Page 1: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Gexol-331HFFire Resistant

Gexol-HFFlame Retardant

The Global Cable Solutions CompanyThe Global Cable Solutions Company

Fire Resistant and Flame Retardant Constructions

Fire Resistant and Flame Retardant Constructions

Low SmokeHalogen-Free

Cables

Low SmokeHalogen-Free

Cables

Gexol®Gexol®

Page 2: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

IInnddeexx

AmerCable believes the information presented throughoutthis catalog to be reliable and current. All information issubject to change without notice. The information listedis approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application.

Gexol® is a registered trademark of AmerCable Incorporated. Registered in the U.S. Patent and Trademark Office. © 2008 AmerCable Incorporated

Low SmokeHalogen-FreeWorld Class Oil & Gas Cables

Low SmokeHalogen-FreeWorld Class Oil & Gas Cables

Gexol-331HF Fire Resistant Low Smoke / Halogen-Free

Power Cables• Single Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

• Two Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5• Three Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . 7• Four Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9• Five Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Control Cable• Multi-Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Instrumentation Cables• Individually Shielded Pairs . . . . . . . . . . . . . . . . . . . . . . 15

• Individually Shielded Triads . . . . . . . . . . . . . . . . . . . . . 17

Gexol-HF Flame Retardant Low Smoke / Halogen-Free

Power Cables• Single Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

• Two Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . 21• Three Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . 23• Four Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . 25• Five Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Control Cable• Multi-Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Instrumentation Cables• Individually Shielded Pairs . . . . . . . . . . . . . . . . . . . . . . 31

• Individually Shielded Triads . . . . . . . . . . . . . . . . . . . . . 33

Type VFD Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Public Address/General Alarm (PA/GA) . . . . . . . . . . . . 37

Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Gexol®

� Fastest Lead Times• Standard 6 - 8 weeks• Emergency 2 - 4 weeks

� Best On Time Delivery Rate

(99%+ in the last 36 months)*

� Highest AmpacityRatings

• DNV: 95°C• ABS: 100°C• Lloyd’s: 95°C

� Extremely Flexible*Visit www.AmerCable.com for our most current on time delivery rate

Flame RetardantCertified to IEC 92-3 (332-3A)

and IEEE 1202

Severe Cold DurabilityExceeds CSA Cold Bend /

Cold Impact (-40°C/-35°C)

Page 3: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

1

Diameter Conversion (inches to millimeters): Multiply by 25.4

Bend RadiusUnarmored Armored Armored & Sheathed

IEEE 45 6X Diameter 8X Diameter 8X Diameter

IEC 92 <1" (25mm) 6X Diameter 8X Diameter4 x Diameter>1" (25mm)6X Diameter

Transport <1" (25mm) 6X Diameter 6X DiameterCanada 4X Diameter

>1" (25mm)6X Diameter

Gexol® Low Smoke Halogen-Free Oil & Gas Cables are the industry’s standard for premium power, control andinstrumentation performance. Gexol cablesprove their value daily in the punishingoperating environments of offshore drillingand petroleum facilities around the world.

Offshore applications challenge cable construction with relentless heat, vibration, salt corrosion, drilling mud and mechanical stress.

For environments that require Fire Resistant/Retardant Low Smoke Halogen-Free cables – you can depend on AmerCable.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I , Zone 2 Class I , Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Hawke Gland Types

110°C (Free Air) Ratings Based on IEEE Std. 835-1994 for isolated cables in free air with full sun, 2 ft/s air movement, and a 45°C ambient.

110°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the 110°C ampacities should be multiplied by 0.8.

100°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the 100°C ampacities should be multiplied by 0.8.

95°C Ratings Based on Table 4/3C.10 of the 1997 ABS MODU rules and a 45°C ambient.

Ampacities for four conductor cables are based on one conductor not acting as a normal current-carrying conductor (e.g., grounded neutral or grounding conductor).

Ampacity Ratings

Oil & Gas Cables

Page 4: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Individual Closest Equivalent UninsulatedSize Number Strand Dia. IEEE 45 Metric Size Conductor

AWG/kcmil of Strands (inches) Std. Size (mm2) Dia. (inches)

18

16

14

12

10

8

6

4

2

1

1/0

2/0

3/0

4/0

262

313

373

444

535

646

777

1111

19

19

19

19

37

37

61

133

133

209

266

342

418

532

646

777

925

1110

1332

1591

1924

2745

0.0100

0.0117

0.0147

0.0185

0.0167

0.0201

0.0201

0.0177

0.0223

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

0.0201

2

3

4

6

10

16

26

41

66

83

106

133

168

212

262

313

373

444

535

646

777

1111

0.96

1.32

2.08

3.29

5.23

7.57

12.49

21.11

33.51

42.79

54.45

70.01

85.57

108.91

132.25

159.06

189.36

227.23

272.68

325.70

393.87

561.94

0.049

0.059

0.074

0.093

0.113

0.136

0.175

0.258

0.324

0.361

0.407

0.461

0.510

0.575

0.654

0.720

0.785

0.860

0.941

1.029

1.132

1.354

Gexol Insulated Power, Control andInstrumentation Cable

Stranding ProfileOil & Gas Cables

2

Page 5: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire ResistantSingle Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 2kV • Rated 110°C

v2.08.1 3

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A andIEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

Insulation/JacketFire resistant tape +GEXOL®-HF low smoke,Halogen-Free, flameretardant cross-linked,polyolefin insulation meetingthe requirements for TypeLSX of IEEE 1580 and TypeX110 of UL 1309/CSA 245plus a black low smokeHalogen-Free flameretardant, polyolefin jacketmeeting IEEE 1580 and UL 1309/CSA 245.2000V/IEC 1000V.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 6: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

37-1

04Ge

xol®

-331

HF F

ire R

esis

tant

Sing

le C

ondu

ctor

Pow

er C

able

Low

Smok

e Ha

loge

n-Fr

eeEx

trem

ely

Flex

ible

• 2k

V • R

ated

110

°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– S

ingl

e Co

nduc

tor

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Indu

ctiv

eVo

ltage

Dro

pNo

min

alNo

min

alIn

duct

ive

Volta

ge D

rop

DC R

esis

tanc

eAC

Res

ista

nce

atAm

paci

tyAW

G/Pa

rt No

.Di

amet

erW

eigh

tRe

acta

nce

at 1

10°C

Di

amet

erW

eigh

tDi

amet

erW

eigh

tRe

acta

nce

at 1

10°C

at

25°

C11

0°C,

60 H

zFr

ee A

irkc

mil

mm

237

-104

(inch

es)

(lbs/

MFt

.)(O

hms/

1000

ft.)

(Vol

ts/A

mp/

1000

ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

(Ohm

s/10

00 ft

.)(V

olts

/Am

p/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s/10

00 ft

.)11

0°C

110°

C10

0°C

95°C

181.

0-1

010.

258

180.

060

13.5

740.

308

320.

416

420.

071

13.5

867.

210

9.76

330

1716

2016

1.3

-102

0.26

820

0.05

68.

529

0.31

836

0.42

647

0.06

78.

541

4.52

06.

121

3525

2323

142.

1-1

050.

283

280.

053

5.39

60.

333

500.

472

670.

064

5.40

82.

