Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

Partial Stroke

Testing

Copyright © Yokogawa System Center Europe2010

• PST in a safety related system.

As a supplier we have a responsibility to our clients.

What do they want,

and what do they really need?

I like to explain the concept based on a simple example:

HIPPS

Partial Stroke Testing

Copyright © Yokogawa System Center Europe2010

HIPPS

L O G IC S O L V E R

SH U T O F F V A L V E S

M A N IF O L D

&

T R A N S M IT T E R S

• What is a HIPPS?

A HIPPS is a protection device.

It acts like a fuse;

if the current is too high, the fuse blows.

If the pressure is too high;

the valves close.

The system behind is safe!

HIPPS stands for High Integrity Pressure Protection System

Copyright © Yokogawa System Center Europe2010

A HIPPS is that something NEW?

HIPPS are used for more than 30 years.

And HIPPS are still used, all around the world.

In all kind of applications.

Copyright © Yokogawa System Center Europe2010

Why a HIPPS?

A HIPPS is, or can be a protection against…

�Human casualties

�Environmental damage

�Damage to your Investments

�Penalties due to emissions (no flaring policy)

�Too high investments….?

Copyright © Yokogawa System Center Europe2010

When Availability & Integrity Really Count

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

SAFETY

Copyright © Yokogawa System Center Europe2010

process risk

Residual

risk level

Risk inherent

in process

Tolerable

risk level

Risk reduction

Risk

Other ExternalSIS

Process

Copyright © Yokogawa System Center Europe2010

risk graph

� Extent of damage (S)� S1: Minor injury/damage

� S2: Serious injury, death of one person

� S3: Death to several persons

� S4: Catastrophic consequences

� Frequency of exposure (A)� A1: Seldom

� A2: Quite often to permanent

� Avoiding of hazard (G)� G1: Possible

� G2: Almost impossible

� Probability of event (W)� W1: High

� W2: Low

� W3: Very low

4 4

1

1

2

2

3

3

-

-

w3

S1

S2

S3

S4

A2

A2

A1

A1

G1

G1

G2

G2

1

1

2

2

3

3

-

w2

4

1

1

2

2

3

3

w1

Copyright © Yokogawa System Center Europe2010

requirements safety instrumented system

�From the risk graph a Target SIL for the SIS will result

�The target SIL indicates the maximum average Probability of failure on demand (PFD) the safety system may have

≥ 10-5 to < 10-4

≥ 10-4 to < 10-3

≥ 10-3 to < 10-2

≥ 10-2 to < 10-1

Average Probability offailure on demand

4

3

2

1

SafetyIntegrity

Level

0

SafetyAvailability

99.9 - 99.99%

99 - 99.9%

90 - 99%

> 99.99%

Risk ReductionFactor

1 000 - 10 000

100 - 1 000

10 - 100

> 10 000

(Control NA)

Copyright © Yokogawa System Center Europe2010

Industrial standards for safety

� IEC 61508 � Functional safety of electrical/electronic/programmable

electronic safety-related systems (E/E/PE)

� Can be applied to all electro-mechanical systems across a wide range of industries.

� IEC 61511� Functional safety / Safety Instrumented Systems for the

process industry

� Targeted at end users implementing SIS for the process industry, it has with more emphases towards

PROVEN IN USE

Copyright © Yokogawa System Center Europe2010

Fault tolerance

Copyright © Yokogawa System Center Europe2010

three most significant aspects of IEC 61508

��The Safety LifecycleThe Safety Lifecycle

��The The ““PipePipe--toto--PipePipe”” approachapproach

��The quantitative safety assessmentThe quantitative safety assessment

Copyright © Yokogawa System Center Europe2010

Required SIL

Time

1

SIL

2

3

PFD

10-1

10-2

10-3

10-4

10-5

Periodic proof test interval

T0 T1 T2 T3 T4

Copyright © Yokogawa System Center Europe2010

Safety Instrumented System

OOProtection logic

Process pipe

Sensors

Process pipe

Final elements

Safetyvalve

Logic solver

OutputInput

Transmitter

A

D

A

D

Pipe to pipe

AirVent.

Copyright © Yokogawa System Center Europe2010

Quantitative Assessment

�Total Loop

The safety requirements concern (as a minimum) a complete safety loop and are expressed in Safety Integrity Levels (SIL).

�PFD

The SIL levels correspond to the average Probability of failure on demand (PFD target) of a complete safety loop.

�Quantification

Calculations need to be performed to show that a specific safety loop meets its required SIL level.

