choice keys.

  • 7/27/2019 Power Qualkity Analysis

    101/144

    8

    When the solution criteria have been entered, press F1:

    Execute, HI_WAVE executes the distortion calculations.

    After the calculations are complete, the program will return

    control to the Main Menu. You may now view the distortion

    calculation text report.

    View the Distortion Calculation Report

  • 7/27/2019 Power Qualkity Analysis

    102/144

    9

    To view the report results, select F7: Edit/Scan Files from

    the Main Menu. HI_WAVE will prompt you for the report

    name, Enter DIST in response to the prompt, as shownbelow.

    Select F1: Continue to continue.

    Important Features of the Distortion

    Calculation Report

  • 7/27/2019 Power Qualkity Analysis

    103/144

    10

    C R I T E R I A O F D I S T O R T I O N

    S T U D Y

    FUNDAMENTAL FREQUENCY: 60.HZ

    MAXIMUM ORDER OF HARMONICS: 25TH

    TOTAL VOLTAGE AND CURRENT DISTORTION IS BASED ON THE LOAD FLOW STUDY

    TOTAL VOLTAGE DISTORTION WILL BE REPORTED

    HARMONIC RMS VOLTAGE WILL BE REPORTED

    TOTAL CURRENT DISTORTION WILL BE REPORTED

    HARMONIC RMS CURRENT WILL BE REPORTED

    NONLINEAR FREQUENCY DEPENDENT BRANCHES ARE SELECTED

    BOTH AERIAL AND GROUND MODES ARE SELECTED

    MOTORS ARE FROM CONTRIBUTION DATA

    SPECIAL LOADS ARE INCLUDED IN THE STUDY

    IT FACTOR WILL BE REPORTEDTRANSFORMER PHASE SHIFT MODELED

    L E G E N D O F T E R M I N O L O G Y

    LF VOLTS: LOAD FLOW VOLTAGE RESULTS

    V_THD: TOTAL HARMONIC VOLTAGE DISTORTION

    V_RMS: ROOT-MEAN-SQUARE VOLTAGE MAGNITUDE INCLUDING

    FUNDAMENTAL VOLTAGE AND HARMONIC VOLTAGES

    V_TIF: VOLTAGE TELEPHONE INFLUENCE FACTOR

    I_THD: TOTAL HARMONIC BRANCH CURRENT DISTORTION

    I_RMS: ROOT-MEAN-SQUARE CURRENT MAGNITUDE INCLUDING

    FUNDAMENTAL CURRENT AND HARMONIC CURRENTS

    IT: INDUCTIVE INFLUENCE IN TERMS OF ROOT-MEAN-SQUARE OF

    THE PRODUCT OF CURRENTS AND THE INFLUENCE WEIGHTING

    FACTORS

    K: K-FACTOR, TOTAL TRUE-RMS CURRENT REFERENCE

  • 7/27/2019 Power Qualkity Analysis

    104/144

    11

    H A R M O N I C S O U R C E

    BUS: 5 HARM SOURC VOLTAGE: 13800. ID:SKM SIX PULSE KVA: 1000.0

    ORDER MAGNITUDE ANGLE ORDER MAGNITUDE ANGLE ORDER MAGNITUDE ANGLE

    ==============================================================================

    1 100.000 -12.6 5 37.660 107.4 7 12.550 -126.9

    11 7.110 -93.2 13 3.350 -50.2 17 2.930 15.9

    19 1.670 45.0

    H A R M O N I C S O U R C E I N D E XT A B L E

    HARMONIC SOURCES HAVE BEEN FOUND AND

    INJECTED FOR EACH OF

    THE FOLLOWING HARMONIC ORDERS

    5 7 11 13 17 19

  • 7/27/2019 Power Qualkity Analysis

    105/144

    12

    P A S S I V E F I L T E R D A T A

    BUS VOLTAGE R (OHM) JWL (OHM) -JWC (OHM)