850

3.85

941

4037

3212

3.3

-106

0.30

234

0.04

93.

405

0.35

264

0.49

189

0.06

03.

417

1.79

02.

424

6448

4538

105.

2-1

080.

322

560.

046

2.16

50.

372

103

0.51

114

10.

056

2.17

61.

130

1.53

085

6258

518

7.6

-109

0.40

179

0.04

71.

349

0.45

112

90.

590

176

0.05

51.

358

0.69

40.

940

112

7772

686

12.5

-110

0.44

112

00.

043

0.86

20.

491

172

0.63

022

60.

051

0.87

00.

436

0.59

014

810

396

914

21-1

120.

523

192

0.03

80.

591

0.57

325

50.

712

329

0.04

50.

598

0.28

60.

399

196

137

128

121

234

-114

0.58

926

90.

035

0.37

40.

639

336

0.77

840

60.

042

0.38

10.

175

0.24

425

918

116

916

21

43-1

150.

630

371

0.03

50.

306

0.68

045

00.

819

519

0.04

10.

312

0.14

00.

195

298

208

194

187

1/0

54-1

160.

694

466

0.03

40.

252

0.74

454

80.

925

634

0.04

10.

258

0.11

10.

156

344

243

227

217

2/0

70-1

170.

761

548

0.03

30.

207

0.81

164

20.

992

735

0.03

90.

213

0.08

90.

125

396

281

262

250

3/0

86-1

180.

820

747

0.03

30.

172

0.87

087

61.

052

1055

0.03

80.

178

0.07

00.

100

457

321

300

289

4/0

109

-119

0.92

895

30.

033

0.14

50.

978

1100

1.16

012

950.

038

0.15

00.

056

0.08

052

837

635

133

526

213

2-1

201.

030

1150

0.03

20.

126

1.08

013

111.

261

1524

0.03

70.

130

0.04

60.

067

599

436

407

382

313

159

-121

1.09

612

350.

031

0.11

01.

146

1479

1.32

716

550.

036

0.11

50.

038

0.05

660

448

745

542

737

318

9-1

221.

163

1559

0.03

10.

097

1.21

317

421.

394

1979

0.03

50.

102

0.03

20.

047

674

553

516

476

444

227

-123

1.23

918

250.

030

0.08

81.

289

2021

1.47

022

720.

034

0.09

20.

027

0.04

175

063

058

853

153

527

3-1

241.

353

2185

0.03

00.

079

1.40

323

951.

585

2667

0.03

40.

083

0.02

20.

035

839

709

662

597

646

326

-126

1.44

226

060.

029

0.07

21.

492

2840

1.73

530

600.

034

0.07

60.

019

0.03

093

778

373

167

177

739

4-1

271.

540

3102

0.02

90.

066

1.59

033

441.

833

3205

0.03

30.

070

0.01

50.

026

1048

881

822

753

1111

562

-129

1.81

344

200.

028

0.05

41.

863

4583

2.10

649

770.

032

0.05

80.

011

0.01

813

0310

9810

2593

7

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

OOrrdd

eerriinn

gg GG

eexxooll

--333311

HHFF CC

aabbllee

ssEx

ampl

e:• S

ingl

e co

nduc

tor p

ower

cab

le• 2

kV

• 535

kcm

il• b

ronz

e ar

mor

ed &

she

athe

d

Amer

Cab

le

Gex

ol-3

31H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0044––

112244

BBSS

4

Oil &

Gas

Cab

les

Page 7: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire Resistant Two Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 5

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.Color code:Black-White

ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.

Sheath (Optional)A black, low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Aluminum ortinned copper availableby request.

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 8: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Ampa

city

kcm

ilm

m2

37-1

04(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

110°

C10

0°C

95°C

161.

3-5

010.

421

860.

471

161

0.61

023

04.

610

6.12

10.

042

8.51

520

1920

142.

1-5

070.

451

108

0.50

118

80.

640

262

2.90

73.

859

0.03

95.

382

3331

2712

3.3

-515

0.50

813

30.

558

221

0.69

730

01.

826

2.42

40.

037

3.39

343

4032

105.

2-5

530.

529

169

0.57

926

60.

718

350

1.15

31.

530

0.03

52.

154

5349

438

7.6

-209

0.64

825

20.

698

373

0.83

747

40.

708

0.94

00.

036

1.33

869

6458

612

.5-2

100.

728

351

0.77

848

30.

959

637

0.44

50.

590

0.03

40.

852

9185

774

21-5

940.

935

588

0.98

575

71.

166

952

0.30

00.

399

0.03

00.

583

118

110

103

1/0

54-2

161.

291

1286

1.34

115

211.

522

1781

0.11

70.

156

0.02

80.

246

213

199

184

4/0

109

-219

1.64

122

831.

691

2589

1.93

430

550.

058

0.08

00.

027

0.13

832

930

728

5

37-1

04Ge

xol®

-331

HF F

ire R

esis

tant

Tw

o Co

nduc

tor P

ower

Cab

leLo

w Sm

oke

Halo

gen-

Free

Extre

mel

y Fl

exib

le •

0.6/

1kV

• Rat

ed 1

10°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– T

wo

Cond

ucto

r

Ord

erin

g G

exol

-331

HF C

able

sEx

ampl

e:• T

wo

cond

ucto

r pow

er c

able

• 0.6

/1kV

• #4

AWG

• bro

nze

arm

ored

& s

heat

hed

Amer

Cab

le

Gex

ol-3

31H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0044––

559944

BBSS

6

Oil &

Gas

Cab

les

Page 9: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

7

37-104Gexol®-331HF Fire Resistant Three Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black, low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for TypeLSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.Color code:Black-White-Red

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available byrequest.

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A andIEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

An uninsulated groundconductor may be incorporated

on a make-to-order basis.

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 10: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

Opt.

Unin

sula

ted

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Grou

ndin

g Co

nd.

Ampa

city

kcm

ilm

m2

37-1

04(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

Size

AW

G11

0°C

100°

C95

°C16

1.3

-502

0.44

375

0.49

314

60.

632

207

4.61

06.

121

0.04

28.

515

–17

1616

142.

1-5

080.

475

136

0.52

521

10.

664

293

2.90

73.

859

0.03

95.

382

–27

2522

123.

3-5

160.

535

185

0.58

529

20.

726

352

1.82

62.

424

0.03

73.

393

–33

3127

105.

2-3

080.

585

234

0.63

534

30.

775

455

1.15

31.

530

0.03

52.

154

–44

4136

87.

6-3

090.

688

335

0.73

844

30.

919

595

0.70

80.

940

0.03

61.

338

–56

5248

612

.5-3

100.

766

456

0.81

657

60.

997

742

0.44

50.

590

0.03

40.

852

875

7064

421

-312

0.99

377

31.

043

961

1.22

411

450.

300

0.39

90.

030

0.58

38

9992

852

34-3

141.

135

1125

1.18

511

021.

366

1566

0.18

40.

244

0.02

90.

368

613

112

211

31

43-3

151.

257

1407

1.30

716

621.

490

1910

0.14

70.

195

0.02

90.

300

615

314

313

11/

054

-316

1.37

716

511.

427

2030

1.60

922

970.

117

0.15

60.

028

0.24

66

176

164

152

2/0

70-3

171.

