IEC 61850 Certificate Level A 1 No. 30920191-Consuling 09-0564 Issued to: For the product: AREVA T&D UK Ltd Products Plant St. Leonards Avenue ST174LX ENGLAND AREVA MiCOM P143 Feeder Management Relay Firmware version 42C Issued by: The product has not shown to be non-conforming to: IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Communication networks and systems in substations The conformance test has been performed according to IEC 61850-10 with product’s protocol, model and technical issue implementation conformance statements: "MiCOM P143 Feeder Management Relay Version 42C PICS and MICS", "MiCOM P14x Feeder Management Relay Version 42C TICS" and product’s extra information for testing: "MiCOM P14x Feeder Management Relay Version 42 PIXIT". The following IEC 61850 conformance blocks have been tested with a positive result (number of relevant and executed test cases / total number of test cases as defined in the UCA International Users Group Device Test procedures v2.2): 1 Basic Exchange (19/24) 2 Data Sets (3/6) 4 Setting Group Selection (2/3) 5 Unbuffered Reporting (13/18) 6 Buffered Reporting (15/20) 9a GOOSE Publish (8/11) 9b GOOSE Subscribe (9/10) 12a Direct Control (4/12) 12b SBO Control (5/16) 12c Enhanced Direct Control (4/13) 12d Enhanced SBO Control (10/20) 13 Time Synchronization (3/5) 14 File Transfer (6/7) This Certificate includes a summary of the test results as carried out at KEMA in Arnhem, The Netherlands with UniCAsim 61850 version 3.18.00 with test suite 3.18.00 and UniCA 61850 analyzer 4.18.01. The test is based on the UCA International Users Group Device Test Procedures version 2.2. This document has been issued for information purposes only, and the original paper copy of the KEMA report: No. No. 30920191-Consuling 09-0563 will prevail. The test has been carried out on one single specimen of the products as referred above and submitted to KEMA by AREVA. The manufacturer’s production process has not been assessed. This Certificate does not imply that KEMA has certified or approved any product other than the specimen tested. Arnhem, 3 April 2009 W. Strabbing M. Flohil Manager Intelligent Networks and Communication Senior test engineer 1 Level A - Independent Test lab with certified ISO 9000 or ISO 17025 Quality System KEMA Nederland B.V. Utrechtseweg 310, 6812 AR Arnhem P.O.Box 9035, 6800 ET Arnhem The Netherlands T +31 26 356 61 42 F +31 26 351 54 56 [email protected] www.kema.com Page 1/2 Copyright © KEMA Nederland B.V., Arnhem, the Netherlands. All rights reserved. Please note that any electronic version of this KEMA certificate is provided to KEMA’s customer for convenience purposes only. It is prohibited to update or change it in any manner whatsoever, including but not limited to dividing it into parts. In case of a conflict between the electronic version and the original version, the original paper version issued by KEMA will prevail.

Upload: buitruc

Post on 05-Feb-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: IEC 61850 Certificate Level A 1 - · PDF fileIEC 61850 Certificate Level A1 No. 30920191-Consuling 09-0564 Issued to: ... "MiCOM P143 Feeder Management Relay Version 42C PICS and MICS",

IEC 61850 Certificate Level A1

No. 30920191-Consuling 09-0564

Issued to: For the product: AREVA T&D UK Ltd Products Plant St. Leonards Avenue ST174LX ENGLAND

AREVA MiCOM P143 Feeder Management Relay Firmware version 42C

Issued by:

The product has not shown to be non-conforming to:

IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Communication networks and systems in substations

The conformance test has been performed according to IEC 61850-10 with product’s protocol, model and technical issue implementation conformance statements: "MiCOM P143 Feeder Management Relay Version 42C PICS and MICS", "MiCOM P14x Feeder Management Relay Version 42C TICS" and product’s extra information for testing: "MiCOM P14x Feeder Management Relay Version 42 PIXIT". The following IEC 61850 conformance blocks have been tested with a positive result (number of relevant and executed test cases / total number of test cases as defined in the UCA International Users Group Device Test procedures v2.2): 1 Basic Exchange (19/24) 2 Data Sets (3/6) 4 Setting Group Selection (2/3) 5 Unbuffered Reporting (13/18) 6 Buffered Reporting (15/20) 9a GOOSE Publish (8/11)

