monthly operating repts for aug 1982.18. net electrical energy generated (mwhi ^^1 m 1 nsa ca7...

10
c_ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ __-______ _ | E i OPERATING DAT A REPORT DOCKET NO. _50-317 DATE 9/14/82 COMPLETED BY Elaine lotito TELEPHONE (301)787535- OPERATING STATUS 1. Ur.i: Name: -Cilvert Cliffs #1 Notes 2. Reporting Period: August 1%2 3. Licensed Thermal Power (MWt): 2700 918 ' 4. Nameplate Rating (Grms MWe); 5. Desi;;n Electrical Ratmg INet MWe): 845 6. Maximum Dependable Capacity (Gross MWe): 860 ( 7. Makimum Dependable Capacity (Net MWe): 825 8. If Char ;;es Oects in Cap.icity Ratings (1: ems Nunter 3 Through 7) Since Last Report.Gise Reasons: * 9. Poser Lesel To hhich Hestricted,if Any (Net Mbe): 10. Reasons For Restrictions,if Any: __ . This Month Yr..to Date Ct.mubtive . 11. ticurs in Reporting Period 744.0 _ 5.831.0 64,140.0 12. Number Of Hoiirs Reactor Was Critical 600.6 3,798.7 50,398.4 13. Reacter Resenc Shutdown Hours 0.0 3.1 1,795.5 I4. Hours Genersfor On-Line 580.8 3,753.0 49,354.7, 15. Unit Resene Shutdown flours 0.0 0.0 0.0 16. Grors Thermal Energy Generated (MWH) 1,499,914 9,692,290 119,611,768 . 17. Gross Electrical Energy Generated IMWill 487,641 3,229, % 1 39,223,958 18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _ ; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r -78.1 64.4 77.0 23. Unit Capacity Factor !Using MDC Neti 75.5 64.1 71.9 22. Unit C:rpacity f actoi tusing DER Nett 73.7 62.6 69.0 23. Unit f orced Outage Rate 12.4 2.4 8.4 24. Shutdowns Scheduled 0.cr Nest 6 Montin (Type. Date.snd Duration of Eacht: _ 25. Il Sht Down At End Of Report Period. Estimated Date of Startup: 16. Uniss in Test Status (Prior to Commercial Operation). Forecast Achieved . INITIA L CRITICAL.lTY INITIA L ELECTRICITY COMMERCIAL OPERATION . __ B209210069 820915 PDR ADOCK 05000317 (967) R pop - - - - - _ . - - _ - - _ - _ . --

Upload: others

Post on 19-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

c_ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ __-______ _

|

E

i

OPERATING DAT A REPORT

DOCKET NO. _50-317DATE 9/14/82

COMPLETED BY Elaine lotitoTELEPHONE (301)787535-

OPERATING STATUS

1. Ur.i: Name: -Cilvert Cliffs #1 Notes

2. Reporting Period: August 1%2

3. Licensed Thermal Power (MWt): 2700918 '

4. Nameplate Rating (Grms MWe);5. Desi;;n Electrical Ratmg INet MWe): 8456. Maximum Dependable Capacity (Gross MWe): 860 (

7. Makimum Dependable Capacity (Net MWe): 825

8. If Char ;;es Oects in Cap.icity Ratings (1: ems Nunter 3 Through 7) Since Last Report.Gise Reasons:*

9. Poser Lesel To hhich Hestricted,if Any (Net Mbe):10. Reasons For Restrictions,if Any:

__

.

This Month Yr..to Date Ct.mubtive.

11. ticurs in Reporting Period 744.0 _ 5.831.0 _64,140.0

12. Number Of Hoiirs Reactor Was Critical 600.6 3,798.7_

50,398.413. Reacter Resenc Shutdown Hours 0.0 3.1 1,795.5I4. Hours Genersfor On-Line -

580.8 3,753.0 49,354.7,15. Unit Resene Shutdown flours 0.0 0.0 0.0

16. Grors Thermal Energy Generated (MWH) 1,499,914 9,692,290 119,611,768.

17. Gross Electrical Energy Generated IMWill 487,641 3,229, % 1 39,223,95818. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20

_

;

19. Unit Senice Factor 78.1 64.4 77.020. Unit Assitability Factc.r -78.1 64.4 77.023. Unit Capacity Factor !Using MDC Neti 75.5 64.1 71.922. Unit C:rpacity f actoi tusing DER Nett 73.7 62.6 69.023. Unit f orced Outage Rate 12.4 2.4 8.424. Shutdowns Scheduled 0.cr Nest 6 Montin (Type. Date.snd Duration of Eacht:

_

25. Il Sht Down At End Of Report Period. Estimated Date of Startup:16. Uniss in Test Status (Prior to Commercial Operation). Forecast Achieved

.