473

2217

1.52

323

731.

767

2763

0.09

30.

125

0.02

80.

201

620

118

817

53/

086

-318

1.59

324

951.

643

2748

1.88

331

760.

074

0.10

00.

027

0.16

64

234

218

202

4/0

109

-319

1.79

331

741.

843

3456

2.08

439

330.

058

0.08

00.

027

0.13

84

270

252

235

262

132

-320

2.03

139

352.

081

4423

2.32

550

550.

048

0.06

70.

027

0.12

03

315

294

267

313

159

-321

2.15

345

542.

203

4901

2.44

354

650.

040

0.05

60.

026

0.10

53

344

321

299

373

189

-322

2.30

752

852.

357

5657

2.59

762

580.

034

0.04

70.

026

0.09

23

387

361

334

444

227

-323

2.44

564

642.

495

7041

2.73

978

250.

028

0.04

10.

026

0.08

32

440

411

372

535

273

-324

2.68

877

342.

738

8541

3.04

594

050.

024

0.03

50.

026

0.07

52

498

465

418

646

326

-326

3.00

990

753.

059

9592

3.36

010

554

0.02

00.

030

0.02

60.

069

155

351

647

077

739

4-3

273.

219

1091

33.

269

1147

43.

570

1247

70.

016

0.02

60.

026

0.06

31

602

562

529

37-1

04Ge

xol®

-331

HF F

ire R

esis

tant

Th

ree

Cond

ucto

r Pow

er C

able

Low

Smok

e Ha

loge

n-Fr

eeEx

trem

ely

Flex

ible

• 0.

6/1k

V • R

ated

110

°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– T

hree

Con

duct

or

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-331

HF C

able

sEx

ampl

e:• T

hree

con

duct

or p

ower

cab

le• 0

.6/1

kV• b

ronz

e ar

mor

ed &

she

athe

d• w

ith g

roun

d

Amer

Cab

leG

exol

-331

HF

Pref

ixSp

ecifi

c C

able

Num

ber

(from

tabl

e)Ar

mor

Req

uire

men

tBS

– a

rmor

ed &

shea

thed

Blan

k –

no a

rmor

Gro

und

Con

duct

orG

– w

ith g

roun

d Bl

ank

– no

gro

und

8

3377––11

0044––

332200

BBSSGG

Oil &

Gas

Cab

les

Page 11: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire Resistant Four Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 9

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580and Type X110 of UL1309/CSA 245.Color code:Black-White-Red-Green

ConductorSoft annealed flexiblestranded tinnedcopper per IEEE 1580Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Aluminum ortinned copper available by request.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

An uninsulated groundconductor may be incorporated

on a make-to-order basis.

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 12: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-1

04Ge

xol®

-331

HF F

ire R

esis

tant

Fo

ur C

ondu

ctor

Pow

er C

able

Low

Smok

e Ha

loge

n-Fr

eeEx

trem

ely

Flex

ible

• 0.

6/1k

V • R

ated

110

°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– F

our C

ondu

ctor

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-331

HF C

able

sEx

ampl

e:• F

our c

ondu

ctor

pow

er c

able

• 0.6

/1kV

• #6

AWG

• bro

nze

arm

ored

& s

heat

hed

• with

gro

und

Amer

Cab

leG

exol

-331

HF

Pref

ixSp

ecifi

c C

able

Num

ber

(from

tabl

e)Ar

mor

Req

uire

men

tBS

– a

rmor

ed &

shea

thed

Blan

k –

no a

rmor

Gro

und

Con

duct

or

G –

with

gro

und

Blan

k –

no g

roun

d

3377––11

0044––

441100

BBSSGG

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

Opt.

Unin

sula

ted

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Grou

ndin

g Co

nd.

Ampa

city

kcm

ilm

m2

37-1

04(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

Size

AW

G11

0°C

100°

C95

°C16

1.3

-529

0.47

911

30.

529

176

0.66

825

94.

610

6.12

10.

045

8.51

8–

1716

1614

2.1

-509

0.51

514

60.

565

243

0.70

431

42.

907

3.85

90.

042

5.38

5–

2725

2212

3.3

-517

0.57

119

20.

621

292

0.76

136

81.

826

2.42

40.

039

3.39

6–

3331

2710

5.2

-408

0.60

927

70.

659

357

0.79

845

51.

153

1.53

00.

037

2.15

7–

4441

368

7.6

-409

0.75

440

50.

804

531

0.98

567

40.

708

0.94

00.

039

1.34

1–

5652

486

12.5

-410

0.85

060

80.

900

763

1.08

192

10.

445

0.59

00.

036

0.85

58

7570

644

21-4

121.

091

1002

1.14

112

111.

322

1409

0.30

00.

399

0.03

30.

586

899

9285

234

-414

1.25

012

771.

300

1533

1.48

119

120.

184

0.24

40.

032

0.37

06

131

122

113

143

-415

1.38

818

261.

438

2176

1.61

924

440.

147

0.19

50.

032

0.30

36

153

143

131

1/0

54-4

161.

521

2174

1.57

124

851.

814

2775

0.11

70.

156

0.03

10.

249

617

616

415

22/

070

-417

1.62

928

901.

679

3038

1.92

334

770.

093

0.12

50.

030

0.20

46

201

188

175

3/0

86-4

181.

810

3655

1.86

040

792.

104

4563

0.07

40.

100

0.03

00.

169

423

421

820

24/

010

9-4

192.

020

4292

2.07

048

042.

313

5324

0.05

80.

080

0.02

90.

141

427

025

223

526

213

2-4

202.

261

5273

2.31

154

662.

554

6395

0.04

80.

067

0.02

90.

123

331

529

426

731

315

9-4

212.

430

6118

2.48

066

892.

723

7290

0.04

00.

056

0.02

90.

108

334

432

129

937

318

9-4

222.

551

7367

2.60

178

122.

902

8637

0.03

40.

047

0.02

90.

095

338

736

133

444

422

7-4

232.

709

8618

2.75

991

053.

066

9986

0.02

80.

041

0.02

80.

086

244

041

137

253

527

3-4

243.

045

1058

42.

095

1112

93.

402

1205

00.

024

0.03

50.

029

0.07

82

463

432

418

646

326

-426

3.33

312

051

3.38

312

478

3.68

413

498

0.02

00.

030

0.02

90.

071

155

351

647

0

10

Oil &

Gas

Cab

les

Page 13: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire ResistantFive Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v4.03.1 11

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for TypeLSX of IEEE 1580 andType X110 of UL1309/CSA 245.Color code:Black-White-Red-Green-Orange

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A andIEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 14: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

12

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Ampa

city

kcm

ilm

m2

37-1

04(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

110°

C10

0°C

95°C

181.

0-5

580.

493

114

0.54

319

50.

682

252

7.35

49.

763

0.04

813

.562

1110

1116

1.3

-559

0.51

812

50.

568

215

0.70

930

14.

610

6.12

10.

045

8.51

814

1313

142.

1-5

100.

560

170

0.61

026

70.

749

343

2.90

73.

859

0.04

25.

385

2120

1812

3.3

-560

0.61

222

30.

662

303

0.81

438

11.

826

2.42

40.

039

3.39

627

2522

105.

2-5

610.

666

337

0.71

646

30.

