metasys system extended ... - product documentation

26
Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 1 Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Smoke Control Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Smoke Control Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Smoke Control System Requirements per UL 864 UUKL . . . . . . . . . . . . . . . . . . . . . . . . 6 DX-9100 Controller Application Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 FSCS Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Smoke Control Restrictions per UL 864 UUKL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 DX-9100 Controller Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 N1 Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Fiber-Optic Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Copper Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Media Converters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Ethernet Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Copper Switch with RJ45 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Fiber-Optic Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Smoke Control Network Automation Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 N2 Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Metasys Field Interface Point Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Type 2, Modules Rated as Power-Limited Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Type 3, Modules Rated as Both Power-Limited and Non-power-Limited (Application Specific) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin Code No. LIT-1201753 Release 1.2 Issued February 10, 2005

Upload: others

Post on 15-Jun-2022

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring TechnicalBulletin 1

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Smoke Control Wiring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Smoke Control Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Smoke Control System Requirements per UL 864 UUKL . . . . . . . . . . . . . . . . . . . . . . . . 6

DX-9100 Controller Application Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

FSCS Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Smoke Control Restrictions per UL 864 UUKL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10DX-9100 Controller Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

N1 Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Fiber-Optic Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Copper Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Media Converters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Ethernet Network Interface Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Copper Switch with RJ45 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Fiber-Optic Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Smoke Control Network Automation Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

N2 Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Metasys Field Interface Point Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Type 2, Modules Rated as Power-Limited Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Type 3, Modules Rated as Both Power-Limited and Non-power-Limited (Application Specific) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Metasys® System Extended Architecture Smoke Control WiringTechnical Bulletin Code No. LIT-1201753

Release 1.2Issued February 10, 2005

Page 2: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin2

Repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Power Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Wiring Segregation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Input/Output (IO) Wiring Transient Protection Requirements . . . . . . . . . . . . . . . . 21XTM/XPx Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

AP-VMA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

DX-9100 Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

NAE55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

NIE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

NCM350-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

NU-RPT101-0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

AHU, UNT, VAV Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Metasys System Extended Architecture Smoke Control System Design . . . . . . . . . . 24

Page 3: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin3

Metasys® System Extended Architecture Smoke Control WiringTechnical Bulletin

Document IntroductionThis document describes how to wire a Metasys® system extended architecture smoke control system to comply with the National Electrical Code (NEC) and National Fire Protection Association (NFPA) specifications for smoke control systems.

Related DocumentationTable 1 lists related Metasys system extended architecture smoke control information.

Smoke Control Wiring OverviewFor Metasys® system field wiring to comply with the National Electrical Code (NEC) and National Fire Protection Association (NFPA) specifications for smoke control systems, separate power-limited wiring from non-power-limited wiring as specified in NFPA 70, National Electrical Code. Field wiring terminals used for power-limited wiring must be labeled as such. If terminals are not labeled, they are regarded as non-power-limited.

Table 1: Related DocumentationFor Information On Refer To LIT No./Part No.Engineering a Metasys System Extended Architecture Smoke Control System

Metasys System Extended Architecture Smoke Control System Technical Bulletin

LIT-1201684

Common Requirements to Configure a Metasys System to Comply with Underwriters Laboratories (UL), UL 864 UUKL Smoke Control Listing.

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist

LIT-1201754

DX-9100 Controller Applications Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

LIT-1201736

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

LIT-1201737

Warehouse Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

LIT-1201738

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Application Note

LIT-1201743

Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Application Note

LIT-1201739

Installing an NAE NAE55/NIE Installation Instructions Part No. 24-10051-0

Page 4: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin4

Some Metasys system hardware may be used in both power-limited and non-power-limited circuits. These circuits must be segregated during system design to comply with the appropriate codes. The wiring system must be designed in groups, with each Field Terminal Board (TBF) bay being chosen to house all power-limited or non-power-limited field wiring. See the Wiring Segregation section in this document for details on wiring segregation requirements for Metasys system extended architecture products.

In order to meet the requirements of Underwriters Laboratories, Inc.® (UL) under UL 864 UUKL Smoke Control, some of the Metasys system field wiring must be protected by installing transzorbs or Metal Oxide Varistors (MOVs). This protection is only required if the field wiring to the monitored and controlled equipment leaves the room where the controller is installed. A more detailed description of the requirements including tables showing which point types require protection may be found in the Metasys Field Interface Point Types section in this document.

Isolate the Smoke Control System on a dedicated backbone. If you are using an existing backbone, consult the customer’s Information Technology (IT) department to physically isolate the backbone.

