lec-gen1 ip address manual setting procedure (edd) fältbuss/ip config för...

9
Document No: DKR50685-C-002 Setting Instructions LEC-GEN1 IP address setting procedure PRODUCT NAME EtherNet/IP Gateway for LEC*6 Series Actuator Controllers MODEL / Series / Product Number LEC-GEN1

Upload: others

Post on 19-Jun-2020

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

Document No: DKR50685-C-002

Setting Instructions

LEC-GEN1 IP address setting procedure

PRODUCT NAME

EtherNet/IP Gateway for

LEC*6 Series Actuator Controllers

MODEL / Series / Product Number

LEC-GEN1

Page 2: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

1. Connect the LEC-GEN1 gateway unit to a PC STEP 1.1: Connect port CN3 of the LEC-GEN1 gateway unit to the LAN port of your PC, using a CAT5 LAN cable. Turn the power ON to the LEC-GEN1 gateway unit.

2. Set the IP address of the PC to match the LEC-GEN1 gateway unit STEP 2.1: Open active [Network Connections].

Page 3: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 2.2: Right click on [Local Area Connection] and select [Properties].

STEP 2.3: Select [Internet Protocol (TCP/IP)] and The PC is usually set to “Obtain an IP click [Properties]. address automatically”.

Page 4: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 2.4: STEP 2.5: Select [Use the following IP address]. Set the IP address of the PC to [192.168.0.25]. [Left click] inside the “Subnet mask” text box.

Note) Do not use the same IP address the LEC-GEN1 gateway unit has been set to. (Default factory setting is “192.168.0.1” or “192.168.250.2” depending on firmware version.)

The following “Caution!” may appear. Click [OK].

STEP 2.6: The “Subnet mask” will be STEP 2.7: Click [Close] to exit the [Local automatically set to “255.255.255.0”. Area Connection Properties] Window. Click [OK] to complete the settings.

Page 5: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 2.8: The [Network Connections] window can now be closed.

3. Change the IP address of the LEC-GEN1 gateway unit STEP 3.1: Start [Internet Explorer].

Page 6: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 3.2: 1. In the address bar type in the current IP address of the gateway unit. 2. Click “Refresh” to establish a connection to the gateway unit. (Default address: 192.168.0.1)

STEP 3.3: The gateway unit user interface will open when the connection between the PC and the gateway unit has been established. If the connection cannot be established check that the LAN cable is appropriate and then try with another IP address for example by changing the last digit of the address to a higher number.

1. 2.

Page 7: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 3.4: Select [Network interface].

STEP 3.5: Select [Network configuration].

Page 8: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

STEP 3.6: The “Network configuration” window shows the current settings.

STEP 3.7: 1. To change the IP address of the gateway unit, type in the new address in the “IP address” box. This example shows IP address “192.168.0.5”.) 2. Turn the DHCP function off by un-ticking the “DHCP” check box. 3. Click [Store settings].

STEP 3.8: Turn OFF the power from the LEC-GEN1 gateway unit, and turn it back ON again. The new IP address will now be effective.

1.

2.

3.

Page 9: LEC-GEN1 IP address manual setting procedure (EdD) fältbuss/IP config för LEC-GEN1/LEC-GEN1_IP_ad… · 1. To change the IP address of the gateway unit, type in the new address

SMC European Technical Centre Electrical & Instrumentation Section Vincent Avenue, Milton Keynes MK8 0AN, U.K. This document is subject to change without prior notice and any obligation on the part of the manufacturer. For SMC internal use only. Please do not distribute to customers, but instruct customers based on these instructions.

Revision history

First edition 15 Feb 2012 Edition B 09 Mar 2012: IP address range removed (PJ). Edition C 03 July 2012: New default factory setting “192.168.250.2” added. Edition D 23 Aug 2013: Document number added and layout standardized.