897

563

1.15

31.

530

0.03

72.

157

3533

298

7.6

-562

0.82

751

60.

877

649

1.05

880

30.

708

0.94

00.

039

1.34

145

4238

612

.5-5

630.

976

744

1.02

692

71.

207

1109

0.44

50.

590

0.03

60.

855

6056

514

21-5

651.

199

1223

1.24

914

731.

430

1688

0.30

00.

399

0.03

30.

586

7974

682

34-5

661.

377

1552

1.42

718

661.

608

2116

0.18

40.

244

0.03

20.

370

105

9890

143

-567

1.53

224

281.

582

2499

1.82

628

290.

147

0.19

50.

032

0.30

312

211

410

51/

054

-568

1.68

029

071.

730

3130

1.97

335

430.

117

0.15

60.

031

0.24

914

013

112

22/

070

-569

1.86

433

681.

914

3763

2.15

842

570.

093

0.12

50.

030

0.20

416

115

014

04/

010

9-7

462.

229

4121

2.27

945

092.

523

5235

0.05

80.

080

0.02

90.

141

216

202

188

37-1

04Ge

xol®

-331

HF F

ire R

esis

tant

Five

Con

duct

or P

ower

Cab

leLo

w Sm

oke

Halo

gen-

Free

Extre

mel

y Fl

exib

le •

0.6/

1kV

• Rat

ed 1

10°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– F

ive

Cond

ucto

r

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-331

HF C

able

sEx

ampl

e:• F

ive c

ondu

ctor

pow

er c

able

• 0.6

/1kV

• #2

AWG

• b

ronz

e ar

mor

ed &

she

athe

d

Amer

Cab

le

Gex

ol-3

31H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0044––

556666

BBSS

Oil &

Gas

Cab

les

Page 15: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire Resistant Multi-Conductor Control CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 13

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

InsulationFire resistant tape + GEXOL®-HF low smokeHalogen-Free flame retardantcross-linked polyolefin,meeting the requirements for Type LSX of IEEE 1580and Type X110 of UL1309/CSA 245.Color code:ICEA K-1, Method 1. For less than minimum order quantities, Method 3may be used.

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580and UL 1309/CSA 245.

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Sheath (Optional)JacketA black low smoke Halogen-Free flame retardant polyolefin, meeting IEEE 1580and UL 1309/CSA 245.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant; IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 16: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.114

37-104Gexol®-331HF Fire Resistant Multi-Conductor Control CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

GEXOL® is a registered trademark of AmerCable Incorporated

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter Weight Ampacity

AWG mm2 Conductors 37-104 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.) 110°C 100°C 95°C16 1.3 4 -529 0.429 119 0.529 185 0.668 272 17 16 1616 1.3 5 -559 0.518 132 0.568 227 0.709 317 14 13 1316 1.3 7 -505 0.562 186 0.612 306 0.751 396 12 11 1116 1.3 8 -503 0.605 197 0.655 318 0.794 408 12 11 1116 1.3 10 -504 0.719 247 0.769 439 0.950 534 9 8 1116 1.3 16 -546 0.821 359 0.871 558 1.052 722 9 8 1116 1.3 20 -687 0.908 432 0.958 672 1.139 869 9 8 1116 1.3 24 -525 1.051 554 1.101 862 1.282 971 8 7 1116 1.3 37 -526 1.196 790 1.246 983 1.427 1187 6 6 816 1.3 44 -577 1.341 968 1.391 1176 1.572 1410 6 6 816 1.3 60 -527 1.486 1264 1.536 1507 1.780 1795 6 6 816 1.3 91 -581 1.776 1914 1.826 2275 2.069 2617 6 6 814 2.1 4 -509 0.515 154 0.565 256 0.704 330 27 25 2214 2.1 5 -510 0.560 179 0.610 281 0.749 361 21 20 1814 2.1 6 -511 0.628 218 0.678 317 0.817 402 21 20 1814 2.1 7 -521 0.628 251 0.678 349 0.817 453 19 18 1514 2.1 10 -512 0.779 336 0.829 487 1.010 618 14 13 1514 2.1 12 -585 0.804 368 0.854 514 1.035 670 14 13 1514 2.1 14 -523 0.870 572 0.920 709 1.102 893 14 13 1514 2.1 20 -513 1.030 672 1.080 974 1.261 1051 14 13 1514 2.1 24 -571 1.141 738 1.191 1070 1.372 1358 12 11 1514 2.1 30 -573 1.207 936 1.257 1158 1.438 1416 12 11 1314 2.1 37 -514 1.301 1051 1.351 1362 1.532 1686 11 10 1314 2.1 44 -574 1.461 1304 1.511 1512 1.754 1772 10 9 1114 2.1 91 -582 2.003 2640 2.053 2958 2.296 3426 10 9 1112 3.3 4 -517 0.571 192 0.621 292 0.761 368 33 31 2712 3.3 5 -560 0.612 235 0.662 319 0.814 401 27 25 2212 3.3 6 -547 0.679 336 0.729 486 0.910 600 27 25 2212 3.3 10 -518 0.859 443 0.909 600 1.090 755 17 16 1912 3.3 20 -519 1.136 841 1.186 1068 1.367 1266 17 16 1912 3.3 24 -572 1.261 1033 1.311 1400 1.492 1762 15 14 1912 3.3 37 -520 1.441 1514 1.491 1760 1.672 2012 13 12 16

Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance

Flexible Control Cable – Multi-Conductor

Oil & Gas Cables

Ordering Gexol-331HF CablesExample:

• Multi-Conductor control cable• 0.6/1kV• #12 AWG• bronze armored & sheathed

AmerCable Gexol-331HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

3377––110044 –– 551199 BBSS

Page 17: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire ResistantShielded Pairs Instrumentation CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 15

GEXOL® is a registered trademark of AmerCable Incorporated

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Aluminum or tinnedcopper available by request.

PairsEach pair is twisted with a bare tinned drain wire.Each pair is shielded withpolyester-backed aluminum foil tape toafford 100% coverage.Pair-to-pair isolation plusoverall shield is provided.Pair color code:Black-White

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.

Sheath (Optional)A black low smokeHalogen-Free flame retardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245. Cable available with

blue stripe to signify intrinsically safe circuit.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 18: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

16

GEXOL® is a registered trademark of AmerCable Incorporated

37-104Gexol®-331HF Fire ResistantShielded Pairs Instrumentation CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

Cable diameters shown asnominal are subject to a ±5%manufacturing tolerance

Flexible Instrumentation Cable – Individually Shielded Pairs

#18 PairsCapacitance = 22 nF/1000 ft.Inductance = 0.12 mH/1000 ft.Resistance = 7.21 ohms/1000 ft.

#16 PairsCapacitance = 22 nF/1000 ft.Inductance = 0.11 mH/1000 ft.Resistance = 4.52 ohms/1000 ft.

#14 PairsCapacitance = 25 nF/1000 ft.Inductance = 0.11 mH/1000 ft.Resistance = 2.85 ohms/1000 ft.

