installation and maintenance manual - high · pdf fileinstallation and maintenance manual for...

54
0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 1/54 M SERIES M116-M145-M180 M330-M390-M450 INSTALLATION AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS Type : B23 Country BE CH ES FR GB IE IT LU NL PT Category I2E(R)B I2H I2H I2Esi I2H I2H I2H I2E (G20) I2L I2H This device complies with the following European Community directives: - Low voltage (73/23/CEE) - Electromagnetic compatibility (89/336/EEC) - Efficiency (92/42/EEC) - Gas device (90/396/EEC) - BS 5978 parts 1 & 3 Customer service for your boiler is ensured by: ATLANTIC 2000 PO Box 11 Ashton Under Lyne OL6 7TR +44. (0) 161 621 5960 Fax +44. (0) 161 621 5966 [email protected] www.atlanticboilers.com

Upload: buidan

Post on 14-Mar-2018

226 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 1/54

M SERIES

M116-M145-M180 M330-M390-M450

INSTALLATION AND MAINTENANCE MANUAL

FOR MODULATING-CONTROL BOILER

WITH GAS BURNER EQUIPPED FOR NATURAL GAS

Type : B23

Country BE CH ES FR GB IE IT LU NL PT

Category I2E(R)B I2H I2H I2Esi I2H I2H I2H I2E (G20) I2L I2H

This device complies with the following European Community directives:

- Low voltage (73/23/CEE) - Electromagnetic compatibility (89/336/EEC) - Efficiency (92/42/EEC) - Gas device (90/396/EEC) - BS 5978 parts 1 & 3

Customer service for your boiler is ensured by:

ATLANTIC 2000�PO Box 11 Ashton Under Lyne OL6 7TR +44. (0) 161 621 5960 Fax +44. (0) 161 621 5966 [email protected] www.atlanticboilers.com

Page 2: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 2/54

Page 3: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 3/54

TABLE OF CONTENTS

1. Dimensional characteristics._____________________________________________________ 4

2. Technical characteristics. _______________________________________________________ 8

3. Installation. __________________________________________________________________ 9 3.1. Installation regulatory requirements in mainland U.K.__________________________________ 9 3.2. Regulatory installation requirements outside UK. ______________________________________ 9 3.3. Accessibility. ____________________________________________________________________ 10 3.4. Electromagnetic compatibility._____________________________________________________ 10 3.5. Electrical connection._____________________________________________________________ 11 3.6. Gas supply. _____________________________________________________________________ 15 3.7. Hydraulic circuits. _______________________________________________________________ 16 3.8. Flue Gas. _______________________________________________________________________ 17 3.9. Ventilation. _____________________________________________________________________ 18 3.10. Evacuation of condensates. _______________________________________________________ 18

4. User interface and boiler regulation. _____________________________________________ 19 4.1. Description of interface ___________________________________________________________ 19 4.2. LCD display ____________________________________________________________________ 19 4.3. Operating modes ________________________________________________________________ 20 4.4. Setting the setpoints ______________________________________________________________ 22 4.5. Boiler status information__________________________________________________________ 23 4.6. Parameter definitions ____________________________________________________________ 26

5. Control unit operation. ________________________________________________________ 27

6. Commissioning.______________________________________________________________ 28 6.1. Checks before starting up boiler. ___________________________________________________ 28 6.2. Startup. ________________________________________________________________________ 28

7. Checks to be performed after startup. ____________________________________________ 28 7.1. Condensate drain. _______________________________________________________________ 28 7.2. Gas supply. _____________________________________________________________________ 28

8. Maintenance operations._______________________________________________________ 29 8.1. Removal of upper casing. _________________________________________________________ 30 8.2. Cleaning the burner. _____________________________________________________________ 31 8.3. Check of ignitor electrode. ________________________________________________________ 33 8.4. Servicing the fan. ________________________________________________________________ 34 8.5. Cleaning the exchanger. __________________________________________________________ 35 8.6. Draining the boiler. ______________________________________________________________ 36

9. Procedure for replacement of gas valve. __________________________________________ 37

10. Spare parts. ________________________________________________________________ 38

Page 4: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 4/54

1. Dimensional characteristics.

Model M116 M145 M180 Boiler diameter ∅ A 692 692 692 Connection distance-between-centers

B 416 416 416

Drain height C 42 42 42 Siphon height (condensates) D 206 206 206 Smoke outlet height E 540 632 705 Return connection height F 960 1050 1125 Outlet connection height H 1310 1400 1475 Gas supply Q 380 380 380 Condensate outlet R 115 115 115 Gas supply S 18 18 18 Gas supply U 249 249 249

� Gas connection; � Outlet connection; � Return connection; � Valve sleeve; � Condensate drain; � Drain connection; � Smoke outlet; �Purge connection.

Back view

Plan view

Models M116-M145-M180

Page 5: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 5/54

Model M116 M145 M180 Smoke outlet position I 511 511 511 Condensate outlet position J 558 558 558 Drain position K 388 388 388 Total height N 1561 1651 1726 Position of outlet/return connections P 511 511 511

Boiler front position T 364 364 364 Height under ceiling (excluding height of leveling feet)

Z 1800 1900 1950

Gas supply dia � 1" 1" 1" Outlet connection dia � 2" 2" 2" Return connection dia. � 2" 2" 2" Valve connection dia. � 1" 1" 1" Condensate evacuation dia. � PVC 32 PVC 32 PVC 32 Drain dia. � 1" 1" 1" Smoke outlet inside dia. � 153 153 180 Purge connection dia � 1/2" 1/2" 1/2"

Front view

Feet adjustment between 38-50 mm

Side view

Z

Page 6: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 6/54

Model M330 M390 M450 Boiler diameter ∅ A 877.5 877.5 877.5 Connection distance-between-centers B 597 597 597

Drain height C 38.5 38.5 38.5 Siphon height (condensates) D 183 183 183 Smoke outlet height E 550 837 837 Return connection height F 1242 1387 1532 Outlet connection height H 1542 1687 1832 Gas supply Q 428 428 431 Condensate outlet R 100 100 100 Gas supply S 33 33 100 Gas supply U 206 206 206

Back view

� Gas connection; � Outlet connection; � Return connection; � Valve sleeve; � Condensate drain; � Drain connection; � Smoke outlet; �Purge connection.

Plan view

Models M330-M390-M450

Page 7: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 7/54

* Optional extra comes un-assembled and excluding hoist Model M330 M390 M450 Smoke outlet position I 610 610 610 Condensate outlet position J 666 666 666 Drain position K 430 430 430 Total height N 1700 1845 1990 Position of outlet/return connections P 610 610 610

Boiler front position T 474 474 474 Height under ceiling (excluding height of leveling feet)

Z 2250 2550 2850

Gas supply dia � 1"1/4 1"1/4 1"1/4 Outlet connection dia � 3" 3" 3" Return connection dia. � 3" 3" 3" Valve connection dia. � 1"1/4 1"1/4 1"1/4 Condensate evacuation dia. � PVC 32 PVC 32 PVC 32 Drain dia. � 1" 1" 1" Flue outlet inside dia. � 250 250 250 Purge connection dia � 1/2" 1/2" 1/2"

Burrner removal crane*

Front view Side view

Feet adjustment between 38-50 mm

Page 8: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 8/54

2. Technical characteristics. Each M Series boiler is factory adjusted for group H natural gas (type G20) with supply pressure of 20 mbar. If the gas network used is a 300 mbar system, mount the Gas pressure regulator kit.

Any intervention on a sealed component will result in loss of warranty. Nominal, maximum and minimum gas supply pressures.