ReferencesWhen designing your smoke control system, you must read and become familiar with the following documents, codes, and standards:

• NFPA 92A Recommended Practice for Smoke Control Systems

• American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) publication entitled Design of Smoke Control Systems for Buildings

• NFPA 70 National Electrical Code

• NFPA 72 National Fire Alarm Code

• NFPA 101 Life Safety Code

• NFPA 90A Air Conditioning Systems

• NFPA 92B Smoke Management Systems in Malls, Atria, and Large Areas

• Building Officials and Code Administrators International (BOCA) model code

• International Conference of Building Officials (ICBO) model code

• Southern Building Code Congress International (SBCCI) regulations

Page 5: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 5

Smoke Control RequirementsThis section contains the Metasys system configuration requirements for a UL 864 UUKL Listed smoke control system. These must be followed in order to comply with the UL Listing. Assume any reference to UL Listing to mean UL 864 UUKL Listing, unless otherwise stated.

The Johnson Controls Smoke Control Listing described in this document is valid only with Metasys system extended architecture components Listed for smoke control.

Agency RequirementsThe National Fire Protection Association (NFPA) and UL have published documents, which include provisions for the control of smoke. These documents are:

• NFPA 92A Recommended Practice for Smoke Control Systems

• NFPA 90A Air Conditioning Systems

• UL 864 Control Units for Fire Protective Signaling Systems

• UL 555S Standard for Leakage Rated Dampers for Use in Smoke Control Systems

• NFPA 72 National Fire Alarm Code

• NFPA 70 National Electrical Code

• NFPA 101 Life Safety Code

• In Canada, refer to the following documents:

• ULC/ORD-C539 Fire Alarm Devices, Single and Multiple Station, Mechanically Operated

• ULC/ORD-C2043 Fire Test for Smoke and Visible Heat Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces

Current versions of NFPA documents can be purchased by calling the National Fire Protection Association at 1-800-344-3555. Current versions of UL documents can be purchased by calling UL at 1-888-853-3503.

As with other types of systems designed and installed to protect life and property, the responsibility for approving equipment, installations, and procedures lies with the local Authority Having Jurisdiction (AHJ). The phrase Authority Having Jurisdiction refers to the agency or individual responsible for approving equipment, an installation, or a procedure and giving permission to occupy a building.

Page 6: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin6

In most municipalities, that responsibility lies with the fire chief, fire marshal, electrical inspector, or others having statutory authority. Become familiar with the building codes of your community as their requirements may differ from those of the NFPA.

Other entities, such as an insurance carrier or hospital accreditation organization, may have influence and/or right of approval of the configuration of the smoke control system.

Smoke Control System Requirements per UL 864 UUKLThe following requirements must be followed in configuring and assembling a Metasys Network in order to comply with the UL 864 UUKL Smoke Control Listing:

• All field wiring must be done in compliance with the Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin (LIT-1201753).

• The Ethernet card used for connecting the NU-NCM350-8 to the N1 Local Area Network (LAN) must be the NU-ETH101-0 (available directly from Johnson Controls).

• A UL 864 UUKL Listed Firefighters’ Smoke Control Station (FSCS) must be used to provide manual control of smoke control systems. The UL Listed annunciator panel, made by Automation Displays, Inc., is the UL Listed FSCS for the Johnson Controls Smoke Control System..

• Each Binary Output (BO) object, used for pressurization and exhaust control outputs, must be configured with positive feedback which monitors the associated controlled equipment status. Typically, smoke control dampers provide a pair of feedback binary inputs for the two damper end switches. For fans used for smoke control, provide positive indication of airflow with either a flow switch or static pressure sensor to determine the On/Off status of the fan.

• Positive indication on the FSCS of the operation of all smoke control equipment must be provided, such as both the open and the closed damper end switches for each smoke damper, airflow measurement, or static pressure measurement for each smoke control fan.

• When any smoke control equipment does not respond to automatic or manual commands, this trouble condition must be visibly and audibly indicated on the FSCS.

• The FSCS controls the Sonalert logic for all smoke control systems; no extra application is necessary.

• The Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Application Note (LIT-1201739) application must be used on all dedicated smoke control systems.

Page 7: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 7

• The status of all smoke control systems must be displayed simultaneously on the FSCS. Once a system has been accessed, you must display on the FSCS all control points (fans, dampers, and so forth) in that system simultaneously.

• Duct smoke detectors are often located in the return duct of a Heating, Ventilating, and Air Conditioning (HVAC) fan and connected to stop the fan when smoke is detected, which is in compliance with NFPA 90A. However, if the fan is used for smoke control, and the smoke control strategy is such that the return duct is configured to exhaust smoke from the building during the smoke control system operation, then the duct detector should be prevented from stopping the fan, once the smoke control system has been activated.