INITIA L CRITICAL.lTYINITIA L ELECTRICITYCOMMERCIAL OPERATION

.__

B209210069 820915PDR ADOCK 05000317 (967)R pop

- - - - - _ . - - _ - - _ - _ . -- _

Page 2: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

~

*.

.

OPER ATihG DAT A REPORT

DOCKET NO. 50-318DATE 9/14/_82

COMPLETED BYE g lotitoTELEPHONE (101) 7874363-

OPERATING ST AT US

1. Urti: Name: Calvert Cliffs #2 Not'5

2. Reportmg Period. August 1982

3. Licenwd T hermal Power (3ths): 2.700

4. Narneplate Rating (Grus MWer 911

8455. Desi;;n E!ntrical Rat;ng (Net Mhe):6. Maximum Dependable Capacity IGrms MWe): 860

8257. Maximum Dependatle Capacity (Net MWe):

8. If Char ges Occur in Cap. city Ratings titems Nunter 3 Through 7) Since Lat Report.Gise Reasons.

9. Power Lesello bhich He.fricted. lf Any (Net 4the):10. Reasons For Restnctieru. lf Any:

Thh Month Yr..to-Date Ct.tnalative.

*II. Ilours in Reporting PerioJ 744.0 5,831.0

_

47,495.0

12. Number Oi Hours Reactor Was Criticci 684.3 _ 5,450.1 41,081.1

13. Reactor Rescne Shutdown Hours 59.7 81.0 795.2I4. Hours Generator On Line 683.2 5,416.7 40,461.1

15. Unit Resene Shutdown flours 0.0 0.0 0.0

16. Gross Thermal Ener2y Genciated IMWH) 1,381,140 13,607,575 99,652,131 .

17. Cross Electrical Energy Generated IMWill 423,246_

4,428,985 32,6%,m~

18. Net Electrical Energy Generated (MWH) 397.553 4.236.204 _31,322,01519. t.imt Senice factor 91.8 92.9 85.220. Unit Assilability Factor 91.8 92.9 85.221. Unit Capaci 3 Factor IUsing MDC Net, 64.8 88.1 80.622. Unit Capacity factor IUsing DER Net! 63.2 86.0 78.0

_

23. Unit Forced Outage Rate 8.2 7.1 3.6

24. Shutdowns Scheduled 0,er Nes: 6 Monttis (Type. Date.and Duration of Eacht._ No. 2 scheduled for refueling, unit gereral inspection & retube condenser fran 10/17/82 until 1/30/83.

| 25. If Shut Down At End Of Report Period. Estimated Date of Startup:'

lo. Units in Test Status (Prior to Commercial 0peration). Forecast Achined.

INITIA L CRITICA LITY ,

INITIAL ELECTRICITYCOMMERCI AL OPER ATION

(4/77).

Page 3: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

* . , .- ,

~ AVER AGE DAILY UNIT POWER LEVEL

.

DOCKET NO. 50-317

UNIT Calvert Cliffs #19/14/82DATE

**

COMPLETED BY'

TELEPflONE (301) 787-5363'

MONT!! August 1%2

DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL(MWe Net) ;ywe. Net)

I 825 g7 290

# 8342 gg

8353 39

639 8234 20

5-

21-

4796 n -

7 827 23 461

8 832 Y828

9 826 839'25

#IO 26

11 834 61427

12 830 28 842

80513 29 848

714-

30

IS -

31 846

16-

|

|

|INSTRUCTIONS'

i On this format list the average dady unit power level in MWe Net for each day in the reporting month. Compute tothe nearest whole megawatt.

(9/77)

!

;

_ . .-. ..-.-m

Page 4: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

.,

9 .

* . , -., . .

AVERAGE DAILY UNIT POWER LEVEL

DOCKET NO. 50-318

Calvert Cliffs #1E'lT

DATE 9/14/82

COMPLETED BY Elaine lotito*

TELEPHONE (301) 787-5363*

1

MONTH A - r 1982

DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL(MWe Net) (MWe-Net)

1 63637 580

638 5892 gg

3 -

634 590y9

626 6074

3473 633

316 6396 22

5813437 23

8 597 _

3

5799__ 73

_

10 578 26 477

II589 844y

12 28

13 574 29 616

576 62714 30

15 573 6583g

57916

l

:

INSTRUCTIONSt

On this format. list the average daily unit power level in MWe-Net for each day in the reporting inonth. Compute to'

the nearest whole megawatt.