    ==============================================================================

    4 FILTER 13800.

    POS SEQ. .00 .00 190.44

    ZERO SEQ. .00 .00 .00

    5 HARM SOURC 13800.

    POS SEQ. .00 .00 476.10

    ZERO SEQ. .00 .00 .00

    C O N T R I B U T I O N D A T A

    CONTRIBUTION VOLTAGE BASE

    NAME No. NAME L-L MVA XD"(PU) X/R

    ==============================================================================

    UTILITY 1 UTILITY 500000. 3P-KA: 1.155 30.0

    TYPE: UTILITY 1P-KA:

    POS SEQUENCE IMPEDANCE (100 MVA BASE) .00333 + J .09994 PER UNIT

    MOTOR 5 HARM SOURC 13800. 1.000 .25000 15.0

    TYPE: IND. MOTOR KW/HP: 1000. RPM: 1800.

    POS SEQUENCE IMPEDANCE (100 MVA BASE) 1.66667 + J 25.00000 PER UNIT

  • 7/27/2019 Power Qualkity Analysis

    106/144

    13

    F E E D E R D A T A

    FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER DESCRIPTION

    No. NAME No. NAME /PH L-L FEET SIZE TYPE DUCT INSUL

    ==============================================================================

    1 UTILITY 2 TRX PRI 1 500000. 264000.

    IMPEDANCE: .0300000 + J .0900000 PER UNIT

    B/2: .004000 PER UNIT % SERIES COMP: 200.0

    TO SHUNT(KVAR): 200. FROM SHUNT(KVAR): 0.

    3 TRX SEC 4 FILTER 1 13800. 1000. 250 C N XLP

    POS seq Z .0891 + J .0396 OHMS/M FEET .04679 + J .02079 PU

    3 TRX SEC 5 HARM SOURC 1 13800. 1000. 250 C N XLP

    POS seq Z .0891 + J .0396 OHMS/M FEET .04679 + J .02079 PU

    T R A N S F O R M E R D A T A

    PRIMARY SIDE VOLTS PRI * SECONDARY SIDE VOLTS SEC NOMINAL

    No. NAME CONN L-L FLA * No. NAME CONN L-L FLA KVA

    ==============================================================================

    2 TRX PRI D 500000. 6. 3 TRX SEC YG 13800. 209. 5000.

    POS SEQ Z .7960 + J 7.9603 PERCENT .15921 + J 1.59206 PER UNIT

  • 7/27/2019 Power Qualkity Analysis

    107/144

    14

    T O T A L V O L T A G E D I S T O R T I O NBUS NAME NOMINAL VOLTS V_RMS V_THD(%) V_TIF

    ==============================================================================

    1 UTILITY 500000. 500589.60 .0003 .5003

    2 TRX PRI 500000. 501026.60 2.0522 $ 11.6989

    3 TRX SEC 13800. 14043.35 9.0340 $ 36.7486

    4 FILTER 13800. 14046.98 9.0903 $ 37.2840

    5 HARM SOURC 13800. 14038.08 9.0715 $ 36.5682

    V O L T A G E D I S T. S U M M A R YTHERE ARE 4 VOLTAGE DISTORTION EXCEEDING IEEE STD 519 STANDARD

    ==============================================================================

    BUS NAME NOMINAL VOLTS V_RMS V_TH(%) V_TIF

    ==============================================================================

    2 TRX PRI 500000. 501026.60 2.0522 $ 11.6989

    3 TRX SEC 13800. 14043.35 9.0340 $ 36.7486

    4 FILTER 13800. 14046.98 9.0903 $ 37.2840

    5 HARM SOURC 13800. 14038.08 9.0715 $ 36.5682

  • 7/27/2019 Power Qualkity Analysis

    108/144

    15

    T O T A L C U R R E N T D I S T O R T I O N

    FROM/NAME TO/NAME VOLTAGE I_RMS(A) I_THD(%) K IT

    ==============================================================================

    1 UTILITY 2 TRX PRI 500000. 1.68 .01 1.00 1.33

    2 TRX PRI 3 TRX SEC 500000. 1.97 111.14 16.19 480.16

    3 TRX SEC 4 FILTER 13800. 47.50 50.47 8.17 13356.21

    3 TRX SEC 5 HARM SOURC 13800. 39.74 57.54 7.55 8852.18

    Only the harmonic voltage spectrum report for Bus 3 is shown. When you view the

    distortion report in HI_WAVE, every bus will be reported in the same format.