Ordering Gexol-331HF CablesExample:

• Instrumentation cable• 0.6/1kV• #14 AWG, 1 Pair• bronze armored & sheathed

AmerCable Gexol-331HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

Oil & Gas Cables

3377––110044 –– 662200 BBSS

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG mm2 Pairs 37-104 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)

18 1.0 1 -601 0.408 102 0.458 173 0.597 25418 1.0 2 -602 0.639 211 0.689 312 0.828 41618 1.0 3 -603 0.661 231 0.711 338 0.915 48518 1.0 4 -604 0.726 273 0.776 392 0.960 55018 1.0 5 -605 0.801 294 0.851 478 1.032 61818 1.0 7 -606 0.870 411 0.920 553 1.101 69618 1.0 8 -607 0.940 484 0.990 641 1.171 84118 1.0 10 -608 1.144 599 1.194 846 1.375 105718 1.0 12 -609 1.185 700 1.235 893 1.416 113418 1.0 16 -645 1.317 905 1.367 1008 1.548 143018 1.0 18 -641 1.389 997 1.439 1270 1.620 157318 1.0 24 -646 1.630 1433 1.680 1713 1.924 215616 1.3 1 -610 0.436 91 0.486 158 0.625 23516 1.3 2 -611 0.634 236 0.689 339 0.871 48416 1.3 3 -612 0.711 299 0.761 416 0.942 58016 1.3 4 -613 0.776 312 0.826 433 1.007 59716 1.3 5 -614 0.871 345 0.921 560 1.102 70616 1.3 7 -615 0.920 482 0.970 648 1.151 81516 1.3 8 -616 1.036 640 1.086 816 1.267 103916 1.3 10 -617 1.215 703 1.265 913 1.446 127416 1.3 12 -618 1.255 825 1.305 1071 1.486 132016 1.3 16 -619 1.403 1100 1.453 1428 1.634 176016 1.3 18 -626 1.473 1276 1.523 1462 1.766 182116 1.3 20 -688 1.547 1409 1.597 1712 1.840 219716 1.3 24 -699 1.730 1433 1.780 1713 2.023 215614 2.1 1 -620 0.458 112 0.508 175 0.646 25514 2.1 2 -621 0.709 234 0.759 365 0.940 55814 2.1 3 -622 0.752 291 0.802 454 0.983 59714 2.1 4 -623 0.826 349 0.876 544 1.057 73414 2.1 5 -624 0.907 434 0.957 705 1.137 91314 2.1 7 -625 1.033 608 1.083 817 1.264 102814 2.1 8 -630 1.119 578 1.169 931 1.350 117314 2.1 10 -627 1.316 867 1.366 1163 1.547 138714 2.1 12 -628 1.360 1039 1.410 1395 1.591 1663

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 19: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-104Gexol®-331HF Fire ResistantShielded Triads Instrumentation CableLow Smoke Halogen-Free Extremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 17

GEXOL® is a registered trademark of AmerCable Incorporated

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

E111461 � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world. Primarilyused on critical circuits that must continue tofunction even in a fire condition. This productshould be used on any circuit dedicated toemergency lighting, fire detection/suppression,alarms and personnel egress.

Features� Fire resistant: IEC 60331.

� Flame retardant; IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Aluminum or tinnedcopper available by request.

TriadsEach triad is twistedwith a bare tinned drainwire. Each triad isshielded with polyester-backed aluminum foiltape to afford 100%coverage. Triad to triadisolation plus overallshielding is provided.Triad color code:Black-White-Red

JacketA black low smokeHalogen-Free flameretardant polyolefin, compound meeting IEEE 1580 and UL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.

Sheath (Optional)A black low smoke Halogen-Free flameretardant polyolefin, meeting IEEE 1580 and UL 1309/CSA 245.

Cable available with blue jacket or stripe to signify

intrinsically safe circuit.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 20: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

18

GEXOL® is a registered trademark of AmerCable Incorporated

37-104Gexol®-331HF Fire ResistantShielded Triads Instrumentation CableLow Smoke Halogen-Free Extremely Flexible • 0.6/1kV • Rated 110°C

Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance

Flexible Instrumentation Cable – Individually Shielded Triads

#18 TriadsCapacitance = 22 nF/1000 ft.Inductance = 0.12 mH/1000 ft.Resistance = 7.21 ohms/1000 ft.

#16 TriadsCapacitance = 22 nF/1000 ft.Inductance = 0.11 mH/1000 ft.Resistance = 4.52 ohms/1000 ft.

Ordering Gexol-331HF CablesExample:

• Instrumentation cable• 0.6/1kV• #18 AWG, 4 triad• bronze armored & sheathed

AmerCable Gexol-331HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

Oil & Gas Cables

3377––110044 –– 668822 BBSS

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG mm2 Triads 37-104 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)

18 1.0 1 -647 0.431 91 0.481 174 0.620 24118 1.0 2 -681 0.743 221 0.793 351 0.974 46018 1.0 3 -648 0.789 230 0.839 369 1.020 47618 1.0 4 -682 0.867 340 0.917 494 1.098 66718 1.0 5 -649 0.995 346 1.045 507 1.226 67918 1.0 7 -650 1.084 495 1.134 684 1.315 87618 1.0 8 -683 1.176 640 1.226 1007 1.407 123418 1.0 12 -640 1.431 927 1.481 1168 1.662 144616 1.3 1 -668 0.450 116 0.500 189 0.639 27016 1.3 3 -669 0.836 264 0.886 409 1.067 56416 1.3 4 -698 0.919 496 0.969 641 1.150 84716 1.3 6 -676 1.149 762 1.199 908 1.380 115616 1.3 7 -670 1.149 762 1.199 908 1.380 127116 1.3 8 -677 1.240 882 1.290 1060 1.471 1335

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 21: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantSingle Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 2kV • Rated 110°C

v2.08.1 19

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that mightdamage expensive electronic equipment, makingit ideal for use in control rooms that house this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

Insulation/JacketGEXOL®-HF low smoke,Halogen-Free flame retardant cross-linked,polyolefin insulation meetingthe requirements for TypeLSX of IEEE 1580 and TypeX110 of UL 1309/CSA 245plus a black low smokeHalogen-Free flame retardant polyolefin jacketmeeting IEEE 1580 and UL 1309/CSA 245.2000V/IEC 1000V.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 22: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

37-1

03Ge

xol®

-HF

Flam

e Re

tard

ant

Sing

le C

ondu

ctor

Pow

er C

able

Low

Smok

e Ha

loge

n-Fr

eeEx

trem

ely

Flex

ible

• 2k

V • R

ated

110

°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– S

ingl

e Co

nduc

tor

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Indu

ctiv

eVo

ltage

Dro

pNo

min

alNo

min

alIn

duct

ive

Volta

ge D

rop

DC R

esis

tanc

eAC

Res

ista

nce

atAm

paci

tyAW

G/Pa

rt No

.Di

amet

erW

eigh

tRe

acta

nce

at 1

10°C

Di

amet

erW

eigh

tDi

amet

erW

eigh

tRe

acta

nce

at 1

10°C

at

25°

C11

0°C,

60 H

zFr

ee A

irkc

mil

mm

237

-103

(inch

es)

(lbs/

MFt

.)(O

hms/

1000

ft.)

(Vol

ts/A

mp/

1000

ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

(Ohm

s/10

00 ft

.)(V

olts

/Am

p/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s/10

00 ft

.)11

0°C

110°

C10

0°C

95°C

181.

