  • Packaged Rooftop Air ConditionersPrecedent™ — Cooling and Gas/Electric3 – 10Tons — 60 Hz

    May 2012 RT-PRC023-EN

    Product Catalog

  • © 2012Trane All rights reserved RT-PRC023-EN

    Introduction

    Packaged Rooftop Air Conditioners

    Trane customers demand products that provide exceptional reliability, meet stringent performancerequirements, and are competitively priced.Trane delivers with Precedent™.

    Precedent features cutting edge technologies: reliable compressors, Trane engineered ReliaTelcontrols, computer-aided run testing, and Integrated Comfort™ Systems. So, whether you’re thecontractor, the engineer, or the owner you can be certain Precedent products are built to meet yourneeds.

    Through the years, Trane has designed and developed the most complete line of Packaged Rooftopproducts available in the market today. Trane was the first to introduce the Micro—microelectronicunit controls—and has continued to improve and revolutionize this design concept.

    Electromechanical controls are available for simpler applications, and for the more sophisticated,ReliaTel™ microprocessor controls.

    The ReliaTel control platform offers the same great features and functionality as the original Micro,with additional benefits for greater application flexibility.

    With its sleek, compact cabinet, Precedent continues to provide the highest standards in qualityand reliability, comfort, ease of service, and the performance of Trane light commercial products.

    TrademarksCompleteCoat, Frostat, Integrated Comfort Systems, Precedent, ReliaTel,Tracer,Tracker,Trane andtheTrane logo are trademarks ofTrane in the United States and other countries. BACnet is aregistered trademark. All trademarks referenced in this document are the trademarks of theirrespective owners.

    Figure 1. Packaged Cooling Figure 2. Packaged Gas/Electric

  • Table of Contents

    RT-PRC023-EN 3

    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    Packaged Rooftop Air Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Other Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Air Delivery Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Dehumidification Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Model Number Description - 3-10 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Model Number Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    Direct Drive - Evaporator Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

    Evaporator Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

    Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182

    Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193ReliaTel™ Controlled Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193

    Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196

    Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208

    Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

    Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225

    Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232

  • Features and Benefits

    Standard Features• 5-year Limited Compressor Warranty

    • 5-year Limited Heat Exchanger Warranty

    • 1-year Limited Parts Warranty

    • Anti-Short CycleTimer (Standard with ReliaTel™)

    • Colored and Numbered Wiring

    • Convertible Airflow

    • Crankcase Heaters1

    • Direct Drive Plenum Fan2

    • Easy Access Low VoltageTerminal Board (LTB)

    • Electromechanical or ReliaTel Microprocessor Controls

    • Filters are Standard on all Units

    • Foil-Faced and Edge Captured Insulation

    • High Pressure Control

    • IAQ Dual Sloped and Removable Drain Pans

    • Liquid Line Refrigerant Drier

    • Low Ambient Cooling to 0°F on Microprocessor Models

    • Low Ambient Cooling to 40°F on Electromechanical Models

    • Low Pressure Control

    • Microchannel Coils3

    • Multispeed Direct Drive Motors

    • Operating Charge of R-410A

    • Patent-Pending Hybrid Condenser Coil for easy cleaning

    • Phase Loss Protection

    • Phase Monitor

    • Phase Reversal Protection

    • Phase Balance Protection

    • ProgressiveTubular Aluminized Steel Heat Exchanger

    • Provisions forThrough-the-Base Gas and Condensate Drain Connections

    • Quick Access Panels

    • Quick Adjust Fan Motor Mounting Plate

    • Single Point Power

    • Single Side Service

    • Standardized Components

    • Thermal Expansion Valve

    • Trane built Scroll Compressors

    1 Crankcase heaters are optional on: (T,Y)SC(036,048,060)E, (T,Y)SC(072,090,092,102,120)F2 Standard on: (T,Y)SC120F, (T,Y)HC092E,F, (T/,Y)HC102,120E3 The microchannel type condenser coil is standard for T/YSC(072,090,092,102,120)F and T/YHC (048,060,072,092)F models. The micro-

    channel type condenser coil is not offered on the T/YHC(048,060,092)F dehumidification model.

    4 RT-PRC023-EN

  • Features and Benefits

    Options1

    Factory Installed Options

    • Belt Drive Motors2 (Three-phase)

    • Black Epoxy Pre-Coated Coils3

    • CompleteCoat™ Condenser Coil

    • Crankcase Heaters

    • Dehumidification Option

    • Hinged Access Doors

    • Novar Return Air Sensor

    • Novar Unit Controls

    • Powered or Unpowered Convenience Outlet

    • Single Zone Variable Air Volume (SZVAV)

    • Stainless Steel Heat Exchanger with 10-year warranty

    • Supply and/or Return Air Smoke Detector

    • Through the Base Electrical Access

    • Multi-Speed Indoor Fan System

    • Through the Base Electrical with Circuit Breaker

    • Through the Base Electrical with Disconnect Switch

    • 2” MERV 7 Filters or 2” MERV 13 Filters

    Factory or Field Installed Options

    • Barometric Relief

    • Clogged Filter/Fan Failure Switch

    • Discharge Air Sensing Kit

    • Economizer

    • Electric Heaters

    • Frostat™

    • LonTalk® Communications Interface (LCI)

    • BACnet™ Communications Interface (BCI)

    • Reference or Comparative Enthalpy

    • Tool-less Hail Guards

    • Trane Communications Interface (TCI)

    Field Installed Options

    • CO2 Sensor

    • DualThermistor Remote Zone Sensor

    • High Altitude Kit

    • High Static Drive

    1 Refer to Model Number Description for option availability.2 Option on 3-5 Ton High Efficiency Units3 Not available on Microchannel coils.

    RT-PRC023-EN 5

  • Features and Benefits

    • Humidity Sensor/Humidistat

    • LP Conversion Kit

    • Manual Outside Air Damper

    • Motorized Outside Air Dampers

    • Powered Exhaust

    • Quick Adapt Curbs

    • Quick Start Kit

    • Remote Potentiometer

    • Roof Curb

    • Thermostat

    • Ventilation Override Accessory

    • Wireless Zone Sensor

    • Zone Sensor

    Other Benefits• Cabinet design ensures water integrity

    • Ease of Service, Installation and Maintenance

    • Mixed model build enables “fastest in the industry” ship cycle times

    • Outstanding Airflow Distribution

    • ReliaTel Controls

    • Unmatched Product Support is one of our finest assets. Trane Sales Representatives are aSupport Group that can assist you with:

    • Product

    • Application

    • Service

    • Training

    • Special Applications

    • Specifications

    • Computer Programs and much more

    Standard FeaturesAnti-Short CycleTimer (Standard with ReliaTel)Provides a 3 minute minimum “ON” time and 3 minute “OFF” time for compressors to enhancecompressor reliability by assuring proper oil return.

    Direct Drive MotorsFor additional static requirements, single-phase units offer multi-speed, direct drive motors. All 10ton units and 7½-8½ high efficiency units offer variable speed direct drive motors.

    Colored And Numbered WiringSave time and money tracing wires and diagnosing the unit.

    6 RT-PRC023-EN

  • Features and Benefits

    Controls – ReliaTel or ElectromechanicalReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizinginput from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTelalso provides outputs for building automation systems and expanded diagnostics. For a completelist of ReliaTel offerings, refer to the “Other Benefits” section within the Features and Benefitssection of this catalog.

    For the simpler job that does not require a building automation system, or expanded diagnosticscapabilities, Precedent offers electromechanical controls.This 24-volt control includes the controltransformer and contactor pressure lugs for power wiring.

    CoolingStandard or High Efficiency cooling available.

    Compressors Condenser CoilPrecedent contains thebest compressortechnology available toachieve the highestpossible performance.Dual compressors areoutstanding for humiditycontrol, light load coolingconditions and systemback-upapplications.Dual

    compressors are available on 7½ to 10 tonmodels and allow for efficient cooling utilizing3-stages of compressor operation (highefficiency models only).

    Precedent boasts a patent-pending 1+1+1condenser coil, permanently gapped for easycleaning.

    Microchannel Condenser CoilsDue to flat streamlined tubes with small ports, andmetallurgical tube-to-fin bond, microchannel coil hasbetter heat transfer performance. Microchannelcondenser coil can reduce system refrigerant charge byup to 50% because of smaller internal volume, whichleads to better compressor reliability. Compact all-aluminum microchannel coils also help to reduce the unitweight.These all aluminum coils are recyclable. Galvaniccorrosion is also minimized due to all aluminumconstruction. Strong aluminum brazed structureprovides better fin protection. In addition, flatstreamlined tubes also make microchannel coils moredust resistant and easier to clean.

    Convertible UnitsThe units ship in a downflow configuration.They can be easily converted to horizontal bysimply moving two panels.