9b GOOSE Subscribe (9/10) 12a Direct Control (4/12) 12b SBO Control (5/16) 12c Enhanced Direct Control (4/13) 12d Enhanced SBO Control (10/20) 13 Time Synchronization (3/5) 14 File Transfer (6/7)

This Certificate includes a summary of the test results as carried out at KEMA in Arnhem, The Netherlands with UniCAsim 61850 version 3.18.00 with test suite 3.18.00 and UniCA 61850 analyzer 4.18.01. The test is based on the UCA International Users Group Device Test Procedures version 2.2. This document has been issued for information purposes only, and the original paper copy of the KEMA report: No. No. 30920191-Consuling 09-0563 will prevail. The test has been carried out on one single specimen of the products as referred above and submitted to KEMA by AREVA. The manufacturer’s production process has not been assessed. This Certificate does not imply that KEMA has certified or approved any product other than the specimen tested.

Manager Intelligent Networks and Communication Senior test engineer 1 Level A - Independent Test lab with certified ISO 9000 or ISO 17025 Quality System

Page 1/2

Copyright © KEMA Nederland B.V., Arnhem, the Netherlands. All rights reserved. Please note that any electronic version of this KEMA certificate is provided to KEMA’s customer for convenience purposes only. It is prohibited to update or change it in any manner whatsoever, including but not limited to dividing it into parts. In case of a conflict between the electronic version and the original version, the original paper version issued by KEMA will prevail.

KEMA Nederland B.V. Utrechtseweg 310, 6812 AR Arnhem P.O.Box 9035, 6800 ETT +31 26 356 61 42 F +31 26 351 54 56 [email protected]

M. Flohil

Arnhem, 3 April 2009

W. Strabbing

Arnhem The Netherlands www.kema.com

Page 2: IEC 61850 Certificate Level A 1 - · PDF fileIEC 61850 Certificate Level A1 No. 30920191-Consuling 09-0564 Issued to: ... "MiCOM P143 Feeder Management Relay Version 42C PICS and MICS",

Applicable Test Procedures from the UCA International Users Group Device Test Procedures version 2.2 Conformance Block Mandatory Conditional 1: Basic Exchange Ass1, Ass2, Ass3, AssN2, AssN3, AssN4,

AssN5 Srv1, Srv2, Srv3, Srv4, Srv5, SrvN1abcd, SrvN4

Srv6, Srv7, Srv8, SrvN1e, SrvN3

2: Data Sets Dset1, Dset10a, DsetN1ae 4: Setting Group Selection Sg1, SgN1 5: Unbuffered Reporting Rp1, Rp2, Rp3, Rp4, Rp7

RpN1, RpN2, RpN3, RpN4 Rp5, Rp10, RpN5, RpN6

6: Buffered Reporting Br1, Br2, Br3, Br4, Br7, Br8, Br9, Br12 BrN1, BrN2, BrN3, BrN4, BrN5

Br5, Br10

9a: GOOSE publish Gop2, Gop3, Gop4, Gop7 Gop1, Gop5, Gop6, GopN1 9b: GOOSE subscribe Gos1, Gos2, Gos3, GosN1, GosN2, GosN3,

GosN4, GosN5, GosN6

12a: Direct control CltN3, CtlN8 DOns1, DOns3

12b: SBO control Ctl3, CltN1, CltN2, CltN4 SBOns2

12c: Enhanced Direct Control CltN3, CtlN8 DOes2, DOes5

12d: Enhanced SBO control Ctl3, CltN1, CltN2, CltN3, CltN4, CtlN9 SBOes1, SBOes2, SBOes3

CtlN11

13: Time sync Tm1, Tm2, TmN1 14: File transfer Ft1, Ft2ab, Ft4, FtN1ab FtN1c, Ft2c