• Automatic activation of any smoke control sequence of operation must have priority over any automatic environmental control strategy and over any non-smoke control manual commands. When an automatic smoke control sequence is initiated, the system design must bypass the following operational overrides:

- High and Low Temperature Protection Devices (i.e., A-11 and A-25 Series Temperature Protection Devices)

- Return and Exhaust Air Duct Smoke Detectors

• Manual activation or deactivation of any predefined smoke control strategy from the manual override station must have priority over any automatic smoke or environmental sequence of operation. The FSCS serves as the manual override station.

• To protect against signal transients, use an American Power Conversion (APC®) ProtectNet® model PNET1 Ethernet/token ring port surge protector on each end of the copper lines with RJ45 connectors. Contact American Power Conversion at 1-800-800-4272. A transient surge suppressor is not needed if the line stays in the same room as the two devices it connects and is less than 20 feet (6 meters) long.

• Use a Tripp Lite® ISOBAR®8ULTRA power line surge protector or a Tripp Lite IBAR®12ULTRA power line surge protector on all 110-120 VAC power sources. Use one of these two surge protectors on all devices in the smoke control system that use AC power (including AC to DC adapters). Contact Tripp Lite at www.tripplite.com.

• After an alarm is received and acted upon automatically by the smoke control system, additional alarms must not cause the smoke control system to take automatic secondary actions. However, the system will execute any manual commands from the FSCS.

• All communication links between buildings must be fiber-optic cable or copper cable buried in a conduit that is separate from power wiring.

Page 8: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin8

• Response time for individual smoke control components to achieve their desired operational state should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 10 seconds to annunciate; 75 seconds for completion of damper travel plus 10 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuance of an appropriate command to the equipment.)

• In smoke control applications, you must reserve Priority 2 commands for BOs used for smoke control functions, such as fan and damper control. All other non-smoke control logic should use lower command priorities.

• To design a smoke control system that sends commands across the N1 LAN, you must use the NAE/NIE to interface all input and output smoke control points.

DX-9100 Controller Application RequirementsThe following requirements apply when using hardwired DX-9100 controller applications:

• A DX base with transient protection devices (Metal Oxide Varistors (MOVs) must be used. The Johnson Controls product code number for the DX base with MOVs is DX9100-8990F.

• All alarm input Digital Inputs (DIs) must be monitored and report critical alarms at the FSCS when they close (turn On), such as a fire alarm control panel smoke detector alarm point.

• You must monitor the fuse on the DI circuit of each DX-9100 controller when the DI is used for smoke control. To do this, connect a jumper wire across one spare DI, so that it will always indicate an On condition. If the fuse fails, this point will go off, indicating a fuse failure. Map this point to the FSCS directly connected to the NAE as a critical alarm with a normal state of Closed (On).

• Any time that you use Analog Outputs (AOs) in your configuration for smoke control, you must monitor the fuse on the AO. To do this, set one AO for voltage and define an Analog Input (AI) for voltage. Connect Analog Constants (ACs) set for 50.0 to the AO that is ranged for 0–100. This gives the AO a 50 percent signal or a 5 volt output. This output is hardwired to the AI defined for voltage with a range of 0–100 and a low limit of 20. If the AO fuse blows, the voltage will go to 0 and the AI will go into low alarm. This alarm must be monitored as a critical alarm.

• Any DX-9100 controller used in a smoke application must have a Metasys system poll priority of 1 or 2.

Page 9: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 9

• All fans controlled by the DX-9100 controller must have an airflow status switch. Any mismatch of command and HVAC equipment controller status of the fans must report a critical alarm at the FSCS.

FSCS RequirementsRequirements of an FSCS include the following. The FSCS must:

• have full monitoring and manual control capability over all smoke control systems and equipment

• have the capability to override (partially or in full) any operation in progress, including programmed actions, non-smoke control manual overrides, and non-smoke control bypasses

• have highest priority over all smoke control systems and equipment

• have a building diagram clearly indicating the type and location of all smoke control equipment

• have indication of the actual status (not the command status) of systems and equipment used for smoke control. This includes both the full open status and the full closed status of each smoke control damper, the status of each fan used for smoke control.

• activate an audible signal if the operation proof sensor (binary feedback point) failed to provide positive feedback that its command was executed within the allowed response time

• have its alarm horn turned on by all hardware supervision alarms, such as binary feedback alarms on fans and dampers, as well as the system troublepoints

• be the only FSCS on a Metasys network used for smoke control applications, unless multiple FSCSs are approved by the AHJ

Note: Use the UL listed annunciator panel as your FSCS. The panel is available from:

Automation Displays, Inc. (ADI)3533 N. White AvenueEau Claire, WI 54703(715) 834-9595

A custom annunciator-type FSCS can be connected to any UL 864 UUKL Listed NAE55 in the network.