    Units come complete with horizontal ductflanges so the contractor doesn’t have to fieldfabricate them.These duct flanges are a timeand cost saver.

    RT-PRC023-EN 7

  • Features and Benefits

    Crankcase Heaters1

    These band heaters provide improved compressor reliability by warming the oil to preventmigration during off-cycles or low ambient conditions.

    Heat ExchangerThe compact cabinet features a progressive tubular heat exchanger in low, medium and high heatcapacities.

    The heat exchanger is fabricated using stainless steel burners and corrosion-resistant aluminizedsteel tubes as standard on all models. It has an induced draft blower to pull the gas mixture throughthe burner tubes.The heater has a direct spark ignition system which doubles as a safety deviceto prove the flame.

    Gas/Electric Precedent models exceed all California seasonal efficiency requirements.They alsoperform better than required to meet the California NOx emission requirements.

    High Pressure ControlAll units include High Pressure Control as standard.

    Low Ambient CoolingAll Precedent microprocessor units have cooling capabilities down to 0°F as standard.Electromechanical models have cooling capabilities to 40°F as built, or to 0°F by adding the optionallow ambient control (frostat).

    1 Crankcase heaters are optional on: (T,Y)SC(036,048,060)E

    Dual Sloped Drain PansEvery Precedent unit has a non-corrosive, removable, double-sloped drain pan that’s easy to clean and reversible to allowinstallation of drain trap on either side of the unit.

    Easy Access Low VoltageTerminal Board Foil Faced InsulationPrecedent’s Low VoltageTerminal Board is externalto the electrical controlcabinet. It is extremelyeasy to locate and attachthe thermostat wire andtest operation of all unitfunctions.This is anothercost and time savinginstallation feature.

    All panels in theevaporator sectionof the unit havecleanable foil-facedinsulation. All edgesare either capturedor sealed to ensureno insulation fibersget into theairstream.

    Low Voltage ConnectionsThe wiring of the low voltage connections to the unit andthe zone sensors is as simple as 1-1, 2-2, and 3-3.Thissimplified system makes it easy for the installer to wire.

    8 RT-PRC023-EN

  • Features and Benefits

    Phase Monitoring ProtectionPrecedent™ units with 3-phase power are equipped with phase monitoring protection as standard.These devices protect motors and compressors against problems caused by phase loss, phaseimbalance and phase reversal indication.

    Plenum Fan1

    The following units are equipped with a direct drive plenum fan design (all 10 ton units and 7½-8½ ton high efficiency units). Plenum fan design includes a backward-curved fan wheel along withan external rotor direct drive variable speed indoor motor. All plenum fan designs have a variablespeed adjustment potentiometer located in the control box.

    Quick-Access PanelsRemove two screws for access to the standardized internal components and wiring.

    Single Point PowerA single electrical connection powers the unit.

    Single Side ServiceSingle side service is standard on all units.

    Standardized ComponentsComponents are placed in the same location on all Precedent units.

    Due to standardized components throughout the Precedent line, contractors/owners can stockfewer parts.

    Thermal Expansion ValveThis feature is standard on all units.

    Through the Base CondensateEvery unit includes provisions for through the base condensate drain connections.This allows thedrain to be connected through the roof curb instead of a roof penetration.

    Variety of Options

    Factory Installed Options2

    Black Epoxy Pre-Coated Coils3

    The pre-coated coils are an economical option for protection in mildly corrosive environments.

    CompleteCoat™ Condenser CoilThese coils provide excellent corrosion resistance as well as uniformity of coverage and coatingthickness.This option is available for both fin-tube and microchannel condenser coils.

    Novar Unit ControlsNovar 3051 and 2024 are available for Precedent Gas and Electric Heat models.

    1 Standard on: (T,Y)SC120F, (T,Y)HC092E,F, (T/Y)HC102,120E2 Refer to Model Number Description for option availability.

    3 Not available on Microchannel condenser coils.

    RT-PRC023-EN 9

  • Features and Benefits

    Disconnect Switch (Available on units equipped withThrough-the-BaseElectrical)Factory installed 3-pole, molded case, disconnect switch for through-the-base electricalconnections.

    Codes require a method of assured unit shutdown for servicing. Field-installed disconnectssometimes interfere with service access. Factory installation of unit disconnects reduces costs,assures proper mounting and provides the opportunity to upgrade to unit circuit breakerprotection.

    Single Zone VAV – One Zone Variable Air Volume ModeSingle zone VAV is designed for use in single zone applications like gymnasiums, auditoriums,manufacturing facilities, retail box stores, and any large open spaces, where there is a lot ofdiversity in the load profile. Single Zone VAV (SZ VAV) is an ideal replacement to “yesterday’s”constant volume (CV) systems, by reducing operating costs while improving occupant comfort. SZVAV systems combineTrane application, control and system integration knowledge to exactlymatch fan speed with cooling and heating loads, regardless of the operating condition.Tranealgorithms meet/exceed ASHRAE 90.1- 2010 SZ VAV energy-saving recommendations, and those

    of CATitle 24.The result is an optimized balance between zone temperature control and systemenergy savings. Depending on your specific application, energy savings can be as much as 20+%.

    Belt Drive Motors (Three-phase)For additional static requirements, Precedent3-5 ton units offer an optional belt drive motorto meet a wide range of airflow needs.

    Dehumidification (Hot Gas Reheat) OptionThis option allows for increased outdoorair ventilation. It reduces humidity levelswhile increasing comfort level in the airspace. Cooling can operate without ademand for dehumidification.The hot gasreheat coil is designed to deliver maximumreheat temperatures and pivot to allow foreasy access cleaning.

    Circuit Breaker (Available on unitsequipped withThrough-the-BaseElectrical)

    Hinged Access Doors

    This option is afactory installedthermal magnetic,molded case, HACRCircuit Breaker withprovisions forthrough the baseelectricalconnections.

    These doors permiteasy access to the filter,fan/heat andcompressor/controlsections.They reducethe potential roofdamage from screws orsharp access doorcorners.

    10 RT-PRC023-EN

  • Features and Benefits

    Note: Building system modeling in energy simulation software likeTRACE is recommended toevaluate performance improvements for your application.

    SZVAV is fully integrated into the ReliaTel™ control system and is available today. It provides thesimplest and fastest commissioning in the industry through proven factory-installed, wired, andtested system controllers. All control modules, logic and sensors are factory installed, and testedto assure the highest quality and most reliable system available.This means no specialprogramming of algorithms, or hunting at the jobsite for sensors, boards, etc. that need to beinstalled in the field. Single zone VAV is a quick and simple solution for many applications and isavailable from your most trusted rooftop VAV system solution provider -Trane.

    Multi-Speed Indoor Fan SystemMulti-speed indoor fan system is designed for use in applications for meeting the minimumrequirement of CATitle 24.

    This system incorporates a multi-speed fan control to change the speed of the fan to 67% of fullairflow based off of compressor stages.

    Stainless Steel Heat ExchangerThe optional stainless steel heat exchanger is constructed of 409 stainless steel. It is resistant tocorrosion and oxidation and easy to clean.The high strength to weight ratio allows for highventilation rates with gas units. It is an excellent option to compliment the dehumidification optionas a high outside air ventilation unit. With this option, a 10-year stainless steel heat exchangerwarranty is standard.

    Supply and/or Return AirSmoke Detector

    Through-the-Base Electrical Utility Access

    With this option installed, ifsmoke is detected, all unitoperation will be shut down.Reset will be manual at the unit.Return Air Smoke Detectorsrequire minimum allowableairflow when used with certainmodels.

    An electrical serviceentrance shall be providedallowing electrical accessfor both control and mainpower connections insidethe curb and through thebase of the unit. Option willallow for field installation ofliquid-tight conduit and anexternal field installeddisconnect switch.

    Factory provided through thebase openings simplify wiringand piping. Because theseutility openings frequentlyminimize the number of roofpenetrations, the integrity ofroofing materials is enhanced.

    Powered or Unpowered ConvenienceOutlet

    This option is a GFCI, 120V/15amp, 2 plug,convenience outlet, either powered orunpowered.This option can only be orderedwhenThrough the Base Electrical with either theDisconnect Switch or Circuit Breaker option isordered.Note: Not available on 10 Ton 575V units.Note: Not available on 3-5 Ton High Efficiency units with Direct

    Drive Indoor Motor.

    RT-PRC023-EN 11

  • Features and Benefits

    Factory or Field Installed Options1

    Barometric ReliefDesigned to be used on downflow units, barometric relief is an unpowered means of relievingexcess building pressure.

    Clogged Filter/Fan Failure SwitchA dedicated differential pressure switch is available to achieve active fan failure indication and/orclogged filter indication.

    These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirtyfilter or a fan that’s not working.The field installation charges for these valuable feedback devicesoften eliminate them from consideration. Factory installation can make such features a goodinvestment.