    HARMONIC VOLTAGES FOR BUS 3 TRX SEC VOLTAGE: 13800.0

    ==============================================================================

    HARMONIC HARMONIC PHASE DISTORTION IEEE-519

    ORDER VOLT ANGLE PERCENT LIMIT

    ==============================================================================

    1 13986.400 -.91

    5 1115.062 -79.19 7.972$ 3.000

    7 587.273 -78.49 4.199$ 3.000

    11 82.987 175.88 .593 3.000

    13 30.174 -40.28 .216 3.000

    17 19.608 -131.83 .140 3.000

    19 8.273 -3.71 .059 3.000

    Harmonic Voltage Spectrum Report

  • 7/27/2019 Power Qualkity Analysis

    109/144

    16

    ++SUMMARY+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

    VOLTAGE V_RMS V_TIF V_THD(%) IEEE-519 LIMIT

    13800.0 14043.3 36.74 9.03$ 5.0

    $ INDICATES A VIOLATION OF IEEE STD 519 LIMITS FOR VOLTAGE

    Harmonic Current Spectrum Report

  • 7/27/2019 Power Qualkity Analysis

    110/144

    17

    Only the harmonic current spectrum report for Branch 2-3 is shown. When you view

    the distortion report in HI_WAVE, every branch will be reported in the same format.

    HARMONIC CURRENT FOR BRANCH 2 TRX PRI 3 TRX SEC

    IEEE-519 IS NOT APPLICABLE TO THIS BRANCH

    ==============================================================================

    HARMONIC HARMONIC PHASE DISTORTION IEEE-519

    ORDER AMPS ANGLE PERCENT LIMIT

    ==============================================================================

    1 1.322

    5 1.360 -162.09 102.823

    7 .557 -160.11 42.137

    11 .026 -110.92 1.986

    13 .008 33.41 .622

    17 .006 132.92 .426

    19 .005 -98.04 .356

    ++SUMMARY+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

    VOLTAGE:500000. I_RMS: 1.97 IT: 480.16 K: 16.19 I_THD(%): 111.14

    $ INDICATES A VIOLATION OF IEEE STD 519 LIMITS FOR CURRENT

  • 7/27/2019 Power Qualkity Analysis

    111/144

    18

    Capacitor and Filter Spectrum Report

    Only the capacitor/filter spectrum report for the

    capacitor at Bus 4 is shown. When you view the

    distortion report in HI_WAVE, every capacitor

    bank and filter will be reported in the same format.

    HARMONIC SPECTRUM FOR CAPACITOR BANK ON BUS 4 FILTER

    ==============================================================================

    HARMONIC CURRENT

    NUMBER (AMPS) KW KVAR KVA PF

    ==============================================================================

    1 42.41 .0000 -1027.6320 1027.6320 .00

    5 16.99 .0000 -32.9866 32.9866 .00

    7 12.59 .0000 -12.9393 12.9393 .00

    11 2.83 .0000 -.4185 .4185 .00

    13 1.23 .0000 -.0667 .0667 .00

    17 1.07 .0000 -.0388 .0388 .00

    19 .51 .0000 -.0079 .0079 .00

  • 7/27/2019 Power Qualkity Analysis

    112/144

    19

    ++SUMMARY+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

    CAPACITOR RATED VOLTAGE: 7967.40 (L-N)

    V_RMS: 8110.029 | V_CREST:9150.833 | I_RMS: 47.5072 | KVA: 1155.856

    % V_RMS: 101.7897 |%V CREST:114.8530 | % I: 114.0206 | % KVA: 115.5856

    LIMIT: 110.0% | LIMIT: 169.7% | LIMIT: 180.0% | LIMIT: 135.0%

    Warning Message

    $ INDICATES A VIOLATION OF IEEE STD 519

    LIMITS FOR CURRENT

  • 7/27/2019 Power Qualkity Analysis

    113/144

    20

    View Graphical Output of the Voltage

    Distortion

    From the HI_WAVE Main Menu, select F4:

    Graphics Output, and the HI_WAVE Graphing

    Utility window will appear. From this window,

    select F2: Voltage Distortion, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    114/144

    21

    As for the frequency scan, a list of the available distortion

    report files will appear in a window on the right side of the

    screen. Select the DIST file, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    115/144

    22

    When the file has been selected, press F1: Select and

    Return, and a list of the buses that were selected for

    graphical output during the voltage distortion calculations

    will appear in a window on the right side of the screen.