Page 10: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin10

Smoke Control Restrictions per UL 864 UUKL Smoke control system restrictions per UL 864 UUKL follow. Do not use:

• the fire alarm system manual pull stations to initiate automatic smoke control sequences. Only automatic alarm initiating devices such as smoke, heat, or flame detectors should be used.

• a duct-type smoke detector to initiate a smoke control strategy except as detailed in the Smoke Control Strategies section of Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684).

• the web browser user interface to provide smoke control. The UL listing does not include the Web browser user interface for smoke control and as an FSCS.

• any Ethernet communication equipment that is not UL listed. All NAE networks are Ethernet-based. Refer to the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684) for more information.

• NIE to perform smoke control sequence operation

• any equipment that is not UL Listed

DX-9100 Controller ApplicationsThe following are smoke control system restrictions per UL 864 UUKL for the DX-9100 controller applications:

• The buttons on the face of the DX-9100 controller cannot be used to override smoke control points.

• Any DX-9100 controller used for smoke control must be locked in an enclosure (for example, EN-EWC25-0) to prevent unauthorized access.

N1 Network ConnectionsFor information beyond what is in this section, refer to:

• Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684)

• the manufacturer’s information packaged with the devices

Follow these additional guidelines when installing the equipment in this chapter:

• Use an American Power Conversion (APC) ProtectNet model PNET1 Ethernet/token ring port surge protector for LAN equipment on all RJ45 lines to protect against signal transients. Contact American Power Conversion at 1-800-800-4272.

Page 11: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 11

• Use a Tripp Lite ISOBAR8ULTRA power line surge protector or a Tripp Lite ISOBARBAR12ULTRA power line surge protector on all 110-120 VAC power sources. Use one of these two surge protectors on all devices in the smoke control system that use AC power. Contact Tripp Lite at www.tripplite.com.

Fiber-Optic CablesUse fiber-optic cable that has the following characteristics:

• 10BaseFL

• plastic optical fibers

• multimode

• 6560 feet (2000 meters) maximum length

• ST-style connectors (820nm wavelength) or MTRJ-style connectors (1300 nm wavelength)

Step 1: Line up the peg on the cable with the slot on the connector.

.

Step 3: Push forward and twist to lock in place.

Push

Twist

Collar

Peg

Twist

Step 2: Twist the collar on the cable to line up with the peg on the connector.

Figure 1: Using ST-Style Connectors on Fiber-Optic Lines

Page 12: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin12

Copper CablesUse copper cables (10BaseT, Twisted Pair) with 4-pair RJ45 connectors for connections between RJ45 ports on switches, media converters, and Ethernet Network Interface Cards (NICs). Use cables less than 100 meters (328 feet) in length. Use straight-through cables, do not use crossover cables.

Use copper cable that has the following characteristics:

• 10BaseT, Unshielded Twisted Pair

• 2.5 meters (8.2 feet) minimum distance between nodes

• 100 meters (330 feet) maximum length

• RJ45 connectors

MTRJ-style Connector for Multimode Fiber-Optic Lines

Step 1. Align plug on cable with port on device.

Step 2. Insert plug into port.

Step 3. Push forward slightly to lock into place.

MTRJ-Style Porton Device for

Multimode Fiber-Optic Lines

Figure 2: Using MTRJ-Style Connectors on Fiber-Optic Lines

Page 13: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 13

Verify that copper cable connected to media converters does not leave the room in which the media converter is installed. Use an American Power Conversion (APC) ProtectNet (Model PNET1) surge protector on each cable segment to prevent electrical surges.

Media ConvertersFollow these additional guidelines when installing the media converters:

• Keep copper cables in the same room as media converters. Use Category 5 copper cables with RJ45 connectors. Cables must be 6 meters (20 feet) or less in length.

• Use an AC to DC power adapter to provide power to the media converters. Secure the power adaptors in a locked enclosure with a UL Listed terminal strip. See the Universal Packaging Module Technical Bulletin (LIT-6363070).

Step 1. Align plug on cable with port on device.

Step 2. Insert plug into port.

Step 3. Push forward slightly to lock into place.

R 45 Female Port on DeviceJ

Figure 3: Using RJ45 Style Connectors on Copper Cables

Back ViewPort for Plug

from Power Adapter

ST-style Connectors for Fiber-Optic lines

PWRNML

REC

LNK

10Base-T

MDI-XMDI

RECLNK

10Base-FRXTXFiber Link Test

10 Mbps (Media Converter NU-MC101-0)

Front View

R 45 Connectors for Copper CablesJ

Figure 4: 10 Mbps Media Converter Connector Locations

Page 14: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin14

Ethernet Network Interface CardWhen using an NCM connected to an NIE for output, the NU-ETH101-0 Ethernet Network Interface Card (NIC) is configured at the factory for smoke control applications. The end user must not alter the Ethernet network interface card in any way.