    Discharge Air Sensing KitProvides true discharge air sensing in heating models.The kit is functional only with the ReliaTelOptions Module.

    Electric HeatersElectric heat modules are available within the basic unit. If ordering theThrough the Base Electricaloption with an Electrical Heater, the heater must be factory installed.

    Fresh Air Options – Dampers and Economizer0 - 25% manual or 0 - 50% motorized outside air hoods are available.

    Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing.These economizers provide free cooling as the outdoor temperature and/or humidity decreases.Correctly installed, they offer a valuable energy savings. Factory-installed economizers save timeand ensure proper installation.

    The economizers come with three control options — dry bulb is standard, enthalpy and differentialenthalpy are optional.

    FrostatThis capillary bulb embedded in the face of the evaporator coil monitors coil temperature toprevent evaporator icing and protect the compressor. Recommended for applications with lowleaving air temperatures, low airflow and or high latent load applications.

    LonTalk® Communications InterfaceThe LonTalk communications interface allows the unit to communicate as aTracer™ LCI-V deviceor directly with the generic LonTalk Network Building Automation System Controls.

    BACnet™ Communications InterfaceThe BACnet communications interface allows the unit to communicate directly with a generic openprotocol BACnet MS/TP Network Building Automation System Controls.

    Reference or Comparative EnthalpyMeasures and communicates humidity while maximizing comfort control.

    Trane Communication Interface (TCI)Available factory or field installed.This module when applied with the ReliaTel™ easily interfaceswithTrane’s Integrated Comfort™ System.

    1 Refer to Model Number Description for option availability.

    12 RT-PRC023-EN

  • Features and Benefits

    Field Installed Options1

    CO2 Sensor - Demand Control Ventilation (DCV)Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand(need) for ventilation by regulating the rate at which the HVAC system brings outdoor air into thebuilding. A CO2 sensor measures the concentration (parts per million, ppm) of CO2 (CarbonDioxide) in the air. As the CO2 concentration changes, the outside air damper modulates to meetthe current ventilation needs of the zone.The CO2 sensor kit is available as a field installedaccessory.

    High Altitude KitPreviously a Canadian Agency requirement for units applied above 2000 feet, it is not required bythe U.S. Domestic contractors should consult with local authority on best practice. Derates gasorifices by 10%.

    High Static DriveAvailable on many models, this high static drive accessory extends the capability of the standardmotor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

    Humidity Sensor/HumidistatThe humidity sensor/humidistat, when used in conjunction with our Dehumidification (Hot GasReheat) units will provide outstanding humidity control and comfort. Humidity sensors can be wallor duct mounted.The humidity deadband can be set between 40% and 60% relative humidity.

    LP Conversion KitProvided for field conversion of gas/electric units from Natural gas to Propane.

    Quick Adapt CurbsEnables easy conversion of existingVoyager 3-10 ton units to Precedent units on replacement jobs.

    Quick Start KitsSingle phase equipment to enable startup and prevent building lighting dimming during lowvoltage.

    Roof CurbsAvailable for downflow units. Only three roof curbs for the entire line simplifies curb selection.

    Remote PotentiometerWhen properly installed in the economizer control circuitry, this accessory provides a remotevariable resistance to enable the operator to adjust the minimum damper position.

    Tool-less Hail GuardsTool-less, hail protection quality coil guards shall be eitherfactory or field-installed for condenser coil protection.Thisoption protects the condenser coil from vandalism and/or haildamage.

    1 Refer to Model Number Description for option availability.

    RT-PRC023-EN 13

  • Features and Benefits

    Ventilation Override AccessoryWith theVentilation OverrideAccessory installed, the unit can be set to transition to up to 3 differentpre-programmed sequences for Smoke Purge, Pressurization, and Exhaust.The transition occurswhen a binary input on the RTOM is closed (shorted).This would typically be a hard wired relayoutput from a smoke detector or fire control panel.The ventilation override kit is available as a fieldinstalled accessory.

    Zone Sensors/ThermostatsAvailable in programmable, automatic and manual styles.

    Other BenefitsEasy to Install, Service and MaintainBecause today’s owners are very cost-conscious when it comes to service and maintenance, thePrecedent was designed with direct input from service contractors.This valuable informationhelped to design a product that would get the service person off the job quicker and save the ownermoney. Precedent offers outstanding standard features enhanced by a variety of factory and fieldinstalled options, multiple control options, rigorously tested proven designs and superior productand technical support.

    Airflow DistributionAirflow is outstanding. Precedent can replace an older machine with old ductwork and, in manycases, improve the comfort through better air distribution.

    FlexibilityPrecedent offers ultimate flexibility. Units are built to order in our standard “shortest in theindustry” ship cycle time.

    Cabinet IntegrityFor added water integrity, Precedent has a raised 1 1/8”lip around the supply and return of the downflow unitsto prevent water from blowing into the ductwork.

    ReliaTel™ ControlsReliaTel controls provide unit control for heating, cooling andventilating utilizing input from sensors that measure outdoorand indoor temperature.

    ReliaTel Control Logic Enhances Quality and Reliability

    – prevents the unit from short cycling, considerablyimproving compressor life.

    – ensures that the compressor will run for a specificamount of time which allows oil to return for betterlubrication, enhancing the reliability of thecompressor.

    Precedent units with ReliaTel reduces the number ofcomponents required to operate the unit, thereby reducingpossibilities for component failure.

    14 RT-PRC023-EN

  • Features and Benefits

    ReliaTel Makes Installing and Servicing Easy

    ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTelcontrols provide these functions as an integral part of the unit.The contractor no longer has topurchase these controls as options and pay to install them.

    The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2,and 3-3.This simplified system makes wiring easier for the installer.

    ReliaTel MakesTesting Easy

    ReliaTel requires no special tools to run the Precedent unit through its paces. Simply place a jumperbetweenTest 1 andTest 2 terminals on the Low VoltageTerminal Board and the unit will walkthrough its operational steps automatically.

    The unit automatically returns control to the zone sensor after stepping through the test mode asingle time, even if the jumper is left on the unit.

    As long as the unit has power and the “system on” LED is lit, ReliaTel is operational.The lightindicates that the controls are functioning properly.

    ReliaTel features expanded diagnostic capabilities when utilized withTrane Integrated Comfort™Systems.

    Some zone sensor options have central control panel lights which indicate the mode the unit is inand possible diagnostic information (dirty filters for example).

    Other ReliaTel Benefits

    The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time controlfunctions are factory tested to assure proper operation.

    ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.

    Intelligent Fallback is a benefit to the building occupant. If a component fails, the unit will continueto operate at predetermined temperature setpoint.

    IntelligentAnticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zonesensor(s) work together in harmony to provide much tighter comfort control than conventionalelectro-mechanical thermostats.

    The same ReliaTel Board fits all Packaged Gas/Electric and Cooling with Electric Heat models.Thisprovides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.

    Unit CabinetThe compact cabinet with rounded corners takes up less room.The beveled and ribbed topaesthetically pleasing and designed to prevent water from pooling.

    RigorousTestingAll of Precedent’s designs were rigorously rain tested at the factory to ensure water integrity.

    VariTrac® – Building Automation SystemWhenTrane’s changeover VAV System forlight commercial applications is coupledwith Precedent, it provides the latest intechnological advances for comfortmanagement systems and can allowthermostat control in every zone served byVariTrac®.

    Note: VariTrac® is not recommended forSZVAV and Multi-Speed Indoor FanApplications.

    RT-PRC023-EN 15

  • Features and Benefits

    Actual shipping tests were performed to determine packaging requirements. Units were testshipped around the country to determine the best packaging design. Factory shake and drop testswere used as part of the package design process to help assure that the unit arrives at the job sitein top condition.

    Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the liftinglugs and rails hold up under stress.

    We perform a 100% coil leak test at the factory.The evaporator and condenser coils are leak testedat 600 psig.The assembled unit is leak tested to 465 psig.

    All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejectedimmediately.

    Every unit receives a 100% unit run test before leaving the production line to make sure it meetsrigorous Trane requirements.

    16 RT-PRC023-EN

  • Application ConsiderationsApplication of this product should be within the cataloged airflow and cooling considerations.

    Barometric ReliefThis product line offers an optional barometric relief damper for use in conjunction witheconomizer option.This accessory consists of gravity dampers which open with increasedpressure. As the building air pressure increases, the pressure in the unit return air section alsoincreases, opening the dampers and relieving the conditioned space.

    Note: The effectiveness of barometric relief damper during economizing operation is systemrelated. Pressure drop of the return air system should be considered to control buildingpressurization.

    Black Epoxy CoilThe coils are manufactured with a thermoset, vinyl coating that is bonded to the aluminum fin stockprior to the fin stamping process.These coils are an economical option for protection in mildlycorrosive environments.