Copyright © Yokogawa System Center Europe2010

Probabilities / Safety Integrity Level

Safety Interlocks

Safety InterlocksTR

TR

TRTR

TRTR

Safety valve

Air

Vent

Pfd loop =

Pfd sensors + Pfd logic solver + Pfd final elements

SIL = Pfd target

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

HIPPS Functionality

Copyright © Yokogawa System Center Europe2010

Process parameter range

Process value

Trip level

Mechanical safety level

High level

High alarm level

Low level

Time

Normal Condition

Alarm Condition

Unsafe Condition

Operator takes action

ESD action

Boom?

Control

Safety

Copyright © Yokogawa System Center Europe2010

What is a HIPPS

�HIPPS, the last line of defenseHIPPS

ESD

PSD

DCS

4-20 mA

4-20 mA Prog.

Tripamp

AI-917

Prog.

Tripamp

AI-917

4-20 mA

Input

DI-511

8-channel

Inputs for:

Reset, valve test

Proximity switches,

other

2oo3

4 * 5 W Solenoid driver

Prog.

Tripamp

AI-917

Prog.

Tripamp

AI-917

Alarm

Logic

2oo3 manifold

HIPPS valve HIPPS valve

HIPPS

solenoid

local reset

HIPPS

solenoid

local reset

HIPPS

solenoid

local reset

HIPPS

solenoid

local reset

P

T

P

T

P

T

Communication to PLC/DCS/SCADA

Modbus

Prog.

Tripamp

AI-917Analog value discrepancy

HIPPS

Logic

Solenoid

Driver

Output

FO-529

ProSafe COM / Sequent of event / Alarm handling

Status information / Analogue values

Modbus RS-232, RS-485

DO-523

Lamp

driver

MC-562

AI repeat

Flow direction

Local SOE

recorder

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

Pressure Transmitter

Copyright © Yokogawa System Center Europe2010

TÜV SIL 2 Approved

Copyright © Yokogawa System Center Europe2010

Measuring

�Transmitters; certified for use in a SIL 2 loop…

�3 transmitters meeting SIL 3 … SIL 4

voting 2oo3 or 1oo2.

�What is the influence of a common fault...

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

MANIFOLD

Copyright © Yokogawa System Center Europe2010

Triple Manifold

Copyright © Yokogawa System Center Europe2010

Locking Manifolds

�Key controlled procedures in single manifolds.

� Double block and bleed

� Mechanical interlock

� Detection

� SIL approval

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

LOGIC SOLVER

Copyright © Yokogawa System Center Europe2010

MagLog 3

1960

Innovation and Continuity

MagLog 14

1970MagLog 24

1990ProSafe-SLS

1997

A PROVEN CONCEPT

COMFORTABLE IN SAFETY

Copyright © Yokogawa System Center Europe2010

Magnetic CoreMagnetic Core

Anticlockwise magnetisation Clockwise magnetisation

B B

H H

Rectangular Hysteresis loop Flat Hysteresis loop

Magnetic particle orientation

Copyright © Yokogawa System Center Europe2010

& Z

Y

X

“Write”

“Read”

output

““ANDAND”” FunctionFunction

Copyright © Yokogawa System Center Europe2010

AND functionAND function

X

Z

Y

+20V0A

B-pulse(Clock)

+20V0

A

A-pulse(Clock)

B+20V0

A

B

& Z

Y

XLogical 0

Logical 1

A

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

HIPPS Valves

Copyright © Yokogawa System Center Europe2010

Control of the Valves

�Solenoids

�Actuator

�Valve

Copyright © Yokogawa System Center Europe2010

Copyright © Yokogawa System Center Europe2010

HIPPS Valves

�Testing of a Valve

�Partial stroke testing

What are we testing?

What do we claim?

Is that safe?

Please note that Partial Stroke test can never replace

a full stroke test!!!

�Full stroke test

Copyright © Yokogawa System Center Europe2010

HIPPS Philosophy

Isolate the source of the problem rather than releasing to

the atmosphere.

To do so;

High reliable equipment is required!

A failure in your HIPPS will result in

damage of equipment or endanger the

safety of personnel.

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

CERTIFICATION

Copyright © Yokogawa System Center Europe2010

Wherever you need safety expertise,Wherever you need safety expertise,

whether in bid phase, whether in bid phase,

early project involvement, early project involvement,

or in project execution or in project execution ……

contact acontact a

Safety Assurance & ConsultancySafety Assurance & Consultancy

safety consultancy

Copyright © Yokogawa System Center Europe2010

A.F.M. Prins

Conclusion

Copyright © Yokogawa System Center Europe2010

Conclusion on PST

Copyright © Yokogawa System Center Europe2010

Conclusion

In general you can say:

A well designed HIPPS,

not only saves money but

“makes the world

a little safer after all”.

Copyright © Yokogawa System Center Europe2010

Thank you for your attention.