Product Information HABeR-24 kV
Model
HABeR-24 kVMedium Voltage Switchgear and Controlgear
IEC 62271-200 7.2/12/17.5kV/24kV
25, 31.5, 40kA
24 kV Medium Voltage Switchgear and Controlgear
Product Information HABeR-24 kV
1
DESCRIPTION Our HABeR-24 kV switchgear conforms fully to
200 standard and is designed and manufactured utilising state
of-the-art technology, comprehensively taking into account
present and future power system requirements.
Mitsubishi Electric has manufactured hundreds of thousands of
medium voltage panels over the last almost 6
HABeR-24 kV MV Switchgear panel utilises our highest quality
vacuum circuit breaker and vacuum contactor components for
which Mitsubishi Electric has gained a sound reputation.
HABeR-24 kV represents an up-to-date and reliable medium
voltage panel design.
FEATURES
High Reliability
9 Type testing of the HABeR-24 kV was performed by an
independent external testing and certification authority
IEL, in Europe
9 HABeR-24 kV is designed with the benefit of Mitsubishi’s
vast medium voltage panels production experience of
hundreds of thousands of panels over the last almost 60
years.
9 All components, such as current transformers, voltage
transformers and multi-function relays are made of the
highest quality materials.
9 Heat stress analysis of the switchgear structure has led
to a heat-resistant design in which circuit breakers up to
4000A are self-cooled (i.e. cooling fans not required).
9 Strongly reduced number of parts reduces the chance of
failure.
Easy Installation
9 Installation and testing duration are considerably r
duced as the panel is tested and adjusted in the fa
tory and then delivered as a complete unit.
Flexible Design
9 Panels with main circuit and control cable entry from
either the top or bottom are available.
to the IEC 62271-
200 standard and is designed and manufactured utilising state-
taking into account
present and future power system requirements.
Mitsubishi Electric has manufactured hundreds of thousands of
medium voltage panels over the last almost 65 years – the
es our highest quality
vacuum circuit breaker and vacuum contactor components for
sound reputation.
date and reliable medium
Type testing of the HABeR
testing and certification authority,
(Instytut Elektrotechniki, IEL)
40kA internal arc fault test of MS
MS-EBG with gas exhaust duct
was performed by an
independent external testing and certification authority,
is designed with the benefit of Mitsubishi’s
vast medium voltage panels production experience of
hundreds of thousands of panels over the last almost 60
All components, such as current transformers, voltage
function relays are made of the
Heat stress analysis of the switchgear structure has led
resistant design in which circuit breakers up to
cooled (i.e. cooling fans not required).
d number of parts reduces the chance of
Installation and testing duration are considerably re-
duced as the panel is tested and adjusted in the fac-
tory and then delivered as a complete unit.
and control cable entry from
Safety
9 Partitions between compartments and an automatic
shutter system (for withdrawable equipment primary
junctions) completely isolate live parts.
9 Safe operation and maintenance is
adoption of comprehensive interlocking mechanisms.
9 In the event of an internal arc fault, the
signed to withstand the huge pressur
effect of the arc
panel open to limit pressur
9 Withdrawable equipment is inserted / withdrawn
whilst the front panel door is closed so that any arc
proof rating is not compromised (compliant with IEC
62271-200 requirements).
Protection
9 Mitsubishi Melpro-
tection relays are installed as standard. These relays
provide protection, measurement, communications
and control functionality
Standard multiple protection relay options available
Model EMC Model MEprotect
-24 kV by the independent external
testing and certification authority, Electrotechnical Institute
, IEL) in Warsaw, Poland.
ternal arc fault test of MS-EBG at IEL laboratory, Warsaw
EBG with gas exhaust duct
MS-EBG with gas screen
Partitions between compartments and an automatic
shutter system (for withdrawable equipment primary
junctions) completely isolate live parts.
Safe operation and maintenance is ensured with the
adoption of comprehensive interlocking mechanisms.
In the event of an internal arc fault, the MS-EBG is de-
signed to withstand the huge pressure and scorching
effect of the arc (relief flaps located on top of the
panel open to limit pressure).
Withdrawable equipment is inserted / withdrawn
whilst the front panel door is closed so that any arc
proof rating is not compromised (compliant with IEC
200 requirements).
-D, EMC or MEprotect Multiple Pro-
s are installed as standard. These relays
provide protection, measurement, communications
and control functionality
Standard multiple protection relay options available
Model MEprotect
Model Melpro-D
Product Information HABeR-24 kV
2
3
APPLICATIONS
9 HABeR-24 kV from HULANICKI BEDNAREK Ltd.
provides control and protection of the power supply
to motors, transformers, capacitors and other feeder
circuits.
9 The HABeR-24 kV is available at rated voltages of 3.6
to 24 kV, with rated short-circuit breaking capacities
from 25 to 40 kA.