    Select all of the buses for graphical output in the same

    manner as for the frequency scan. In the Plot Data Choices

    choice field, select Wave form in PU using the choice keys;

    press F2: Plot Selected to generate the graph shown below.

  • 7/27/2019 Power Qualkity Analysis

    116/144

    23

    You will notice that there is moderate voltage distortion,

    particularly at Buses 3 and 4.

    Press F10: Exit/Save to return to the HI_WAVE Graphing

    Utility Window.

    View Graphical Output of the Current

    Distortion

    From the Graphing Utility Window, select F3:

    Current Distortion as shown below.

  • 7/27/2019 Power Qualkity Analysis

    117/144

    24

    Select the DIST file, as shown below.

    A list of all of the branches that were selected for inclusion in

    the current distortion calculation will appear in a window on

    the right side of the screen. Select Branches 2-3 and 3-4 for

    graphical output.

  • 7/27/2019 Power Qualkity Analysis

    118/144

    25

    In the Plot Data Choices choice field, select Wave form in

    PU using the choice keys; press F2: Plot Selected to generate

    the graph shown below.

  • 7/27/2019 Power Qualkity Analysis

    119/144

    26

    As the figure above illustrates, there is extreme current

    distortion in both branches.

    When finished reviewing the current distortion graphical

    results, press F10: Exit until the HI_WAVE Main Menu

    appears.

    E1. Make System Improvements........

    The next phase of the tutorial deals with modifying the

    power system to compensate for the harmonic distortion

    that the reports and graphics indicate.

    The capacitors at Buses 4 and 5 will be

    tuned into single-tuned filters.

  • 7/27/2019 Power Qualkity Analysis

    120/144

    27

    How To Design a Filter:

    1. Select base power frequency : 25, 50 or 60 Hz.

    2. Select SF, HP or C

    3. Select connection Y, D or YG

    4. Select target harmonic number

    5. Select capacitor can voltage rating

    6. Select rated capacitor size in kVAR's

    7. For SF filters specify Q

    Q = X/R

    X = filter resonant inductance

    Q factor graph can be obtained from filter mfg.

    Normal range of Q is 50-150

    8. For HP filters specify an optimal factor:

    M = L / (R*R*C)

    9. This provides steady state data, see filter manufacturer for

    transient and changing load limits.

  • 7/27/2019 Power Qualkity Analysis

    121/144

    28

    Filter Design

    1. Target harmonic order can be a decimal value, usually

    lower than the harmonic to be attenuated.

    2. Select type of filter:

    SF = single tuned low pass filter

    C in series with

    L in series with

    R

    HP = High pass or multiple order filter

    C in series with

    L R which are in parallel

    C = Capacitor bank only

    3. You can model up to five filters on each bus.

    4. You can use the interactive filter designer.

    5. See SKM page UG 6-17 for more details.

  • 7/27/2019 Power Qualkity Analysis

    122/144

    29

    Turn the Capacitor at Bus 4

    into a Single-Tuned Filter

    Now that the distortion has been calculated and

    the system resonance points determined, a filter

    can be effectively designed and applied at Bus 4.

    Select F3: Bus Records from the HI_WAVE Main Menu;

    the HI_WAVE Bus Record editor screen will appear.

    Position the marker bar over the Bus 4 record; press F9:

    Load/Filter and then Enter to access the Harmonic Filter

    Data window shown below and begin filter design.

  • 7/27/2019 Power Qualkity Analysis

    123/144

    30

    Notice that the capacitor data has been saved in the bus record

    and is available for editing. Access the capacitor record (any

    data field associated with the capacitor) and press F6: Filter or

    Capacitor.