Natural gas G20 Nominal pressure (mbar) 20 Minimum pressure (mbar) 17 Maximum pressure (mbar) 25 Characteristics of combustion at 15°C and at 1013 mbar. Model M116 M145 M180 M330 M390 M450 Nominal power P (kW) 116 145 180 330 390 450 Maximum Heat release Q (kW) 122 155 192 349 415 472 Minimum Heat release Q (kW) 31.5 39 48 88 105 118 Gas flowrate : G20 (m3/h) 12.9 16.4 20.3 36.9 43.9 50.0 Diameter diaphragm G20 (mm) - - - - 17,3 17,7 Smoke flowrate (g/s) 52.1 66.3 81.4 150.6 179 203.6 Smoke temperature (°C) 110 115 120 130 130 130 Fresh air flowrate (m3/h) 146.0 185.5 227.7 421.7 501.4 570.4

Hydraulic loss (daPa) 850 à 5m3/h

1050 à 6.25m3/h

1350 à 7.75m3/h

920 à 14.3m3/h

1150 à 16.3 m3/h

1480 à 19.4 m3/h

100 daPa = 0.102 mCE Characteristics for electrical connection. Model M116 M145 M180 M330 M390 M450 Electrical power absorbed (boiler without accessories) (W) 420 440 460 620 640 820

Electrical power supply (V) 230 V AC +10 % -15 % 50 Hz Full load amperes (A) 8 8 8 10 10 12

DHW sensor : 10 m Comfort thermostat : 40 m Max. length of sensor cables External sensor : 40 m Ambient temp. sensor : 50 m

230 V AC +10 % -15 % Power terminal strips Outlet 5 mA à 2 A

Other characteristics. Maximum working pressure PMS (see nameplate) :

4 bar for M116-M145-M180 6 bar for M330-M390-M450

Maximum operating temperature : 85 °C, (factory adjusted for 80°C).

Page 9: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 9/54

3. Installation.

3.1. Installation regulatory requirements in mainland U.K.

Installation and maintenance of the unit must be performed by a qualified professional in accordance with all applicable rules and regulations and trade practices.

BRITISH STANDARDS BS 5440 Part 1 + 2 (Flue Installation) BS 6644 Installation of gas fired hot water boilers from 60 kW to 2000 kW BS 6880 Parts 1,2, +3 code of practice for low temperature hot water heating systems of outputs greater than 45 kW CP 342 Centralised hot water supply Part 2 Buildings other than individual dwellings

GAS PUBLICATIONS IGE/UP/1 –Soundness testing + purging of industrial + commercial gas installations IGE/UP/1A – Soundness testing + purging of small low pressure industrial + commercial natural gas installations IGE/UP/2 – Gas installation pipework, boosters + compressors in industrial + commercial premises IGE/UP/10 – Installation of gas appliances in industrial + commercial premises PT1 flued appliances

HEALTH + SAFETY EXECUTIVE GUIDANCE NOTE PM5 – Automatically controlled steam + hot water boilers.

3.2. Regulatory installation requirements outside UK.

Installation and maintenance of the unit must be performed by a qualified professional in accordance with all applicable rules and regulations and trade practices of the country in which the boiler is installed. For Switzerland, note in particular Gas Boiler Directives G1 and G3 and those of the local (canton) authorities (e.g. fire and police regulations).

Page 10: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 10/54

3.3. Accessibility. Sufficient clearance must be provided to facilitate servicing on the boiler. Minimum clearances must be provided on the sides, free of all obstacles (partitions; pipes; other boiler; …) to ensure that the right and left exchanger doors can be opened. See dia below. For models M116 to M180, the minimum height above the boiler is Z + 50 mm (see « dimensional characteristics » section); this area must remain free of all obstacles to allow inspection and cleaning of burner. For models M330 to M450, the minimum height above the boiler is Z + 50 mm (see “dimensional characteristics” section). This height is defined by a burner removal tool (supplied). When installing the boiler, a tool installation test must be performed to ensure that the necessary height under the ceiling for use of the tool has been observed. This area must always remain free of all obstacles to allow inspection and cleaning of the burner. Failure to observe these requirements will result in LOSS OF WARRANTY. The M Series boilers must not be installed on a combustible surface (wood floor, plastic floor covering, etc.).

3.4. Electromagnetic compatibility.

The M Series boilers satisfy the requirements of the European directive concerning electromagnetic compatibility in a residential, commercial and light industry environment.

Boiler door opening dimensions Models M116-M145-M180

Boiler door opening dimensions Models M330-M390-M450

Page 11: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 11/54

3.5. Electrical connection. Unlock the front panel (item �), by turning the screw located at the middle by at least two turns. Open the front panel. The control panel is accessed by opening and removing the left casing door (single hinge at rear part) (left door not shown). Remove the screws (item �), then remove the control panel cover (item �). CAUTION : The area volume located above the boiler must remain free of all obstacles to allow inspections on the burner (see chapter 8.2 – Cleaning the burner)

To the left of the control panel, use the cable glands (item �) to run the power supply, alarm transfer and circulator control cables (High current). To the right of the control panel, use the cable glands (item �) to run the power supply, sensor and other low voltage signal cables (Low current). The cable/wire ways can be mounted at the locations where the cables pass; be careful not to mount wire/ways in such a way that they interfere with removal of the boiler roof. For connection, observe wiring diagram specifications, in particular, phase, neutral and ground polarities (see figure on next page). Boiler must be properly connected to ground and satisfy the requirements of standards in the country. For electrical connection characteristics, see table in “Technical Characteristics” chapter. It is highly advised to equip the electric installation with a differential protection of 30 mA. To envisage a double-pole switch on the power supply boiler.

3 1

5

Passage for low voltage cables

2

Passage for power cables

4

2

CAUTION : The model shown in the diagram is a M180 ; the connection principle is strictly the same for all the other models

Page 12: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 12/54

Detail of customer terminal strips

Power terminal strips (located left on control panel)

Signal terminal strip (located right on control panel)

Mains power supply

Sytem pump 1

Alarm transfer / programmable output

DHW pump

Fan supply transfer

Internal pump supply transfer

Inst

alle

rs C

onn’

s.

.

2A maxi

2A maxi

2A maxi

L L

N N

K1 K1

N N

K2 K2

N N

K3 K3

N N

L L

N N

L L

N N

Lower DHW sensor (QAZ 36). (accessory, commercial reference : 059261). To be used by default

External sensor (QAC 34) (Accessory, commercial reference : 059260).

Insufficient water (26V dry contact)/ flue gas temperature limiter.

Not to use like a controller contact, to use for a prolonged stop. The shunt must be withdrawn if a 0-10 V signal is active.

Programmable ambient temp. sensor (QAA 73). (accessory, commercial reference : 059262)

B3 B3

M M

B9 B9

M M

CD CD

CD CD

RT RT

RT RT

OT OT

OT OT

Page 13: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 13/54

Wiring diagram with hot surface ignition for M145-M180 / M330-M450

Page 14: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 14/54

Wiring diagram with spark ignition for M116

Page 15: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 15/54

Gas supply connection

Pressure tap (ValveP) Pressure tap (upstream pressure)

Pressure tap (ValveP)

Pressure tap (upstream pressure)

Gas supply connection

3.6. Gas supply.

Prior to actual commissioning, check that the natural gas supply corresponds to the boiler’s nominal pressure indicated on the nameplate (20mbar). Before supplying the installation with gas, check that the various connections are properly executed and that there are no leaks. In particular, check that a removable coupling is provided between the sectional valve and the gas supply connection on the boiler. To measure the upstream pressure, use the pressure connection available on the connection flange when the boiler is operating (“Upstream pressure” connector). CAUTION : The gas line connection must not be subject to any mechanical stress (risk of

loss of tightness on gas valve). If the gas network used is a 300 mbar system, check that there is a pressure regulator and a gas filter upstream.

The gas valve is factory-adjusted for type G20 gas.

