michael johnston executive director standards and … · michael johnston executive director...
TRANSCRIPT
MICHAEL JOHNSTON
EXECUTIVE DIRECTOR STANDARDS AND SAFETY – NECA
Top Changes 2014 NEC®
2/12/13 Copyright NECA 2013
General Information
� This presentation previews significant changes for the 2014 NEC.
� Two-part series on 2014 NEC changes to follow.
� There were 3745 proposals submitted and acted on (includes CMP proposals)
� There were 1625 comments submitted and acted on (includes CMP comments)
2/12/13 Copyright NECA 2013
2014 NEC – New Articles
� Article 393 Low Voltage Suspended Ceiling Power Distribution Systems [ROP 18-10a]
� Article 646 Modular Data Centers [ROP 12-147]
� Article 728 Fire Resistive Cable Systems [ROP 3-170] � Article 750 Energy Management Systems [ROP
13-180]
2/12/13 Copyright NECA 2013
Code-Wide Changes
� Revisions in the NEC Style Manual require INs to follow the rule they pertain to [3.1.3].
� Requirements for DC systems and wiring
incorporated throughout the NEC.
� Raising the 600 Volts threshold to 1000 Volts in multiple articles throughout the NEC.
2/12/13 Copyright NECA 2013
CHAPTER 1
General
2/12/13 Copyright NECA 2013
100 Coordination (Selective)
� Proposal 10-5, Comment 10-2 � The word “choice” has been replaced by the words
“selection and installation” to clarify it is selection and installation of overcurrent protection that achieves selective coordination.
� Selective coordination is across the “full range” of
available overcurrents.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
110.16 Arc-Flash Hazard Warning
� Proposals 1-105, 9-14a, Comment 1-47 � Revision adds the words “or factory” and
“switchgear” to the rule. � Clarifies that the marking could be applied in the
field or at the factory by a manufacturer.
� Reference to 110.21(B) has been added.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 110.21(B) Field-Applied Hazard Markings
� Proposal 1-114, Comment 1-61 � New subdivision (B) adds
requirements for warning, caution, or danger, markings, labels, or signs required by the NEC.
� Informational Notes refer to
ANSI Z535.4.
2/12/13 Copyright NECA 2013
110.25 Lockable Disconnecting Means
� Proposal 1-130 � New section provides consistent requirements for
Code rules that require a lockable disconnecting means.
� Coordinated revisions remove text from all sections
that provide the specific requirements for lockable disconnecting means.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 110.26(C)(3) Personnel Doors
� Proposal 1-143a � Revision reduces the ampere value “1200” to “800” amperes.
� Clarifies the requirements for panic hardware are
required for large equipment with an 800-ampere rating or greater.
2/12/13 Copyright NECA 2013
Section 110.26(C)(3) Personnel Doors
� Proposal 1-145
� Revised to include only the term “panic hardware.”
� Revision removes the terms “simple pressure plates” and other devices that are normally latched but are released under simple pressure.
� Promotes consistency with applicable Building Codes that only use the term “panic hardware.”
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
CHAPTER 2
Wiring and Protection
2/12/13 Copyright NECA 2013
Section 210.8(A)(10) Laundry Areas
� Proposal 2-47 � New list item (10) added to Section 210.8(A).
� (10) Laundry Areas now required to have GFCI protection for 125-volt, single phase, 15- and 20-ampere receptacles.
2/12/13 Copyright NECA 2013
Section 210.12(A)
� Proposals 2-80 and 2-82a, Comments 2-48 – 2-50 � Change adds laundry areas and kitchen branch circuits
and outlets to the AFCI protection requirements.
� Continues the progression toward “whole-house” protection originally sought by CPSC in the 1999 NEC development cycle.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 210.12(A)(4) AFCI Protection
� Proposal 2-92, Comment 2-52 � Revision recognizes use of
circuit breakers or outlet devices at the first outlet in the circuit.
� Specific conditions must be
met to apply for outlet AFCI devices.
2/12/13 Copyright NECA 2013
Courtesy Pass and Seymour Legrand
Courtesy Eaton Corporation
Section 210.64 Electrical Service Areas
� Proposal 2-191 � New Section 210.64 added to Article 210 and
exception for one- and two-family dwelling units.
� At least one 125-volt, single-phase, 15- or 20-ampere receptacle outlet within 15 m (50 ft) of the electrical service equipment.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 250.102(C) – New Table
� Proposal 5-42 � New table provides minimum sizes for other than
grounding electrode conductors bonding jumpers for the grounding electrode system.
� Minimum sizing of line-side bonding jumpers,
grounded conductors, main bonding jumpers, system bonding jumpers.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
CHAPTER 3
Wiring Methods and Materials
2/12/13 Copyright NECA 2013
Section 310.10(H)(2) Conductor Characteristics
� Proposal 6-15, Comment 6-7
� A new list item (6) expands the requirements for parallel conductor installations.