Install the Ethernet network interface card (NU-ETH101-0) into the NU-NCM350-8 using information in the previously mentioned documents and the Network Control Module 300 Series Technical Bulletin (LIT-6360251).

Back ViewPort for Plug

from Power Adapter

PWRFXTX

RXTX

ST-style Connectors for Fiber-Optic lines

Front View

100 Mbps Media Converter (NU-MC102-0) in Enclosure (NU-CH101-0)

R 45 Connectorfor Copper Cables

J

Figure 5: 100 Mbps Media Converter Connector Locations

Coaxial cable conectionDo Not Use

AUI Port

If Present)Do Not Use (

R 45 port for copper cableJ

Green LED

Figure 6: Ethernet Network Interface Card

Page 15: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 15

SwitchesSwitches are rack-mounted isolating devices, allowing connection of smoke control systems and non-smoke control systems. Use 10 Mbps cables for Metasys system communication. Use 100 Mbps cables for uplink to other systems.

Copper Switch with RJ45 ConnectorsThe ports on the NU-RJ45SW1-0 Copper Switch with RJ45 Connectors are 10/100 Mbps and automatically detect which communication speed is used, allowing any of the ports to be used for 100 Mbps uplink. It also automatically detects whether the communication is half-duplex or full duplex.

Fiber-Optic SwitchThe NU-FIBSW1-0 and NU-FIBSW2-0 Fiber-Optic Switches have twelve ST-style fiber-optic ports, two MTRJ-style fiber-optic ports, and two RJ45-style ports. The RJ45 ports are 10/100 Mbps. Use a straight-through RJ45 cable to connect to a computer. Use a crossover RJ45 cable to connect to another switch. This switch requires power to be hard-wired.Table 2: Fiber-Optic Switch Ports Ports Connector Style Communication Speed1-12 ST 10 Mbps13-14 MTRJ 100 Mbps1

1. 100 Mbps ports can be used for uplink.

15-16 RJ452

2. Lines from RJ45 ports must stay in the same room unless surge protectors are used. With surge protectors installed, lines can extend up to 100 meters.

Back View

100-240VAC

Front View

1

13

12

24

R 45 Connectors for Copper CablesJ

R 45 Connectors for Copper CablesJ

Figure 7: RJ45 Copper Switch

Page 16: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin16

WiringCommunication wiring of all products is supervised. Power wiring of all products is unsupervised. Use wire with the following specifications when wiring power to the fiber-optic switch:

• 3-conductor cable

• 600 Volts, 20 Amperes AC Insulated wire

• 12 to 18 AWG (without terminal lugs);14 to 18 AWG (with terminal lugs)

• Less than 10 meters (32 feet) length

Smoke Control Network Automation EngineThe MS-NAE5510-0U Network Automation Engine (NAE) is the only acceptable network automation engine for smoke control. Refer to the NAE55/NIE Installation Instructions (Part No. 24-10051-0) for information on installing the NAE. The Smoke Control NAE cannot have an internal modem or LONWORKS® interface card. The Smoke Control NAE must be in a locked enclosure.

Front View

Port 12Port 11Port 10Port 9Port 8Port 7Port 6Port 5Port 4Port 3Port 2Port 1

Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx Rx RxTx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx Tx

ST-style Connectors for Fiber-Optic lines

P 1SP 2S

Port 16

Port 14

Port 15

Port 13

Reset

MTRJ-Style Connectors

for Fiber-Optic lines

R 45 Connectorsfor copper lines J

Back View

R 232 PORTS

Do not use

FAILSAFE

Do not use

POWER SUPPLY 1

Input Power Terminals

Do not change or remove this ground wire.Figure 8: Fiber-Optic Switch

Page 17: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 17

Electrical SpecificationsSee Table 3 for basic electrical specifications on Ethernet communications devices. All Ethernet-specific N1-level devices (except switches) listed in Table 3 have power-limited, supervised wiring. Switches have non-power-limited wiring for the input power source. See the Universal Packaging Module Technical Bulletin (LIT-6363070) for information on installing an enclosure with a power box. See the manufacturer’s information packaged with each device for more device-specific information.

N2 Network ConnectionsMetasys Field Interface Point Types

See Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684) and the N2 Integration with NAE Technical Bulletin (LIT-1201683) for more information.

Type 2, Modules Rated as Power-Limited OnlyFor Type 2 modules (power-limited only), field wiring must be segregated from non-power-limited wiring. In application specific products, this is not a problem because all field wiring is power-limited.