9 HABeR-24 kV is designed for indoor use and is pa
ticularly suitable for electric power plants, subst
tions, industrial plants, commercial buildings, pum
ing stations, pipeline stations and transportation sy
tems.
MS-EBG Panel Detail
STANDARD RATINGS
Control (low voltage)
compartment
Reinforced
inspection window
Multiple
protection relay
Withdrawable
vacuum circuit breaker
Withdrawable
fused vacuum contactor
Option: voltage
transformers
HULANICKI BEDNAREK Ltd.
provides control and protection of the power supply
to motors, transformers, capacitors and other feeder
is available at rated voltages of 3.6
circuit breaking capacities
is designed for indoor use and is par-
ticularly suitable for electric power plants, substa-
tions, industrial plants, commercial buildings, pump-
ing stations, pipeline stations and transportation sys-
ATINGS
1. Switchgear and control
Control (low voltage)
compartment
Self-cooled
horizontal busbars
Cable
compartment
Option: current
transformers
Option: voltage
transformers
Ratings Manufacturer Type designation Applied standard Rated voltage
(2)
Rated frequency Rated insulation level
(3)
Short - duration power frequency
withstand voltage, 1 min Lightning impulse withstand
voltage
kV peak
Rated normal main busbar current
Rated short -time withstand
current, symmetrical Rated peak withstand current kA peak
Rated duration of short -circuit Loss of Service Continuity
category Internal Arc Classification
(5)
Accessibility type Arc test current Arc test current duration
Service Conditions Location Ambient temperature Altitude above sea level Humidity R.H. Water vapour pressure Earthquake protection
(6)
Horizontal seismic withstand
(7)
Vertical seismic withstand
Features Type test
(8)
Withdrawable equipment
(9)
position Withdrawal / insertion method
Maintenance access
1 High- voltage switchgear and control - gear
control -gear for rated voltages above 1 kV and up to and including 52 kV.
2 12 kV and 15 kV apply to switchgear.
3 28 kV rms (75 kV peak) and 36 kV rms (95 kV peak) apply to switchgear.
4 3150 A apply to 7,2 kV and 12 kV switchgear.
5 Optional
6 General use, class B on the upper floor or roof of building according to JEM
7 Static acceleration of horizontal is 3,92 m/s2 at base of structure.
8 Internal arc fault test.
9 Circuit breaker / Fused contactor /
Voltage transformer.
Switchgear and control-gear
HULANICKI BEDNAREK Ltd.
HABeR-24 kV
IEC 62271-200 (1)
kV rms Ur 7.2 12 17.5 24
Hz f r 50, 60
kV rms Ud 20 28 36 xx
kV peak Up 60 75 95 xx
A rms Ir 630, 1250, 2000, 3150, 4000(4)
kA rms Ik 25, 31.5, 40
kA peak Ip 50 Hz: 2.5 × Ik, 60 Hz: 2.6 × Ik
sec t k 1, 3
LSC2B -PM
IAC AFL, AFLR
kA 25, 31.5, 40 sec 0.1, 0.5, 1.0
Indoor °C - 5 to +40 m 1000 max. % 95 max.
kPa 2.2 average
m/s
2
9.80 m/s
2
3.24
IEL (Warsaw)
Mid -mount
External operation (with door closed)
Front & rear, Front
gear - Part 200: AC metal -enclosed switchgear and
gear for rated voltages above 1 kV and up to and including 52 kV.
and 36 kV rms (95 kV peak) apply to switchgear.
kV and 12 kV switchgear.
General use, class B on the upper floor or roof of building according to JEM -TR 144.
Static acceleration of horizontal is 3,92 m/s2 at base of structure.
Voltage transformer.
Product Information HABeR-24 kV
2. Vacuum circuit breaker
Withdrawable vacuum
circuit breaker
Short-duration power frequency
withstand voltage, 1 min.
kV rms Ud 20 28
Lightning impulse withstand voltage kV peak Up 60 75
Rated short-time withstand
current
kA rms Ik
Rated peak withstand current kA rms Ip 50 Hz: 2,5
Rated duration of short-circuit sec T k Rated cable -charging breaking
current
A rms Ic
Rated short-circuit breaking
current
kA rms Isc 25, 31
Transient Recovery Voltage (TRV) Reference voltage kV Uc 12.3 20
Rate of Rise of Recovery Voltage
(RRRV)
kV/µ s U c /t3 0.24 0.
Rated break time cycles Rated short-circuit making
current
kA peak 63, 78
Rated control voltage Vdc U a 48, 110, 220
Rated operating sequence O-3min
O-0.3sec
CO
Closing operation Motor current (at 110Vdc)
A 1,2 (peak 6 A)Spring charging time
sec Approx. 6 (after
Closing control current (at 110 Vdc) A Tripping control current (at 110Vdc) A Auxiliary switch (contacts) Weight kg M 630 A, 1250
2000
3150
4000A: 440
1 Rated short - circuit breaking current
25 kA :
2 5 31.5 kA :
3 2 40 kA :
4 0
2 North American rating (range I, series II in IEC).
3 3150 A appl ies only to 7.2 kV and 12 kV switchgear.
