mitsubishi fx3u-enet en citectscada · citectscada communications with mitsubishi fx3u-enet open fx...
TRANSCRIPT
CitectSCADA Communications with
Mitsubishi FX3U-ENET
Open FX configuartor-EN to define
the FX3U-ENET ethernetcard
• And Set module nummer � Module 1 = 2de special module at the right side
Operational settings
• Select “Binary code”
• Select “Always wait for open”
• Give in the IP adress
– PLC1 192.168.3.1
– PLC2 192.168.3.2
• Check all setting and
save these with End
Operational settings
• Define one or more ports as MELSOFT connections for GX IEC Developer and
FX configutor-EN
• Define a port for CitectSCADA
– TCP
– Unpassive
– Procedure exit (MC)
– Portnumber 1300
• Check all setting and
save these with End
Write settings to the FX3U-ENET
• Push the Write button
• Select the right COM-port
to connect to the PLC
and press OK
• Push the Write button to
download the settings
• Set the PLC to stop
• Click OK on the message
• With Yes the PLC comes back in run
• Power the PLC OFF and ON to reset the ethernet card
Diagnose via serial
• Push the Diagnostics button
• Connection interface is still set to a COM-port
• Push the Diagnostics button in this window as well
• Select the different diagositics tabs
Diagnose via ethernet
• Push the Diagnostics button
• Change the transfer setup
to the IP adress of this PLC
• Push the Diagnostics button in this window as well
• Select the different diagositics tabs
GX IEC Developer via ethernet
• Select the Ethernet board on the PC side
• Select the Ethernet module in thePLC side
• Give in the IP adressof the PLC
• Set the timeout to 5 sec
• Press Connection test
• Save these setting byclosing all windwos with OK
Operational settings
• Define one or more ports as MELSOFT connections for GX IEC Developer and
FX configutor-EN
• Define a port for CitectSCADA
– TCP
– Unpassive
– Procedure exit (MC)
– Portnumber 1300
• Check all setting and
save these with End
Open Citect project en
start de Express Communications wizard
Express Communications wizard steps
• IOserver
– name = IOserver
• IOdevice
– name = PLC1
– external I/Odevice
– Mitsubishi FX Serie FX3U
Ethernet(TCP/IP)
– Adress 255 (host PLC)
• IP adress en port are not asked. See next page.
Set IP - and port adress
• Open de port settings of PLC1
• Set the special opt
-i10.10.10.160 -p1300
• Press replace to save settings
(PLC has IP adress 10.10.10.160 and
port 1300 open for Citect)
Cluster needed in Citect v7
• Open clusters
• Make a cluster and
press “Add”
• Open I/O servers
• Attach your IOServer to a your cluster and
press Replace
Open Variable tags and define tags
• Define a 16 bits tag
– Name = RegD0_PLC1
– Adress = D0
– IO Device Name = PLC1
– Data type = INT
• Press add
• Define a 16 bits tag
– Name = RegX0_PLC1
– Adress = X0
– IO Device Name = PLC1
– Data type = Digtal
• Press add
Create a page
Place a register on the page
• Past genie
• Select libary keyentery
• Select parameter2
• Press OK
• Set tag
• Press OK
• Move object and resize
to your wish
Place a register on the page
• Set symbol
• Place it on the page
• Insert a tag
• Press OK
Save your page
Check your Communications settings
Cluster1 > IOServer > BOARD1 > PORT1_BOARD1 > PLC1 > D0_PLC1
PORT
• IP adres ENET192.168.3.1
• Portnumber ENET1300
• Special Opt-i10.10.10.160 –p1300
• Default TCP & BIN
IO DEVICE
• Adress255 (host)
• ProtocolMELSCNET1
Tag = D0_PLC1
Compile your Project
Run Computer setup wizard
Run your project in demo mode
• Run your project
• Press OK and
run in demo mode for 15 minutes
• Via menu update pages and select page01
Connect more FX3U-ENET modules
• Open de ports
• Change
– portname to PORT2_BOARD1
– Port Number to 2
– IP adress to 10.10.10.X
– Press Add
• Open de IOdevices
• Change
– Name to PLC2
– Number to 2
– Press Add
• You have now 2 record of ports and of IOdevices
Define tags of PLC2
• Open the tag RegD0_PLC1
• Change
– Name to RegD0_PLC2
– IO Device Name to PLC2
• Press add
• Open the tag RegX0_PLC1
• Change
– Name to RegX0_PLC2
– IO Device Name = PLC2
• Press add
Add the PLC2 object on the page
• Copy the 2 object
from PLC1
• Change the tags
of the copied
objects
• Close the page
and save it
Run Citect