    This accesses the Interactive Filter Designer. The filter designer

    screen with the capacitor data will appear.

    Tune the capacitor into a single tuned filter by changing the datain this window to match that below.

  • 7/27/2019 Power Qualkity Analysis

    124/144

    31

    The capacitor is now tuned into a 3.6th harmonic order

    single-tuned filter. Press F6: Calculate Filter or Capacitor

    & Return Data, and HI_WAVE will return to the Harmonic

    Filter Data window, automatically inserting the calculated

    positive sequence filter data into the bus record, as shown

    below.

  • 7/27/2019 Power Qualkity Analysis

    125/144

    32

    Press F1: Save to save the filter data and return to the list of

    bus records. You are now ready to modify the capacitor at

    the harmonic source bus.

  • 7/27/2019 Power Qualkity Analysis

    126/144

    33

    Tune the Bus 5 Capacitor Bank into a

    Single-tuned Filter

    You will now tune the capacitor at Bus 5 into a 5th order,

    single-tuned filter.

    The procedure is identical to that used for Bus 4. When you

    return to the list of bus records, the load/filter data should still

    be visible.

    Position the marker bar over the Bus 5 record; press Enter to

    access the Harmonic Filter Data window shown below.

  • 7/27/2019 Power Qualkity Analysis

    127/144

    34

    Press F6: Filter or Capacitor to access the interactive filter

    design screen, and edit the capacitor data to match the single-

    tuned filter data shown below.

  • 7/27/2019 Power Qualkity Analysis

    128/144

    35

    The capacitor is now tuned into a 5th harmonic order single-

    tuned filter.

    Press F6: Calculate Filter or Capacitor & Return Data,

    and HI_WAVE will return to the Harmonic Filter Data

    window, automatically inserting the calculated positive and

    zero sequence filter data into the bus record, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    129/144

    36

    Press F1: Save to save the data and return to the list of bus

    records. The filters are now completed, and the harmonic

    studies may be re-executed and the results compared to the

    previous studies.

    Press F10: Exit to return to the HI_WAVE main menu.

  • 7/27/2019 Power Qualkity Analysis

    130/144

    37

    E2. Comparing Results........

    Re-execute HI_WAVE Studies

    Now that the filters have been designed and applied

    to the system, the harmonic studies must be re-

    executed to determine how the changes have affected

    the system resonance and distortion. Refer to

    Sections D1 through D4 to execute the harmonic

    studies and review the study results.

    Since the aim is to compare the new study results with the old

    ones, make certain that different report names are used for the

    new studies so that the original reports are not overwritten.

    In this project provided, the suffix _FLT has been

    added to the report names, indicating that FiLTers

    have been applied. Thus the original frequencyscan report name SCAN becomes SCAN_FLT in

    the new case, and so on for the other studies.

  • 7/27/2019 Power Qualkity Analysis

    131/144

    38

    Compare Old and New Graphical OutputResults

    When the HI_WAVE studies have been re-executed on

    the new case and the report results reviewed, graphical

    results may be compared by combining output from

    both cases on a single graph.

    From the HI_WAVE Main Menu, select F4:

    Graphics Output, and the Graphing Utility

    Window shown below will appear.

  • 7/27/2019 Power Qualkity Analysis

    132/144

    39

    Compare the Frequency Scan Plots at Bus 4

    From the Graphing Utility window, select F1: Frequency

    Scan Drawings. A list of scan files will appear on the right

    of the screen. Position the marker bar over the SCAN_FLT

    file, and press Enter.

  • 7/27/2019 Power Qualkity Analysis

    133/144

    40

    From the list of buses that appears in the right-hand window,

    select Bus 4 by positioning the marker bar over the bus name

    and pressing F1: Select Data.

    Ensure that H Order V Z appears in the Plot Data Choices

    data field, and press F2: Plot Selected. The drawing

    illustrated below will appear.

  • 7/27/2019 Power Qualkity Analysis

    134/144

    41

    To compare these new results with the previous results,

    combine the old and new frequency scan drawings on a single

    graph by first pressing F5: Add New File.