4 4000 A appl ies
to 12 kV /50kA switchgear.
5 31.5kA
and 40kA not for 17.5k and 24kV switchgear
Manufacturer .
Type designation 6/10 /20
Applied standard IEC 62271
Rated voltage kV rms Ur 7.2 12
Rated frequency Hz f r Rated normal current (self-
cooling)
A Ir
Rated insulation level
HULANICKI BE
630-4000
25; 31,5;
3. Fused vacuum contacto
Withdrawable vacuum
circuit breaker
Manufacturer Type designation Applied standard Rated voltage kV rms
Rated insulating voltage kV rms
Rated frequency
Rated operation al current (self-
cooling) Rated insulation level
Short -duration power frequency
withstand voltage, 1 min.
kV rms
Lightning impulse withstand voltage kV peak
Rated short -circuit breaking
current
kA rms
Rated control voltage Closing control current (at 100Vdc) Tripping control current (at 110Vdc) Auxiliary switch (contacts) Rated short -time withstand
current
kA
Weight
1 Power fuse rating
25 k A:
02 50 kA:
05
100kA: 10
150kA: 15
200kA: 20
300kA: 30
400kA: 40
Contactor rating: 200A – suffix 2VN, 400A –
suffix 4VN
28 36 50
75 95 125
50 Hz: 2,5xIk, 60 Hz: 2,6xIk 3
10, 25
25, 31.5, 40 (5)
20.6 25.7 xx
.34 0.34 xx
3 63, 78.8, 100
48, 110, 220 in- CO-3minCO
sec-CO- 3min-CO CO- 15sec -CO
1,2 (peak 6 A)
x. 6 (after closing) 3.4 3.4
5a, 5b A, 1250 A: 140 2000 A: 160 3150 A: 210 4000A: 440
/20 -VPR -
D (1 )
IEC 62271- 100
12 17.5(2)
24 50, 60
(
)
HULANICKI BEDNAREK Ltd.
4000 630
- 3150
630
- 2500
31,5; 40 25
- 31,5
ontactor
.
F2VN or - 4VN (1)
IEC 60470 kV rms Ur 6.6 kV rms 7.2
Hz f r 50, 60
A Ir 200, 400
kV rms Ud 20
kV peak Up 60 kA rms Isc 40 (Power fuse)
Vdc Ua 100, 110, 200, 220 A 4.8 A 4.5 (mech. latch type)
2a, 2b kA rms Ik 25, 31.5, 40
kg M 200 A: 90 400A: 90 (for 3.3kV)
400A: 100 (for 6.6kV)
suffix 4VN
HULANICKI BEDNAREK Ltd.
Product Information HABeR-24 kV
4
CONSTRUCTION
1. Enclosure and partitions
9 The all-metal enclosure is completely earthed. Each co
partment (control, withdrawable equipment, busbar and c
ble) is segregated from other compartments by earthed
metal partitions.
9 The front of the HABeR-24 kV is divided into
ments. The upper or low-voltage compartment is the control
compartment; the middle one is the withdrawable equi
ment compartment, while the bottom compartment can be
used for maintenance access. (See Figure 4
9 Multi-function relays, meters, protective relays, control
switches, etc.are semi-flush mounted on the door of the
control compartment.
Front compartments of HABeR-24 kV
switchgear
metal enclosure is completely earthed. Each com-
partment (control, withdrawable equipment, busbar and ca-
ble) is segregated from other compartments by earthed
is divided into 3 compart-
compartment is the control
the middle one is the withdrawable equip-
he bottom compartment can be
used for maintenance access. (See Figure 4-1.)
meters, protective relays, control
flush mounted on the door of the
1. Gas exhaust duct or gas
screen (optional)1
2. Ventilator 2
3. Control compartment
4. Withdrawable equipment
compartment
5. Busbar compartment
6. Cable compartment
7. Circuit breaker
8. Earthing switch (optional)
9. Power cable
1. Gas exhaust duct or gas screen
required when Internal Arc Classific
tion selected. Refer to p. 11for more
detail.
2. When the current within a compar
ment is 2000 A or greater, a ventil
tor is required for that compartment.
However, not required if gas exhaust
duct used.
3. Earthing truck is applied for 17.5 &
24kV switchgear with Ik> 25 kA
2. Busbar
9 The main busbar is made of copper
conductor.
9 HABeR-24 kV has bare busbars as stan-
dard. However, when required, the
busbar can be insulated.
9 Furthermore, bus joints – suchas busbar joints between
can be shrouded with insulating covers.