0-1

010.

238

170.

058

13.5

720.

288

310.

396

410.

070

13.5

857.

210

9.76

330

1716

2016

1.3

-102

0.24

819

0.05

58.

528

0.29

835

0.40

646

0.06

68.

539

4.52

06.

121

3525

2323

142.

1-1

050.

263

270.

051

5.39

40.

313

490.

452

660.

063

5.40

72.

850

3.85

941

4037

3212

3.3

-106

0.28

233

0.04

73.

404

0.33

262

0.47

187

0.05

93.

416

1.79

02.

424

6448

4538

105.

2-1

080.

302

540.

044

2.16

40.

352

101

0.49

113

90.

055

2.17

51.

130

1.53

085

6258

518

7.6

-109

0.38

177

0.04

51.

348

0.43

112

70.

570

174

0.05

51.

357

0.69

40.

940

112

7772

686

12.5

-110

0.42

111

60.

042

0.86

10.

471

168

0.61

022

20.

050

0.86

90.

436

0.59

014

810

396

914

21-1

120.

503

186

0.03

70.

590

0.55

324

90.

692

323

0.04

40.

598

0.28

60.

399

196

137

128

121

234

-114

0.56

926

20.

035

0.37

40.

619

329

0.75

839

90.

041

0.38

00.

175

0.24

425

918

116

916

21

43-1

150.

610

364

0.03

40.

305

0.66

044

30.

799

512

0.04

00.

312

0.14

00.

195

298

208

194

187

1/0

54-1

160.

674

458

0.03

30.

251

0.72

454

00.

905

626

0.04

00.

258

0.11

10.

156

344

243

227

217

2/0

70-1

170.

741

540

0.03

30.

206

0.79

163

40.

972

727

0.03

90.

213

0.08

90.

125

396

281

262

250

3/0

86-1

180.

800

738

0.03

20.

171

0.85

086

71.

032

1046

0.03

80.

177

0.07

00.

100

457

321

300

289

4/0

109

-119

0.90

894

30.

032

0.14

40.

958

1090

1.14

012

850.

037

0.15

00.

056

0.08

052

837

635

133

526

213

2-1

201.

010

1139

0.03

20.

125

1.06

013

001.

241

1513

0.03

60.

130

0.04

60.

067

599

436

407

382

313

159

-121

1.07

612

230.

031

0.11

01.

126

1467

1.30

716

430.

035

0.11

50.

038

0.05

660

448

745

542

737

318

9-1

221.

143

1546

0.03

00.

097

1.19

317

291.

374

1966

0.03

50.

101

0.03

20.

047

674

553

516

476

444

227

-123

1.21

918

120.

030

0.08

81.

269

2008

1.45

022

590.

034

0.09

20.

027

0.04

175

063

058

853

153

527

3-1

241.

333

2171

0.03

00.

079

1.38

323

811.

565

2653

0.03

30.

083

0.02

20.

035

839

709

662

597

646

326

-126

1.42

225

920.

029

0.07

21.

472

2826

1.65

330

460.

033

0.07

50.

019

0.03

093

778

373

167

177

739

4-1

271.

520

3088

0.02

80.

066

1.55

033

301.

813

3191

0.03

30.

070

0.01

50.

026

1048

881

822

753

1111

562

-129

1.79

344

050.

028

0.05

41.

843

4568

2.08

646

920.

032

0.05

80.

011

0.01

813

0310

9810

2593

7

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

Ord

erin

g G

exol

-HF

Cabl

esEx

ampl

e:• S

ingl

e co

nduc

tor p

ower

cab

le• 2

kV• 5

35 k

cmil

• bro

nze

arm

ored

& s

heat

hed

Amer

Cab

le

Gex

ol-H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0033––

112244

BBSS

20

Oil &

Gas

Cab

les

Page 23: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantTwo Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 21

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 andType X110 of UL 1309/CSA 245.Color code:Black-White

ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Aluminum ortinned copper availableby request.

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 24: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

at 1

10°C

,60

HzRe

acta

nce

at 1

10°C

Am

paci

ty

kcm

ilm

m2

37-1

03(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

110°

C10

0°C

95°C

161.

3-5

010.

373

750.

423

141

0.56

220

24.

610

6.12

10.

039

8.51

120

1920

142.

1-5

070.

403

950.

453

165

0.59

223

02.

907

3.85

90.

036

5.37

933

3127

123.

3-5

150.

441

117

0.49

119

40.

630

263

1.82

62.

424

0.03

43.

390

4340

3210

5.2

-553

0.48

114

80.

531

233

0.67

030

71.

153

1.53

00.

032

2.15

153

4943

87.

6-2

090.

600

221

0.65

032

70.

789

416

0.70

80.

940

0.03

41.

336

6964

586

12.5

-210

0.68

030

80.

730

424

0.91

155

90.

445

0.59

00.

032

0.85

091

8577

421

-594

0.88

751

60.

937

664

1.11

883

50.

300

0.39

90.

029

0.58

211

811

010

31/

054

-216

1.24

311

281.

293

1334

1.47

415

620.

117

0.15

60.

028

0.24

521

319

918

44/

010

9-2

191.

593

2003

1.64

322

711.

886

2680

0.05

80.

080

0.02

60.

138

329

307

285

37-1

03Ge

xol®

-HF

Flam

e Re

tard

ant

Two

Cond

ucto

r Pow

er C

able

Low

Smok

e Ha

loge

n-Fr

eeEx

trem

ely

Flex

ible

• 0.

6/1k

V • R

ated

110

°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

1063

3 W

est L

ittle

Yor

k • B

ldg.

#1

• Sui

te #

100

• Hou

ston

, TX

7704

1 • w

ww

.am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– T

wo

Cond

ucto

r

Ord

erin

g G

exol

-HF

Cabl

esEx

ampl

e:• T

wo

cond

ucto

r pow

er c

able

• 0.6

/1kV

• #4

AWG

• bro

nze

arm

ored

& s

heat

hed

Amer

Cab

le

Gex

ol-H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0033––

559944

BBSS

22

Oil &

Gas

Cab

les

Page 25: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantThree Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 23

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for TypeLSX of IEEE 1580 andType X110 of UL1309/CSA 245.Color code:Black-White-Red

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available byrequest.

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment, making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

An uninsulated ground conductor may be incorporated

on a make-to-order basis.

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 26: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

Opt.

Unin

sula

ted

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Grou

ndin

g Co

nd.

Ampa

city

kcm

ilm

m2

37-1

03(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

Size

AW

G11

0°C

100°

C95

°C16

1.3

-502

0.39

266

0.44

212

80.

581

182

4.61

06.

121

0.03

98.

511

–17

1616

142.

1-5

080.

424

102

0.47

417

60.

613

236

2.90

73.

859

0.03

65.

379

–27

2522

123.

3-5

160.

465

133

0.51

521

20.

654

276

1.82

62.

424

0.03

43.

390

–33

3127

105.

2-3

080.

508

189

0.55

828

10.

697

352

1.15

31.

530

0.03

22.

151

–44

4136

87.

6-3

090.

637

274

0.68

738

50.

826

477

0.70

80.

940

0.03

41.

336

–56

5248

612

.5-3

100.