• AP-VMA Series

• AS-AHU Series

• AS-UNT Series

• AS-VAV Series

• XPA-8x1-5

Table 3: Electrical Specifications for Ethernet-Specific N1-level DevicesProduct Code Number

Product Electrical Specifications

NU-FIBSW1-0 Unmanaged Fiber-Optic Switch 120 VAC, 60 Hz, 0.3 A, 35 VA

NU-FIBSW2-0 Managed Fiber-Optic Switch 120 VAC, 60 Hz, 0.3 A, 35 VA

NU-RJ45SW1-0 Copper Switch 120 VAC, 60 Hz, 0.5 A, 30 Watts continuous

NU-ETH101-0 Ethernet Network Interface Card 5 VDC ±5%, 1 A, 5 Watts

NU-MC101-0 10 Mpbs Media Converter External power (AC/DC Adapter) 120 VAC, 60 HzPower Draw of Converter: 12 VDC, 0.5 A, 6 Watts

NU-MC102-0(requires NU-CH101-0)

100 Mbps Media Converter Power supplied from NU-CH101-0Power Draw: 12 VDC, 3.4 Watts

NU-MC103-0(requires NU-CH101-0)1

1. NU-MC103-0 is an alternate to NU-MC101-0 and is available only if NU-MC101 is obsoleted.

10 Mbps Media Converter Power supplied from NU-CH101-0Power Draw: 12 VDC, 2.3 Watts

NU-CH101-01 Single Slot Chassis for NU-MC102-0 and NU-MC103-0

External Power (AC/DC Adapter) 120 VAC, 60 HzAdapter Output to Chassis: 12 VDC, 0.8A, 9.6 Watts

Page 18: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin18

• XPB-8x1-5

• XPT-4x1-5

• XPT-8x1-5

Type 3, Modules Rated as Both Power-Limited and Non-power-Limited (Application Specific)

For Type 3 modules (power-limited/non-power-limited), it is up to the system designer to ensure that modules are segregated, based on application.

In base frame applications, wiring must be grouped by bays. Each bay in a base frame must be dedicated as either power-limited or non-power-limited. Base frames are shipped with a label on each bay stating Power-Limited Field Terminal.

When configuring a base frame and using a bay for non-power-limited field connections, you must use a permanent black marking pen to cover the wording on the label. The only bays that should display this label must be totally dedicated to power-limited field wiring. Bays that do not display this label must be totally dedicated to non-power-limited field wiring. In no case should power-limited field wiring be mixed with non-power-limited field wiring.

The XTM/XPx-xxx product line has labels displaying whether it is power-limited or non-power-limited. For the XPx modules shown in Figure 4, if the field wiring is non-power-limited, the power-limited label must be covered with a black permanent marking pen as explained above. For a specific module, only one type of wiring may be used per side on the module.Table 4: Power-Limited and Non-Power-Limited ModulesModule TypeXPE-4xx-5XPL-4xx-5XPM-4xx-5

Input (also with Relay): Connect these contacts to a UL Listed Class II or Class III source of supply to be considered a power-limited module. If not connected as described above, follow the guidelines defined in the Wiring Segregation section.

Page 19: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 19

RepeaterInstall the repeater inside a UL Listed enclosure (see Enclosures). The repeater provides isolation on the N2 end of a smoke control system. Input and output wiring is supervised and power-limited. The repeater has non-power-limited wiring for the input power source. Refer to the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684) and the N2 Communications Bus Technical Bulletin (LIT-636018).

Use wire with the following specifications when wiring power to the repeater:

• 600 Volts, 20 Amperes AC Insulated 3-conductor cable

• 12 to 18 AWG (without terminal lugs); 14 to 18 AWG (with terminal lugs)

• Less than 32 feet (10 meters) length

Table 5: Electrical Specifications for the N2-Level Repeater Product Code Number

Product Electrical Specifications

NU-RPT101-0 N2 Repeater 120 VAC, 60 Hz, 0.5 A, 60 VAPOWERFAULT

ATXA B

TXB A

FAULT B S1

1 - 3002 - 6003 - 12004 - 2400

5 - 48006 - 96007 - 19.2K8 - 38.4K

BAUDRATE

T 2B TB3T 1B

NC

CO

M D D R RT T RS-

485

SID

E A

ACINPUT

G W L124VD

C

24VD

C

CO

M D R RT TDR

TM RS-

485

SID

E B

Not Used

N2 IN (+)

N2 IN (-)

Ground Line 1Not Used Not Used

N2 OUT (+)N2 OUT (-)

REF-OUT REF-IN GND

LO

HINeutral

Figure 9: N2 Repeater

Page 20: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin20

EnclosuresMount NAE55, NIE, NCM350 controllers, DX-9100 controllers, switches, routers and all other equipment in the smoke control network in a UL Listed enclosure. See the installation information packaged with each product.