9 Other joints, such as those at the cable terminals, are covered with insula
ing tape.
9 Connecting bars, such as those between busbars and circuit breaker bus
ings, or circuit breaker bushings and cable terminals, may also be optionally
insulated.
9 Tin-plating at joints is standard. Tin-plating of the entire busbar is optional.
Gas exhaust duct or gas
Withdrawable equipment
Earthing switch (optional)3
Gas exhaust duct or gas screen
required when Internal Arc Classifica-
for more
within a compart-
ment is 2000 A or greater, a ventila-
tor is required for that compartment.
However, not required if gas exhaust
Earthing truck is applied for 17.5 &
24kV switchgear with Ik> 25 kA
The main busbar is made of copper
n-
dard. However, when required, the
Main busbars (air insulated)
suchas busbar joints between adjacent panels,
can be shrouded with insulating covers.
Other joints, such as those at the cable terminals, are covered with insulat-
Connecting bars, such as those between busbars and circuit breaker bush-
ble terminals, may also be optionally
plating of the entire busbar is optional.
Product Information HABeR-24 kV
3. Vacuum circuit breaker
9 The VCB is easy to operate, with the closing spr
charge indicator, the manual close and trip buttons,
the operation counter and mechanical ON / OFF ind
cator all being located on the front of the circuit
breaker. (See Figure 4-3.)
9 The circuit breaker has two positions, Service and
Test/Disconnected, and may be optionally padlocked at
each position. When the VCB is closed, the VCB locks
in each position by mechanical interlock. When the
VCB is opened, the interlock pin is released.
9 The circuit breaker can be easily drawn out or inserted
by a simple rotation action. (See Figure 4
complished with the circuit breaker compartment door
closed. Unauthorised racking can be prevented by pa
locking the shutter for the draw-out handle aperture.
9 Circuit breakers of different ratings other than spec
fied are mechanically prevented from being inserted
into the Service position.
9 The control circuit terminal of the circuit breaker is of manual connection type. The connector (see Figure 4
tached when the VCB is in the Test/ Disconnected
i. The circuit breaker cannot be inserted to the Service position when the control circuit terminals are not connected.
ii. The control circuit terminals cannot be disconnected when the circuit breaker is in
4. Fused vacuum contactor
9 The fused vacuum contactor is easy to operate, with
ual trip button for mechanical latch type,
counter and mechanical ON / OFF indicator all lo
front of the fused contactor. (Fig. 4-4)
9 The fused contactor has two positions, Service and
Test/Disconnected, and may be optionally padlocked at each
position. When the contactor is closed, the fused contactor
locks in each position by mechanical interlock. When the co
tactor is opened, the interlock is released.
9 The fused contactor can be easily drawn out or inserted by a
simple rotation action (Fig. 4-4) with the fused contactor
compartment door closed.
9 Unauthorised racking can be prevented
shutter for the draw-out handle aperture.
9 The control circuit terminal of the fused contactor is of ma
ual connection type. The connector (Fig
tached when the fused contactor is in the Test/ Disconnected
position, with following mechanical interlocks:
i. The contactor cannot be inserted to the Service position
when the control circuit terminals are not connected.
ii. The control circuit terminals cannot be disconnected
when the contactor is in the Service position.
9 Contactor of different ratings other than specified can be (o
tionally) mechanically prevented from being inserted into the
Service position.
Fig 4.3 Vacuum circuit breaker details
The VCB is easy to operate, with the closing spring
charge indicator, the manual close and trip buttons,
the operation counter and mechanical ON / OFF indi-
cator all being located on the front of the circuit
The circuit breaker has two positions, Service and
and may be optionally padlocked at
each position. When the VCB is closed, the VCB locks
in each position by mechanical interlock. When the
VCB is opened, the interlock pin is released.
The circuit breaker can be easily drawn out or inserted
ation action. (See Figure 4-3.) This is ac-
complished with the circuit breaker compartment door
closed. Unauthorised racking can be prevented by pad-
out handle aperture.
Circuit breakers of different ratings other than speci-
ied are mechanically prevented from being inserted
The control circuit terminal of the circuit breaker is of manual connection type. The connector (see Figure 4
tached when the VCB is in the Test/ Disconnected position, and has the following mechanical interlocks.
The circuit breaker cannot be inserted to the Service position when the control circuit terminals are not connected.
The control circuit terminals cannot be disconnected when the circuit breaker is in the Service position.
Fig 4.3 Fused v
The fused vacuum contactor is easy to operate, with a man-
ual trip button for mechanical latch type, an operation
counter and mechanical ON / OFF indicator all located on the
The fused contactor has two positions, Service and
Test/Disconnected, and may be optionally padlocked at each
position. When the contactor is closed, the fused contactor
ical interlock. When the con-
tactor is opened, the interlock is released.