    Note: Not to be used where seacoast applications exist.

    Note: Not available on Microchannel condenser coils.

    Clearance RequirementsThe recommended clearances identified with unit dimensions should be maintained to assureadequate service maximum capacity and peak operating efficiency. Actual clearances whichappear inadequate should be reviewed with the localTrane sales personnel.

    CompleteCoat™ Condenser CoilThe coils provide protection from corrosive environments and are ideal for seacoast applications.

    CondensateTrapThe evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on thecooling cycle.

    Model NumberClearance required from duct to combustible surfaces (inches)

    T(S/H)C036E 0

    T(S/H)C048E 0

    THC048F 0

    T(S/H)C060E 0

    THC060F 0

    TSC072F 0

    THC072F 1

    TSC090F 1

    TSC092F 0

    THC092E 1

    THC092F 1

    TSC102F 0

    THC102E 1

    TSC120F 1

    THC120E 1

    RT-PRC023-EN 17

  • Application Considerations

    Heating OperationThe heat exchanger is manufactured with aluminized steel.To prevent condensation within theheat exchanger, do not exceed 50% outside air or a minimum mixed air temperature of 40°F.

    Low Ambient CoolingThe Precedent™ line features, with ReliaTel™ microprocessor controls, low ambient cooling downto 0°F. With electromechanical controls, Precedent features low ambient cooling to 40°F.Thefollowing features or options need to be included/considered when low ambient applications arerequired: continuous fan operation, crankcase heaters, thermal expansion valves, frostat.

    Contact a local Trane Representative for more assistance with low ambient cooling applications.

    Optional Stainless Steel Heat ExchangerThe optional stainless steel heat exchanger is manufactured with 409 stainless steel.To preventcorrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowedacross the heat exchanger is 20°F.

    The stainless steel heat exchanger option is an excellent option that compliments thedehumidification package. Whenever high outside air or outside applications exist, these optionsshould be utilized.

    Single Zone Variable Air Volume (SZVAV)Not to be utilized with change-over bypass VAV system. Not to be utilized with VariTrac® systems.

    Unit PitchThese units have reversible sloped condensate drain pans. Units must be installed level. Any unitslope must be toward the side of unit where condensate drain is connected.

    18 RT-PRC023-EN

  • Selection Procedure

    Cooling CapacityNote: Cooling Capacity Procedure is the same for electric heat (T*C) and gas heat (Y*C).

    Step 1.

    Calculate the building’s total and sensible cooling loads at design conditions. Use the Tranecalculation methods or any other standard accepted method.

    Factors used in unit selection:• Packaged Cooling with Optional Electric Heat• Total Cooling Load: 59 MBh• Sensible Cooling Load: 40 MBh• Airflow: 2000 cfm• Electrical Characteristics: 460/60/3• Summer Design Conditions: Entering Evaporator Coil: 80 DB• 67 WB Outdoor Ambient: 95• External Static Pressure: 0.36 in. wg• Downflow Configuration• Efficiency: 13 SEER• Economizer

    Step 2.As a starting point, a rough determination must be made of the size of the unit.The final selectionwill be made after examining the performance at the given conditions. Divide the total cooling loadby nominal Btuh per ton (12 MBh per ton); then round up to the nearest unit size.

    59 MBh / 12 MBh = approx. 5 tons

    Step 3.

    Table 13, p. 45 shows that aTSC060E4 has a gross cooling capacity of 62.3 MBh and 48.1 MBhsensible capacity at 2000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering theevaporator.

    To Find Capacity at Intermediate Conditions not in the table.

    When the design conditions are between two numbers that are in the capacity table, interpolationis required to approximate the capacity.

    Note: Extrapolation outside of the table conditions is not recommended.

    Step 4.

    In order to select the correct unit which meets the building’s requirements, the fan motor heat mustbe deducted from the gross cooling capacity.The amount of heat that the fan motor generates isdependent on the effort by the motor - cfm and static pressure.To determine the total unit staticpressure:

    Note: The Evaporator Fan Performance Table 36, p. 81 has deducted the pressure drop for a filteralready in the unit (see note below Table 36, p. 81).Therefore, the actual total static pressureis 0.535 -0.049 (from Table 145, p. 186) = 0.486 wg.

    External Static Duct System 0.36 wgStandard Filter 2 in. from Table 145, p. 186 0.049 wgEconomizer from Table 145, p. 186 (100% Outside Air) *worst case

    0.105 wg

    Electric Heater Size 6 kW from Table 145, p. 186 0.021 wg(reference "Heating Capacity" section on this page for determination of heater size)Total Static Pressure 0.535 wg

    RT-PRC023-EN 19

  • Selection Procedure

    With 2000 cfm and 0.5 wg.Table 36, p. 81 shows 0.575 bhp for this unit.

    Note: Below the table is the formula to calculate Fan Motor Heat

    2.87 x bhp + 0.75 = MBh.2.87 x 0.575 + 0.15 = 1.8 MBh.

    Now subtract the fan motor heat from the gross cooling capacity of the unit:

    NetTotal Cooling Capacity= 62.3 MBh - 1.8 = 60.5 MBh.

    Net Sensible Cooling Capacity= 48.1 MBh - 1.8 = 46.3 MBh.

    Subtracting Sensible fromTotal Capacity to find Latent Capacity

    Net Latent Capacity= 60.5 - 46.3 = 14.2 MBh.

    Step 5.

    Compare your resulting capacities to the building load. If the performance will not meet therequired load of the building’s total or sensible cooling load, try a selection at the next higher sizeunit.

    Heating CapacityNote: Heating capacity procedure DIFFERS for electric heat (T*C) and gas heat (Y*C) units

    Step 1.

    Calculate the building heating load using the Trane calculation form or other standard acceptedmethod.

    Step 2.

    Size the system heating capacity to match the calculated building heating load.The following arebuilding heating requirements:Total heating load of 15 MBh2000 cfm

    T*C units with optional electric heat: 460V/3 phase Power Supply

    The electric heat accessory capacities are listed in Table 148, p. 189. From the table, a 6 kW heaterwill deliver 20.48 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltagecorrection factor from Table 150, p. 191 must be used.Therefore, 20.48 MBh x 0.918 (voltagecorrection factor) = 18.8 MBh.

    Y*C units with gas heat: Fuel- natural gas.

    60 MBh, 80 MBh and 130 MBh input models shown in Table 146, p. 187.The output capacities ofthese furnaces are 48 MBh, 64 MBh and 104 MBh respectively.The low heat model with 48 MBhbest matches the building requirements.

    Air Delivery SelectionNote: Air Delivery procedure is the same for electric heat and gas heat units.)

    External static pressure drop through the air distribution system has been calculated to be 0.5inches of water. Enter Table 52, p. 97 for aTSC060E4 at 2000 cfm and 0.5 static pressure.Thestandard direct drive motor will give the desired airflow at a rated bhp of 0.73 and 951 rpm.

    20 RT-PRC023-EN

  • Selection Procedure

    Dehumidification Selection

    Note: Dehumidification selection procedure is the same for both electric heat (THC) and gas heat(YHC) models).

    Typical 5 tonTHC060E

    2000 cfmTotal Supply airflow400 cfm Outside Air (40%)600 cfm Return Air0.34” External Static Pressure

    OA ConditionsPart load day and raining68°F db67°F wb95% RHRA conditions75°F db63°F wb

    Step 1:

    Determine the mixed/entering air condition (MA)

    MA = (% outside air*outside air dry-bulb temperature) + (% return air*return air dry-bulbtemperature)

    MA = (0.40*68°F) + (0.60*75°F)

    MA = 72.20°F db

    Repeat for wet-bulb temperature (wb).

    MA72.2°F db64.6°F wb

    Step 2:

    Determine the additional static pressure drop for a reheat unit

    Table 145, p. 186 shows a static pressure drop of 0.13” for the reheat coil and an additional 0.08 forthe mandatory 2” pleated filters required when ordering the dehumidification option.Total staticpressure =

    .34 + 0.08 + 0.13= 0.55

    Do not forget to also add any additional static from other accessories.This selection does notinclude additional accessories.

    Table 101, p. 146 (airflow table for 5 ton downflow unit) indicates that a standard motor and driveis needed for this airflow and static pressure range.

    Step 3a:

    Determine leaving evaporator temperature (SA’)

    Leaving EvaporatorTemperature = SA’

    Utilizing the manual Cooling Capacity selection method as previously described, find the leavingevaporator temperatures with the formula:

    Temp = gross sensible orgross latent coolingcapacity in Btuh________________(cfm) (1.085)

    RT-PRC023-EN 21

  • Selection Procedure

    Subtract your sensible temp from the entering db and latent temp from the entering wb todetermine the leaving evaporator db & wb (temperatures without the addition of fan heat).