Power EntryBring input power (120 VAC) into the enclosure in the corner nearest its termination location. For example, the EN-EWC10-45 Series enclosure has a conduit entry area molded into the cover.

Bring power into only these locations based on where the power box is located.

Wiring SegregationThe Air Handling Unit (AHU), Variable Air Volume (VAV) Controller, Unitary (UNT) Controller, and the Variable Air Volume Modular Assembly (VMA), contain only power-limited field connections; therefore, they are not discussed here.

Segregate power-limited/non-power-limited wiring. N1 and N2 communication lines are considered power-limited. Route these communication lines only with other power-limited wiring.

POWER FAULTA TX

A BTX

B AFAULT

BS1

1 - 3002 - 6003 - 12004 - 2400

5 - 48006 - 96007 - 19.2K8 - 38.4K

BAUDRATE

NC

COMDDRR TTRS-485

SIDE A

ACINPUT

GWL1 24VDC

24VDC

COMDRRTT D RTM

RS-485

SIDE B

T2 BTB3 T1 B

EN-EWC10-45 Series Enclosure(Shown with Cover Removed)

Figure 10: N2 Repeater in EN-EWC10-45 Series Enclosure (Shown with cover removed)

Page 21: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 21

Handle the XTM/XPx product line in a similar way (Figure 11). There are no wire trays; maintain segregation of cables using wire ties. For more wiring information on the XTM/XPx product line, see XTM-105 Extension Module, XPx-xxx Expansion Modules Technical Bulletin (LIT-6364200).

Input/Output (IO) Wiring Transient Protection Requirements

UL 864 UUKL Smoke Control Listing requires that any field I/O wire, from monitored or to controlled equipment, respectively, that leaves the room in which the controller is mounted, must be able to withstand signal line transient of 2400 volts and energy levels not less than 0.03 joule or greater than 1.2 joules. To meet this requirement, some of the Metasys system field wiring must be protected by either transzorbs or MOVs. If the hardware you are using is not mentioned in the following sections, no transient protection is required.

When installing the transient protectors (MOVs, transzorbs), care must be taken when installing a protector in close proximity to other protectors. Before installing the protective device in the terminal block, twist it together with the field lead and insert it into the terminal block as one wire. Twist the wire tightly around the transient protection device a minimum of two turns before inserting it into the terminal block.

XTM XPA XPL

XTM XPA XPL

XTM XPA XPL

Power LimitedWiring

Non-power Limited Wiring

3xpmxpa

Figure 11: Power-Limited/Non-Power-Limited Wiring

Transient Protector Leadtrans

Figure 12: Wire for Transient Protection

Page 22: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin22

XTM/XPx ProductsKeep all field wiring, with the exception of the N2, in the same room as the controllers.

AP-VMAKeep all field wiring, with the exception of the N2, in the same room as the controllers.

DX-9100 ProductsWhen using the DX-9100 product line for Listed Smoke Control, there are only two I/O restrictions.

1. Use the DX-9100-xxxxF base. (This base has the transient protection already installed.)

2. When using the XP-9102, if the field wiring leaves the room in which the XP-9102 is installed, install the protection shown in Table 6. (The MOV must be a Johnson Controls Code No. SMOKE-MOVKIT.)

For further information on the DX-9100 product line, refer to the DX-9100 Applications sections in the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684).

NAE55No transient protection is required on any of the I/O terminals of the NAE55. Use only the UL 864 UUKL Listed NAE for smoke control.

NIENo transient protection is required on any of the I/O terminals of the NIE. Use only the UL 864 UUKL Listed NIE inside a smoke control system.

NCM350-8No transient protection is required on any of the I/O terminals of the NCM350-8. Use only the -8 version of the NU-NCM350 for smoke control.

Table 6: Transient Protection for XP-9102I/O Type Protection NeededAnalog Outputs (AOs) Place an MOV from AOx to AOcom for each AO wiring pair

that leaves the room.(x = Analog Output Number)Place an MOV from any AOcom to earth ground for any XP-9102 that has a field wire that leaves the room.

Analog Inputs (AIs) Place an MOV from AIx to AIcom for each AI wiring pair that leaves the room.(x = Analog Input Number)Place an MOV from any AIcom to earth ground for any XP-9102 that has a field wire that leaves the room.

Page 23: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 23

NU-RPT101-0Install tranzorbs on the NU-RPT101-0 on both terminal blocks TB1 and TB2. The tranzorbs must be from tranzorb kit SMOKE-TRNKIT-1, which must be ordered separately.