The fused contactor can be easily drawn out or inserted by a
4) with the fused contactor
Unauthorised racking can be prevented by padlocking the
out handle aperture.
The control circuit terminal of the fused contactor is of man-
ual connection type. The connector (Fig. 4-4) can be only at-
tached when the fused contactor is in the Test/ Disconnected
chanical interlocks:
cannot be inserted to the Service position
when the control circuit terminals are not connected.
The control circuit terminals cannot be disconnected
is in the Service position.
f different ratings other than specified can be (op-
tionally) mechanically prevented from being inserted into the
Fig 4.3 Vacuum circuit breaker details
The control circuit terminal of the circuit breaker is of manual connection type. The connector (see Figure 4-3) can be only at-
position, and has the following mechanical interlocks.
The circuit breaker cannot be inserted to the Service position when the control circuit terminals are not connected.
the Service position.
Fused vacuum contactor details
Product Information HABeR-24 kV
5. Automatic Shutters
9 Inserting the withdrawable equipment into the Service pos
tion causes the shutters toautomatically open. Drawing the
withdrawable equipment out to the
Test/Disconnectedposition causes the shutters to move and
cover the primary junction contacts.
9 As shown to the right, the shutters operate on the busbar and
cable sides. The shutters forthe upper and lower primary
junctions can be closed and opened individually, and canbe
(optionally) padlocked in the closed position.
9 The shutters are made of galvanised steel
labels are provided.
i. “BUSBAR” on shutter for busbar (line) side.
ii. “CABLE” on shutter for cable (load
9 The shutters can be (optionally) provided with a manually
operated device to keep it in the opening position. The fun
tion of the device is cancelled by insertion of withdrawable
equipment.
7. Wiring
9 Necessary control equipment such as auxiliary relays, term
nal blocks and fuses are located in the control compartment.
9 Ducting and bundling ensure that control wiring is systematic
and neat.
9 External control cable can be terminated to both sides of the
compartment.
9 All wiring to devices mounted on the door
damage during opening orclosing by vinyl
Shutters open
ent into the Service posi-
tion causes the shutters toautomatically open. Drawing the
withdrawable equipment out to the
Test/Disconnectedposition causes the shutters to move and
erate on the busbar and
cable sides. The shutters forthe upper and lower primary
junctions can be closed and opened individually, and canbe
(optionally) padlocked in the closed position.
galvanised steel and the following
“BUSBAR” on shutter for busbar (line) side.
“CABLE” on shutter for cable (load or feed) side.
The shutters can be (optionally) provided with a manually
operated device to keep it in the opening position. The func-
d by insertion of withdrawable
Shutters operated individually
6. Cable compartment / Current transformers
9 Moulded-type current transformers are installed in the cable
compartment.
9 Only the highest quality IEC 61869-2 compliant CTs are deployed
in the HABeR-24 kV
Necessary control equipment such as auxiliary relays, termi-
nal blocks and fuses are located in the control compartment.
that control wiring is systematic
External control cable can be terminated to both sides of the
iring to devices mounted on the door is protected from
damage during opening orclosing by vinyl spiral tubing.
Shutters closed
Shutters operated individually
Cable compartment / Current transformers
type current transformers are installed in the cable
2 compliant CTs are deployed
Product Information HABeR-24 kV
5
STANDARD DESIGN
1. Enclosure & Structure
9 Steel thickness is a minimum of 2 mm
- Side cover (both ends of arrangement) : 2.0 mm
- Frame: 2.0 mm
- Door: 2.0 mm
- Ceiling plate: 2.0 mm
- Bottom plate: 2.0 mm
- Internal partitions: 2.0 mm
- Mounting plates: 2.0 mm
9 Standard front door / rear cover
Position Structure Hinge location Handle location
Front: Hinged doors (× 3) Left
Rear: Bolted covers (× 2) -
9 Degree of protection
- Enclosure: IP4X
- Internal partitions: IP2X
2. Busbar and connecting copper
9 Conductor material: copper (DIN EN 13601
9 Surface treatment: tin plating at busbar joints
9 Auxiliary apparatus: high voltage insulated wire
3. Busbar and connecting copper
9 Conductor material: copper (DIN EN 13601
9 Surface treatment: none (bare)
9 Standard dimensions: 6 mm × 25 mm
4. Busbar and connecting copper
9 Wiring system: duct or bundled
9 Insulation: 600 V heat-resistant plastic (PVC)
9 Size: 1.25 mm2
9 Colour: yellow, except for earth wire (green)
9 Wire numbering: indicated by "tube" ferrule
The VT / CT test terminals and terminal blocks show
adopted as standard:
GN
Side cover (both ends of arrangement) : 2.0 mm
Handle location Handle lock
Right Optional
- -
DIN EN 13601)
Surface treatment: tin plating at busbar joints
Auxiliary apparatus: high voltage insulated wire
DIN EN 13601)
resistant plastic (PVC)
Colour: yellow, except for earth wire (green)
Wire numbering: indicated by "tube" ferrule
rminals and terminal blocks shown below are
5. Phase / polarity arrangement and colour
coding
9 Main circuit and control circuit arrangements are as
follows:
AC 3-phase: Wire
1st phase
2nd phase
3rd phase
Neutral (if present)
(Viewed from front to back, top to bottom, or left to right from front.)