    HI_WAVE recalls the list of available frequency scan files.

    Position the marker bar over the SCAN file and press Enter.

    Ensuring that the Plot Data Choices field reads H Order V Z,

    position the marker bar over Bus 4. Press F1: Select Data to

    select the bus, and F2: Plot Selected to create the drawing.

    HI_WAVE automatically combines the drawings, as shown

    below. Notice that the Plot Legend shown on the graph is

    also updated to include both buses and both file names.

  • 7/27/2019 Power Qualkity Analysis

    135/144

    42

    Notice that the large resonance peak at the sixth harmonic

    order has been reduced from 69.29 ohms in the SCAN

    report to less than 10 ohms in the SCAN_FLT report.

    The 70 ohm peak in the SCAN_FLT curve at the 20th

    harmonic order is not significant because the 20th harmonic

    order is too high to cause serious distortion, and because the

    SKM Six Pulse does not generate 20th order harmonics.

  • 7/27/2019 Power Qualkity Analysis

    136/144

    43

    Press F10: Exit/Save to return to the HI_WAVE Graphing

    Utility Window.

    Compare the Current Distortion Plots at

    Branches 2-3 and 3-4

    Select F3: Current Distortion from the Graphing Utility

    Window. From the list of distortion report files, select

    the DIST_FLT file and, using the same method

    outlined above, produce a drawing of the current

    distortion in Branches 2-3 and 3-4 as shown below.

  • 7/27/2019 Power Qualkity Analysis

    137/144

    44

    Ensure that the Plot Data Choices choice field

    reads Wave form in PU.

    For clarity in comparison, and since nearly all distortion

    in Branch 2-3 has been eliminated, only Branch 3-4

    results will be compared to the original.

  • 7/27/2019 Power Qualkity Analysis

    138/144

    45

    De-select Branch 2-3 by positioning the marker bar over the

    branch name and pressing F1: Select Plot; the arrow

    indicators will disappear indicating that Branch 2-3 has been

    de-selected. Press F2: Plot Selected, and the graph will be

    updated to exclude that branch.

    Using the same procedure outlined above, create a

    current distortion graph for Branch 3-4 from the original

    distortion calculation report (DIST), and combine the two

    drawings. The results are illustrated below.

    Using the same procedure outlined above, create a current

    distortion graph for Branch 3-4 from the original distortion

    calculation report (DIST), and combine the two drawings.

    The results are illustrated below.

  • 7/27/2019 Power Qualkity Analysis

    139/144

    46

    The current distortion has been reduced from 50.47% to

    3.26%. After reviewing the results, press F10: Exit/Save to

    return to the Graphing Utility window.

  • 7/27/2019 Power Qualkity Analysis

    140/144

    47

    Compare the Voltage Distortion Plots

    at Bus 3

    From the Graphing Utility window select F2:

    Voltage Distortion. From the list of distortion

    files, select DIST_FLT. Using the method

    outlined above, create a voltage distortion graph

    for Bus 3, as shown below.

  • 7/27/2019 Power Qualkity Analysis

    141/144

    48

    Ensure that the Plot Data choice field reads Wave form

    in PU. Combine the voltage distortion graph for Bus 3

    from the original distortion calculation report (DIST),

    and the new distortion calculation report (DIST_FLT).

    The results are illustrated below.

  • 7/27/2019 Power Qualkity Analysis

    142/144

    49

    As indicated above, the voltage distortion has been

    reduced from 9.03% in the DIST report to 2.01% in

    the DIST_FLT report.

  • 7/27/2019 Power Qualkity Analysis

    143/144

    50

    You have now completed this HI_WAVE project. Over the

    course of executing the tutorial, you have seen the effects of

    capacitor bank implementation on the level of harmonic

    distortion in the power system.

    Using the filter design and implementation techniques

    outlined, you have significantly mitigated the harmful effects

    of sinusoidal distortion. If so desired, you may continue to

    use the completed project as a sample case on which to test

    different scenarios or apply different harmonic sources and

    filters.

  • 7/27/2019 Power Qualkity Analysis

    144/144

    Have a nice day!