723

390

0.77

351

90.

954

650

0.44

50.

590

0.03

20.

850

875

7064

421

-312

0.94

267

80.

992

843

1.17

310

040.

300

0.39

90.

029

0.58

28

9992

852

34-3

141.

084

987

1.13

496

71.

315

1374

0.18

40.

244

0.02

80.

366

613

112

211

31

43-3

151.

206

1234

1.25

614

581.

439

1675

0.14

70.

195

0.02

80.

299

615

314

313

11/

054

-316

1.32

614

481.

376

1781

1.55

820

150.

117

0.15

60.

028

0.24

56

176

164

152

2/0

70-3

171.

422

1945

1.47

220

821.

653

2424

0.09

30.

125

0.02

70.

200

620

118

817

53/

086

-318

1.52

823

791.

578

2720

1.82

231

060.

074

0.10

00.

027

0.16

64

234

218

202

4/0

109

-319

1.76

528

641.

815

3233

2.05

836

520.

058

0.08

00.

026

0.13

84

270

252

235

262

132

-320

1.98

034

522.

030

3880

2.27

444

340.

048

0.06

70.

026

0.11

93

315

294

267

313

159

-321

2.13

140

232.

181

4434

2.42

649

190.

040

0.05

60.

026

0.10

53

344

321

299

373

189

-322

2.23

147

722.

281

5219

2.52

557

180.

034

0.04

70.

025

0.09

23

387

361

334

444

227

-323

2.39

456

702.

444

6176

2.68

868

640.

028

0.04

10.

025

0.08

32

440

411

372

535

273

-324

2.63

767

842.

687

7492

2.99

482

500.

024

0.03

50.

026

0.07

52

498

465

418

646

326

-326

2.95

879

613.

008

8414

3.30

992

580.

020

0.03

00.

026

0.06

91

553

516

470

777

394

-327

3.16

895

733.

218

1006

53.

519

1094

50.

016

0.02

60.

026

0.06

31

602

562

529

37-1

03Ge

xol®

-HF

Flam

e Re

tard

ant

Thre

e Co

nduc

tor P

ower

Cab

leLo

w Sm

oke

Halo

gen-

Free

Extre

mel

y Fl

exib

le •

0.6/

1kV

• Rat

ed 1

10°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– T

hree

Con

duct

or

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-HF

Cabl

esEx

ampl

e:• T

hree

con

duct

or p

ower

cab

le• 0

.6/1

kV• 2

62 k

cmil

• bro

nze

arm

ored

& s

heat

hed

• with

gro

und

Amer

Cab

leG

exol

-HF

Pref

ixSp

ecifi

c C

able

Num

ber

(from

tabl

e)Ar

mor

Req

uire

men

tBS

– a

rmor

ed &

shea

thed

Blan

k –

no a

rmor

Gro

und

Con

duct

orG

– w

ith g

roun

dBl

ank

– no

gro

und

24

3377––11

0033––

332200

BBSSGG

Oil &

Gas

Cab

les

Page 27: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame Retardant Four Conductor Power CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 25

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linked,polyolefin, meeting therequirements for Type LSXof IEEE 1580 and Type X110 of UL 1309/CSA 245.Color code:Black-White-Red-Green

ConductorSoft annealed flexiblestranded tinnedcopper per IEEE 1580Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Aluminum ortinned copper available by request.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

An uninsulated ground conductor may be incorporated

on a make-to-order basis.

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 28: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-1

03Ge

xol®

-HF

Flam

e Re

tard

ant

Four

Con

duct

or P

ower

Cab

leLo

w Sm

oke

Halo

gen-

Free

Extre

mel

y Fl

exib

le •

0.6/

1kV

• Rat

ed 1

10°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– F

our C

ondu

ctor

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-HF

Cabl

esEx

ampl

e:• F

our c

ondu

ctor

pow

er c

able

• 0.6

/1kV

• #6

AWG

• bro

nze

arm

ored

& s

heat

hed

• with

gro

und

Amer

Cab

leG

exol

-HF

Pref

ixSp

ecifi

c C

able

Num

ber

(from

tabl

e)Ar

mor

Req

uire

men

tBS

– a

rmor

ed &

shea

thed

Blan

k –

no a

rmor

Gro

und

Con

duct

orG

– w

ith g

roun

dBl

ank

– no

gro

und

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

Opt.

Unin

sula

ted

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Grou

ndin

g Co

nd.

Ampa

city

kcm

ilm

m2

37-1

03(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

Size

AW

G11

0°C

100°

C95

°C16

1.3

-529

0.42

399

0.47

315

40.

612

227

4.61

06.

121

0.04

28.

514

–17

1616

142.

1-5

090.

459

128

0.50

921

30.

648

275

2.90

73.

859

0.03

95.

382

–27

2522

123.

3-5

170.

505

168

0.55

525

60.

694

323

1.82

62.

424

0.03

73.

393

–33

3127

105.

2-4

080.

553

243

0.60

331

30.

742

390

1.15

31.

530

0.03

52.

154

–44

4136

87.

6-4

090.

698

355

0.74

846

60.

929

591

0.70

80.

940

0.03

71.

339

–56

5248

612

.5-4

100.

794

533

0.84

466

91.

025

808

0.44

50.

590

0.03

50.

853

875

7064

421

-412

1.03

587

91.

085

1062

1.26

612

360.

300

0.39

90.

032

0.58

58

9992

852

34-4

141.

194

1120

1.24

413

451.

425

1677

0.18

40.

244

0.03

00.

369

613

112

211

31

43-4

151.

332

1602

1.38

219

091.

563

2144

0.14

70.

195

0.03

10.

302

615

314

313

11/

054

-416

1.46

519

071.

515

2180

1.75

824

340.

117

0.15

60.

030

0.24

86

176

164

152

2/0

70-4

171.

573

2535

1.62

326

651.

867

3050

0.09

30.

125

0.03

00.

203

620

118

817

53/

086

-418

1.75

432

061.

804

3578

2.04

840

030.

074

0.10

00.

029

0.16

84

234

218

202

4/0

109

-419

1.96

437

652.

014

4214

2.25

746

700.

058

0.08

00.

029

0.14

04

270

252

235

262

132

-420

2.20

546

252.

255

4795

2.49

856

100.

048

0.06

70.

029

0.12

23

315

294

267

313

159

-421

2.37

453

672.

424

5868

2.66

763

950.

040

0.05

60.

028

0.10

73

344

321

299

373

189

-422

2.49

564

622.

545

6853

2.84

675

760.

034

0.04

70.

028

0.09

53

387

361

334

444

227

-423

2.65

375

602.

703

7987

3.01

087

600.

028

0.04

10.

028

0.08

62

440

411

372

535

273

-424

2.98

919

284

3.03

997

623.

346

1057

00.

024

0.03

50.

028

0.07

72

463

432

418

646

326

-426

3.27

710

571

3.32

710

946

3.68

211

840

0.02

00.

030

0.02

90.