AC 1-phase: Wire
1st wire
Neutral
(Viewed from front to back, top to bottom, or left to right from front.)
DC: Wire
1st wire
2nd wire
(Viewed from front to back, top to bottom, or left to right from front.)
9 Main circuit colour i
nyl tape or coloured label at bus end where main c
bles are connected.
9 Unless specially requested, the control circuit is not
colour coded.Identifying colour tube markers, with
the standard colours shown
installed.
6. Withdrawable equipment
Apparatus
Vacuum Circuit
Breaker
Fused Vacuum
Contactor
Voltage Trans-
former
7. Withdrawable equipment
9 The withdrawable equipment has the following two
positions:
Service:
Test/Disconnected:
9 The front door can be opened / closed when the
withdrawable equipment is
tion.
Phase / polarity arrangement and colour
Main circuit and control circuit arrangements are as
Designation IEC60445 Optional
L1 Brown Red
L2 Black Yellow
L3 Grey Blue
N Blue Black
(Viewed from front to back, top to bottom, or left to right from front.)
Designation IEC60445 Optional
L1 Brown Red
N Blue Black
om front to back, top to bottom, or left to right from front.)
Designation IEC60445 Optional
Positive Red Red
Negative Black Blue
(Viewed from front to back, top to bottom, or left to right from front.)
Main circuit colour identification is achieved with vi-
nyl tape or coloured label at bus end where main ca-
bles are connected.
Unless specially requested, the control circuit is not
colour coded.Identifying colour tube markers, with
the standard colours shown above, can be optionally
Withdrawable equipment
Main circuit Control
circuit
Earthing
circuit
Automatic
connection
(self-
aligning)
Manual
Connection
Automatic
connection
(earthing
shoe)
Withdrawable equipment positions
The withdrawable equipment has the following two
Main and control circuit – Connected
: Main circuit – Disconnected
Control circuit – Connected (manual
disconnection possible)
he front door can be opened / closed when the
withdrawable equipment isTest/Disconnected posi-
Product Information HABeR-24 kV
8. Safety interlocks
Action
Interlock Conditions VCB / VMC
State
Rack withdrawable eqpt. OFF
Operate earthing switch --
Open withdrawable eqpt. door --
Close withdrawable eqpt. door --
Open cable door --
Disconnect control circuit --
Close VCB /VMC n/a
1. The earthing switch can be optionally provided
2. Excludes VT panel
9. Painting and colour
9 External enclosure surfaces: Surfaces are first cleaned and pre
applied.
9 Internal enclosure surfaces: As for external coa
9 Finish colour:
- Enclosure: Light beige (RAL 9001).
- Frame, meter covers, control devices and protection relay cases:
10. Nameplates
Nameplates are of plastic with black lettering on white background, fastened by plasticrivets, and are the following sizes:
9 Panel arrangement name: 63 mm × 315 mm
9 Panel section name: 16 mm × 50 mm
11. Surge protective devices
Load type Rotary machine
(electric motor &
generator)
Protection device for
switching surge of VCB CR Suppressor
Withdrawable
eqpt. position
Withdrawable
eqpt. door
Control circuit
connector
Earthing
switch
n/a closed -- OFF
disconnected(2)
-- --
disconnected n/a --
-- n/a attached(2)
-- -- --
disconnected -- n/a
service/
disconnected -- --
: Surfaces are first cleaned and pre-treated for rust. Then a durable coat of
: As for external coat: acrylic epoxy, or alkyd primer, applied.
(RAL 9001).
Frame, meter covers, control devices and protection relay cases: galvanized steel sheet
Nameplates are of plastic with black lettering on white background, fastened by plasticrivets, and are the following sizes:
63 mm × 315 mm
16 mm × 50 mm
Dry-type transformer Oil-immersed trans-
former
Lightning arrestor Not needed
Earthing
switch(1)
Cable door
OFF --
n/a closed
-- --
-- --
ON n/a
-- --
-- --
Then a durable coat of acrylic epoxy paint is
alvanized steel sheet.
