March 2014
A National Energy Efficiency Program
Accredited Assessor Training Course - Lighting
2015
![Page 2: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/2.jpg)
Housekeeping
Duration
Breaks
OH&S
Evacuation
Turn off mobile phones
![Page 3: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/3.jpg)
Course coverage
1. About CBD Lighting Assessments
2. Understanding the rules
3. The assessment form
4. Example assessments
5. Assessing your knowledge
![Page 4: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/4.jpg)
Topic 1
About CBD Tenancy Lighting Assessment’s
![Page 5: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/5.jpg)
The CBD program is the initiative of the Council of Australian Governments (COAG).
The program was established under the Building Energy Efficiency Disclosure Act 2010 and is managed by the Australian Government Department of Industry
Designed to promote the disclosure of energy efficiency information of large Australian office buildings with an outcome of improving the energy efficiency of these buildings.
What is the CBD program
![Page 6: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/6.jpg)
Objective of the CBD program
To disclose consistent and meaningful energy efficiency information about large office buildings that are for sale or lease to everyone (buyers, sellers and tenants).
This information empowers the market with information that encourages energy efficiency improvements.
Twin impacts – better price for efficient buildings, and lower greenhouse gas impacts.
![Page 7: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/7.jpg)
What is Building Energy Efficiency Certificate
Under the Building Energy Efficiency Disclosure (BEED) Act 2010─ A Building Energy Efficiency Certificate (BEEC) is required for
sale, lease or sub-lease office space of 2,000m² or more.
The BEEC is comprised of three parts─ Part 1 - A base/ whole building NABERS rating─ Part 2 - A Tenancy Lighting Assessment─ Part 3 - Energy efficiency guidance for building owners and
tenants
![Page 8: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/8.jpg)
What is a CBD Tenancy Lighting Assessment? An assessment of the energy efficiency of
office lighting systems─ Lighting power density
“General lighting system” - primarily open plan lighting Nominal – not the same as BCA Part J6
─ Control capacity No judgment on effectiveness
Doesn’t assess actual consumption─ What it can do – not how it is currently used
![Page 9: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/9.jpg)
Why have the assessments?
Provide information to prospective tenants or owners about the efficiency of the system─ Effects cost to run of different spaces─ Effects NABERS Tenancy Energy ratings.
Provides guidance to owners / tenants to upgrade inefficient lighting systems
Leasa App – assisting tenants to choose energy efficient office space
![Page 10: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/10.jpg)
Guiding principles
Fair comparison between tenancies Robust and repeatable Cost effective and timely
![Page 11: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/11.jpg)
Extract from sample BEECBEEC – Cover page
NABERS Rating
Building details
Assessor details
Lighting Assessment coverage
Energy efficiency guidance
![Page 12: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/12.jpg)
Extract from sample BEECBEEC – Part 1
NABERS Energy Star Rating
Assessment of building energy performance NABERS Assessor who conducted the rating
NABERS Rating scope, area and hours
![Page 13: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/13.jpg)
BEEC – Part 2
Assessment of General Lighting System efficiency
─ Power density─ Control capacity
Extract from sample BEEC
Note: Base building lighting efficiency covered by NABERS rating
![Page 14: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/14.jpg)
Extract from sample BEECBEEC – Part 3
General energy efficiency guidance
This information comes with all BEECs
![Page 15: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/15.jpg)
Who can do a Tenancy Lighting Assessment Accredited CBD assessor
─ Check the CBD website www.cbd.gov.au
Training requirements─ Must be a fully accredited NABERS assessor
─ Attend this session and pass the accreditation exam
─ Pass the CBD program module (online via CBD website)
─ Register for the CBD assessor portal (instructions provided by CBD team)
![Page 16: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/16.jpg)
Processes and procedures
Customer─ Agree fee for services including possible initial site
investigation─ Obtain required information
Tenants─ Negotiate access, ensure all parties are aware that someone
will be entering their offices to assess lighting, sometimes you may need to do it after hours
Security and OH&S─ Follow all site and tenant induction and OH&S requirements─ Have general and site specific safe work methods statements
![Page 17: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/17.jpg)
Lighting Assessment process
Site inspection
Complete the Tenancy Lighting Assessment (TLA) form
Submit TLA form to CBD team
CBD team auditing the TLA application
CBD team issue a TLA assessment number
![Page 18: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/18.jpg)
Assessment timing
Lodge assessment within 4 months of assessment date (1st day of site inspection)
Up to 15 days to process TLA application
Up to 28 days to process a BEEC application
Inform clients of processing timeframes
No prioritisation
![Page 19: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/19.jpg)
Record keeping processes
Retain records for seven years Retain primary data from assessment
─ Site photos notes and marked up drawings─ Leases or contractual agreements used in assessments
Summary data only is not acceptable─ Must be sufficient for an assessor / auditor to repeat
accurately the assessment from documentation only
All evidence needs to be provided to the CBD administrator upon request
![Page 20: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/20.jpg)
Record keeping processes
Logical filing of evidence is essential
Poor documentation is the primary cause for failing audits
Rating form provides guidance on documentation requirements
Lighting assessments can be audited up to seven years after the BEEC has been issued
![Page 21: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/21.jpg)
Administrative processes Submission requirement
─ 4 months from date of first inspection to submission
Validity of assessment─ Valid for 12 months from certification date
Interpretation of rules – CBD administrator
Dispute resolution─ With client─ With CBD administrator
![Page 22: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/22.jpg)
Topic 2
Understanding the rules
![Page 23: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/23.jpg)
Functional spaces Break areas to assess into separate functional
spaces Separate assessment per functional space
Acceptable names for a functional space when part floor is selected:─ Level 1, West Tenancy─ Level 10, East
Not acceptable part floor functional space name:─ 10 or 12.03─ Open office─ Suite 103
![Page 24: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/24.jpg)
Functional space area
Maximum size is the smaller of:─ Whole tenancy; or ─ Whole floor
Can define functional spaces to be the same as used for the NABERS rating
NLA required for the whole functional space─ NLA to give perspective but not critical─ Areas already required for NABERS rating so should be
available
![Page 25: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/25.jpg)
Naming functional spaces - example
This is on level 2 of the building
Acceptable use names of:─ Level 2 Suite 1─ Level 2 Suite 2
Unacceptable use names of:─ 12.03─ Open Office─ Suite 103
![Page 26: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/26.jpg)
General lighting system
Lighting to illuminate the workstation areas of the tenancy
May include “base building” and “fit-out” fittings
Not desk-top task lighting
Feature lighting is captured under some assessment methodologies
Both are part of the general lighting system
![Page 27: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/27.jpg)
General lighting system
Do not assess the quality of luminaires─ Poor optics
─ Dirty / old
─ Failed lamps
Do not assess the quantity of light─ Low lux levels
─ Dark areas
![Page 28: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/28.jpg)
General lighting system - example
Included─ Troffers
─ Up lights
Excluded─ Exit lights
─ Emergency lights
Both are part of the general lighting system
Exit lights are excluded
![Page 29: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/29.jpg)
General lighting system identification
YesNo
Yes
Yes
No
Yes
![Page 30: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/30.jpg)
Group exercise – identify the general lighting system
Work in a group, identify the general lighting system from the photos and plans downloaded
You have 15 minutes
![Page 31: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/31.jpg)
General lighting system exercise 1
![Page 32: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/32.jpg)
General lighting system exercise 2
![Page 33: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/33.jpg)
General lighting system exercise 3
![Page 34: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/34.jpg)
General lighting system exercise 3a
![Page 35: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/35.jpg)
General lighting system exercise 4
1200x600 grid
![Page 36: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/36.jpg)
General lighting exercise 5
1200x600 grid
![Page 37: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/37.jpg)
Nominal Lighting Power Density
NLPD─ Applies to general lighting system only
─ Dependent on luminaire power, number of luminaires and area
─ The possible assessment methods are Grid based
Aggregate method (contains 3 options )
Typical range 6 – 20 W/m2
─ Most buildings in 8 – 15 W/m2 range
![Page 38: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/38.jpg)
Nominal Lighting Power Density
Five categories:─ “Very poor” >18.1W/m²─ “Poor” 15.1-18W/m²─ “Median” 10.1-15W/m²─ “Good” 7.1-10.0W/m²─ “Excellent” <7W/m²
![Page 39: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/39.jpg)
Identifying luminaires
Definition of terms
Luminaire naming conventions
Counting lamps
Determining nominal lamp power
![Page 40: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/40.jpg)
Luminaire naming conventions
Suggested option─ XXabb
XX is a luminaire body code (2 or more letters) a is the number of lamps (single digit number) bb is the nominal power of each lamp - typically 2 digits but may
be 3 or more
─ If you need more information, precede with a plus sign
RT236 is a 2x36W recessed troffer
RT236 + LVR for louvred diffuser
![Page 41: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/41.jpg)
Counting lamps
Must physically sight the lamps
Diffusers and reflectors can give misleading lamp images
Luminaire on the right has a single T8 lamp
![Page 42: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/42.jpg)
Determining lamp power
Use the nominal lamp power
Written on the lamp’s tube or base
Where unsafe to inspect use nominal 50W lamp power for halogen downlights
![Page 43: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/43.jpg)
Luminaire control gear fundamentals
Identifying ballast types
Identifying transformer types
Determining luminaire power
![Page 44: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/44.jpg)
Identifying Ballast Types
Using the ballast discriminator
T5 – electronic only
Looking up lamp model
Inspecting lamp connection
![Page 45: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/45.jpg)
Identifying Transformer Types
Visual inspection─ Magnetic – larger, heavier
─ Smaller – details written on transformer
─ Use of ballast discriminator is not permitted, too unreliable
![Page 46: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/46.jpg)
Total luminaire power
NLP = nominal lamp power
Standardised figures only – NLP may differ from actual power
![Page 47: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/47.jpg)
Total luminaire power Standardised figures only – NLP may differ from actual power
![Page 48: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/48.jpg)
Other luminaire cases Voltage reduction devices, dimmers:
─ Assess as if no voltage reduction device or dimmer present
T5 adapters─ Assess as per T5 lamp of same type
If still not covered:─ Directly measure luminaire power or take from nameplate─ Ensure safe work methods are followed─ Engage specialist trades person if required
![Page 49: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/49.jpg)
Luminaire defaults Where inspection not possible, defaults may
be used:─ Fluorescent: Highest T8 of same length─ GU10 Halogen downlight: 50W+mag transformer─ Other halogen/mercury vapour: 250W─ LED downlight: default figure based on aperture diameter─ LED retrofit linear: default based on length─ LED strip: 21W/m
These are conservative figures
![Page 50: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/50.jpg)
T5 adapters
![Page 51: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/51.jpg)
LED fittings
![Page 52: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/52.jpg)
Luminaires – Documentation Requirements
Photos of each luminaire depicting lamp type, lamp power, number of lamps and control gear
AND/OR
As installed equipment lists
AND/OR
Results of individual luminaire power tests
![Page 53: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/53.jpg)
X
X
OK for # lamps
OK for # lamps
Not OK for lamp W
Not OK for lamp W
![Page 54: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/54.jpg)
X
XOK for grid
OK for lamp W
![Page 55: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/55.jpg)
Group activity– identifying and naming luminaires Identify and name the luminaires shown in
each of the photographs provided
Try to identify
─ Luminaire type
─ Lamp power
─ Control gear type
─ Any additional information needed to work out total luminaire power
![Page 56: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/56.jpg)
ANSWER• Recessed T5 troffer, • Can’t tell the power
without checking the lamp label
• Could be 28W (T5 HE) or 54W (T5 HO)
Luminaire identification 1
Dimensions 1.2m x 0.3m
T5 lamp
![Page 57: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/57.jpg)
ANSWER• Recessed T8 troffer, • Can’t tell the power
without checking the lamp label
• Must use ballast discriminator to check control gear type
Luminaire identification 2
![Page 58: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/58.jpg)
ANSWER• CFL Downlight • 2 lamps• Lamp power is 13W• Control gear – need to
check with ballast discriminator (or look up lamp model – this one is magnetic)
Luminaire identification 3
![Page 59: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/59.jpg)
Luminaire identification 4
ANSWER• Halogen downlight• Can’t tell lamp power
from photo, could be 20W, 35W or 50W
• Visual inspection to find control gear type
• If unsafe to inspect – assume 50W lamp with magnetic transformer
![Page 60: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/60.jpg)
Luminaire type evidence
Visual inspection of the luminaires
Photographs of the system components
─ Lamps─ Evidence of ballast/transformer type─ Overall luminaire
![Page 61: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/61.jpg)
Luminaires
Any questions on luminaire identification?
![Page 62: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/62.jpg)
Assessing NLPD
Four methods
Grid method – works for open plan with regular grid
3 aggregate methods – increasingly flexible methods for sites that are more complex
![Page 63: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/63.jpg)
Assessing NLPD
![Page 64: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/64.jpg)
When is a Functional Space assessable?
A functional space is assessable if:
─ It contains >50m² of qualifying office space AND─ Qualifying office space is >15% of area AND─ There is an existing or proposed lighting system for these
areas
Qualifying office space = space for workstations or desks
─ Excludes meeting rooms, reception areas, function rooms, toilets, kitchens, storage and utility, 2-walled corridors
![Page 65: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/65.jpg)
Aggregate Method 2 - suitable space
Building Core – NO
Open plan - OK
Cell office - OK
Cell office - OK
Cell office - OK
Cell office - OK
Meeting rooms, etc NO
Server room – NO
Tea room – NO
Resource room – NO
Corridors – not OK
![Page 66: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/66.jpg)
Non-assessable functional space documentation requirementsFloor plan or dimensioned mock-up showing
qualifying office space <50m² or <15% of functional space area AND/OR
Photos showing lack of lighting system AND Site notes identifying lack of proposed system
![Page 67: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/67.jpg)
Grid method of assessment
Permitted when
─ Simple repeating block consisting of up to two luminaires covering open plan area of at least 50% of the space area or 250m², whichever is smaller; AND
─ Less than 5% (by wattage) deviation from the repeated block; AND
─ Documentation requirements for grid method can be met
![Page 68: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/68.jpg)
Grid method of assessment
Use for regular arrays
Identifying the array
Measure the grid spacing
─ Need actual measurement of tile size – don’t assume
1.2m0.6m
4 tiles2 tiles
![Page 69: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/69.jpg)
Grid spacing
1350
450
1200
400
![Page 70: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/70.jpg)
Grid spacing
Look for repeating patterns
In this example, assume a 1200x600 grid tile
Alternate spacing 2400 and 1800
Average 2400x2100 spacing
![Page 71: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/71.jpg)
Grid spacing
Staggered array
Area per luminaire
![Page 72: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/72.jpg)
Grid spacing
Another staggered array
Do not be confused
─ Look for the symmetry
![Page 73: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/73.jpg)
Grid Method Documentation Requirements
Reflected ceiling plan (Plan/mock up/photo) demonstrating grid; AND
Plan/mock up showing that the minimum coverage requirement is met; AND
Photos/site notes/drawings showing that non-standard fittings < 5% watts across open plan; AND
Photos/site notes identifying qualifying luminaire types in grid
![Page 74: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/74.jpg)
Grid Method - suitable space Repeating
block:
─ >50% functional space area
─ >250m²
<5% of luminaires in open plan not same as main luminaire
![Page 75: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/75.jpg)
Grid Method - unsuitable space Perimeter
luminaire>5% by wattage
![Page 76: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/76.jpg)
Aggregate Method 1 – Open Space
Permitted when
─ There is open plan area of at least 50% of the space area or 250m², whichever is smaller; AND
─ Documentation requirements for Aggregate Method 1 can be met
Use for most irregular or multi luminaire configurations where there is enough open plan
![Page 77: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/77.jpg)
Aggregate Method 1
Identify an open plan space that:
─ Is either>50% of space area or>250m², whichever is smaller
─ Contains all the luminaire types used in the open plan area in a similar proportion to the open plan area as a whole
OR, if no such space available
─ Use the whole open plan qualifying office space
![Page 78: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/78.jpg)
Aggregate Method 1
Prepare drawing of sample space
Calculate sample space area better than 5% accuracy
Count all luminaires in sample space
Enter data into spreadsheet
![Page 79: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/79.jpg)
Aggregate Method 1 Documentation Requirements Reflected ceiling plan (Plan/mock up/photo)
demonstrating irregularity of layout; AND
Plan/mock up showing aggregate method sample space; AND
Photos/site notes identifying qualifying luminaire types in grid; AND
Site notes count of all luminaires within aggregate method sample space
![Page 80: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/80.jpg)
Example: Mix of luminaires
Open plan space
Two different luminaires
No regular spacing
Aggregate method 1 suitable provided documentation requirements can be met
![Page 81: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/81.jpg)
Aggregate Method 1 - suitable space Sample space:
─ Open plan─ >250m² (316m²)─ Representative
mix of luminaires
![Page 82: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/82.jpg)
Aggregate Method 1 - unsuitable space Includes non-open plan area
X
![Page 83: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/83.jpg)
Aggregate Method 1 - unsuitable space Does not
include representative sample of luminaires
X
![Page 84: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/84.jpg)
Aggregate Method 1 - unsuitable space Too small
─ <250m²
96m²
![Page 85: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/85.jpg)
Aggregate Method 2 – Open space + cell offices
Permitted when
─ There is qualifying office space (open plan + cell offices) of at least 50% of the space area or 250m², whichever is smaller; AND
─ Documentation requirements for Aggregate Method 2 can be met
Use where there is inadequate open plan for the grid method or aggregate method 1
![Page 86: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/86.jpg)
Aggregate Method 2
Identify a qualifying office space made up of open plan and cell offices that:
─ Is either>50% of space area or>250m², whichever is smaller
─ Contains all the luminaire types used in the open plan area in a similar proportion to the open plan area as a whole
OR, if no such space available
─ Use the whole qualifying office space
![Page 87: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/87.jpg)
Aggregate Method 2
Prepare drawing of sample space
Calculate sample space area better than 5% accuracy
Count all luminaires in sample space
Enter data into spreadsheet
![Page 88: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/88.jpg)
Aggregate Method 2 Documentation Requirements Reflected ceiling plan (Plan/mock up/photo)
demonstrating irregularity of layout; AND
Plan/mock up showing aggregate method sample space; AND
Photos/site notes identifying qualifying luminaire types in aggregate method sample space; AND
Site notes count of all luminaires within aggregate method sample space
![Page 89: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/89.jpg)
Aggregate Method 2 - suitable space
Aggregate Method 2 – sample spaces
115m²Open plan space <250m² and <50% - too small for
aggregate method 1
![Page 90: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/90.jpg)
Aggregate Method 2 - suitable space
Aggregate Method 2 – sample spaces
286m² - OK
![Page 91: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/91.jpg)
Aggregate Method 2 - suitable space
Aggregate Method 2 – sample spaces
386m² - OK
![Page 92: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/92.jpg)
Aggregate Method 2 - suitable space
Aggregate Method 2 – sample spaces
179m² - too small
![Page 93: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/93.jpg)
Aggregate Method 2 - suitable space
Aggregate Method 2 – sample spaces
294m² - OK
![Page 94: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/94.jpg)
Aggregate Method 3 – Entire Functional Space
Permitted when
─ Space cannot be assessed under Grid Method, Aggregate Method 1 or Aggregate Method 2; OR
─ Space is under 250m²
Use for small functional spaces or where the documentation is too poor to meet requirements for the other methods.
![Page 95: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/95.jpg)
Aggregate Method 3
Identify area of Functional Space to 5% accuracy
Count all luminaires in sample space
Enter data into spreadsheet
![Page 96: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/96.jpg)
Aggregate Method 3 Documentation Requirements Area of functional space to 5% accuracy
Photos/site notes identifying qualifying luminaire types in space; AND
Site notes count of all luminaires within functional space
![Page 97: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/97.jpg)
Grid and Aggregate Methods exercise 1
How would you assess this space?
Tenancy is a single open office area of 240m²
![Page 98: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/98.jpg)
Grid and Aggregate Methods exercise 2
How would you assess this space?
![Page 99: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/99.jpg)
Grid and aggregate method assessment
Any questions on grid or aggregate method assessment?
![Page 100: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/100.jpg)
Lighting control assessment
Assessed as “control capacity”
Assess only the control system’s capacity to deliver outcomes
No assumptions on how well it is actually working
![Page 101: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/101.jpg)
Lighting controls
Control capacity assessed as Good, Moderate or Poor
Look at the main control system for the space
Two factors to consider
─ Switching zone size─ Control strategy
![Page 102: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/102.jpg)
Control strategy
Three basic control strategies to assess
─ Manual─ Time based─ Occupancy based
![Page 103: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/103.jpg)
Occupancy sensorsOccupancy control
─ Luminaires on supervisory control with occupancy sensors available
─ Luminaires hardwired to occupancy sensors─ Luminaires with occupancy sensor and timer control
![Page 104: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/104.jpg)
Timer ControlTimer control
─ Luminaire connected to a supervisory control system─ Luminaire controlled by time switch─ Luminaire interlinked to turn off when security alarm set
![Page 105: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/105.jpg)
Manual ControlManual control
─ Anything which doesn’t meet the requirements of timer or occupancy sensor control
Bell press switch is not sufficient evidence of a timer control system
![Page 106: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/106.jpg)
Daylight sensors
Not included in control grading
May be integrated into occupancy sensors
![Page 107: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/107.jpg)
Control Type Flow Chart
![Page 108: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/108.jpg)
Control Technology Documentation Presence of occupancy control
─ Photos/docos for sensors AND─ Drawing/mock up of sensor locations OR count of sensors
Presence of supervisory control
─ Manuals, photo of interface, controllers, switch type
Presence of time switch
─ Manuals, photos, drawings
Manual Control – no documentation
![Page 109: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/109.jpg)
Control Technology Documentation
Sketch or commentary reasonably demonstrating coverage of the occupancy/timer system is greater than 50%
Can’t document it?
─ Then you can’t claim that level of control─ Try the level below
![Page 110: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/110.jpg)
Switching zone size
Three switching zone sizes to assess
─ Up to 100m²─ From 100 to 250m²─ Over 250m²
Assessment is based on the largest switching zone in the functional space
![Page 111: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/111.jpg)
Control Capacity
![Page 112: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/112.jpg)
Control Zone Documentation
Lighting control zone area documentation
─ Only required for spaces claiming occupancy control─ Marked up scale drawing showing fittings, control zones
and area of each control zone
Functional space area documentation
─ Only required for manual space control spaces under 250m²
![Page 113: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/113.jpg)
Switching size example
Sensors marked in red
All areas are controlled by the occupancy sensors
Ceiling tile is 1.2m x 0.4m
![Page 114: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/114.jpg)
Switching size example
Case 1 – motion on any sensor turns all the lights on
Switching zone size is >250m2
Control capacity is “moderate”
![Page 115: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/115.jpg)
Switching size example
Case 2 – motion sensors control local area only
Largest switching zone size is <100m2
Control capacity = “good”
![Page 116: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/116.jpg)
Effect of switching zone size
Small switching zone (50m²)
Large switching zone (2,000m²)
![Page 117: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/117.jpg)
Control Capacity
Any questions on control capacity identification?
![Page 118: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/118.jpg)
Proposed systems
Lighting system is to be upgraded within 3 months of the assessment date
Assessments cover both NLPD and control capacity
Must assess the existing system too
─ Proposed systems are not a substitute for an existing system assessment
Proposed system assessments are optional
![Page 119: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/119.jpg)
Assessment of proposed systemMay arise from contractual commitment to
upgrade lighting system
─ Owner proposed lighting upgrade─ Make good provision
Must be contracted with an agreed completion date within 3 months of assessment date
Contract must be sighted by assessor
─ Retain copy of contract or relevant pages as evidence
![Page 120: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/120.jpg)
Assessment of proposed system
Must be fully documented
─ Luminaire selections complete─ Control strategy clearly set out─ Control equipment selected
Assess existing and proposed
![Page 121: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/121.jpg)
Difficult Buildings
Exemptions for Buildings
Denial of access or information to complete ratings
Non-assessable spaces for the TLA component
![Page 122: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/122.jpg)
Exemptions from Disclosure Obligations
A building may apply for an exemption if:
─ It is used for police or security operations; or─ It can’t be assessed due to the characteristics of the
building or area of the building.
Submission of exemption application does not allow marketing or negotiation of the property until the exemption is granted.
![Page 123: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/123.jpg)
Exemption - Process
Police or security operations
─ Gather details on the nature of operations within the building
─ Seek exemption from the Department of Industry under BEED Act Clause 17 (3) (a)
─ Note: Security is generally interpreted as being national as opposed to corporate or commercial security
• Provide detailed reasons in the application form why exemption is required.
• Exemptions are provided at the discretion of the Department.
![Page 124: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/124.jpg)
Exemption - Process
Non assessable Building
─ Gather detailed evidence demonstrating why building is not assessable, e.g.Detailed reasons why rating can’t be completedAny statement from NABERS indicating a rating can’t be provided
─ Seek exemption from Department of Industry under clause 17(3)(b)
─ Record details on application form specifically identifying reasons why building is not assessable
![Page 125: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/125.jpg)
Access Denial - Process
If a tenant/owner refuses access or information
─ Assessors can require information or access be provided by owners or tenants (lessees) if it is necessary for an assessment.The Department provides templates for requests
─ If an owner or lessee still refuses access or information after a request, they must apply for an exemption under clause 18(7). If access or information is refused without an exemption, this is a
breach of a civil penalty provision. Penalties apply.Exemptions granted under 18(7) may support claims of inability to
conduct an assessment under clause 17(3)(b);
![Page 126: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/126.jpg)
Where a functional space does not allow a TLA Assessment An assessment may not be possible because
space is:
─ Under refurbishmentNo lighting system in place; orLighting system is incomplete (luminaires missing)
─ Non office fit-out Extensively fitted out with small cellular offices, meeting rooms or
conference rooms
![Page 127: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/127.jpg)
Where a space does not qualify for an exemptionAssessor needs to include the space in the
assessment form
Mark the space as not assessable on the FS tab
Provide a reason why the space was not assessable
─ Include a reference to the clause in the rules used to determine the space as not assessable
![Page 128: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/128.jpg)
Difficult Buildings
Any questions on exemptions, non-assessable spaces or denial of access?
