Page 1: History of  Firestopping

04/13/23 1

The History of Firestopping?07 84 00

By:

Bob Poole

Page 2: History of  Firestopping

04/13/23 2

What is firestopping?

• Firestopping is the process of containing fire or smoke through the use of UL tested and approved assemblies.

Page 3: History of  Firestopping

04/13/23 3

History of Firestopping

• Firestopping in the US got its start in the 1960’s onboard Navy combat ships.

• A company called Lucab Sweden invented the first known Firestop. MCT (Multi Cable Transit)

• A gentleman by the name of Mr. Joe O'Brien ('Mr. MCT') is credited with being the father of firestopping.

• Firestopping as we know it has been around for about 30 years. It got its start in the Nuclear, Telecommunications and Power Plant Industries.

Page 4: History of  Firestopping

04/13/23 4

History of Firestopping cont’d

• The Firestopping industry really took off in the 1970’s.

• Large Electrical Manufacturers and Silicone Manufacturers teamed up to do R&D on new products.

• Land based use of Firestopping began in earnest in the 1980’s.

• The Insurance industry also played a big role in promoting the development of Firestop products to minimize the risks from property lost.

Page 5: History of  Firestopping

04/13/23 5

History of Firestopping cont’d

• The increased demand for Firestopping lead to changes in the codes. For example shafts were no longer the only way to run services between floors. As new Products were developed, new Firestopping systems were also developed to allow wiring and cables to be routed through rated assemblies with out the need for shafts.

Page 6: History of  Firestopping

04/13/23 6

History of Firestopping cont’d

• Two of the original Firestopping materials were Silicone foam and fire rated mortars. These products did not provide the flexibility of re entry into existing penetrations. As a result of the need for this flexibility, fire pillows and Intumescent caulks were developed. These products were improvements but still had re entry issues. Intumescent caulk revolutionized the industry. The next generation of products was the moldable putty. It offered the benefit of the intumescent

Page 7: History of  Firestopping

04/13/23 7

History of Firestopping cont’d

• caulk, except it did not dry and become hard. This product made great strides in the re-entry of penetrations. New products continued to be developed right up to today.

Page 8: History of  Firestopping

04/13/23 8

Firestopping Standards

• Originally Firestopping design standards were covered by ASTM E 119 and UL 263.

• With the need for standards for testing procedures and Installation methods, ASTM E 814 and UL 1479 were developed.

Page 9: History of  Firestopping

04/13/23 9

Where is Firestopping used

• There are 4 primary locations where Firestopping is used to prevent the spread of fire, smoke or gases.

Page 10: History of  Firestopping

04/13/23 10

Where is Firestopping used cont’d

• Joints - Any joint between fire rated components. i.e. wall/wall (WW), floor/ wall (FW), wall/ceiling or structure (HW).

• Floors - (CEJ) perimeter slab edges/ exterior wall cavities ( curtain walls)

• Penetrations - (Floor,Wall,Combination) Any opening(s) in rated walls or floors. ( M.E.P. penetrations)

Page 11: History of  Firestopping

04/13/23 11

Where is Firestopping used cont’d

• Blank Openings – Openings with no penetrating items.

Page 12: History of  Firestopping

04/13/23 12

Joints

• Wall/Wall Dynamic & Static (WWD &WWS)Drywall construction usually does not

require joints that need to be firestopped.

Concrete and Masonry walls are where wall to wall joints are most commonly used.

Page 13: History of  Firestopping

04/13/23 13

Floors

• Slab edges - (CEJ) exterior wall cavity (Curtain Wall construction)

• Expansion Joints - (CEJ)• Floor to floor - (FFD)• Floor to wall - (FWD)

Page 14: History of  Firestopping

04/13/23 14

Blank Openings

• This is a condition that is not commonly seen in the Healthcare Construction arena.

• Most of what we deal with is Drywall construction. In most cases a opening/hole in the wall is covered with what is referred to as a “Blow Out patch”

Page 15: History of  Firestopping

04/13/23 15

Penetrations

• (F, W, C) These would mainly consist of pipes, conduits, cabling and ductwork.

• There are Firestop systems for virtually every condition listed above with some exceptions.

• These exceptions would be for penetrations which are not the norm; i.e., perpendicular to and are usually skewed or partially penetrate the wall/floor plane.

Page 16: History of  Firestopping

04/13/23 16

Penetrations cont’d

• When there are penetrations for which there are no known UL approved details, An Engineering Judgment may be issued.

• These judgments usually come from the Engineering staff of one of the major Firestopping Manufacturers. They will make a judgment that the condition in question closely resembles that of an UL tested condition and therefore they issue an Engineering Judgment that tells the Contractor what detail to follow. Most AHJ’s accept these judgments.

Page 17: History of  Firestopping

04/13/23 17

UL Designations For Firestop Systems

For example, System # CAJ-1044 is deciphered as follows:

C = Either floor or wallA or J = Concrete floor or wall, with minimum thickness less than or equal to 5 or 8 inches, respectively.1000 to 1999 = Specific types of metallic piping and specific diameters.#1044 is the 44th system in the 1000 series of metallic penetrations.