� If paralleled in raceways or enclosures, conductors shall be grouped to minimize imbalance and prevent inductive heating.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
310.15(B)(3)(c) and Table 310.15(B)(3)(c)
� Proposal 6-31, Comment 6-29
� Revised to remove the term “circular raceways” and add the term cables.
� Where conductors or cables installed in raceways or cables are exposed to direct sunlight on or above rooftops, the adjustments shown in Table 310.15(B)(3)(c) apply.
2/12/13 Copyright NECA 2013
310.15(B)(3)(c) and Table 310.15(B)(3)(c)
� Proposal 6-41, Comment 6-37 � Ambient temperature correction factors in Table
310.15(B)(2)(a) or Table 310.15(B)(2)(b) do not apply to XHHW-2 insulated conductors in raceways and cables on or above rooftops and exposed to direct sunlight.
� Performance testing by both General Cable and Underwriters Laboratories.
2/12/13 Copyright NECA 2013
Article 393 Low Voltage Suspended Ceiling Power Distribution Systems
� Proposal 18-10a, 18-7 � New Article added to Chapter 3. � Provides requirements for low voltage DC equipment
(lighting and power) connected to a ceiling grid systems built for this purpose.
2/12/13 Copyright NECA 2013
INFRASTRUCTURE:
Ceiling
Walls
Furniture
Floors
© 2010 EMerge Alliance
380 VDC Bus
24 VDC Bus
208-277 VAC
P4 P2
P2
P1 P3
2/12/13 Copyright NECA 2013
CHAPTER 4
Equipment for General Use
2/12/13 Copyright NECA 2013
Section 406.3(E) Controlled Receptacle Marking
� Proposal 18-15, Comment 18-13 � New marking symbol required for receptacles
controlled by an automatic control device or by an automatic energy management system.
� Change includes new Figure 406.3(E):
2/12/13 Copyright NECA 2013
Section 410.6 Listing Required
� Proposal 18-59 � Revision expands the listing requirement to retrofit
kits for lampholders and luminaires.
� New definition of the term "retrofit kit" added to Article 100.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 422.23 Tire Inflation and Automotive Vacuum Machines
� Proposal 17-31 � Any tire inflation equipment or vacuum machine for
public use must be protected by ground-fault circuit-interrupter (GFCI) protection for personnel.
� The GFCI protection (circuit breaker or outlet
device) is required to be readily accessible.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Section 440.9 Grounding and Bonding
� Proposal 11-83, Comment 11-32 � This revision requires a wire-type equipment
grounding conductor(s) be installed in the outdoor portion of EMT and LFMC for air-conditioning and refrigeration equipment in outdoor locations.
� The EGC must be a wire type as required in
350.60(B) and 358.60(B).
2/12/13 Copyright NECA 2013
501.40 Multiwire Branch Circuits
l Proposal 14-59
l Section 501.40 and the exception have been deleted. l The requirements for simultaneous disconnection of
all ungrounded conductors of multiwire branch circuits are already provided in 210.4(B).
2/12/13 Copyright NECA 2013
517.18(B) Patient Bed Location Receptacles
� Proposal 15-36
� This change increases the minimum number of receptacles required from four to eight.
� Aligns with NFPA 99 relative to the increases in quantity of receptacles and normal care patient bed locations.
2/12/13 Copyright NECA 2013
517.19(B) Patient Bed Location Receptacles
� Proposal 15-39
� This revision in subdivision (B) changes the required minimum number of receptacles from six to fourteen.
� Aligns with changes in NFPA 99-2012
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
517.19(C) Operating Room Receptacles
l Proposal 15-41
l The minimum number of receptacles required in an operating room is thirty-six, twelve of these must be connected to either the normal system branch or the critical system branch.
l The grounding terminal of these receptacles must be connected to the reference grounding point by means of an insulated copper equipment grounding conductor.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
690.12 Rapid Shutdown of PV Systems on Buildings
� Proposal 4-253, Comment 4-153
� PV system circuits installed on or in buildings must include a rapid shutdown function that controls specific conductors in accordance with 690.12(A) through (D).
� Controlled conductors shall be limited to no more than 30 volts and 240VA within 10 seconds of rapid shutdown.
� Voltage and power measured between any two conductors and between any conductor and ground.
2/12/13 Copyright NECA 2013
2/12/13 Copyright NECA 2013
Article 750 Energy Management Systems
� Proposal 13-180
� New article is titled “Energy Management Systems” and includes definitions, requirements for alternate power sources, load management provisions, and field marking requirements.
� Energy codes include performance requirements for managing and conserving energy in buildings or structures.
2/12/13 Copyright NECA 2013
Summary
� Preview significant changes for the 2014 NEC.
� New articles to provide rules for new technology.
� This presentation is a preview of a two-part series covering several significant 2014 NEC changes.
� March 5 and 12, 2013 – 11:00 am - 12:00 noon EST.
2/12/13 Copyright NECA 2013
MICHAEL JOHNSTON
EXECUTIVE DIRECTOR STANDARDS AND SAFETY – NECA
Top Changes 2014 NEC®
2/12/13 Copyright NECA 2013