(9/77)|i

e

*e- e,e v rT -t w-- -,~'---e- v- - -- - -- - -- - - , - ee

Page 5: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

. . .- - ,. - - _ --.

!.

.

DOCKET NO. 50-317 .

UNIT S!!UTDOWNS AND POWER REDUCTIONS UNIT NAME Calvert Cliffs siDATE 4/14/82

COMPLETED BY Finino inrtenREPORT MONnt Aumist 1982 TELEPHONE (301) 787-5363

".-

. =e e. s 5

c ;: Licensee h g% Cause & Cosrective.* .2 E s: 9

-

No. DJ'c k 5? i 2s5 Esent ay j?g Action to

$E $ jgg Report * EU ' Prevent Recurrence*

6.

82-04 080482 F 28.5 A 3 WA INSE U Tripped due to an undervoltage spike on reactorbus.

82-05 Obl482 S 80.9 B 1 CB Z222ZZ Repair reactor coolant system leak.

82-06 082182 F 44.9 A 1 XX Ptnp XX Repair leaking upper seal pressure sensing lirxon 12B reactor coolant ptmp.

82-07 082282 r 8.9 C 3 XX ZZZZZZ Tripped on low steam generator level due toloading the nuin turbine tco rapidly.

||

1 2 3 4

F: Forced Reamn: Method: Exhibit C Instructions5: Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data .

B-Maintenance of Test 2-Manual Scram. Entry Sheets for LicenseeC.Refuehng 3-Automatic Scram. Event ReporI (LE R) File (NUREG.D Regulatory Restriction 4sContinuation 0161)

;- li-Operator Trainir;;& Ucense Examination 5-Load Reduction

F-Admuastraine 59-Otheri

G-Operational Er ror (Explam) Exhibit I - Same Source

(9/77) Ilother (Explain)

|

,

...

Page 6: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

_ . --._. _ _ ._. _ . . . _ _ _ _ _, . - -

-

.

50-318DOCKET NO. ,

UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME Calvert c11rfs #9DATE 9/14/R'

COMPLETED BY Elaine Intito

RFPORT MONTIf Aumst 1982 TELEPHONE (301) 787 5363

e.

E e'

-

E "E * I* 3 Licensee En Eg Cause & Corrective .8 -

N. .. Date h j! k 3$$ ($ hO"EAction toEvent

Prevent Recurrence6- 3E $ 3 5 =gReport at m0 o

<. uO

,

82-08 082382 P 60,8 A 3 10 Pmp XX Tripped due to loss of high pressure oilpressure on #22 stcan generator feed pmp.

Note: No. 2 unit has been reduced to various loadlevels alnust the entire month due to con-denser tube leaks.

I 2 3 4F: Forced Reason: Method: Exhibit G -InstructionsS. Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data

B Maintenance of Test 2-Manual Scram. Entry Sheets for LicenseeC Refueling 3 Automatic Scram. Event ReporI (LER) File (NUREG-D-Regulatory Rest iction 4sContinuation 0161)1:-Operator Training & Uecuse Examination 5-Load ReductionF Admmistrative 5

9-OtherG-Operational Error (Explam) Exhibit I - Same Soura

19/77) llother (Explain)

$

Page 7: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

.

September 3,1982

REFUELING INFORMATION REQUEST

1. Name of Facility: Calvert Cliffs Nuclear Power Plant, Unit No. I

2. Scheduled date for next Refueling Shutdown: October 1,1983

3. Scheduled da for restart following refueling: December 11,1983

4. Will refueling or resumption of operation thereaf ter require a technical specificationchange or other license amendment?

Resumption of operation af ter refueling will require changes to TechnicalSpecifications. The changes will be such as to allow operation of the plant with afresh reload batch and reshuffled core.

5. Scheduled date(s) for submitting proposed licensing action and supportinginformation.

June 29,1983

6. Important licensing considerations associated with the refueling.

Reload fuel will be simi'ar to that reload fuel inserted into the previous cycle.

7. The number of fuel assemblies (a) in the core and (b) in the spent fuel storage pool.

(a) 217 (b) 656e

Spent Fuel Pools are common to Units 1 and 2

8. The present licensed spent fuel pool storage capacity and the size of any increase inlicensed storage capacity that has been requested or is planned, in number of fuelassemblies.

1830 Licensed1358 Currently Installed

9. The projected date of the last refueling that can be discharged to the Spent FuelPool assuming the present licensed capacity and maintaining space for one full corecff load.