Models M116-M145-M180

M330-M390

Model M450

Page 16: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 16/54

3.7. Hydraulic circuits.

A « technical requirements book » is supplied with the boiler. This book gives the hydraulic diagrams which are acceptable for correct operation of the boiler. The hydraulic installation must comply with one of these diagrams. The boiler and its installation must be equipped with the following:

• safety valve calibrated for 4 bars for the models M116-M145-M180 et calibrated for 6 bar for the models M330-390-M450 on outlet connection sleeve provided for this purpose,

• isolating valve on outlet and return connections; surge tank, • an expansion vessel, • check valve (supplied with boiler), • a purging. (certificate)

The water flow of the boiler must be, at the minimum, equal to P/20 with P: power supplied, expressed in Th/h. The circulator must be sized taking account of the maximum power supplied. If the circulator is replaced, you must use the genuine spare part specified in the list of spare parts (see section 10). Filling with water The characteristics of the water used, as of commissioning and for the entire service life of the boilers must comply with the following values:

• Filling water When filling a new installation, or when it has been completely drained, the filling water must satisfy the following characteristics:

Hardness : < 100 mg/l CaCO3 (dissolved Calcuim Carbonate)

• Topping-up water A significant addition of raw water would result in significant scale deposits which could cause overheating and subsequent boiler failure. Special monitoring of the supply water is required and use of a water meter is mandatory. The topping-up water must satisfy the following requirement:

Hardness : < 10 mg/l CaCO3

• System water The system water can be the cause of corrosion due to:

The acidity of the medium, Presence of oxygen, The non homogeneity of the metals used.

To avoid these problems from occurring, the system water must be treated to ensure the following requirements:

PH : 8.2 to 9.5 Oxygen reducer: in excess.

The chemical products used must be implemented methodically and rigorously. We recommend calling in specialized companies for water treatment questions. These specialized companies will be able to propose:

The appropriate treatment in accordance with the characteristics of the installation, A service contract for monitoring and ensuring the result.

Where renovation of an existing old boiler system is concerned, prior to installing the new boilers, the installation must be flushed.

• The use of glycol water is prohibited.

Page 17: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 17/54

After filling with water :

• Check the water pressure on the pressure gauge (not supplied): For models M118-M145-M180, the water pressure should be at 4 bars max. when hot and at 1 bar minimum when cold, For models M330-M390-M450 the water pressure should be at 6 bars max. when hot and at 1 bar minimum when cold. • Check that the boiler and its installation are properly bled before boiler operation.

3.8. Flue Gas.

The dimensions of the flue conduits should be calculated on the basis of a flue gas pressure at the boiler outlet equal to 0 Pa. The flue exhaust conduits must be made of a condensate-resistant material for condensates which can form during boiler operation. These materials must also be capable of withstanding smoke temperatures of up to 160°C. The conduits should contain no horizontal sections, so as to avoid condensate retention. Check that the combustion gas exhaust is formed by a tight conduit equipped with a tight condensate exhaust connection (see diagram below) M Series boilers are very efficient and therefore their flue gas temperatures are very low. The boiler flue outlet must consequently be oriented with a positive slope so to ensure a sufficient draft It is also necessary to follow local legislation for chimney installations. IMPORTANT: If several boilers are connected to a single flue, check: 1. That the flue is not pressurized, with all boilers operating. 2. If one of the boilers is stopped, that the others do not discharge into the stopped boiler

Connection clamp + seals (not supplied)

Boi

ler s

ide

Page 18: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 18/54

Example of advised configurations :

3.9. Ventilation.

Check that the upper and lower ventilations exist, that they comply with the applicable regulations, and are not obstructed.

3.10. Evacuation of condensates. The condensates must be evacuated to the drain by means of a PVC pipe (min. diameter 32 mm) since the condensates are acid and aggressive (pH between 3 and 5). An adequate slope of at least 3% should be provided to ensure proper condensate evacuation. Neutralize the condensates before evacuation in accordance with applicable regulations.

Upper ventilation

Ground Ground

Lower ventilation

Upper ventilation

Ground

Smoke conduit

Condensate connection

Condensate connection

Condensate connection

Lower ventilation

Smoke conduit

Front view Side view Ground

Page 19: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 19/54

4. User interface and boiler regulation.

4.1. Description of interface The boiler customer interface comprises a main switch, a drawer-type fuse-holder, an electronic board with a backlighted LCD screen (two 4-digit lines + pictograms) and 10 buttons. A pre-cut mounting position for 2 regulators (96x96) or 1 regulator (144x96) is also provided. All the customer settings and possible parameter definitions are performed using this interface. The interface also enables the user to read information concerning operation of the boiler.

4.2. LCD display In its standard version, the screen displays the boiler status (operating mode, time, heating time program, boiler temperature, presence of flame, possible fault).

Mode selection buttons Programming buttons Information button Boiler main on/off switch

Setpoint adjustment buttons

Reset button

Pre-cut position for regulators

Boiler fuse-holder

Summary of heating time clock : Each small square represents a heating period in comfort mode (in slots of 1 hour). The flashing square indicates the current hour.

Heating mode Time Boiler temperature

DHW mode Symbols :

DHW preparation in progress or display of DHW temp.

Heating active, or boiler setpoint temp. or ambient temp.

Comfort mode

Economy heating mode External temp. display

Flame present Alarm

Page 20: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 20/54

When a non-blocking fault appears, the time display alternates with the fault code display. This does not result in a lockout condition. When a fault places the boiler in a lockout condition, the fault code is displayed flashing in place of the boiler temperature. A small bell appears at the lower left of the display. Refer to the paragraph on “Error messages” to interpret the fault codes. In the last two cases, briefly press the information button to display the fault code alone. Simultaneously press the and buttons to display the extended fault code (Press then or

to return to the standard display).

4.3. Operating modes Heating mode button This button selects the heating mode among the Stop, Auto, Comfort and Eco modes

Standby 1. No request for internal heat is taken into account. The frost protection remains active.

2. The requests for external heat (0-10v or bus LPB) remain active, except cascade application.

Comfort Permanent “comfort” mode. The boiler power is

adapted to satisfy the heating setpoint (heating setpoint button).

Eco Permanent reduced heating mode. The boiler power

is adapted to satisfy the ECO setpoint (parameter no. 5) (see paragraph 4.6, parameter definitions).

Page 21: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 21/54

Auto Depending on the heating time program, the regulator alternates between the Comfort and Eco modes.

Two additional “Service” modes are available. These are used to perform measurements on the boiler: Boiler This mode is used to run the boiler at full load. cleaning Simultaneously press and for around

3 seconds. The burner starts up (if not already operating) and increases his power to supply the maximum heat release. The burner stops when controlled by the limiting

thermostat (88°C). This value is an independent safety feature on the limit operating temperature which can never exceed 85°C. When this function is active, a forcing signal1 is generated to evacuate the calories.

Regulator This mode is used to manually define the burner override heat release. Simultaneously press and for around 6

seconds from one of the standard modes, or 3 seconds followed by the boiler cleaning mode. The relative power setpoint2 of the burner is displayed on the screen.

The or buttons are used to adjust the setpoint value in steps of 1 %. The and buttons are used to pass directly to the min. or max. power setpoints (0% or 100%). To exit one of the two modes and return to the standard operating mode, simultaneously press and for 1 second. 1 Forcing signal: triggers pumps, and/or opening of the three-way valves of the heating circuits connected to evacuate the calories. They are triggered by the following functions:

- Electronic temperature limiter. - Safety thermostat. - Boiler cleaning mode. - Regulator override mode. - Boiler no-frost mode. -

2 Relative power: this is the effective power of the burner, transferred to its modulation range. 0% corresponds to the minimum power and 100% to the maximum power of the burner. To convert the heat release to a %, the following formula is used:

iirelative

cal QQPower

Q minmin %

100)%100(

% +−⋅

=

Page 22: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 22/54

DHW mode button Active / in-active Domestic Hot Water

active DHW production in-active DHW production

4.4. Setting the setpoints Setting the heating setpoint Depending on the regulation mode selected, the setpoint temperature takes a different meaning: • In constant temperature mode, the setpoint is a water temperature at the heater outlet.

• In regulation mode, depending of the outside temperature, or the ambient temperature, or both, the setpoint is an ambient temperature.

Press the heating setpoint button . The current setpoint value is displayed. Press the or buttons to adjust the heating temperature setpoint. Press the heating mode button , the DHW mode button , or the heating setpoint button to exit the setpoint adjustment screen. If no button is pressed for around 8 minutes, the interface returns to the standard display. Setting the DHW setpoint This function can only be accessed provided an DHW production is connected to the boiler. Press on the domestic hot water setpoint button . The current setpoint value is displayed. Press the or buttons to adjust the domestic hot water temperature setpoint. Press the heating mode button , the DHW mode button , or the DHW setpoint button to exit the setpoint adjustment screen. If no button is pressed for around 8 minutes, the interface returns to the standard display.

The DHW setting must be defined according to the regulation required in the country to avoid all risks with respect to the legionnella.

1

Page 23: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 23/54

4.5. Boiler status information Info button At any time, you can scroll the basic boiler information by pressing the Info button . Each time the Info button is pressed, the next variable is displayed.

1 DHW temperature

2 Not used

3 Burner operating phase code (refer to “Burner phase codes” sub-paragraph)

4 Outdoor temperature

5 Albatros3 error code (refer to “Error messages” sub-paragraph)

6 Boiler temperature

To return to the standard display, press on either of the or buttons 3 Albatros : name given by SIEMENS for fault codes.

Page 24: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 24/54

Extended information list Using the info mode (info button ( ) pressed once), you can obtain additional data concerning operation of the boiler. To do so, simultaneously press and for around 3 seconds. The time display is replaced by an address formed by a letter (b, C, d) and a digit (from 0 to 7). Use the and buttons to modify the letters. Use the or buttons to modify the digit. Press the button to return to info mode or the or to return to the default display.

Display level Description

b0 LMU…-internal software diagnostic code b1 Boiler return temperature b2 DHW temperature sensor 2 b3 - b4 Outdoor temperature b5 Composite outdoor temperature b6 Attenuated outdoor temperature b7 Flow temperature 3-way valve C1 Ionization current C2 Fan speed C3 Current fan control PWM C4 Relative output C5 - C6 Control differential setpoint / value measured d1 Boiler temperature setpoint (including DHW and other heating circuits) d2 Current boiler temperature setpoint d3 Room temperature setpoint d4 DHW temperature setpoint d5 Maximum degree of modulation in heating mode d6 Maximum speed at maximum output in heating mode

Page 25: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 25/54

Error code display In the event of a fault resulting in lockout of the LMU, the alarm signal is displayed continuously and the fault code flashes. To reset the LMU, eliminate the source of the fault, then press the reset

button for at least 2 seconds.

Fault code. Potential cause

0 No entry in Albatros code made 10 Fault outside sensor 20 Fault boiler temperature sensor 1 40 Fault return temperature sensor 1 50 Fault domestic hot water temperature sensor 1 52 Fault domestic hot water temperature sensor 2 61 Fault room unit 1 62 Wrong room unit 1 or wrong radio clock connected 81 Short-circuit on LPB bus, or no bus power supply 82 Address collision on LPB bus (several identical addresses) 91 Data overflow in EEPROM 92 Hardware fault in electronics

100 Two clock time masters in system 105 Preventive maintenance 110 Safety thermostat tripped 111 Limit thermostat has tripped 119 Water pressure switch has tripped 132 Safety shutdown (e.g. by gas pressure switch) 133 No establishment of flame on completion of safety time

128/134 Loss of flame during operation 129/135 Wrong supply of air*

140 inadmissible LPB… segment number or device number 148 Incompatibility LPB… interface/basic unit 151 Internal fault LMU 152 Fault in connection with LMU… parameter settings 153 LMU… has locked out 154 Plausibility criteria violated 160 Fan speed threshold not reached 161 Maximum fan speed exceeded 164 Fault heating circuit flow switch / pressure switch 180 Chimney sweep function active 181 Controller stop function active 183 LMU… in parameter setting mode

* For the M450 model, the appearance of this error code can be related to the detection of a variation of speed between the 2 fans, via the electronic chart Twin Fan located in the control panel (See chapter Exploded view of control panel). Under normal operation, the red indicator of this chart flickers. At the time of a setting in safety for the code defect described above, this indicator remains lit permanently.

Page 26: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 26/54

Burner phase codes To consult the burner phase codes, press the Info button three times. (As indicated on page 17)

Display code Meaning

0 Standby (no demand for heat) 1 Startup blocked 2 Fan start 3 Pre-purging 4 Waiting time 5 Pre-ignition time 6 Safety time

10 Heating operation 11 DHW operation 12 Parallel operation of space heating and DHW heating 20 Post purging 22 Home running 99 Lockout position (display of the current error code)

4.6. Parameter definitions To best define the boiler configuration, a certain number of parameters can be modified by the end-user or installer. To secure the boiler configuration, all the parameters are not accessible to the end user. These are therefore grouped by access levels. Starting from the standard display, the end-user parameter definition mode is accessed by pressing either of the or buttons. The display indicates a P followed by a parameter number with 3 digits. The and buttons enable you to scroll the list of parameter numbers. Once you have reached the parameter you wish to modify, adjust its value using the and buttons. The new value is validated as soon as you go to the next or previous parameter or if you exit the mode by pressing the buttons. Caution, if you exit the programming mode using the or buttons, the current parameter change will not be validated. Refer to the client parameter summary table at the end of this manual. Parameters accessible at installer level The installer level is accessed from the end-user configuration mode by simultaneously pressing the and buttons for 3 seconds. The letter P is replaced by the letter H. Refer to the client parameter summary table at the end of this manual.

Page 27: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 27/54

5. Control unit operation.

Button : PG = Gas pressure switch. CD = Flow controller. TL = Limiter thermostat. = Alarm = Flame detection. = Ignitor electrode = Gas valve = Fan Nmax = Max. speed authorized. N_VL = Max. speed authorized with modulation. N_ZL = Speed on ignition. N_TL = Min. speed authorized with modulation Nzero = Speed less than 200 rpm, therefore considered as null

NOTA : The control unit automatically starts again a new start-up of the burner in the event of failure of the first start-up. For model M116, there is no pre-heating phase No.5 since this model utilizes arc ignition.

Fan speed

0 2 3 4 5 6 10, 11, 12 20 22 1 99 Standby Run up Pre- Wait Pre- Safety Operation Post- Return to Startup Safed

ventilation Heating for hot surface ignition

time ventilation zero blocked

Nmax N_VL N_ZL N_TL Nzero

0

11 s. 3 s. 1,8 s. t

Phase code

PG, CD, TL

Page 28: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 28/54

6. Commissioning.

6.1. Checks before starting up boiler.

Check hydraulic balancing of boilers. Check that pressure when cold is at least 1 bar and that boiler is equipped with a safety valve. Check a pressure regulator was installed if the network gas is to 300 mbar For a renovation, check that the system has been properly flushed.

6.2. Startup. Before packaging, all boilers are tested in factory with group H natural gas (type G20) during which all the adjustments are performed. For this reason, startup is limited to the following points: The power is limited to 65% of its rated value and the maximum temperature is also limited to 70°C up to commissioning. It is strongly recommended the commissioning procedure to be performed by our Customer Technical Assistance Department. Provisional commissioning can be performed as follows :

1. Switch on the main power switch. 2. Initiate a heat request in comfort mode using the customer interface (see “Interface presentation”

paragraph). 3. Once the burner is operating, check the tightness of the gas line couplings using a non

combustible product. Check the performance of the combustion (via a calibrated combustion analyzer).

4. Set the clock to the correct time (Refer to the client parameter summary table at the end of this manual.)

Any tampering or interference with sealed components will result in loss of warranty.

7. Checks to be performed after startup.

7.1. Condensate drain.

During inspections, check that the condensate drain is not obstructed, either boiler side or pipe side.

7.2. Gas supply.

Check that the gas supply pipe has the correct diameter.

All the boilers must be abruptly stopped together using the main circuit-breaker of the heating system to check that the safety device of the gas pressure regulator station does not trip.

If the device trips, the gas supply pipe is too small. Following this procedure, re-engage the circuit-breaker. The boilers should automatically start up again; contact the gas pressure regulator station supplier.

Page 29: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 29/54

8. Maintenance operations. The maintenance operations must be performed by a qualified professional. Before proceeding with the operations listed below:

Set the main switch to the off position. Close the gas supply shutoff valve. Hydraulically isolate the boiler.

Condensate evacuation siphon Check that condensate flows freely Refill with water after checking

Annually or every 3000 h

Hot surface ignition electrode Disassemble the electrode unit Check the electrode. If white deposit visible, replace the ignition electrode preventively

Annually or every 3000 h

Recycling pump

Check that the pump is working properly. Annually or every 3000 h

Air filter

Replace or clean the air filter Annually or every 3000 h

Exchanger doors Check the tightness of door seals and replace them if necessary M116-M145-M180: Check the membrane state which is fixed below flue outlet and change it if necessary.

Annually or every 3000 h

Check of burner

Check that the pressure indication hose between the venturi mixer and the gas valve is properly connected

Annually or every 3000 h

Cleaning of heat exchanger Outer tube set Check the cleanliness of the tubes visually If necessary, disassemble the baffles and clean the tubes chemically with a spray then rinse with a spray of water (do not use a high-pressure jet).

Annually or every 3000 h

Condensate evacuation siphon

Clean the condensate evacuation siphon. Annually or every 3000 h

Inner tube set Disassemble the fan motor / mixer unit Disassemble the water circuits of the burner after partial drainage of the boiler. ( drainage of sludge trap) Checking that connecting hoses are not clogged Check the aluminium ranges. Do not modify their fixing torque. In the event of a problem, contact the Client Technical Assistance department. Clean the tubes if the inner set chemically and rinse with water. Remove deposit from the lower part of the body by suction, make sure that the male hydraulic connecting is not obstructed so to ensure a good waterprroofness boiler body/burner. Protect and clean the hydraulic connecting, Remember to change joint when re-mounting.

Every 3 years or 9000 h

If the pipework is likely to be clogged with sludge Rinse the water circuits of the boiler in a horizontal position

Page 30: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 30/54

8.1. Removal of upper casing. For models M116-M145-M180 : • Remove the screws (item �) securing the boiler roof

(top panel) (item �) and remove the roof. • Unlock the front panel (item �) by turning the screw at

the center by at least 2 turns. • Open the front panel. • Open the casing doors (item �). For models M330-M390-M450 : • Remove the screws (item �) and the lifting rings (item

�) securing the boiler roof (top panel) (item �) and remove the roof.

• Unlock the front panel (item �) by turning the screw at the center by at least 2 turns.

• Open the front panel. • Open the casing doors (item �). NOTE: To facilitate disassembly of the burner, fully remove the doors (by lifting them out of their hinges after having disconnected ground wires located behind each of them).

Caution : When reinstalling the doors, be sure to properly connect the ground wires to the doors.

4 4

1

2

3

2

5

1

3

44

Page 31: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 31/54

8.2. Cleaning the burner. Before disassembly of the burner, take care to get the small pocket of joints mentioned to you in the list of spare parts. After removing the boiler roof (top panel) (see previous section). • Remove the gas connection from the gas valve plate (item �) ; • Remove the air filter bracket (item �) • Remove the igniter (item�) Caution : after removal, protect pipe assemblies to prevent ingress of foreign matter.

• For models M116-145-180-330-390, using a 13mm wrench, loosen the three mounting nuts (item �) securing the fan assembly (see fig. 1).

• For model M450, loosen the six mounting nuts of the air-gas mixer (item �) and remove the gas valve + air-gas mixer block. Loosen the four mounting nuts (item �) securing the fan assembly (see fig. 1).

Never remove the fan side plates. • Lift out and remove the fan assembly (venturi + fan + gas valve (see fig. 2). • Create an air intake at the top of the return and outlet pipes of the boiler (safety valve open) and

open the boiler drain tube valve to partially drain the system so that the two boiler pipe assemblies are free of water.

• Disconnect the hose (item �) connecting the boiler body to the burner. (burner pipe assembly side only).

• Using a 13mm wrench, loosen the 3 mounting screws (item �) securing the burner (see fig. 2); remove compression springs and ensure to keep them in a safe place.

FIGURE 1

Models M116-M145-M180

M330-390

3

1

2

4

1

2

3

4

5

Model M450

6 7

8

8

7

6

Models M116-M145-M180

M330-M390

FIGURE 2

Model M450

Page 32: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 32/54

• Slowly lift out and remove the burner. For models M330, M390 and M450, a burner removal

tool is supplied with each boiler (see figure above). A lifting accessory matched to this tool is available from the boiler manufacturer (see list of spare parts). For safe and easy work, we recommend that you use this tool.

• Clean the burner using compressed air. • Before reassembly : replace the socket seal (fig2, item ����), and those of the hose and those

of the hydraulic connections between the boiler body and the burner (fig3, item ����). Check the seal between the burner and the exchanger body (item ����), and replace it if necessary.

• To reassemble the burner, perform the disassembly procedure in reverse order taking care not to knock the aluminum ranges or the ignitor electrode bracket.

• When restarting the system, check that all couplings which have been removed or loosened are air-tight.

CAUTION

ALUMINUM RANGES

NEVER REMOVE OR TURN THE ALUMINUM RANGE MOUNTING SCREWS

Burner removal crane for models M330-

M390-M450

Aluminum ranges

FIG 3

9

10

Page 33: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 33/54

8.3. Check of ignitor electrode. The ignitor electrode on the M Series boilers is factory-adjusted to ensure optimum startup of the boiler. The various components are located as follows : M SERIES type M116 with spark ignition: M SERIES type M145, M180, M330, M390 and M450 with hot surface ignition:

Bottom view

Ground electrode

Ionization electrode

Ignition electrode

Ignition electrode

Ionisation electrode

Ground Electrode

2 checks alignment for the ionization electrode

Bottom view (scale 1)

Ionization electrode

Ignition electrode

Check alignment for the ionization electrode

Ionization electrode

Ignition electrode

Page 34: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 34/54

8.4. Servicing the fan. Reminder : Removal of fan side plates is PROHIBITED. Only the air filter can be removed and cleaned using a compressed-air blower. (In the event of strong clogging of the air filter, the operation of cleaning must be carried out before the recommended 3000 H period as stated in chapter 8).

Fan

Filter bracket

Venturi

Models M116-M145-M180

M330-M390

Model M450

Filter bracket

Fans

Venturi

Page 35: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 35/54

8.5. Cleaning the exchanger.

• Open the four quick-fasteners (item �) securing the doors closed ; • Open the stainless steel exchanger doors (item�)

For models M116-M145-M180, the door must be raised in order to remove the base stops. For models M330-M390-M450, the 2 pintles on the rear part of the door must be removed.

• Open the quick-fasteners (item �) securing the smoke baffle banding (item �). • Remove the banding and remove the smoke baffles (items � and �)

2 2

3

Models M116-M145-M180

2

3 3

Models M330-M390-M450

Page 36: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 36/54

• Brush the smoke baffles using a stainless steel or plastic brush. • If necessary, clean the exchanger tubes. • When reassembling, suspend the baffle assembly between each upper part of the exchanger tubes

using their attachment fittings (see detail). Be sure to properly position the banding-holder baffles (item �) as shown in the diagram below.

• Place the bandings in the pins of the banding holder baffles. • Tighten the quick-fasteners and check that each of the baffles is properly bearing against the

exchanger tubes. • Before closing the doors, check the condition of the door seals and replace them if necessary. • Close the doors.

8.6. Draining the boiler.

If the user decides to drain the boiler, he is responsible for ensuring that no water remains in it.

• Close the stop valves of the outlet and return connections ; • Create an air inlet at the tope of the boiler pipe assembly (by opening the safety valve) ; • Open the boiler drain cock (refer to chapter 1).

Exchanger tube assembly (top view)

Flue outlet

Exchanger tubes

Attachement fitting

Page 37: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 37/54

9. Procedure for replacement of gas valve.

The valve adjustment must only be performed by a ‘competent’ person and with the boiler operating at maximum power and at minimum power (use “regulator override” mode see “Operating modes” paragraph”). CAUTION ! : measurements used for valve adjustment must be taken from the pressure taps marked valve P and upstream P, and not from the gas filter pressure taps. Adjustment at maximum power “Regulator override” mode, Max. power = display : 100% • Remove the cover (item �). • Measure the gas supply pressure (Upstream pressure). • Adjust the valve pressure (Valve P) keeping in mind

that ( )PvalvePupstreamPvalve −=∆ given in the table below (adjust pressure by acting on adjustment screw located on top of valve below black cover (item �), (using a 3mm-male hex wrench).

Boiler type Valve type Gas type ∆Pvalve(mbar)

M116 VR 415 G20 3.6

M145 VR 415 G20 6,4

M180 VR 420 G20 4,4

M330 VR 432 G20 5,0

M390 VR 434 G20 4.2

M450 VR 434 G20 5,6

( )PvalvePupstreamPvalve −=∆

• If necessary, adjust the valve pressure to obtain a CO2 rate of between 9.3% and 9.7%. example : Boiler type: M 180 Gas type: G20 Supply pressure = Upstream Pressure = 21,0 mbar Valve Pressure = 21,0 - 4,4 = 16,6 mbar CAUTION, for models M390 and M450 only : You must use the specific diaphragm supplied as a spare part with the gas valve VR 434. The diaphragms are identified by a marking: G20/390 or G20/450. Adjustment at minimum power Regulator override” mode, minimum power = display : 0% • adjust the offset regulator (item �) to

obtain a CO2 rate at minimum power of between 8.7% and 9.1%.

• To validate correct adjustment of the valves (Pmin. between 8.7% and 9.1% and Pmax. between 9.3% and 9.7%) go back and forth between Pmin. and Pmax. (HMI = 0% and 100%).

Gas supply

Gas valve

3

Upstream Pression

Valve Pression

4

3

Top view of gas valve

Gas valve

Valve Pressure

Page 38: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 38/54

10. Spare parts.

1 Fuse T12.5A 5x20 (boite de 10) for control panel 060427

2 Fuse T2A 5x20 (boite de 10) isoling transformer 060448

3 Fuse F1A 5x20 (boite de 10) burner control device LMU 060449 4 Burner control device LMU64. M116 070932 4 Burner control device LMU64. M145 070931 4 Burner control device LMU64. M180 070930 4 Burner control device LMU64. M330 071205 4 Burner control device LMU64. M390 071206 4 Burner control device LMU64. M450 071350

7 Control panel (without burner control device) M116-M145-M180-M330-M390 070933

7 Control panel (without burner control device) M450 071376

8 On-off switch 070385

9 HMI-LCD interface/display 060430

10 Outlet or return sensor QAZ36 060431

11 Pump or alarm transfer relay 060084

12 Isolating transformer 060432

13 Safety thermostat 071197

14 Igniter electrode unit + complete electrode (hot surface) M145/M450 070935

14 Igniter electrode unit + complete electrode (spark) M116 070979

15 Igniter electrode (hot surface) M145 to M450 060434

16 Ionizing electrode M116 to M450 070934 17 M116 and M145 : Gas valve VR415 Honeywell 070936 17 M180 : Gas valve VR420 Honeywell 060436 17 M330 : Gas valve VR 432 Honeywell 071207 17 M390 : Gas valve VR 434 Honeywell + diaphragm 390/G20 071208 17 M450 : Gas valve VR 434 Honeywell + diaphragm 450/G20 071410

18 Attach intermediate burner for M330 – M390 071238 19 M116, M145, M180, M330 and M450 : Fan EBM G1 G170 - AB31 - 15 060438 19 M390 : Fan EBM G1 G170 – AB31 - 32 071209

20 0-40mbar min. gas pressure switch C60VR40040 Honeywell 060439 21 Seals (kit) for burner M116, M145 and M180 070937 21 Seals (kit) for burner M330 and M390 071210 21 Seals (kit) for burner M450 071351 22 Seals (kit) for exchanger door M116 070938 22 Seals (kit) for exchanger door M145 070939 22 Seals (kit) for exchanger door M180 070940 22 Seals (kit) for exchanger door M330 071211 22 Seals (kit) for exchanger door M390 071212 22 Seals (kit) for exchanger door M450 071352 25 Recycling pump hose M116, M145 and M180 071365 25 Recycling pump hose M330, M390 and M450 071213 26 Recycling pump M116, M145 and M180 071365 26 Recycling pump M330, M390 and M450 071214

27 Membrane M116 071010

Page 39: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 39/54

28 Flow controler 070942 29 Check valve M116, M145 and M180 070943 29 Check valve M330, M390 and M450 071215

30 Condensate drain siphon 060447

31 Pyrex glass with seal for flame window dia 38 060407

32 Filtering sheet M116, M145 and M180 070944

32 Filtering sheet M330, M390 and M450 071216 33 Gas filter M116, M145 and M180 000366 33 Gas filter M330, M390 and M450 071217 34 Air filter sub element M116 070945 34 Air filter sub element M145 070946 34 Air filter sub element M180 070947 34 Air filter sub element M330 and M450 071218 34 Air filter sub element M390 071273 37 Left casing door M116 062905 37 Left casing door M145 062906 37 Left casing door M180 062907 37 Left casing door M330 071219 37 Left casing door M390 071220 37 Left casing door M450 071353 40 Right casing door M116 062908 40 Right casing door M145 062909 40 Right casing door M180 062910 40 Right casing door M330 071221 40 Right casing door M390 071222 40 Right casing door M450 071354 43 Front strip M116 062911 43 Front strip M145 062912 43 Front strip M180 062913 43 Front strip M330 071223 43 Front strip M390 071224 43 Front strip M450 071355

47 Trade mark « YGNIS » 062916 48 Burner M116 070948 48 Burner M145 070949 48 Burner M180 070950 48 Burner M330 071225 48 Burner M390 071226 48 Burner M450 071356 51 Boiler body M116 070951 51 Boiler body M145 070952 51 Boiler body M180 070953 51 Boiler body M330 071227 51 Boiler body M390 071228 51 Boiler body M450 071357 54 Roof M116, M145 and M180 062914 54 Roof M330 and M390 071229

Page 40: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 40/54

55 Superior water box isolation M116, M145 and M180 000367 55 Superior water box isolation M330, M390 and M450 071230 56 Flow and return isolation connection M116, M145 and M180 000368 56 Flow and return isolation connection M330, M390 and M450 071231 57 Burner fixings (Compression springs, rings, nuts &�pins of a moulding flask) M116,

M145 et M180 071049

57 Burner fixings (Compression springs, rings, nuts &�pins of a moulding flask) M330, M390 et M450 071232

58 Smoke baffles with banding M116 070954 58 Smoke baffles with banding M145 070955 58 Smoke baffles with banding M180 070956 58 Smoke baffles with banding M330 071233 58 Smoke baffles with banding M390 071234 58 Smoke baffles with banding M450 071358 61 Boiler body door with fixing system M116 062918 61 Boiler body door with fixing system M145 062919 61 Boiler body door with fixing system M180 062920 61 Boiler body door with fixing system M330 071235 61 Boiler body door with fixing system M390 071236 61 Boiler body door with fixing system M450 071359 64 Burner removal crane M116, M145 and M180 070957 64 Burner removal crane M330, M390 and M450 071237

65 Igniter electrode (spark) M116 070980

66 Ground electrode (spark) M116 070981

67 Ignition transformer M116 060006

68 Membrane M145 and M180 071011

69 Twin Fan electronic board M450 071360

Page 41: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 41/54

Exploded view of control panel.

Page 42: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 42/54

Exploded view of front of boiler – Models M116 – M145 – M180

The smoke baffles and the banding are not shown

Page 43: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 43/54

Exploded view of front of boiler – Models M330 – M390 – M450

The smoke baffles and the banding are not shown

Page 44: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 44/54

Exploded view of rear of boiler M116 – M145 – M180

Page 45: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 45/54

Exploded view of rear of boiler M330 – M390 – M450

Page 46: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 46/54

Exploded view of burner M116 – M145 – M180

Mod

ulo

Con

trol

M11

6

Mod

ulo

Con

trol

M14

5 - 1

80

VIEW A

Page 47: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 47/54

Exploded view of burner M330 – M390

The diaphragm is present only on the M390 model

VIEW A

Page 48: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 48/54

Exploded view of burner M450

Gas valve + diaphragm

VIEW A

Page 49: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 49/54

Page 50: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 50/54

Summary table of client parameters

Boiler model: series: site : Please note all modifications to parameters in this document!

Adjustm. line Function Unit Adjustment range Résolution

Default value

Client setting

Time setting P 1 Current hour hh :mm 00 :00 … 23 :59 0 :01 00 :00 P 2 Current day day 1:monday 7:sunday 1 ---

P 5 Reduced room temperature setpoint or reduced boiler temperature setpoint (depending of the regulation mode) °C Tdépartmin…Tdépartmax /

Tambmin…Tambmax 0,5 40 / 15

Time programer heating circuit N°1

P 10

Pre-selection of the day(s) to be programmed: 1-7 => Block complete week 1…7 => Day of the week 1-5 => Block of Monday to Friday 6-7 => Block of Saturday and Sunday

P 11 Time switch switch-on time 1st period hh :mm 00 :00 … 24 :00 0 :10 06 :00 P 12 Time switch switch-off time 1st period hh :mm 00 :00 … 24 :00 0 :10 22 :00 P 13 Time switch switch-on time 2nd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 14 Time switch switch-off time 2nd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 15 Time switch switch-on time 3rd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 16 Time switch switch-off time 3rd period hh :mm 00 :00 … 24 :00 0 :10 24 :00

Time programer heating circuit N°2

P 20

Pre-selection of the day(s) to be programmed: 1-7 => Block complete week 1…7 => Day of the week 1-5 => Block of Monday to Friday 6-7 => Block of Saturday and Sunday

P 21 Time switch switch-on time 1st period hh :mm 00 :00 … 24 :00 0 :10 06 :00 P 22 Time switch switch-off time 1st period hh :mm 00 :00 … 24 :00 0 :10 22 :00 P 23 Time switch switch-on time 2nd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 24 Time switch switch-off time 2nd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 25 Time switch switch-on time 3rd period hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 26 Time switch switch-off time 3rd period hh :mm 00 :00 … 24 :00 0 :10 24 :00

Time programer DHW

P 30

Pre-selection of the day(s) to be programmed: 1-7 => Block complete week 1…7 => Day of the week 1-5 => Block of Monday to Friday 6-7 => Block of Saturday and Sunday

P 31 Time switch program DHW 1st period on hh :mm 00 :00 … 24 :00 0 :10 06 :00 P 32 Time switch program DHW 1st period off hh :mm 00 :00 … 24 :00 0 :10 22 :00 P 33 Time switch program DHW 2nd period on hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 34 Time switch program DHW 2nd period off hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 35 Time switch program DHW 3rd period on hh :mm 00 :00 … 24 :00 0 :10 24 :00 P 36 Time switch program DHW 3rd period off hh :mm 00 :00 … 24 :00 0 :10 24 :00

P 45 Return to the standard time programming for the heating and the DHW (press both buttons – and + for 3 seconds.) 0

H 90 Reduced DHW temperature setpoint °C 50…65 0,5 60

H 91 Release of DHW :

0 Timed DHW program 1 24h/24

0

H 93 Not used 0 H 94 Not used

H 501 Minimum room setpoint temperature (10°C<=TrSmin<=TrSmax) °C 10…30 0,5 10

H 502 Maximum room setpoint temperature (TrSmin<=TrSmax<=30°C) °C 10…30 0,5 26

H 503 Minimum boiler setpoint temperature (20°C � n°503 � n°504) °C 20…85 0,5 20

H 504 Maximum boiler setpoint temperature (n°503 � n°504 � 85°C) °C 20…85 0,5 85

H 505 Maximum heating setpoint temperature °C 20…85 0,5 80

H 506 Minimum flow setpoint temperature heating circuit n° 2 (20°C � H506 � H507) °C 20…85 0,5 20

H 507 Maximum flow setpoint temperature heating circuit n° 2 (H506 � H507 � 85°C) °C 20…85 0,5 80

H 510 Flow temperature setpoint boost with DHW heating K 0 ... 30 0,5 15

H 511 Boiler frost protection switch-on temperature (5°C�TkSfrostEin<TkSfrostAus) °C 5 … 50 7

Page 51: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 51/54

Adjustm. line Function Unit Adjustment range Résolution

Default value

Client setting

H 512 Boiler frost protection switch-off temperature (TkSfrostEin<TkSfrostAus�50°C) °C 5 … 50 15

H 514 Boiler temperature setpoint boost with mixing circuit n°2 K 0 … 30 0,5 2

P 516 Summer/winter changeover temperature (30°C = S/W changeover deactivated) °C 8 … 30 0,5 19

H 517 Maximum control differential; when exceeded, minimum pause time will be aborted K 0 … 90 10

H 523 Switch-on differential of burner in heating mode K 0,5 … 32 0,5 3 H 524 Minimum switch-off differential of burner in heating mode K 0,5 … 32 0,5 3 H 525 Maximum switch-off differential of burner in heating mode K 0,5 … 32 0,5 6

H 526 Switch-on differential of burner in DHW heating mode (sensor 1) K 0,5 … 32 0,5 3

H 527 Minimum switch-off differential of burner in DHW heating mode (sensor 1) K -32 … 32 0,5 3

H 528 Maximum switch-off differential of burner in DHW heating mode (sensor 1) K -32 … 32 0,5 6

H 529 Switch-on differential of burner in DHW heating mode (sensor 2) K 0,5 … 32 0,5 3

H 530 Minimum switch-off differential of burner in DHW heating mode (sensor 2) K -32 … 32 0,5 3

H 531 Maximum switch-off differential of burner in DHW heating mode (sensor 2) K -32 … 32 0,5 6

P 532 Heating curve slope heating circuit 1 1 … 40 1 15

P 533 Heating curve slope heating circuit 2 (Active depending on hydraulic configuration) 1 … 40 1 15

P 534 Room setpoint temperature readjustment heating circuit 1 K -31 … 31 0,5 0

P 535 Room setpoint temperature readjustment heating circuit 2 (Active depending on hydraulic configuration) K -31 … 31 0,5 0

H 536 Maximum speed at maximum output in heating mode (maximum speed limitation) tr/min 0 … 9950 50

MC 116 = 6200 MC 145 = 6000 MC 180 = 6000 MC 220 = 5750 MC 270 = 5550 MC330= 5750 MC390= 6100 MC450= 5950

H 542

Minimum boiler output (lower calorific value)

kW 0 … 9999 1

MC 116 = 30 MC 145 = 36 MC 180 = 45 MC 220 = 85

MC 270 = 105 MC330= 83 MC390= 98

MC450= 112

H 543

Maximum boiler output (lower calorific value)

kW 0 … 9999 1

MC 116 = 116 MC 145 = 145 MC 180 = 180 MC 220 = 220 MC 270 = 270 MC330= 330 MC390= 390 MC450= 450

H 544 Overrun time of pumps, max. 210 min (setting 255: continuous operation of Q1) min 0 … 255 1 5

