lessons learned from the texas synchrophasor network · ercot vangle = 0 vangle = δ texas nodal...
TRANSCRIPT
1
Lessons Learned from the Texas
Synchrophasor Network
by
Prof. Mack Grady and Mr. Moses Kai
U.T. Austin
Presented at the
Schweitzer Engineering Laboratories
Modern Solutions Power Systems Conference
Chicago
June 7, 2012
Why are Synchrophasors
Important?
Here’s All You Need to Remember
Average Power Flow P Through a Mostly Inductive
Transmission Line (138kV and above)
)sin( 2121
X
VVP
11V 22V
jX
+
+
ground
These are
about 1pu
For small x,
sin(x) = x
Charles Steinmetz,
developed phasor
theory to analyze
AC circuits
Stability limit is when the angle difference reaches 90 degrees
Does anybody
have a GPS
antenna?
2
Bus 2
DFW
Bus 4
SA
Bus 5
VAL
Bus 6
COAL
Bus 7
WIND
300 km
250 km
150 km300 km
400 km
500 km400 km
Bus 3
UT
Bus 1
HOU
Positive-sequence line constants for
each 345kV circuit:
• R = 0.06 Ω/km per conductor
• L = 1 µH/m
• C = 12 pF/m
• Rating = 800 A per conductor
• From the L, XL (500 km) = 188.5 Ω
• For 345 kV, 100 MVA base, Zbase =
1190 Ω
• For each 500 km circuit, XL = 0.158 pu
• Thus, four parallel circuits have XL =
0.040pu, and six parallel circuits have
XL = 0.026 pu
Relatively small phase angle
variation in central ERCOT
McDonald
Observatory
PMU
UT Austin
PMU
Bus 2
DFW
Bus 2
DFW
Bus 4
SA
Bus 4
SA
Bus 5
VAL
Bus 5
VAL
Bus 6
COAL
Bus 6
COAL
Bus 7
WIND
Bus 7
WIND
300 km
250 km
150 km300 km
400 km
500 km400 km
Bus 3
UT
Bus 3
UT
Bus 1
HOU
Bus 1
HOU
Positive-sequence line constants for
each 345kV circuit:
• R = 0.06 Ω/km per conductor
• L = 1 µH/m
• C = 12 pF/m
• Rating = 800 A per conductor
• From the L, XL (500 km) = 188.5 Ω
• For 345 kV, 100 MVA base, Zbase =
1190 Ω
• For each 500 km circuit, XL = 0.158 pu
• Thus, four parallel circuits have XL =
0.040pu, and six parallel circuits have
XL = 0.026 pu
Relatively small phase angle
variation in central ERCOT
McDonald
Observatory
PMU
UT Austin
PMU
U.T. Pan Am
PMU
Synchrophasor Homework Network for ERCOT
U.T. McDonald Observatory
PMU
360º
+60º −30º
Small oscillations in the relative phase angles give an indication grid stability.
Essentially, these oscillations provide an “EKG” for large power grids.
UT Pan Am
Austin
McDonald
Observatory
400 miles
300 miles
The Texas Synchrophasor Network Monitoring 120V Wall Outlet Voltages and Communicating Through the Public Internet
Austin
Majority of load is in the green
area, i.e. “Central ERCOT.”
Little phase angle difference
across Central ERCOT (i.e.,
“one solder blob”)
120V wall outlet at U.T.
Austin, and 69kV 3Φ
monitor at nearby Austin
Energy Harris Sub
Wind Country
• Funding provided by EPRI
• Equipment provided by
Schweitzer Engineering
Labs
Waco
Our PMUs send back
•Vrms,
•Voltage Angle,
•Frequency,
•DFDT
30 times per second.
3
370 miles
280 miles
100 miles
Jaime Ramos, U.T.
Pan Am, South Texas
oscillations
Rex Barrick, McDonald
Observatory, West Texas
wind oscillations
Andrew Mattei, Brazos
Electric Power Coop,
Waco, North-South
interchange indicator
Scott Bayer, Austin
Energy, 69kV grid
benchmark
6
Cloudcroft, NM, Phasor Measurement Unit (PMU). GPS antenna mounted on a
PVC pipe and Christmas tree stand. Two views of the GPS antenna.