April,1991

Page 8: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

\..

|

September 3,1982

REFUELING INFORMATION REQUEST

1. Name of Facility: Calvert Cliffs Nuclear Power Plant, Unit No. 2.

2. Scheduled date for next refuehng shutdown: October 15,1982.

3. Scheduled date for restart following refueling: January 5,1982

4. Will refueling or resumption of operation thereaf ter require a technical specificationchange or other licensed amendment?

Resumption of operation af ter refueling will require changes to TechnicalSpecifications. The changes will be such as to allow operation of the plant with afresh reload batch and reshuffled core.

5. Scheduled date(s) for submitting proposed licensing action and supportinginformation.

October 4,1982

6. Important licensing considerations associated with refueling.

Reload fuel will be similar to that reload fuel inserted in the previous cycle.

7. The number of fuel assemblies (a) in the core and (b) in the Spent Fuel Storage Pool.

(a) 217 (b) 656

Spent Fuel Poolis common to Units 1 and 2.

8. The present licensed spent fuel pool storage capacity and the size of any increase inlicensed storage capacity that has been required or is planned, in number of fuelassemblies.

1830 Licensed1358 Currently Installed

9. The projected date of the last refueling that can be discharged to the Spent FuelPool assuming the present licensed capacity and maintaining space for one full coreoff load.

- April,1991

1

(

, , - - - . .. ,-- . . . _ , , - , - -- -._ - , . , . . , - - . , - . . - , .

Page 9: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

. .

SlMMRY OF INIT 1 OPERATING EXPZ".IEN - ALGST 1%2

8/1 At the beginning of this reporting period Unit 1 was operating at 835 BWe with

the reactor at 977 power conducting variable Tave testing. Inad was increased

to capacity (875 FHe) at 2100.

8/4 At 1828 the reactor tripped due to an undervoltage spike on the reactor trip

bus. This electrical perturbation m s caused by the opening of the electrical

disconnect switch to 13 service m ter ptnp while still energized.

8/5 The reactor was brought critical at 2003 and the unit paralleled at 2302.

8/6 Resuned full load operation (860 FWe) at 1900.

8/14 The unit m s taken off the line at 0107 due to excessive RCS leakage.

8/27 The reactor ms brought critical at 0355 and the unit paralleled at 0959. Ioad

was increased to capacity (865 FHe) at 2100.

8/21 The unit was taken off the line at 0130 to repair a leaking upper seal pressure

sensing line on 12B Reactor Coolant Ptnp.

8/22 The reactor was brought critical at 1815 and the unit paralleled at 2225. At

2237 the reactor tripped on low steam generator level due to loading the nuin

turbine too rapidly.

8/23 The reactor was brought critical at 0100 and the unit paralleled at 0730.

Resumed full load operation (860 FWe) at 2100.

8/31 At the end of this reporting period Unit 1 was operating at 875 FWe with the

reactor at 100% power.

s-

!

_ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ - . _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ . _ _ . _ _ _ - _ _ _ . _ _ _ _ . . _ _ __ _ __

Page 10: Monthly operating repts for Aug 1982.18. Net Electrical Energy Generated (MWHi ^^1 m 1 nsa ca7 __37.386,0_20 _; 19. Unit Senice Factor 78.1 64.4 77.0 20. Unit Assitability Factc.r-78.1

_- - _ - _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

+ .

|

|

|! SUttMRY OF LNIT 2 OPERATING EXPERIDKE - AtX171982

8/1 At the beginning of this reporting period Unit 2 was operating at 680 FWe with

the reactor at 80% power while investigating saltwater leakage into the nnin

condenser.

I 8/5 Decreased load to 270 FWe at 1200 to alh two circulating water punps to be

shutoawn for saltwater leak investigation.

8/7 load was increased to 640 FWe at 0900.

8/8 Decreased load to 550 FWe at 1500 due to increasing circulating water T.

8/9 Increased load to 620 FWe at 0001.

8/20 load was increased to 660 FWe at 2130.

8/23 At 1342 the reactor tripped on low steam generator level due to loss of high

pressure oil pressure on 22 steam generator feed pmp. Startup was delayed for

repair of leaking reactor hot leg sanple valve.

8/25 h reactor was brought critical at 2120.

8/26 h unit was paralleled at 0230. Load was increased to 660 FWe at 1300.

Continuing to investigate saltwter leakage into the nuin condenser.

8/31 Plugged 328 leaking condenser tubes this month. At the end of this reporting

period Unit 2 was opera *.ing at 675 FWe with the reactor at 81*/. power while

investigating saltwater leakage into the nnin condenser.

1- -

__ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .J