heat recovery unit - lmfclima.it · rkh performance heat recovery unit dimensions and weights air...
TRANSCRIPT
rkh
Sheet metal supporting frame and double shell curtain panels externally pre-painted, fully removable with average 20 mm thick internal thermal and acoustic insulation.High efficiency aluminium plated heat recovery, Eurovent certified, of static type with aluminium plate, and airflows separated by special seals.G4 efficiency class air filters, easily removable from every side (bottom, side, top) allowing their periodic cleaning; as an option, M6-F7-F8 efficiency class filters are available.Supply and exhaust centrifugal double suction fans, with electric motor directly coupled for more speeds, mounted on special supports.The unit is complete of electrical terminal box fitted with relay board, to aid the electrical connections and fan control.Aluminium condensate drain tray, with discharge from the bottom side.
“
“
TECHNICAL FEATURES
>70%EFFICIENCY
PARTIAL OUTSIDE
V
H
HEAT RECOVERY UNIT high efficiencyfrom 400 to 5.700 m³/h
INSIDE
ERP 2015
46 Heat pump - Heat recovery unit
rkhHEAT RECOVERY UNIT
Pre-or post-heating elements complete with electrical power board
Direct driven 3 speed fans
Round adapter for circular duct BCCPre or post electric heater SKEWater cooling/heating section SAFDirect expansion section SEDAdjusting damper SKRFlexible connection GATRoof cover TPRClass M6 compact filter FC6Class F7 compact filter FC7Class F8 compact filter FC8Brushless EC engine DDBFan speed control for EC engines RDEExternal hood with wire mesh CFA Humidification/adiabatic cooling section HCPSolenoid valve VSAExternal by-pass for free-cooling CDM
Supports H=180 mm PD23 step fan speed control CVUControl panel PCRRemote temperature sensor for PCR NTCElectronic control LCE3 way valve with actuator V33Multifunction electronic control LC2Continuous modulation of speed MCVFilters differential pressure switch PSTDOn/off damper actuator SSERoom hygrostat HASDuctable hygrostat HCSAntifreeze thermostat TEGDifferential pressure transducer DPSDuct-type CO2 transducer AQS
ACCESSORIES
High efficiency aluminium heat exchanger
47Heat pump - Heat recovery unit
MODELSHEAT RECOVERY UNITrkh
rkh Fan speed 19 25 30 40 60
AirflowMax
m3/h1000 1800 3000 3900 4800
Med 900 1550 2600 - -Min 820 1060 2150 3000 4100
External Static PressureMax
Pa194 158 192 143 170
Med 168 116 119 - -Min 132 81 82 79 125
1m sound pressure levelMax
dB(A)52,0 56,0 56,0 60,0 64,0
Med 50,0 53,0 54,0 - -Min 45,0 48,0 48,0 53,0 56,0
Nom motor power W 2 x 420 2 x 420 2 x 550 2 x 750 2 x 1500
Maximum total current A 2 x 2,40 2 x 3,30 2 x 5,50 2 x 3,30 2 x 5,00
Max. total power absorbed kW 2 x 0,56 2 x 0,70 2 x 1,20 2 x 1,89 2 x 3,28
Specific fan power W/(m3/s) 1404 1120 1140 1132 1420
2009/125/EC ErP Compliance - 2015 2015 2015 2015 2015
Fan speed n° 3 3 3 2 2
Min degree of Protection IP 44 IP 44 IP 44 IP 55 IP 55
Min temperature class F F F F F
Power supply V-Ph-Hz 230-1-50 400-3+N-50
Efficiency (1)Max
%70,9 72,9 72,5 72,1 72,1
Med 71,4 73,6 73,2 - -Min 71,8 75,4 74,1 73,4 72,9
Recovered heating capacity (1)Max
kW6,4 11,8 19,5 25,2 31,1
Med 5,8 10,2 17,1 - -Min 5,3 7,2 14,3 19,8 26,8
Supply temperature (1)Max
°C10,2 10,7 10,6 10,5 10,5
Med 10,3 10,9 10,8 - -Min 10,5 11,3 11,0 10,8 10,7
Efficiency class according to UNI EN 13053. Nom H3 H3 H3 H3 H3
Water cooling accessory SAF
Rows 3 3 3 3 3
Air pressure drop Max Pa 49 53 77 80 80
Total cooling capacity (2) Max kW 8,20 14,0 18,6 24,0 29,9
Sensible cooling capacity (2) Max kW 3,94 7,04 9,79 12,7 16,2
Supply temperature (2) Max °C 16,8 16,8 18,6 18,6 18,3
Water flow rate (2) Max m3/h 1,40 2,39 3,19 4,13 5,11
Water pressure drop (2) Max kPa 6 16 27 29 12
Electric pre or post-heating accessory SKE
Stages 1 1 1 1 1
Heating capacity kW 3,00 4,50 9,00 12,0 12,0
∆T air side Max °C 8,8 7,4 8,8 9,0 7,4Pressure drop Max Pa 4 4 8 8 9Power supply V-Ph-Hz 400-3+N-50
High efficiency filters
FC6 Pressure drop Max Pa 48 48 69 80 62
FC7 Pressure drop Max Pa 113 114 163 190 146
FC8 Pressure drop Max Pa 156 160 228 283 203
Round adapter for circular duct BCC
Diameter mm 315 355 400 450 630
(1) Outdoor air -7°C 90% RH, ambient air 20°C 50% RH(2) Outdoor air 32°C 50% RH, ambient air 26°C 50% RH, water inlet 7°C outlet 12°C
48 Heat pump - Heat recovery unit
PERFORMANCEHEAT RECOVERY UNIT
rkh
Air flow (m3/h)
E.S.
P. (P
a)
66,0
67,0
68,0
69,0
70,0
71,0
72,0
73,0
74,0
0
50
100
150
200
250
300
350
400 600 800 1000 1200 1400 1600 1800
maxmin
med
eff %
Effici
ency
(%)
performance
Air flow (m3/h)
P.D
. (Pa
)
0
50
100
150
200
250
300
400 600 800 1000 1200 1400 1600 1800
AF
F
6
fc8
fc7
saf
ske
fc6
components pressure drop
RKh
19
Air flow (m3/h)
E.S.
P. (P
a)
70,0
71,0
72,0
73,0
74,0
75,0
76,0
0
50
100
150
200
250
300
350
400
450
500
1500 2000 2500 3000 3500 4000 4500
max
min
eff %
Effici
ency
(%)
performance
Air flow (m3/h)
P.D
. (Pa
)
0
50
100
150
200
250
300
1500 2000 2500 3000 3500 4000 4500
fc8
fc7
saf
ske
fc6
components pressure drop
RKh
40
Air flow (m3/h)
E.S.
P. (P
a)
70,0
71,0
72,0
73,0
74,0
75,0
76,0
77,0
78,0
0
50
100
150
200
250
300
350
400
500 700 900 1100 1300 1500 1700 1900 2100 2300
maxmin
med
eff %
Effici
ency
(%)
performance
Air flow (m3/h)
E.S.
P. (P
a)
70,0
71,0
72,0
73,0
74,0
75,0
76,0
0
50
100
150
200
250
300
350
400
450
1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600
max
min
med
eff %
Effici
ency
(%)
performance
Air flow (m3/h)
P.D
. (Pa
)
0
50
100
150
200
500 700 900 1100 1300 1500 1700 1900 2100 2300
fc8
fc7
saf
ske
fc6
components pressure drop
Air flow (m3/h)
P.D
. (Pa
)
0
50
100
150
200
250
300
1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600
fc8
fc7
saf
ske
fc6
components pressure drop
RKh
25RK
h 30
49Heat pump - Heat recovery unit
PERFORMANCErkhHEAT RECOVERY UNIT
DIMENSIONS AND WEIGHTS
Air flow (m3/h)
performance components pressure drop
E.S.
P. (P
a)
0
50
100
150
200
250
300
350
400
450
500
1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
max
min
EFF %
76,0
75,0
74,0
73,0
72,0
71,0
70,0
Air flow (m3/h)
P.D
. (Pa
)
0
50
100
150
200
250
1500 2000 2500 3000 3500 4000 4500 5000
fc8
fc7
saf
ske
fc6
RKh 60
RKH SWL [dB]octave band [Hz] SWL SPL supply SPL return SPL outside
1 m 5 m 10 m 1 m 5 m 10 m 1 m 5 m 10 m
63 125 250 500 1000 2000 4000 8000 dB dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
19 84,6 78,0 82,8 74,6 75,0 74,6 71,6 65,6 88 81 66 55 50 65 54 49 52 41 36
25 95,6 80,4 84,1 75,0 77,3 76,9 73,7 67,5 96 83 68 57 52 66 55 50 55 44 39
30 96,6 81,3 85,2 76,1 78,2 78,0 74,6 68,0 97 84 69 58 53 66 55 50 56 45 40
40 103,4 83,2 88,7 78,6 80,0 79,9 77,6 72,6 104 87 72 61 56 69 58 53 59 48 43
60 106,8 86,5 92,2 82,1 83,2 83,1 81,4 76,1 107 90 74 64 59 71 61 56 62 52 47
SPLSupply
SPLexternal
SPLReturn
The table lists the sound power values (SWL) in octave bands and totals; it also indicates the values of sound pressure level (SPL) at 1 m, 5 m and 10 m at supply, return and at the outside of the unit.All values refer to the operation of the ducted unit at FULL speed and at the nominal flow rate.
NOISE LEVELS
RKh 19 25 30 40 60A mm 1450 1700 1700 1700 1900
B mm 900 1230 1230 1230 1450
C mm 470 490 530 630 755
D mm 100 150 150 150 200
L mm 240 240 339 339 403
H mm 270 270 297 297 350
L1 mm 337 502 502 502 615
H1 mm 327 347 387 487 615
Weight kg 110 155 170 200 300
Horizontal unit Vertical unit
CDM
CD
L
H
L1
H1
A
BU
CDM
90A
BCDH
LL1
H1
U
Efficiency (%)
50 Heat pump - Heat recovery unit
components pressure drop
CONFIGURATIONS AND CONTROLS rkhHEAT RECOVERY UNIT
• Orientation Rkh (Horizontal version)
• Orientation Rkh (Vertical version)
CVU PCR LCE LC2Manual selection of 3 speed · · · ·Automatic/manual selection of speed · · ·Modulating fan management MCV ·EC fans management DDB ·Manual ON-OFF · · · ·Cool/change over valve management SAF+V33 · · ·Heat valve management SAF+V33 · · ·Cold/change over pump management SAF ·Heat pump management SKW ·Direct expansion coil management (0..10V) SED ·Defrost recovery management ·Water coil anti-freeze management · ·Antifreeze thermostat management TEG+SKR+SSE ·ON-OFF electric heater management SKE · · ·Remote probe management NTC ·Filter pressure switch management PSTD · ·Management of ventilation with CO2 probe AQS ·Management of ventilation with one or two pressure sensors DPS ·Free-cooling damper management CDM · ·Management of mixing chamber MS3 ·Management of mixing chamber with CO2 probe AQS+MS3 ·Management of motorized dampers SKR+SSE ·
Management of humidification HCS+HCP+VSA ·HAS+HCP+VSAManagement of Boost by keyboard ·Management of adiabatic cooling HCP+VSA ·Alarms management · ·Post ventilation · · ·Weekly programming · ·Remote ON-OFF · ·Digital input for PIR occupancy ·Digital input for fire alarm ·Mode change (hot/cold) from digital input · ·Minimum thermal hot water temperature ·Remote display with internal sensor · · ·BMS Modbus RS485 protocol · ·Reference diagram 1 2 3 4
exhaust
freshair
insideoutside TyPe A
M90
R90
supply
return
E90
A90
supply
return
exhaust
freshair
TyPe A
M90E90
supply
return
Exhaust
freshair
INside outsideTyPe B
M90
R90
E90
A90
Espulsione
exhaust
return
supply
TyPe B
E90
freshair
M90
51Heat pump - Heat recovery unit