    52.7°F db52.7°F wb52.7°F dp

    Step 3b:

    Determine leaving unit temperature in standard cooling mode

    Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity tofind the leaving unit temperature including fan heat.

    53.7°F db53.1°F wb

    Step 4:

    Determine reheat temperature rise

    Using the leaving evaporator temp (SA’), go to Table 150, p. 191 and determine the reheattemperature rise for that particular cfm: 19.0°F db

    Note: Reheat temperature rise is based on supply airflow and leaving evaporator coiltemperature.

    Step 5:

    Determine leaving unit sensible temperature with reheat active (SA)Reheat temperature (obtained in step 4) + (SA’ + fan heat) = SA

    (SA’ + fan heat) = leaving unit temperature in standard cooling mode from step 3b.

    19.0°F db + 53.7°F = 72.7°F db

    SA=72.7°F

    Since reheat adds only sensible heat, the dewpoint temperature will remain constant so follow thedewpoint temperature line across the psychrometric chart to find the new wb temperature.

    60.5°F wb52.7 dp49.9% RH

    If the space relative humidity is equal to or above the space relative humidity setpoint, theDehumidification option will:

    • Energize compressor or both compressors (2 stage compressor units).

    • Hot gas reheat valve is energized and hot gas is diverted to the reheat coil.

    • Dehumidification/reheat is terminated when space humidity is reduced to 5% below relativehumidity setpoint.

    At MA air enters the RTU.The RTU filters, cools, and dehumidifies the air as it moves through theevaporator coil.Air leaves the evaporator coil saturated at the preset dew point condition (SA’) andis reheated by the hot gas reheat coil to deliver 72.7°F (SA) supply air to the space.

    22 RT-PRC023-EN

  • Model Number Description - 3-10Ton

    Y S C 0 3 6 E 3 R Z B * *

    1 2 3 4 5 6 7 8 9 10 11 12 13

    Digit 1 - UnitTypeT DX CoolingY DX Cooling, Gas Heat

    Digit 2 - EfficiencyS Standard EfficiencyH High Efficiency

    Digit 3 - AirflowC Convertible

    Digit 4,5,6 - Nominal GrossCooling Capacity (MBh)036 3Ton048 4Ton060 5Ton072 6Ton090 7½Ton, Single Compressor092 7½Ton, Dual Compressor102 8½Ton120 10Ton

    Digit 7 - Major Design SequenceE R-410A RefrigerantF MicrochannelType Condenser Coils24

    Digit 8 - Voltage Selection1 208/230/60/13 208-230/60/34 460/60/3W 575/60/3

    Digit 9 - Unit ControlsE ElectromechanicalR ReliaTel™ Microprocessor

    Digit 10 - Heating Capacity

    L Low HeatM Medium HeatH High HeatX Low Heat, Stainless Steel Heat

    ExchangerY Medium Heat, Stainless Steel Heat

    ExchangerZ High Heat, Stainless Steel Heat

    Exchanger

    Digit 11 - Minor Design SequenceA First Sequence21B Second Sequence20

    Digit 12,13 - Service Sequence** Factory Assigned

    0=No Electric Heat F=14 kW (1 phase)1A=5 kW (1 phase)1 G=18 kW (1&3 phase)B=6 kW (3 phase) J=23 kW (3 phase)C=9 kW (3 phase) K= 27 kW (3 phase)D=10 kW (1 phase)1 N = 36 kW (3 phase)E=12 kW (3 phase) P = 54 kW (3 phase)

    RT-PRC023-EN

    Digit 14 - Fresh Air Selection0 No Fresh AirA Manual Outside Air Damper 0-50%4B Motorized Outside Air Damper

    0-50%28C Economizer, Dry Bulb 0-100%

    without Barometric Relief7D Economizer, Dry Bulb 0-100%

    with Barometric Relief7E Economizer, Reference Enthalpy

    0-100% without Barometric Relief3,7F Economizer, Reference Enthalpy

    0-100% with Barometric Relief3,7G Economizer, Comparative

    Enthalpy 0-100% withoutBarometric Relief3,7

    H Economizer, ComparativeEnthalpy 0-100% with BarometricRelief3,7

    Digit 15 - Supply Fan/DriveType/Motor0 Standard Drive61 Oversized Motor2 Optional Belt Drive Motor186 Single Zone VAV267 Multi-Speed Indoor Fan27

    Digit 16 - Hinged Service Access/Filters0 Standard Panels/Standard FiltersA Hinged Access Panels/Standard

    FiltersB Standard Panels/2” MERV 7 FiltersC Hinged Access Panels/2” MERV 7

    FiltersD Standard Panels/2” MERV 13 FiltersE Hinged Access Panels/2” MERV 13

    Filters

    Digit 17 - Condenser CoilProtection0 Standard Coil1 Standard Coil with Hail Guard2 Black Epoxy Pre-Coated Condenser

    Coil253 Black Epoxy Pre-Coated

    Condenser Coil with Hail Guard254 CompleteCoat™ Condenser Coil5 CompleteCoat™ Condenser Coil

    with Hail Guard

    Digit 18 -Through the BaseProvisionsNote: Applicable to Digit 1,T orY models0 NoThrough the Base ProvisionsA Through the Base Electric8

    Note: Applicable to Digit 1,Y modelsonly

    B Through the Base Gas Piping16C Through the Base Electric and Gas

    Piping16

    Digit 19 - Disconnect/CircuitBreaker (three- phase only)0 No Disconnect/No Circuit Breaker1 Unit Mounted Non-Fused

    Disconnect82 Unit Mounted Circuit Breaker8

    Digit 20 - Convenience Outlet0 No Convenience OutletA Unpowered Convenience OutletB Powered Convenience Outlet

    (three-phase only)9

    Digit 21 - CommunicationsOptions3

    0 No Communications Interface1 Trane Communications Interface2 LonTalk® Communications

    Interface3 Novar 2024 Controls304 Novar 3051 Controls without Zone

    Sensor305 Novar 3051Controls Interface with

    DCV306 BACnet™ Communications Interface

    Digit 22 - Refrigeration SystemOption0 Standard Refrigeration System10B Dehumidification Option22,23

    Digit 23 - Refrigeration ControlsNote: Applicable to Digit 7 = E, F0 No Refrigeration Control51 Frostat11,292 Crankcase Heater23 Frostat11,29 and Crankcase Heater2

    Digit 24 - Smoke Detector17

    0 No Smoke DetectorA Return Air Smoke Detector12,13B Supply Air Smoke DetectorC Supply and Return Air Smoke

    Detectors12,13

    Digit 25 - Monitoring Controls0 No Monitoring Control141 Clogged Filter Switch142 Fan Failure Switch143 Discharge Air SensingTube144 Clogged Filter Switch and Fan

    Fail Switch145 Clogged Filter Switch and Discharge

    Air SensingTube146 Fan Fail Switch and Discharge Air

    SensingTube147 Clogged Filter and Fan Fail Switches

    and Discharge Air SensingTube148 Novar Return Air Sensor15,309 Novar 3051 Zone Sensor19,30

    23

  • Model Number Description - 3-10Ton

    Model Number Notes

    1. Available on 3-5 ton models.

    2. Standard on 4-5Ton E3,4,W and6-10Ton Heat Pumps and all HighEfficiency models.

    3. Not available withelectromechanical controls.

    4. Manual outside air damper willship factory supplied within theunit, but must be field installed.

    5. High pressure control is standardon all units.

    6. On 3-5 ton, multispeed direct driveis standard on single phase and 15SEER. On 6-10 ton, multispeeddirect drive is standard on all 10ton and 7.5-8.5 ton high efficiency.Belt drive is standard on all otherunits.

    7. Economizer with BarometricRelief is for downflow configuredunits only. Order Economizerwithout Barometric Relief forhorizontal configuration.Barometric Relief for horizontalconfigured units must be orderedas field installed accessory.

    8. Through the base electric requiredwhen ordering disconnect/circuitbreaker options.

    9. Requires use of Disconnect orCircuit Breaker.

    Digit 15 = 0Standard Efficiency1 Phase = High Efficiency Multispeed Direct Drive Motor3 Phase (3-8½ Ton) = Belt Drive3 Phase (10 Ton) = Ultra High Efficiency Direct Drive Plenum FanHigh Efficiency1 Phase = High Efficiency Multispeed Direct Drive Motor3 Phase (3-5 ton) = High Efficiency Multispeed Direct Drive Motor3 Phase (3-5 ton w/Dehumidification) = Belt Drive Motor3 Phase (7½-10 ton) = Ultra High Efficiency Direct Drive Plenum Fan

    Not AvailableStandard Efficiency10 Ton w/575VHigh Efficiency3-5 ton w/Standard Indoor Motor w/460V

    24

    10. Standard metering devices areTXVs.

    11. Frostat cannot be field installed inelectro-mechanical units.

    12. The return air smoke detector maynot fit up or work properly on thePrecedent units when used inconjunction with 3rd partyaccessories such as bolt on heatwheels, economizers and powerexhaust. Do not order the returnair smoke detectors when usingthis type of accessory.