LOCATION
Latitude Longitude Altitude
N 32.52.54 W 105.39.10 7583 feet
Satellite Signal Strengths (Min for Lock, 3 Sats > 3.0)
12.0 ; 7.0 ; 5.2 ; 6.0 ; 3.6 ; 5.2 ; 1.8 ; 15.2 ; -.- ; -.- ; -.- ; -.-
4
7
The Cloudcroft, NM, Station, Piggy-Backed onto Standard DSL Internet Service
“The Grid Monitor”
(a power strip)
Cloudcroft
GPS Synchronized
Clock
Spare Antenna
SEL 421 Relay/PMU
DSL Modem and Wireless Router
On the Receiving End,
The Schweitzer Synchrophasor Vector Processor, and PC
for Data Logging
and
• Schweitzer’s Modal Analyzer (uses 10-second intervals)
Plus some of my own programs,
• Offline Daily Screener for data checking and integrity
• Offline Waveform Analyzer to screen for events
• A web scraper program to fetch ERCOT 1-minute wind and
load data
• Plus a number of smaller programs for graphs and reports
5
Thur Fri
West Texas voltage
phase angle often
swings nearly 100º and
back with respect to
U.T. Austin in about 24
hours
Because wind
generation in West
Texas varies
dramatically
McDonald Observatory Voltage Phase Angle with respect to U.T. Austin
March 25, 26, 2010
-60
-40
-20
0
20
40
60
24 36 48 60 72
36 Hours Beginning 12am, March 24, 2010
De
gre
es
Wind Generation in ERCOT - MW
March 25, 26, 2010
0
1000
2000
3000
4000
5000
6000
24 36 48 60 72
MW
48
Lesson 1. Every Day Has
Synchrophasor Surprises
59.9
60.0
60.1
0 2 4 6 8 10 12 14 16 18 20
Tuesday, March 31, 2009, 20 Minute Window Beginning 12:53 AM CDT Superimposed Frequency Measurements Taken at
UT Austin (in black) and McDonald Observatory (in red)
20-minute window
Our First Nugget
with strange 0.067 Hz oscillation
Forwarded this to ERCOT chief. Got some attention! Turned out to be throttle valving problem
on generator under test. Slow frequency variation had gone unnoticed.
6
McDonald Observatory Voltage Phase Angle w.r.t U.T. Austin 120V and Harris 69kV
-14
-13
-12
-11
-10
1600 1700 1800 1900 2000 2100 2200
Sample (30 samples per second)
De
gre
es
w.r.t U.T. Austin
w.r.t Harris 69kV
10 seconds
• The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been
removed. The variable but steady 0.1 degree power flow phase shift through the substation
transformer has also been removed.
• Can you see any significant difference between the waveform seen by the 120V wall outlet (in black)
and the waveform seen by the 69kV, 3Φ grid monitor (in red)? (The correct answer is NO!)
Voltage Ringdown at McDonald Observatory Observed at the Following Two Locations in Austin: a
120V Wall Outlet on Campus, and the Harris 69kV Substation that Feeds the Campus
Lesson 2. 120V Wall Outlets Work for Synchrophasors
U.T. Pan Am Voltage Phase Angle w.r.t U.T. Austin 120V and Harris 69kV
-40
-39
-38
-37
-36
-35
-34
-33
-32
1600 1700 1800 1900 2000 2100 2200
Sample (30 samples per second)
De
gre
es
w.r.t U.T. Austin
w.r.t Harris 69kV
10 seconds
• The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been
removed. The variable but steady 0.1 degree power flow phase shift through the substation
transformer has also been removed.
• Can you see any significant difference between the waveform seen by the 120V wall outlet (in black)
and the waveform seen by the 69kV, 3Φ grid monitor (in red)? (The correct answer is NO!)