Page 18: History of  Firestopping

04/13/23 18

Page 19: History of  Firestopping

04/13/23 19

Page 20: History of  Firestopping

04/13/23 20

Page 21: History of  Firestopping

04/13/23 21

UL Designations For Firestop Systems

In a nutshell, the tested firestop system is given a letter designation indicating what type of floor or wall assembly the firestop system has been tested in: concrete, masonry, gypsum, etc. Following the letter is a number designation referring to the type of penetrating item that has been tested, such as metallic pipe, non-metallic pipe, cable, electrical, etc.

Page 22: History of  Firestopping

04/13/23 22

Firestopping Nomenclature

• Annular space – The gap between the penetrating item and the hole.

• Backer rod /material – Materials used as a support for gunned or troweled sealant materials.

• Intumescent – Materials that swell in the presence of heat to seal gaps around a penetration.

Page 23: History of  Firestopping

04/13/23 23

Firestopping Nomenclature cont’d

• Point of contact – when a penetrating item makes contact with the hole.

• UL Fire Resistance Directory – the publication which contains details/descriptions for all Firestopping systems.

• Fire Resistance Rating – an hourly rating defined by building codes for the endurance of types of construction to resist fire.

Page 24: History of  Firestopping

04/13/23 24

Firestopping Nomenclature

Courtesy of 3M

Page 25: History of  Firestopping

04/13/23 25

Firestopping Nomenclature

Courtesy Of 3M

Page 26: History of  Firestopping

04/13/23 26

UL Designations For Firestop Systems

Translation: This system, CAJ-1044, can be specified for use on metallic piping such as steel, iron, or copper tubing and copper pipe with specific outside dimensions, and installed through concrete floors or walls 5 to 8 inches thick or in framed floors.

Page 27: History of  Firestopping

04/13/23 27

Ratings of UL Firestop systems

Also located in the UL Fire Resistance Directory Vol. 2 are the F, T and L ratings for each firestop system. These are hourly ratings that indicate specific performance capabilities and correspond to building code requirements. The Directory defines these ratings as follows:

Page 28: History of  Firestopping

04/13/23 28

Ratings of UL Firestop Systems

The “F” rating provides "the time period for which the system is capable of prohibiting the passage of flame through the system and requires acceptable hose stream performance."

Page 29: History of  Firestopping

04/13/23 29

Ratings of UL Firestop Systems

The “T” designation indicates "the time period for which the system is capable of limiting the maximum temperature rise on the unexposed surface of the wall or floor assembly, on the penetrating item, and on the fill material in the annular space, not to exceed 325° F (181° C) above ambient temperature, and requires acceptable hose stream performance."

Page 30: History of  Firestopping

04/13/23 30

Ratings of UL Firestop Systems

The “L” rating designates "information concerning the amount of air leakage, in cubic feet per minute per square foot of opening through the firestop system and/or 400° F air temperatures at an air pressure differential of 0.30 in W.C."

Page 31: History of  Firestopping

04/13/23 31

Available Products

• Some of the many products available today include:– Intumescent, Silicone, Latex and Acrylic caulks– Elastomeric Sprays– Putty's, putty pads– Collars, wrap strips, adjustable sleeves– Pillows, Foam, Mortar

Page 32: History of  Firestopping

04/13/23 32

Firestopping Industry Today

• Many manufacturers have entered the arena.• The industry also has a trade organization….

Firestop Contractors International Assoc.– They promote industry wide education for

Contractors. – They work with Code officials to improve

codes and standards for firestopping.– They assist Architects in writing tight specs.

Page 33: History of  Firestopping

04/13/23 33

Firestopping Installations

• A large majority of the firestopping work today is not installed correctly.

• The key factor is lack of education and unskilled workers doing the work.

• A General lack of understanding that all firestopping work must be done in accordance with approved UL details exist in the Construction Industry today.

Page 34: History of  Firestopping

04/13/23 34

Example

How will this be Firestopped? Is there an UL detail for this?

Page 35: History of  Firestopping

04/13/23 35

Example

Examples of improperly applied details.

Page 36: History of  Firestopping

04/13/23 36

Example

The incorrect Firestopping material used here.

Page 37: History of  Firestopping

04/13/23 37

Example

How will this be Firestopped?

Page 38: History of  Firestopping

04/13/23 38

Example

One of the many types of re enterable sleeves.

Page 39: History of  Firestopping

04/13/23 39

Example

Improperly installed fire caulk. UL detail not followed. Penetrations not

Firestopped.

Page 40: History of  Firestopping

04/13/23 40

Example

An approved UL detail not followed here.

Page 41: History of  Firestopping

04/13/23 41

The History of Firestopping?07 84 00

The End

Page 42: History of  Firestopping

04/13/23 42

The History of Firestopping?07 84 00

Questions?