    13. ReturnAir Smoke Detector cannotbe ordered with Novar Controls.

    14. These options are standard whenordering Novar Controls.

    15. This option is used when orderingNovar Controls.

    16. Includes gas piping and shutoff(field assembly required).

    17. Not available with hightemperature duct sensoraccessory.

    18. Digit 15 = 2

    19. Novar Sensor utilized withDigit 21 = (4) Novar 3051 Controlswithout Zone Sensor.

    20. Available forT/Y 10 ton standardefficiency models only.

    21. Available forT/Y 3, 4, 5, 6, 7½, 8½ton standard/high efficiencymodels only.

    22. Requires selection of 2” PleatedFilters (option B or C) for Digit 16.

    23. Not available on 6 ton units and allsingle phase or standardefficiency.

    24. Standard onT/YSC 6, 7½ (singleand dual systems), 8½, 10 tonstandard efficiency models andT/YHC 4, 5, 6, 7½ ton high efficiency

    Standard Efficiency1 Phase = Not Available3 Phase = Not AvailableHigh Efficiency1 Phase = Not Available3 Phase (3-5 ton) = May be Ordered3 Phase (3-5 ton w/Dehumidification) = Not Available3 Phase (6-10 ton) = Not Available

    models (except fordehumidification models).

    25. Epoxy coil and epoxy withhailguard options are notavailable for units withmicrochannel condenser coil.

    26. Single Zone VAV is only availableon 7.5-10 ton high efficiency and 10ton standard efficiency productswith ReliaTel™ controls.

    27. Multi-speed indoor fan availableonly on 7.5 & 8.5 ton highefficiency, and 10 ton productswith ReliaTel™ controls.

    28. Motorized Outside Air Damper isnot available on Multi-Speed orSZVAV (Single Zone Variable AirVolume) products.

    29. Frostat standard on Multi-Speedand SZVAV (Single Zone VariableAir Volume) products.

    30. Novar is not available with SZVAVproducts.

    RT-PRC023-EN

  • General Data

    Table 1. General data - 3-4 tons - standard efficiency

    3 Tons 4 Tons

    T/YSC036E1 T/YSC036E3,4,W T/YSC048E1 T/YSC048E3,4,W

    Cooling Performance(a)

    Gross Cooling CapacityEER/SEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacitySystem Power (kW)

    35,62011.5/13.0

    1,200/1,20035,0003.04

    37,15011.2/13.0

    1,200/1,20035,8003.20

    49,21011.1/13.0

    1,600/1,60048,0004.32

    49,45010.9/13.0

    1,600/1,60048,0004.39

    Compressor

    Number/Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll

    Sound

    Outdoor Sound Rating (dB)(c) 81 81 82 82

    Outdoor Coil - Type Lanced Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.312510.962/16

    Full Face0.31259.592/16

    Full Face0.312510.962/16

    Full Face0.312510.962/16

    Indoor Coil - Type Lanced Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.31257.713/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31257.713/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31257.714/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31257.714/16

    Thermal Expansion Valve1¾ NPT

    Outdoor Fan - Type Propeller Propeller Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmMotor hpMotor rpm

    1/22Direct/13,4660.331,075

    1/22Direct/13,3750.331,075

    1/22Direct/13,4110.331,075

    1/22Direct/13,4030.331,075

    Indoor Fan - Type (Standard) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/RPMNumber MotorsMotor hpMotor Frame Size

    1/11x11Direct/5(d)

    10.7548

    1/11x11Belt/Variable/1,750

    11.056

    1/11x11Direct/5(d)

    11.048

    1/11x11Belt/Variable/1,750

    11.056

    Filters(e)

    Type FurnishedNumber Size Recommended

    Throwaway(2) 20x30x2

    Throwaway(2) 20x30x2

    Throwaway(2) 20x30x2

    Throwaway(2) 20x30x2

    Refrigerant Charge(f)

    Pounds of R-410A 6.3 6.0 7.0 7.0

    continued on next page

    RT-PRC023-EN 25

  • General Data

    Heating Performance(g)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    60,00080,000120,000

    60,00080,000120,000

    60,00080,000120,000

    60,00080,000120,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    48,00065,00096,000

    48,00064,00096,000

    49,00065,00096,000

    48,00064,00096,000

    AFUE%(h)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    787878

    808080

    797979

    808080

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808180

    808080

    818180

    808080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    223

    223

    223

    223

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    111

    111

    111

    111

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low Heat Mid HeatHigh Heat

    1/21/21/2

    1/21/21/2

    1/21/21/2

    1/21/21/2

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

    (b) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.(c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143, p. 184.(d) For multispeed direct drive rpm TSC values, reference Table 33, p. 78. For multispeed direct drive rpm YSC (low & medium gas heat) values reference

    Table 34, p. 79. For multispeed direct drive rpm YSC (high gas heat) values reference Table 35, p. 80.(e) Optional 2” MERV 7 and MERV 13 filters also available.(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(g) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

    Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (h)AFUE is rated in accordance with DOE test procedures.

    Table 1. General data - 3-4 tons - standard efficiency (continued)

    3 Tons 4 Tons

    T/YSC036E1 T/YSC036E3,4,W T/YSC048E1 T/YSC048E3,4,W

    26 RT-PRC023-EN

  • General Data

    Table 2. General data - 5 tons - standard efficiency

    5 Tons

    T/YSC060E1 T/YSC060E3,4,W

    Cooling Performance(a)

    Gross Cooling CapacityEER/SEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacitySystem Power (kW)

    59,90011.0/13.0

    2,000/2,00058,0005.25

    62,27011.0/13.0

    2,000/2,00060,0005.46

    Compressor

    Number/Type 1/Scroll 1/Scroll

    Sound

    Outdoor Sound Rating (dB)(c) 82 82

    Outdoor Coil - Type Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.312510.963/16

    Full Face0.312510.963/16

    Indoor Coil - Type Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.31257.714/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31257.714/16

    Thermal Expansion Valve1¾ NPT

    Outdoor Fan - Type Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmNumber Motors/hpMotor rpm

    1/22Direct/13,2710.401,075

    1/22Direct/13,2450.401,075

    Indoor Fan - Type (Standard) FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmMotor hpMotor Frame Size

    1/11x11Direct/5(d)

    1.048

    1/11x11Belt/Variable/1,750

    1.056

    Filters(e)

    Type FurnishedNumber Size Recommended

    Throwaway(2) 20x30x2

    Throwaway(2)20x30x2

    Refrigerant Charge (f)

    Pounds of R-410A 9.5 9.4

    continued on next page

    RT-PRC023-EN 27

  • General Data

    Heating Performance(g)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    60,00080,000130,000

    60,00080,000130,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    48,00065,000104,000

    48,00064,000104,000

    AFUE%(h)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    787978

    808080

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808180

    808080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    223

    223

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    111

    111

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low HeatMid HeatHigh Heat

    1/21/21/2

    1/21/21/2

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

    (b) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.(c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143, p. 184.(d) For multispeed direct drive rpm TSC values, reference Table 33, p. 78. For multispeed direct drive rpm YSC (low & medium gas heat) values reference

    Table 34, p. 79. For multispeed direct drive rpm YSC (high gas heat) values reference Table 35, p. 80.(e) Optional 2” MERV 7 and MERV 13 filters also available.(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(g) Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

    Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (h)AFUE is rated in accordance with DOE test procedures.