Voltage Ringdown at U.T. Pan Am Observed at the Following Two Locations in Austin:
a 120V Wall Outlet on Campus, and the Harris 69kV Substation that Feeds the Campus
Wall Outlets Work. Of Course, We Prefer Grid Monitors.
7
0.52% drop
0.45% drop
1.78% drop
1.07% drop
U.T. Austin
120V wall outlet
Austin Energy
Harris Sub 69kV
3Φ positive seq.
McDonald Observatory
120V wall outlet
U.T. Pan American
120V wall outlet
Vrms plot
Vrms plot
Vrms plot
Vrms plot
Wall Outlets Work. Of Course, We
Prefer Grid Monitors.
2-minute window of a switching
event. June 23, 2010. All four
windows are Vrms readings, 30
samples per second
120V wall outlet voltages are
clearly more noisy than 69kV grid,
but nevertheless 120V wall outlets
together with Schweitzer relays
provide reliable phase angle
measurements
cleaner
14
Start Sec Stop Sec A t1 B Tau1 t2 C Tau2 Wdamp 2010/10/04 18:18:00.000 8-2
15 30 -41.60 21.38 -45.65 0.19 21.37 4.28 1.95 3.82 PMUs = McDonald 1P
Fdamp Zeta Angle reference = Austin
0.608 0.134
UT Pan Am Voltage Angle with respect to U.T. Austin, 2010/10/04 18:18:00.000
-49
-48
-47
-46
-45
-44
-43
-42
-41
-40
15 20 25 30 35
Measured
Curve Fit
Healthy response to a unit trip
Lesson 3. Modal Analysis of Synchrophasor Data Allows Us to Compute Grid
Damping, for Big Events and for Ambient Data. An “Unhealthy” Ringdown Would
Continue Much Longer Than the “Healthy” Ringdown Shown Below.
8
Grady, Brooks, NREL, 1/27/11 15
• 1 hour of modal
analysis, 11am- Noon,
Jan. 22, 2011
• One calculation per 10
seconds, Shows the 3
most significant modes
• Calculations performed
by Schweitzer
Synchrophasor Vector
Processor
Main mode is 0.76
Hz. Damping ratio
ranges from about
0.3 to 0.1
0.1 is threshold of significance
rated
s
s
m
rated
ss
rated
s
Pdtd
P
P
J
P
J
H/2
1
2
12
1 2
dtdfP
fP
dtdf
f
P
P
dtdP
PH
srated
sm
s
s
rated
m
s
s
rated
m
/2/2
2
2/2
1
H has the units of seconds. The correct interpretation is that the kinetic
energy in the equivalent system machine corresponds to H seconds of rated
power. Thus, the machine could provide rated power for H seconds, at which
time it would have spun down to zero RPM.
EPRI Study. Purpose – to compute ERCOT System Inertia Constant H From
Frequency Response During 42 Unit Trips Having 0.1 Hz or Greater Freq.
Drop.
Lesson 4. Wind Generation Does Not Appear to Reduce System Inertia
(but no generator operating at max power can contribute to governor
response)
9
August 2010, Event 7, cont.
Event 7
Voltage
Phase
Angle Event 7, 8/24/2010 07:31:00 PM GMT Minute
59.82
59.84
59.86
59.88
59.90
59.92
59.94
59.96
59.98
60.00
56 57 58 59 60 61 62 63 64 65 66
Second of the Minute
Fre
qu
en
cy UT Austin
Harris 69
McD
UT PanAm
Inertia
slope
Nadir
slope
Zoom
Estimated System H versus % Wind Generation
(42 Unit Trip Events, June through November 2010)
0
2
4
6
8
10
12
0 5 10 15 20
Wind Generation - % of Total Generation
Esti
mate
d H
42 Major Unit Trips, 0.1 Hz or Greater. Any Correlation Between System
Inertia and Wind Generation (% of Total Gen)?
10
Estimated System H versus Wind Generation (MW)
(42 Unit Trip Events, June through November 2010)
0
2
4
6
8
10
12
0 1000 2000 3000 4000 5000 6000 7000
Wind Generation - MW
Esti
mate
d H
42 Major Unit Trips, 0.1 Hz or Greater. Any Correlation Between System
Inertia and Wind Generation (MW)?
Start Sec Stop Sec A t1 B Tau1 t2 C Tau2 Wdamp 2010/10/04 18:18:00.000 8-2
15 30 -41.60 21.38 -45.65 0.19 21.37 4.28 1.95 3.82 PMUs = McDonald 1P
Fdamp Zeta Angle reference = Austin
0.608 0.134
UT Pan Am Voltage Angle with respect to U.T. Austin, 2010/10/04 18:18:00.000
-49
-48
-47
-46
-45
-44
-43
-42
-41
-40
15 20 25 30 35
Measured
Curve Fit
Healthy response to a unit trip
Lesson 5. Wind Generation Does Not Appear to Impact System Damping or
Damped Resonant Frequency
11
Ringing Frequency vs Wind Generation (% of Total), Sep 2009 - Feb 2010
0
0.5
1
1.5
2
2.5
3
0 2 4 6 8 10 12 14 16 18 20
Wind Generation (% of Total)
Fre
qu
en
cy (
Hz)
Ringdown Analysis of More Than 100 Unit Trips Yields No Clear
Relationship Between Wind MW and Damped Resonant Frequency
Does Wind
Generation
Impact Grid
Stability?
Damping Ratio vs Wind Generation (% of Total), Sep 2009 - Feb 2010
0
0.2
0.4
0.6
0.8
1
1.2
0 2 4 6 8 10 12 14 16 18 20
Wind Generation (% of Total)
No
rmal
ize
d D
amp
ing
Rat
io
Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship
Between Wind MW and Normalized Damping Ratio
Does Wind
Generation
Impact Grid
Stability?
12
Bus 7
WIND
Bus 7
WIND500 km
Local conventional
Pload,conv − Pgen,conv
Pexport
Thevenin Impedance
jXTH
Central ERCOT
Vangle = 0
Vangle = δ
Texas Nodal Market Caused Grid Oscillation. We Used it to Compute the Thevenin
Equivalent Impedance from West Texas to Central ERCOT
)sin( 2121
X
VVP
Solve
Lesson 6. Synchrophasor Data Can Be Used to Compute Thevenin
Equivalent Impedances Between Grid Regions
McDonald Observatory Voltage Phase Angle Relative to
Central ERCOT
-20
-10
0
10
20
30
40
0 1 2 3 4 5 6 7 8 9 10 11 12
Hour of March 11, 2011
De
gre
es
ERCOT’s
graph of West-
to-North P flow
Texas
Synchrophasor
Network’s graph
of West-to-
Central ERCOT
Voltage Angle
Grid Oscillation
Induced by ERCOT
Nodal Market Price
Signals with Positive
Feedback
Price went down, then wind gens responded, then
price went up, then wind gens responded, • • •
13
ERCOT Wind Generation MW, Last Two Weeks of May 2012
0
1000
2000
3000
4000
5000
6000
7000
8000
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Day (Starts at Midnight CDT)
MW
ERCOT Wind Generation % of Total, Last Two Weeks of May 2012
0
5
10
15
20
25
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Day (Starts at Midnight CDT)
Pe
rce
nt
MW
Percent
ERCOT Wind Generation MW, Last Two Weeks of May 2012
0
1000
2000
3000
4000
5000
6000
7000
8000
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Day (Starts at Midnight CDT)
MW
McDonald Voltage Phase Angle, One Minute Averages, Last Two Weeks of May 2012
-60
-40
-20
0
20
40
60
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Day (Starts at Midnight CDT)
De
gre
es
MW
Degrees
LOCALPX
VVP )sin( 21
21
About 3000 MW
14
2 Hz
Cluster
March 18, 02:00 – 03:00
Wind Generation > 20%
March 12, 02:00 – 03:00
Wind Generation ≈ 2%
March 12, 02:00 – 03:00
Wind Generation ≈ 2%
Big Wind (20%) with 2 Hz Cluster Small Wind (2%) without 2 Hz Cluster
Lesson 7. A 2 Hz Mode in Ambient Oscillation Sometimes Forms with High
Wind Generation
1 Hour of Damping Plot. 1.8 Hz Mode, Frequent During Spring 2012.
Small. Starts and Stops. Wind Related?
1-Hour,
April 13,
2012
15
Perhaps More Troubling – Sometimes Have Very Low Damping in Main Mode
(but it doesn’t appear to be wind related)
1-Hour,
April 13,
2012
On 01/21/12, a sudden loss of generation occurred at 13:34 totaling 584
MW. Frequency declined to 59.752 HZ, ERCOT load was 31,275 MW.
59.7
59.8
59.9
60.0
60.1
0 1 2 3 4 5 6 7 8 9 10
Minutes
Lesson 8. It is amazing what the loss of 584 MW can do when there is little
reserve. More fallout from the Texas Nodal Market?
Frequencies this low used to be less than once per year. Now ???
16
Lesson 9. There is Still Much to Learn About Event Screening and Analysis
? Freq. gives no
direction clues
DC importing
tie trip?
22 sec
22 sec Pan Am
Waco
McD (stems off North TX)
Heave to support south
Freq. gives no
direction clues
17
Event 5. April 3, 2012. 07:08 GMT.
ERCOT Load = 28,020 MW,
Generation Tripped = 730 MW, Wind
Generation = 1,085 MW.
Freq. gives no
direction clues
2-minute window
10-seconds
Voltage angles
Heaves to support
North & West
Unit trip up north?
A 1-minute window of voltage phase angles. A
small ordinary event is picked up by the PMU
Waveform Analyzer.
Each curve has 1800 points (i.e., 30 points per
second)
A small event, May 29, 2012, probably a
small unit trip, serves as an example.
Not on anybody’s radar screen.
18
Zoom-in of the frequencies
Tiny
Zoom-in of the voltage
phase angles. Swings are
significantly large
Modest West
Texas Wind,
perhaps 50%
of max No significant
change in
steady-state
angles
19
Waco
UT Pan Am
McDonald
Harris 69kV
2.6 peak-peak
≈ 1 peak-peak
1.9 peak-peak
≈ 0.1 peak-peak w.r.t. wall
outlet shows that wall
outlet works well
All freq rings are about 00.03 Hz
peak-peak (tiny, fourth significant
digit), and have no direction
finding characteristics
Degrees wrt U.T. Austin Hz
Hz
Hz
Hz
Degrees wrt U.T. Austin
Degrees wrt U.T. Austin
Degrees wrt U.T. Austin
This plot has two curves – Harris
69kV sub, and UT Austin wall outlet,
identical
Initial angle
drops
Initial angle
drops to reduce
N-S flow
Initial angle rises
to send power
• A small unit trip in North (or West) Texas?
• Would need to also examine the Vrms – it
might be a switching event
• A switching event would diminish in
magnitude according to distance
20
370 miles
280 miles
100 miles
Jaime Ramos, U.T.
Pan Am, South Texas
oscillations
Rex Barrick, McDonald
Observatory, West Texas
wind oscillations
Andrew Mattei, Brazos
Electric Power Coop,
Waco, North-South
interchange indicator
• Idaho National Lab,
equipment going in July
2012, Scott McBride
• Colorado Springs, DOD
affiliate, David Fromme
• Los Alamos National Lab,
115kV sub, working out
firewall details, Mark Hinrichs
• Cloudcroft Cabin, equipment
operating, needs new coax
feed
• Nebraska NPPD, two units
operational, Don Veseth,
Daniel Brooks (EPRI)
• Texas Tech, working out
firewall details, Mike
Giesselmann
• Washington D.C. area,
DOD affiliate, operational,
Mike Bollen
More People are Joining. We’re Not Just Texas
Anymore, and May Need a New Name Soon
Scott Bayer, Austin
Energy, 69kV grid
benchmark
Nebraska Ringdowns Look About the Same as ERCOT
Feb 11, 2012. 17:39 GMT
21
Questions?
Thank you!