H 545 Minimum burner pause time (heat demand-dependent switching hysteresis) sec 0 … 3600 1 300

H 546 Minimum burner running time (heat demand-dependent switching hysteresis) sec 0 … 255 1 120

H 551 Constant for quick setback without room temperature influence 0 … 20 1 0

H 552

Hydraulic system adjusment 2 1 Boiler, 1 heating circuit (with pump) with or without DHW 34 1 Boiler, 2 heating circuits (with pumps) with or without DHW 48 1 Boiler, 1 heating circuit (with mixing valve) with or without DHW 50 1 Boiler, 2 heating circuit (1 pump, 1 mixing valve) with or without DHW 64 1 Boiler, x heating circuits (with mixing valves) without DHW 66 1 Boiler, x heating circuits (1 pump, x mixing valves) with or without DHW 80 Boiler cascade-controlled 85 DHW dedicated boiler cascade-controlled

66

H 553

Configuration of heating circuit (with room temperature sensor only) : Tens : influence on CC2, Units : influence on CC1 0 CC2 not influenced by QAA 73 0 CC1 not influenced by QAA 73 1 CC2 controlled by main channel of QAA 73 1 CC1 controlled by main channel of QAA 73 2 CC2 controlled by secondary channel of QAA 73 2 CC1 controlled by secondary channel of QAA 73 e.g.: 12 corresponds to CC1 controlled by sec. channel of QAA 73 and CC2 controlled by main channel of QAA 73

0

Page 52: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 52/54

Adjustm. line Function Unit Adjustment range Résolution

Default value

Client setting

H 555.b0 Not used 0

H 555.b1 Type of domestic hot water priority 0 Absolute priority

1 No priority 0

H 555.b2 Not used 0 H 555.b3 Not used 0

H 555.b4 Installation no-frost protection:

0 Off 1 On

1

H 555.b5 Not used 0 H 555.b6 Not used 0 H 555.b7 Not used 0 H 558.b0 Not used 0

H 558.b1 Type of construction :

0 Light 1 Heavy

0

H 558.b2 Type of DHW control device:

0 Sensor 1 Thermostat

0

H 558.b3 Not used 0 H 558.b4 Not used 0 H 558.b5 Not used 0 H 558.b6 Not used 0 H 558.b7 Not used 0 H 584 Time for kick function of pump/diverting valve outputs sec 0 … 51 1 30

H 596 Running time of actuator in heating circuit 2 (TimeOpening/TimeClosing) sec 30 … 873 1 150

H 604.b0

604.b1

Synchronisation of local / system clock: b1 b0 0 0 Clock independent 0 1 No system time adjustment 1 0 System Master clock

0 0

H 604.b2 Adjustment of bus power supply:

0 Centralized power supply 1 Automatic power supply by regulators

1

H 604.b3 Display of bus power supply :

0 OFF 1 ON

0

H 604.b4 Not used 1

H 604.b5

604.b6

Allocation of DHW to consumers: b6 b5 0 0 Local consumers only, 0 1 Consumers in same segment, 1 0 All consumers in system

0 0

H 604.b7 Priority of LPB bus over external power demand via 0 … 10 V input:

0 priority to external power demand 1 priority to LPB bus

0

H 605 LPB device number of LMU 0 … 16 1 1

H 606 LPB segment number of LMU:

0 generator segment 1 … 14 consumer segments

0 … 14 1 0

H 614

Programmable input LMU basis: 0 No function 1 Modem normally opened 2 Modem normally closed 3 Warm air curtain

0

H 615

Function programmable output K2 LMU: 0 Inactive (or Pump Q8 if 558.b0 = 1) 2 Alarm output 3 Burner on 5 Pump, second heating circuit 6 DHW circulation pump 7 Warm air curtain function active 8 Pump of pressureless header 12 Analog input signal in operation

2

H 618

Programmable input on clip-in function module: 0 No function 1 Modem normally opened 2 Modem normally closed 3 Warm air curtain

4 Predefined setpoint 5 Predefined output

3

H 619

Function output 1 clip-in function module: 0 Inactive 2 Alarm output 3 Burner on

12

Page 53: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 53/54

Adjustm. line Function Unit Adjustment range Résolution

Default value

Client setting

5 Pump, second heating circuit 6 DHW circulation pump 7 Warm air curtain function active 8 Pump of pressureless header 12 Analog input signal in operation

H 620

Function output 2 clip-in function module: 0 Inactive 2 Alarm output 3 Burner on 5 Pump, second heating circuit 6 DHW circulation pump 7 Warm air curtain function active 8 Pump of pressureless header 12 Analog input signal in operation

3

H 622 Maximum temperature of heat demand with external predefined temperature setpoint °C 5 … 130 1 100

H 623 Threshold of analog signal from witch the external demand for output will be accepted (percentage of maximum value of analog signal)

% 5 … 95 1

M116= 25 M145= 25 M180= 25 M220= 37 M270= 37 M330= 25 M390= 25 M450= 25

H 630.b0 Setting flags of maintenance alarms:

0 Alarm desacitvated 1 Alarm activated

0

H 630.b6 Maintenance alarm main clearance 1 Clears the maintenance alarm 0

H 630.b7 Not used 0

H 632.b0 Pump Q8 active for heat demand in LPB zone:

0 No 1 Yes

0

H 632.b1 Pump Q8 active for heat demand in heating circuit n° 2:

0 No 1 Yes

0

H 632.b2 Pump Q8 active for heat demand in heating circuit n° 1:

0 No 1 Yes

0

H 632.b3 Pump Q8 active for DHW heat demand:

0 No 1 Yes

0

H 700 1st past value of lockout code counter

H 701

1st past value of lockout phase Correspondence of the phase codes : 3 Standby 4 Startup blocked 5, 6 Fan run up 7 Prepurging 8, 9, 10 Waiting time 11 Pre-ignition time (only with hot surface igniter) 12, 13, 14, 15 Safety time 16 Stabilisation of the flame 17 Heating mode with modulation 18, 19, 20, 21 Post-purging 0, 1, 2 Home run 22 Lockout

H 702 1st past value of internal diagnostic code H 703 2nd past value of lockout code counter H 704 2nd past value of lockout phase (see H701) H 705 2nd past value of internal diagnostic code H 706 3rd past value of lockout code counter H 707 3rd past value of lockout phase (see H701) H 708 3rd past value of internal diagnostic code H 709 4th past value of lockout code counter H 710 4th past value of lockout phase (see H701) H 711 4th past value of internal diagnostic code H 712 4th past value of lockout code counter H 713 5th past value of lockout phase (see H701) H 714 5th past value of internal diagnostic code H 715 Current value of lockout code counter H 716 Current value of lockout phase (see H701) H 717 Current value internal diagnostic code H 718 Hours run burner H 0 … 131070 1 H 719 Hours run heating mode H 0 … 131070 1

Page 54: INSTALLATION AND MAINTENANCE MANUAL - High · PDF fileinstallation and maintenance manual for modulating-control boiler with gas burner equipped ... 850 à 5m3/h 1050 à 6.25m3/h 1350

0MEM0153-E_GB M Series 116/145/180-330/390/450 INSTALLATION MANUAL Page 54/54

Adjustm. line Function Unit Adjustment range Résolution

Default value

Client setting

H 720 Hours run DHW heating H 0 … 131070 1 H 721 Hours run zone H 0 … 131070 1 H 722 Start counter 0 … 327675 1

H 724.b0 Selection of summer / Winter operating modes:

0 Summer (no heating) 1 Winter (heating activated)

1

H 725 SW version of LMU for presentation on the OT parameter setting level

H 728 1st past value of ALBATROS error code H 729 2nd past value of ALBATROS error code H 730 3rd past value of ALBATROS error code H 731 4th past value of ALBATROS error code H 732 5th past value of ALBATROS error code H 733 Current value of ALBATROS error code

In italics: read only parameters