    Table 2. General data - 5 tons - standard efficiency (continued)

    5 Tons

    T/YSC060E1 T/YSC060E3,4,W

    28 RT-PRC023-EN

  • General Data

    Table 3. General data - 6-7½ tons - standard efficiency

    6 Tons 7½ Tons 7½ Tons

    T/YSC072F3,4,W T/YSC090F3,4,W T/YSC092F3,4,W

    Cooling Performance(a)

    Gross Cooling CapacityEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacityIEER(c)

    System Power (kW)

    75,00011.2

    2,400/2,10071,20013.06.36

    89,00011.2

    3,000/2,40083,00012.27.48

    94,00011.2

    3,000/2,62589,00013.07.97

    Compressor

    Number/Type 1/Scroll 1/Scroll 2/Scroll

    Sound

    Outdoor Sound Rating (dB)(d) 89 89 91

    Outdoor Coil - Type Microchannel Microchannel Microchannel

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.7116.911/23

    Full Face0.7116.911/23

    Face-Split0.7117.311/23

    Indoor Coil - Type Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.31259.893/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31259.894/16

    Thermal Expansion Valve1¾ NPT

    Face-Split0.312512.363/16

    Thermal Expansion Valve1¾ NPT

    Outdoor Fan - Type Propeller Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmMotor hpMotor rpm

    1/26Direct/16,0370.7

    1,100

    1/26Direct/16,0370.7

    1,100

    1/26Direct/16,6100.751,100

    Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmMotor hp (Standard/Oversized)Motor Frame Size (Standard/Oversized)

    1/12x12Belt/Variable/1,750

    1.0/2.056/56

    1/12x12Belt/Variable/1,750

    1.0/3.056/56

    1/15x15Belt/Variable/1,750

    1.0/3.056/56

    Filters(e)

    Type FurnishedNumber Size Recommended

    Throwaway(4) 16x25x2

    Throwaway(4) 16x25x2

    Throwaway(4) 20x25x2

    Refrigerant Charge (f)

    Pounds of R-410A 5.5 5.9 3.9/3.6

    continued on next page

    RT-PRC023-EN 29

  • General Data

    Heating Performance(g)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    80,000120,000

    150,000/105,000

    120,000150,000/105,000200,000/140,000

    120,000150,000/105,000200,000/140,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    64,00096,000

    120,000/84,000

    96,000120,000/84,000160,000/112,000

    96,200120,000/84,000160,000/112,000

    AFUE%(h)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    808080

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    808080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    233

    334

    334

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    112

    122

    122

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low Heat Mid HeatHigh Heat

    1/21/23/4

    1/23/43/4

    1/23/43/4

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 340/360.

    (b) EER is rated at ARI conditions and in accordance with DOE test procedures.(c) Integrated Efficiency Ratio (IEER) is rated in accordance with ARI Standard 340/360. The IEER rating requires that the unit

    efficiency be determined at 100%, 75%, 50% and 25% load (net capacity) at the specified in ARI Standard.(d) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143,

    p. 184.(e) Optional 2” MERV 7 and MERV 13 filters also available.(f) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(g) Heating performance limit settings and rating data were established and approved under laboratory test conditions using

    American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (h)AFUE is rated in accordance with DOE test procedures.

    Table 3. General data - 6-7½ tons - standard efficiency (continued)

    6 Tons 7½ Tons 7½ Tons

    T/YSC072F3,4,W T/YSC090F3,4,W T/YSC092F3,4,W

    30 RT-PRC023-EN

  • General Data

    Table 4. General data - 8½-10 tons - standard efficiency

    8½ Tons 10 Tons

    T/YSC102F3,4,W T/YSC120F3,4,W

    Cooling Performance(a)

    Gross Cooling CapacityEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacityIEER(c)

    System Power (kW)

    102,00011.2

    3,400/2,72096,60013.08.62

    119,00011.3

    4,000/3,500113,000

    12.510.0

    Compressor

    Number/Type 2/Scroll 2/Scroll

    Sound

    Outdoor Sound Rating (dB)(d) 89 88

    Outdoor Coil - Type Microchannel Microchannel

    ConfigurationTube Size (in.) Face Area (sq. ft.)Rows/FPI

    Face-Split1

    20.771/20

    Face Split1

    20.771/20

    Indoor Coil - Type Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Face-Split0.312512.363/16

    Thermal Expansion Valve1¾ NPT

    Intertwined0.312512.364/16

    Thermal Expansion Valve1¾ NPT

    Outdoor Fan - Type Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmMotor hpMotor rpm

    1/26Direct/16,6100.751,100

    1/26Direct/16,8000.751,100

    Indoor Fan - Type FC Centrifugal BC Plenum

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmMotor hp (Standard/Oversized)Motor Frame Size (Standard/Oversized)

    1/15x15Belt/Variable/1,750

    2.0/3.056/56

    1/19.7x15Direct/Variable(e)

    3.75/——/—

    Filters(f)

    Type FurnishedNumber Size Recommended

    Throwaway(4) 20x25x2

    Throwaway(4) 20x25x2

    Refrigerant Charge (g)

    Pounds of R-410A 4.7/3.9 5.5/4.2

    continued on next page

    RT-PRC023-EN 31

  • General Data

    Heating Performance(h)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    120,000150,000/105,000200,000/140,000

    150,000/105,000200,000/140,000250,000/175,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    96,000120,000/84,000160,000/112,000

    120,000/84,000160,000/112,000200,000/140,000

    AFUE%(i)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    334

    345

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    122

    222

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low Heat Mid HeatHigh Heat

    1/23/43/4

    3/43/43/4

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 340/360.

    (b) EER is rated at ARI conditions and in accordance with DOE test procedures.(c) Integrated Efficiency Ratio (IEER) is rated in accordance with ARI Standard 340/360. The IEER rating requires that the

    unit efficiency be determined at 100%, 75%, 50% and 25% load (net capacity) at the specified in ARI Standard.(d) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143,

    p. 184.(e) For multispeed direct drive rpm T/YSC values, reference Table 142, p. 183.(f) Optional 2” MERV 7 and MERV 13 filters also available.(g) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(h)Heating performance limit settings and rating data were established and approved under laboratory test conditions using

    American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (i) AFUE is rated in accordance with DOE test procedures.

    Table 4. General data - 8½-10 tons - standard efficiency (continued)

    8½ Tons 10 Tons

    T/YSC102F3,4,W T/YSC120F3,4,W

    32 RT-PRC023-EN

  • General Data

    Table 5. General data - 3-4 tons - high efficiency

    3 Tons 4 Tons

    T/YHC036E1 T/YHC036E3,4 T/YHC048F1 T/YHC048E3,4 T/YHC048F3,4

    Cooling Performance(a)

    Gross Cooling CapacityEER/SEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacitySystem Power (kW)

    38,49013.0/15.2

    1,200/1,20037,0002.93

    37,60012.7/15.0

    1,200/1,20037,0002.99

    48,93012.55/15.01,600/1,600

    48,0003.83

    49,93015.0

    1,600/1,60049,0003.67

    49,93013.35/15.01,600/1,600

    49,0003.67

    Compressor

    Number/Type 1/Scroll 1/Scroll 1/Scroll 1/Scroll 1/Scroll

    Sound

    Outdoor Sound Rating (dB)(c) 81 81 87 87 87

    Outdoor Coil - Type Lanced Lanced Microchannel Lanced Microchannel

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.312510.962/16

    Full Face0.312510.962/16

    Full Face0.7116.911/23

    Full Face0.312517.003/16

    Full Face0.7116.911/23

    Indoor Coil - Type Lanced Lanced Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.31257.713/16

    Thermal Expansion Valve

    1¾ NPT

    Full Face0.31257.713/16

    Thermal Expansion Valve

    1¾ NPT

    Full Face0.31259.273/16

    Thermal Expansion Valve

    1¾ NPT

    Full Face0.31259.273/16

    Thermal Expansion Valve

    1¾ NPT

    Full Face0.31259.273/16

    Thermal Expansion Valve

    1¾ NPT

    Outdoor Fan - Type Propeller Propeller Propeller Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmMotor hpMotor rpm

    1/22Direct/13,0640.2

    1,075

    1/22Direct/13,0640.2

    1,075

    1/26Direct/13,9860.4

    1,075

    1/26Direct/13.9820.4

    1,075

    1/26Direct/13,9820.4

    1,075

    Indoor Fan - Type (Standard)(d) FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmNumber MotorsMotor hp (Standard/Oversized)Motor Frame Size (Standard/Oversized)

    1/11x11Direct/5(e)

    10.7548

    1/11x11Direct/5(e)

    1.7548

    1/11x11Direct/5(e)

    11.048

    1/11x11Direct/5(e)

    11.048

    1/11x11Direct/5(e)

    11.048

    Indoor Fan - Type (Optional) FC Centrifugal FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. SpeedsNumber MotorsMotor hp (Standard/Oversized)Motor Frame Size (Standard/Oversized)

    —————

    1/11x11Belt/Variable

    11.056

    —————

    1/11x11Belt/Variable

    11.056

    1/11x11Belt/Variable

    11.056

    Filters(f)

    Type FurnishedNumber Size Recommended

    Throwaway(2) 20x30x2

    Throwaway(2) 20x30x2

    Throwaway(4) 16x25x2

    Throwaway(4) 16x25x2

    Throwaway(4) 16x25x2

    Optional Hot Gas Reheat Coil (Type)

    Tube Size (in.) ODFace Area (sq. ft.)Rows/FPI

    ———

    0.3754.722/18

    ———

    0.3756.832/18

    ———

    Refrigerant Charge (Lbs. of R-410A)(g)

    Standard Optional Hot Gas Reheat Coil

    6.2—

    6.26.6

    5.2—

    —12.0

    5.2—

    RT-PRC023-EN 33

  • General Data

    Heating Performance(h)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    60,00080,000120,000

    60,00080,000120,000

    60,00080,000120,000

    60,00080,000120,000

    60,00080,000120,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    48,00065,00096,000

    48,00064,00096,000

    49,00064,00096,000

    49,00064,00096,000

    49,00064,00096,000

    AFUE%(i)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    787878

    787878

    807979

    807979

    807979

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808180

    808080

    818080

    818081

    818081

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    223

    223

    223

    223

    223

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    111

    111

    111

    111

    111

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low Heat Mid HeatHigh Heat

    1/21/21/2

    1/21/21/2

    1/21/21/2

    1/21/21/2

    1/21/21/2

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

    (b) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.(c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143, p. 184.(d) Belt drive fan is standard on units with reheat option.(e) For multispeed direct drive rpm THC values, reference Table 36, p. 81. For multispeed direct drive rpm YHC (low & medium gas heat) values reference

    Table 37, p. 82. For multispeed direct drive rpm YHC (high gas heat) values reference Table 38, p. 83.(f) Optional 2” MERV 7 and MERV 13 filters also available.(g) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(h)Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

    Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (i) AFUE is rated in accordance with DOE test procedures.