Nameplates are of plastic with black lettering on white background, fastened by plasticrivets, and are the following sizes:
Product Information HABeR-24 kV
6
ACCESSORIES
1. Standard accessories
9 Draw-out handle for withdrawable equipment
9 Manual charging handle for VCB closing spring
9 Test Terminals test plug set for secondary circuit of VT & CT
9 Lifter with bucket for withdrawable equipment
2. Optional accessories
9 Control circuit extension cable for withdrawn VCB / VMC ON / OFF testing
9 Earthing switch operating handle
out handle for withdrawable equipment
g handle for VCB closing spring
Test Terminals test plug set for secondary circuit of VT & CT
Lifter with bucket for withdrawable equipment
Control circuit extension cable for withdrawn VCB / VMC ON / OFF testing
Product Information HABeR-24 kV
3. Earthing devices
Optional earthing devices are available forsafety during cable and busbar maintenanceand/or inspection.The following two type
of earthing devicecan be provided upon request with the
The mechanical indicator for the earthing switch’s state can be checked from the front ofthe panel through a small, circular
spection window.
9 Earthing truck for switchgear
An earthing truck with fault-making capability which has the same operating
mechanism as the circuit breaker.
4. Gas exhaust duct and gas screen
9 For switchgear and controlgear requiring optional Internal Arc Classification
(IAC), thegas exhaust duct must be fitted onto the top of panel. The gas e
haust duct ensures thatin the event of an internal arc fault, any hot gases or
vapours are channelled away frompersonnel in the vicinity of the panel.
9 The gas exhaust duct may extend to the open air. The straight and maximum
two metersdesign, which is standard, is available. The part of extension duct
to reach to the openair will be supplied by others. The design guideline for
them will be shown for consumerconvenience.
9 The gas exhaust duct is dismantled from the panels prior to shipping, and
arere-attached on site.
9 With gas exhaust duct, the switchgear and controlgear are designed to pr
tect personsin the event of an internal arc fault of up to 40kA. Thus, in the
event of internal arcing,there is no ejection of parts, no expulsion of hot
gases (except from the gas exhaustduct) and the enclosure remains earthed.
Minimum clearances of 600 mm, 100 mmand 800 mm from the panel to the
room’s ceiling, side walls and back wall, respectively,ar
Optional earthing devices are available forsafety during cable and busbar maintenanceand/or inspection.The following two type
of earthing devicecan be provided upon request with the HABeR-24 kV:
9
In the case of cable
earthing switch is integrated within the
cablecompartment. A mechanical interlock
between the earthing switch and circuit
breaker(or fused contactor) is provided.
Bus-side earthing switches are usually int
grated within a VT panel, and so employ
lectrical interlocking with the adjacent
panel’s circuit breaker.
The mechanical indicator for the earthing switch’s state can be checked from the front ofthe panel through a small, circular
making capability which has the same operating
and gas screen
For switchgear and controlgear requiring optional Internal Arc Classification
IAC), thegas exhaust duct must be fitted onto the top of panel. The gas ex-
thatin the event of an internal arc fault, any hot gases or
vapours are channelled away frompersonnel in the vicinity of the panel.
to the open air. The straight and maximum
two metersdesign, which is standard, is available. The part of extension duct
to reach to the openair will be supplied by others. The design guideline for
them will be shown for consumerconvenience.
t duct is dismantled from the panels prior to shipping, and
With gas exhaust duct, the switchgear and controlgear are designed to pro-
tect personsin the event of an internal arc fault of up to 40kA. Thus, in the
ing,there is no ejection of parts, no expulsion of hot
gases (except from the gas exhaustduct) and the enclosure remains earthed.
Minimum clearances of 600 mm, 100 mmand 800 mm from the panel to the
room’s ceiling, side walls and back wall, respectively,are required.
Optional earthing devices are available forsafety during cable and busbar maintenanceand/or inspection.The following two types
Integral earthing switch
In the case of cable-side earthing, the
earthing switch is integrated within the
cablecompartment. A mechanical interlock
between the earthing switch and circuit
breaker(or fused contactor) is provided.
side earthing switches are usually inte-
ted within a VT panel, and so employe-
lectrical interlocking with the adjacent
panel’s circuit breaker.
The mechanical indicator for the earthing switch’s state can be checked from the front ofthe panel through a small, circular in-
Product Information HABeR-24 kV
7
9 Classification IAC
- AFLR – signifies that the switchgear and controlgear are designed for access from the
Front, Lateral ends and Rear by Authorised personnel only.
- AFL – signifies that the switchgear and controlgear are designed for access
Front and Lateral ends by Authorised personnel only.
9 A gas screen can be selected instead of the gas exhaust duct on condition that ceiling height
from floor of electrical room is 4400 mm or over.