![Page 129: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/129.jpg)
Topic 3The Online TLA Assessment Form
and Single BEEC Application process
![Page 130: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/130.jpg)
The Online Assessment Form
Online form
Contains all information used in assessments
Submit assessments through Portal
Can pre-fill and save parts before going to site
Downloadable PDF Summaries
![Page 131: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/131.jpg)
The Single step BEEC Application- Complete whole BEEC process in one
application, TLA and NABERS combined.
Tracking of applications.
Increased validations to minimise returns for incorrect data.
CBD Assessor Portal User Manual.
![Page 132: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/132.jpg)
The Online TLA Component
Building Overview
Luminaires
Functional Spaces
Individual area assessment details
Summary
![Page 133: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/133.jpg)
Typical assessment workflow
Site information
Owner details Assessor details
Areas to be assessed
All functional spaces Space sizes
Luminaires used
Lamp types Lamp power Number of lamps
Functional space assessments
![Page 134: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/134.jpg)
Site information
Building owner details
Site contact details
Assessor details
Rules and assessment form versions
Other comments and/or assumptions
![Page 135: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/135.jpg)
Luminaires All luminaires used in
assessment
Can’t modify luminaire names
─ Delete and recreate if necessary
Add luminaires via button click
Delete luminaires via button click only
─ Can’t delete if in use
![Page 136: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/136.jpg)
Functional spaces Data entered to automatically generate description for BEEC
Add new/delete unused spaces via button click
Quickly navigate to space forms
![Page 137: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/137.jpg)
Functional space detailsNLPD
Control capacity
Performance comments
Proposed systems
![Page 138: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/138.jpg)
Grid based methodBlock info
─ Luminaire type, ─ Quantity─ X Spacing (must be in metres)─ Y Spacing (must be in metres)─ Non-standard luminaires─ Standard luminaires
![Page 139: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/139.jpg)
Aggregate methodCount and type of all luminaires
─ Each luminaire type needs a new line in the table
Total size of aggregate area (m²)
![Page 140: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/140.jpg)
Control capacity
Start with control system type
Boxes requiring information will become visible
Automatically grades controls based on inputs
![Page 141: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/141.jpg)
Evidence Describe documentation gathered for functional
space
All evidence fields that are presentmust be completed
![Page 142: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/142.jpg)
Proposed systemDetails recorded on the functional spaces page
Click on “Add / remove proposed system”
![Page 143: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/143.jpg)
Proposed systemAssess NLPD and
control capacity
No performance comments
![Page 144: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/144.jpg)
Summary tabReview the information
Automated data completion check
Automatic submission to CBD administrator
Two downloadable summaries, one with all the data entered and a second to check that the main details are correct which will appear on the final BEEC.
![Page 145: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/145.jpg)
Topic 4Next Steps and Further Information
![Page 146: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/146.jpg)
Next steps
Complete on-line CBD training module
Successfully complete the examination
─ Exam will be sent to you within two weeks
Apply for accreditation within 6 months
─ $375 fee
Any questions?
![Page 147: March 2014 A National Energy Efficiency Program Accredited Assessor Training Course - Lighting 2015](https://reader037.vdocuments.us/reader037/viewer/2022103022/56649cc15503460f94988e31/html5/thumbnails/147.jpg)
Further information
Disclaimer
This presentation is intended to provide a summary about the Commercial Building Disclosure Program. The Program may be subject to change without notice. Readers should not act on the basis of the information provided in this presentation but should instead obtain legal advice.
Readers wanting further information may refer to the Program’s website.
While reasonable efforts have been made to ensure that the contents of this presentation are factually correct, the Australian Government does not accept responsibility for the accuracy or completeness of the contents, and shall not be liable for any loss or damage that may be occasioned directly or indirectly through the use of, or reliance on, this presentation.