    Table 5. General data - 3-4 tons - high efficiency (continued)

    3 Tons 4 Tons

    T/YHC036E1 T/YHC036E3,4 T/YHC048F1 T/YHC048E3,4 T/YHC048F3,4

    34 RT-PRC023-EN

  • General Data

    Table 6. General data - 5 tons - high efficiency

    5 Tons

    T/YH060F1 T/YHC060E3,4 T/YHC060F3,4

    Cooling Performance(a)

    Gross Cooling CapacityEER/SEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacitySystem Power (kW)

    61,00012.85/15.02,000/2,000

    59,5004.63

    61,00015.0

    2,000/2,0006,0004.67

    61,00012.85/15.02,000/2,000

    60,0004.67

    Compressor

    Number/Type 1/Scroll 1/Scroll 1/Scroll

    Sound

    Outdoor Sound Rating (dB)(c) 87 87 87

    Outdoor Coil - Type Microchannel Lanced Microchannel

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.7116.911/23

    Full Face0.3125

    173/16

    Full Face0.7116.911/23

    Indoor Coil - Type Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.31259.894/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31259.894/16

    Thermal Expansion Valve1¾ NPT

    Full Face0.31259.894/16

    Thermal Expansion Valve1¾ NPT

    Outdoor Fan - Type Propeller Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmNumber Motors/hpMotor rpm

    1/26Direct/13,9530.401,075

    1/26Direct/13,9530.401,075

    1/26Direct/13,9530.401,075

    Indoor Fan - Type (Standard)(d) FC Centrifugal FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmMotor hpMotor Frame Size

    1/11x11Direct/5(e)

    1.048

    1/11x11Direct/5(d)

    1.048

    1/11x11Direct/5(d)

    1.048

    Indoor Fan - Type (Optional) FC Centrifugal FC Centrifugal

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. SpeedsMotor hpMotor Frame Size

    ————

    1/11x11Belt/Variable

    1.056

    1/11x11Belt/Variable

    1.056

    Filters(f)

    Type FurnishedNumber Size Recommended

    Throwaway(4) 16x25x2

    Throwaway(4) 16x25x2

    Throwaway(4) 16x25x2

    Optional Hot Gas Reheat Coil - Type

    Tube Size (in.) ODFace Area (sq. ft.) Rows/FPI

    ———

    0.3756.832/18

    ———

    Refrigerant Charge (Lbs. of R-410A) (g)

    StandardOptional Hot Gas Reheat Coil

    6.1—

    —13.9

    6.1—

    continued on next page

    RT-PRC023-EN 35

  • General Data

    Heating Performance(h)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    60,00080,000130,000

    60,00080,000130,000

    60,00080,000130,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    49,00064,000104,000

    49,00064,000104,000

    49,00064,000104,000

    AFUE%(i)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    807980

    807980

    807980

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    818080

    818080

    818080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    223

    223

    223

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    111

    111

    111

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low HeatMid HeatHigh Heat

    1/21/21/2

    1/21/21/2

    1/21/21/2

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

    (b) EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.(c) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table 143, p. 184.(d) Belt drive is standard on units with reheat option.(e) For multispeed direct drive rpm THC values, reference Table 36, p. 81. For multispeed direct drive rpm YHC (low & medium gas heat) values reference

    Table 37, p. 82. For multispeed direct drive rpm YHC (high gas heat) values reference Table 38, p. 83.(f) Optional 2” MERV 7 and MERV 13 filters also available.(g) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.(h)Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards

    Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/Electric units only.

    (i) AFUE is rated in accordance with DOE test procedures.

    Table 6. General data - 5 tons - high efficiency (continued)

    5 Tons

    T/YH060F1 T/YHC060E3,4 T/YHC060F3,4

    36 RT-PRC023-EN

  • General Data

    Table 7. General data - 6-7½ tons - high efficiency

    6 Tons 7½ Tons 7½ Tons

    T/YHC072F3,4 T/YHC092E3,4 T/YHC092F3,4

    Cooling Performance(a)

    Gross Cooling CapacityEER(b)

    Nominal cfm/ARI Rated cfmARI Net Cooling CapacityIEER(c),(d)

    System Power (kW)

    72,00012.6

    2,400/2,10068,00014.55.37

    92,00013.0

    3,000/2,62589,00015.06.85

    92,00012.6

    3,000/2,62589,00014.57.06

    Compressor

    Number/Type 1/Scroll 2/Scroll 2/Scroll

    Sound

    Outdoor Sound Rating (dB)(e) 89 87 88

    Outdoor Coil - Type Microchannel Lanced Microchannel

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPI

    Full Face0.7120.771/23

    Full Face0.312536.13/16

    Face-Split1

    20.771/20

    Indoor Coil - Type Lanced Lanced Lanced

    ConfigurationTube Size (in.)Face Area (sq. ft.)Rows/FPIRefrigerant ControlDrain Connection Number/Size (in.)

    Full Face0.312512.364/16

    Thermal Expansion Valve

    1¾ NPT

    Intertwined0.312516.654/16

    Thermal Expansion Valve

    1¾ NPT

    Intertwined0.312512.364/16

    Thermal Expansion Valve

    1¾ NPT

    Outdoor Fan - Type Propeller Propeller Propeller

    Number Used/Diameter (in.)Drive Type/No. SpeedscfmMotor hpMotor rpm

    1/26Direct/15,9000.7

    1,100

    1/30Direct/17,5400.751,100

    1/26Direct/16,8000.751,100

    Indoor Fan - Type FC Centrifugal BC Plenum BC Plenum

    Number Used/Diameter (in.)/Width (in.)Drive Type/No. Speeds/rpmMotor hp (Standard/Oversized)Motor Frame Size (Standard/Oversized)

    1/15x15Belt/Variable/1,750

    1.0/2.056/56

    1/19.7x15Direct/Variable(f)

    3.75/——/—

    1/19.7x15Direct/Variable(g)

    3.75/——/—

    Filters(h)

    Type FurnishedNumber Size Recommended

    Throwaway(4) 20x25x2

    Throwaway(3) 20x25x2(2) 20x30x2

    Throwaway(4) 20x25x2

    Optional Hot Gas Reheat Coil - Type

    Tube Size (in.) ODFace Area (sq. ft.) Rows/FPI

    ———

    0.37513.892/16

    ———

    Refrigerant Charge (Lbs. of R-410A)(i)

    StandardOptional Hot Gas Reheat Coil

    7.7—

    —14/11.75

    5.5/4.2—

    continued on next page

    RT-PRC023-EN 37

  • General Data

    Heating Performance(j)

    (Gas/Electric Only)

    Heating Input

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    80,000120,000

    150,000/105,000

    120,000150,000/105,000200,000/140,000

    120,000150,000/105,000200,000/140,000

    Heating Output

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    64,00096,000

    120,000/84,000

    96,000120,000/84,000160,000/112,000

    96,000120,000/84,000160,000/112,000

    AFUE%(k)

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    808080

    Steady State Efficiency%

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    808080

    808080

    808080

    No. Burners

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    334

    334

    334

    No. Stages

    Low Heat Input (Btu)Mid Heat Input (Btu)High Heat Input (Btu)

    112

    122

    122

    Gas Supply Line Pressure

    Natural (minimum/maximum)LP (minimum/maximum)

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    4.5/14.011.0/14.0

    Gas Connection Pipe Size (in)

    Low Heat Mid HeatHigh Heat

    1/21/23/4

    1/23/43/4

    1/23/43/4

    (a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 340/360.

    (b) EER is rated at ARI conditions and in accordance with DOE test procedures.(c) Integrated Efficiency Ratio (IEER) is rated in accordance with ARI Standard