ACCESSORIES
Classification Item
Enclosure
1 Degree of protection
2 Padlocking facility for
withdrawable equipment
Position
Shutters
3 Internal Arc Classification
(IAC):
Accessibility type
Arc test current
Arc test current duration
4 Cable entry
Power
Control
Busbars
5 Plating
6 Insulation
7 Short-
8 Earthing busbar
Plating
Size
9 Busbar compartment
segregation between panels
Main circuit
10 Cable lugs
11 Cable glands
12 Cable termination material
Control circuit
13 Wire type
14 Wire size
15 Colour
16 Terminals
17 Terminal blocks
signifies that the switchgear and controlgear are designed for access from the
Front, Lateral ends and Rear by Authorised personnel only.
signifies that the switchgear and controlgear are designed for access from the
Front and Lateral ends by Authorised personnel only.
gas screen can be selected instead of the gas exhaust duct on condition that ceiling height
from floor of electrical room is 4400 mm or over.
Standard design Special specification
options
Degree of protection IP4X IP54 - IP55
Padlocking facility for
withdrawable equipment
Position
Shutters
–
–
Available
Available
Internal Arc Classification
Accessibility type
Arc test current
Arc test current duration
–
–
–
AFL, AFLR
25, 31.5, 40kA
0.1, 0.5, 1.0sec
Cable entry
Power
Control
Bottom
Bottom
Top
Top
Plating Tin Silver
Insulation Bare Epoxy coat or
-time withstand current 25, 31.5, 40 kA rms (1s) 25, 31.5, 40 kA rms (3s
Earthing busbar
Plating
–
6 x 25 mm
Tin
6 x 32, 6 x 40 mm
Busbar compartment
segregation between panels
No segregation With segregation
Cable lugs Not supplied Specify type, size
Cable glands Not supplied Specify type, size
Cable termination material Not supplied Heat-shrinkable material
(Specify size and type)
Wire type 600V, PVC, 75°C (HIV1) Please specify
Wire size CT / VT secondary:
2mm2, other: 1.25mm
2
Please specify
Colour Yellow Please specify
Terminals Up to 5.5 mm2 Please specify
Terminal blocks Screw type: Mitsubishi
TJX
Please specify (e.g. clip
signifies that the switchgear and controlgear are designed for access from the
from the
gas screen can be selected instead of the gas exhaust duct on condition that ceiling height
specification and/or
kA
0sec
or PVC
.5, 40 kA rms (3s)
40 mm
With segregation
Specify type, size
Specify type, size
shrinkable material
(Specify size and type)
Please specify
Please specify
Please specify
Please specify
Please specify (e.g. clip-on)
Product Information HABeR-24 kV
ACCESSORIES (CONTINUED
HULANICKI BEDNAREK Ltd.
22-100 Chelm
Wyszynskiego 2B St.
tel. (+48) 82 564 07 11
fax:(+48) 82 545 24 83
e-mail: [email protected]
HABeR Regional Office
Kasprzaka 31b/475
first floor)
02
tel. +48 22 853 10 12
fax: +48 22 853 11 91
e
Classification Item
Equipment
1 Space heater
2 Thermostat (for space heater)
3 Interior lighting operated by
door position switch
4 Transparent plastic covers
(prevention of accidental
contact with live parts)
5 Integral earthing switch
6 Earthing truck
7 VT
8 Automatic Transfer System
(ATS)
9 Foundation bolts
10 Channel base
CT
11 Secondary rating
12 Accuracy
Measuring
Protection for switchgear
Protection for
13 Burden
Nameplates
14 Material
15 Language
Measurement
& Protection
16 Relay
CONTINUED)
HABeR Regional Office – Centre
Kasprzaka 31b/475 St. (staircase Nr. 9,
first floor)
02-676 Warszawa
tel. +48 22 853 10 12
fax: +48 22 853 11 91
e-mail: [email protected]
HABeR Regional Office
Kamienna 42 St.
32-
mobile: +48 660 778 143
e-mail:
Standard design Special specification
options
Space heater Not supplied Please specify power source
Thermostat (for space heater) Not supplied Please specify power source
Interior lighting operated by
door position switch
Not supplied Available
Transparent plastic covers
(prevention of accidental
contact with live parts)
Not supplied Available (behind door)
Integral earthing switch Not supplied Available
Earthing truck Not supplied Available
Fixed type (floor-mount) Withdrawable (mid
Automatic Transfer System
Not supplied Slow speed
High speed
Foundation bolts Not supplied Available
Channel base Not supplied Available
Secondary rating 5A 1A
Accuracy
Measuring
Protection for switchgear
Protection for controlgear
Class 1,0
10P20
5P10
Please specify
Burden Min. 5VA Please specify
Material Acrylic plastic Stainless steel
Language English Please specify
Mitsubishi MELPRO-D,
MEprotect or EMC-B
Protection Relay
Please specify instruments
and protection relays
HABeR Regional Office – South Kamienna 42 St.
-080 Zabierzow
mobile: +48 660 778 143
mail: [email protected]
specification and/or
Please specify power source
Please specify power source
Available (behind door)
Withdrawable (mid-mount)
Please specify
Please specify
Stainless steel
Please specify
Please specify instruments
and protection relays