Install the tranzorbs to terminal blocks TB1 and TB2 using the following procedure:

1. Strip the N2 bus wiring to 0.5 inches.

2. Twist the N2 bus wiring together with the wires from the tranzorbs (SMOKE-TRNKIT-1).

3. Attach the twisted wires to the terminals. Attach the single wire side of the SMOKE-TRNKIT-1 to the COM terminal and the multiple wire side to the D and D- terminals.

AHU, UNT, VAV ProductsInstall MOVs to the AHU, UNT, and VAV products in Table 7. Only terminals in use, and I/O wiring leaving a room where a controller is installed, need transient protection. The MOV must be a Johnson Controls Code No. SMOKE-MOVKIT-0 for terminal block versions. The MOV must be a Johnson Controls Code No. AS-MOVKIT-0 for faston versions.Table 7: Transient Protection for AHU, UNT, and VAV Products I/O Function Module Protection NeededAnalog Inputs (AIs) AHU, VAV, UNT: Install an MOV from each AI to AIcom.Binary Inputs (BIs) AHU, VAV, Mod UNT: Install an MOV from each BI to BIcom.

UNT: Install an MOV from each BI to a 24 VAC terminal.Analog Outputs (AOs) AHU, VAV, UNT, Mod UNT: Install an MOV from each AO to AOcom.Binary Outputs (BOs) AHU, VAV: Install an MOV from each BO to 24 VAC.

UNT: There are three possible ways to configure BOs:With the triacs jumper connected to Common on UNT, install an MOV from each BO to a 24 VAC terminal on UNT.With the triacs jumper connected to 24 VAC on UNT, install an MOV from each BO to a Common terminal on UNT.If using a separate load transformer, install MOV from each BO to the UNT triacs terminal.

N1 Communication Lines (NCM350-8)

None Needed

N2 Communication Lines

None Needed (Except for NU-RPT101-0. See the NU-RPT101-0 heading in this section.)

Page 24: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin24

Metasys System Extended Architecture Smoke Control System Design

Review the following where applicable when designing smoke control systems. See Figure 13.

• Install all IP Ethernet and N1 fiber-optic lines and copper cables in conduit. Ethernet and N1 Bus Fiber-Optic lines with ST connectors have a maximum length of 2000 meters (6560 feet).

• N1 Bus Copper cables with RJ45 connectors must be Category 5 twisted pair.

• When connecting between a media converter and an NCM350, NAE, or NIE, they have a maximum length of 6 meters (20 feet). These cables must stay in the same room as the media converters.

Page 25: Metasys System Extended ... - Product Documentation

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin 25

)

NAE

)

)

)

1 1213 24

N2

VAV

D 9100X

UNT

AHU

SmokeControlNAE

UL ListedN2 Device

NCM 350

VAV

NIE

Smoke Control Fiber-Optic Switch

SmokeControlNAE

N2

VAV

DX9100

UNT

AHU

SmokeControlNAE

SmokeControlNAE

SmokeControlNAE

N2

VAV

DX9100

UNT

AHU

Non UL ListedN2 Device

BACnet Gateway IFC-3030

IFC-2020

IFC-1010

IFC-640

Smoke ControlAsante Switch 1

Smoke ControlAsante Switch 2

Smoke ControlAsante Switch x

10 Mbps

10/100 Mbps

N2

DX9100

UNT

AHU

SmokeControlNAE

N2

DX9100

UNT

AHU

SmokeControlNAE

Non UL ListedN2 Device

Non UL ListedN2 Device

NCM350

VAV

N2 Repeaterin UL ListedEnclosure

MediaConverterFiber to10 Mbps

MediaConverterFiber to

100 Mbps

MediaConverterFiber to10 Mbps

10 MbpsEthernetto Field

10 MbpsEthernetto Field

100 MbpsEthernetto Field

NCM 350

N2 Repeaterin UL ListedEnclosure

Third partydry contact

input

FSCS Panel

PCPC with browser(user interface)

FiberFiberFiber

Existing Building Network (Ethernet)

PC PC with browser(user interface)

UNT

VAVVAV

100 Mbps 100 Mbps

Ethernet CrossoverCable

smok

e co

ntro

l

Figure 13: Metasys System Extended Architecture Smoke Control System

Page 26: Metasys System Extended ... - Product Documentation

Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.

© 2005Johnson Controls, Inc.

Controls Group507 E. Michigan StreetMilwaukee, WI 53202

Published in U.S.A. www.johnsoncontrols.com

Metasys® System Extended Architecture Smoke Control Wiring Technical Bulletin26