071

155

351

647

0

26

3377––11

0033––

441100

BBSSGG

Oil &

Gas

Cab

les

Page 29: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantFive ConductorLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 27

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for TypeLSX of IEEE 1580 andType X110 of UL 1309/CSA 245.Color code:Black-White-Red-Green-Orange

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Sheath (Optional)A black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 30: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

Arm

ored

and

Unar

mor

edAr

mor

ed (B

)Sh

eath

(BS)

Size

Nom

inal

Nom

inal

Nom

inal

AC R

esis

tanc

eIn

duct

ive

Volta

ge D

rop

AWG/

Part

No.

Diam

eter

Wei

ght

Diam

eter

Wei

ght

Diam

eter

Wei

ght

DC R

esis

tanc

e at

110°

C,60

Hz

Reac

tanc

e11

0°C

Ampa

city

kcm

ilm

m2

37-1

03(in

ches

)(lb

s/M

Ft.)

(inch

es)

(lbs/

MFt

.)(in

ches

)(lb

s/M

Ft.)

25°C

(Ohm

s/10

00 ft

.)(O

hms/

1000

ft.)

(Ohm

s /1

000

ft.)

(Vol

ts/A

mp/

1000

ft.)

110°

C10

0°C

95°C

181.

0-5

580.

431

100

0.48

117

10.

620

221

7.35

49.

763

0.04

413

.558

1110

1116

1.3

-559

0.45

611

00.

506

189

0.64

726

44.

610

6.12

10.

042

8.51

414

1313

142.

1-5

100.

498

149

0.54

823

40.

687

301

2.90

73.

859

0.03

95.

382

2120

1812

3.3

-560

0.55

019

60.

600

266

0.75

233

41.

826

2.42

40.

037

3.39

327

2522

105.

2-5

610.

604

296

0.65

440

60.

973

494

1.15

31.

530

0.03

52.

154

3533

298

7.6

-562

0.76

545

30.

815

569

1.99

670

40.

708

0.94

00.

037

1.33

945

4238

612

.5-5

630.

914

653

.964

813

1.14

597

30.

445

0.59

00.

035

0.85

360

5651

421

-565

1.13

710

731.

187

1292

1.36

814

810.

300

0.39

90.

032

0.58

579

7468

234

-566

1.31

513

611.

365

1637

1.54

618

560.

184

0.24

40.

030

0.36

910

598

901

43-5

671.

470

2130

1.52

021

921.

764

2482

0.14

70.

195

0.03

10.

302

122

114

105

1/0

54-5

681.

618

2550

1.66

827

461.

911

3108

0.11

70.

156

0.03

00.

248

140

131

122

2/0

70-5

691.

802

2954

1.85

233

012.

096

3734

0.09

30.

125

0.03

00.

203

161

150

140

4/0

109

-746

2.16

736

152.

217

3955

2.46

145

920.

058

0.08

00.

029

0.14

021

620

218

8

37-1

03Ge

xol®

-HF

Flam

e Re

tard

ant

Five

Con

duct

orLo

w Sm

oke

Halo

gen-

Free

Extre

mel

y Fl

exib

le •

0.6/

1kV

• Rat

ed 1

10°C

Man

ufac

ture

d by

Am

erCa

ble

Inco

rpor

ated

• 80

0-50

6-94

73 •

713-

896-

5800

• Fa

x: 7

13-8

49-9

009

ww

w.a

mer

cabl

e.co

m •

e-m

ail: m

arin

e@am

erca

ble.

com

v2.0

8.1

Flex

ible

Pow

er C

able

– F

ive

Cond

ucto

r

Cab

le d

iam

eter

s sh

own

as n

omin

al a

re s

ubje

ct t

o a

±5%

man

ufac

turin

g to

lera

nce

GEXO

L®is

a re

giste

red

trade

mar

k of

Am

erCa

ble In

corp

orat

ed

Ord

erin

g G

exol

-HF

Cabl

esEx

ampl

e:• F

ive c

ondu

ctor

pow

er c

able

• 0.6

/1kV

• #2

AWG

• b

ronz

e ar

mor

ed &

she

athe

d

Amer

Cab

le

Gex

ol-H

F Pr

efix

Spec

ific

Cab

le N

umbe

r(fr

om ta

ble)

Arm

or R

equi

rem

ent

BS –

arm

ored

&sh

eath

edBl

ank

– no

arm

or

3377––11

0033––

556666

BBSS

28

Oil &

Gas

Cab

les

Page 31: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantMulti-Conductor Control CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 29

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

InsulationGEXOL®-HF low smokeHalogen-Free flame retardantcross-linked polyolefin, meeting the requirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.Color code:ICEA K-1, Method 1. For less than minimum order quantities, Method 3may be used.

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580and UL 1309/CSA 245.

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Sheath (Optional)JacketA black low smoke Halogen-Free flame retardant polyolefin, meeting IEEE 1580and UL 1309/CSA 245.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 32: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

30

37-103Gexol®-HF Flame RetardantMulti-Conductor Control CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

GEXOL® is a registered trademark of AmerCable Incorporated

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter Weight Ampacity

AWG mm2 Conductors 37-103 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.) 110°C 100°C 95°C16 1.3 4 -529 0.423 99 0.473 154 0.612 227 17 16 1616 1.3 5 -559 0.456 110 0.506 189 0.647 264 14 13 1316 1.3 7 -505 0.494 155 0.544 255 0.683 330 12 11 1116 1.3 8 -503 0.531 164 0.581 265 0.720 340 12 11 1116 1.3 10 -504 0.631 206 0.681 366 0.820 445 9 8 1116 1.3 16 -546 0.719 299 0.769 465 0.950 602 9 8 1116 1.3 20 -687 0.794 360 0.844 560 1.025 724 9 8 1116 1.3 24 -525 0.923 462 0.973 718 1.154 809 8 7 1116 1.3 37 -526 1.048 658 1.098 819 1.279 989 6 6 816 1.3 44 -577 1.173 807 1.223 980 1.404 1175 6 6 816 1.3 60 -527 1.298 1053 1.348 1256 1.529 1496 6 6 816 1.3 91 -581 1.548 1595 1.598 1896 1.841 2181 6 6 814 2.1 4 -509 0.459 128 0.509 213 0.648 275 27 25 2214 2.1 5 -510 0.498 149 0.548 234 0.687 301 21 20 1814 2.1 6 -511 0.539 182 0.589 264 0.728 335 21 20 1814 2.1 7 -521 0.539 205 0.589 297 0.728 377 19 18 1514 2.1 10 -512 0.691 280 0.741 406 0.922 515 14 13 1514 2.1 12 -585 0.713 307 0.763 428 0.944 558 14 13 1514 2.1 14 -523 0.749 415 0.799 540 0.980 665 14 13 1514 2.1 20 -513 0.916 560 0.966 812 1.147 876 14 13 1514 2.1 24 -571 1.013 615 1.063 892 1.244 1132 12 11 1514 2.1 30 -573 1.071 780 1.121 965 1.302 1180 12 11 1314 2.1 37 -514 1.153 876 1.203 1135 1.384 1405 11 10 1314 2.1 44 -574 1.293 1087 1.343 1260 1.524 1477 10 9 1114 2.1 91 -582 1.775 2200 1.825 2465 2.068 2855 10 9 1112 3.3 4 -517 0.505 168 0.555 256 0.694 323 33 31 2712 3.3 5 -560 0.550 196 0.600 266 0.752 334 27 25 2212 3.3 6 -547 0.611 280 0.661 405 0.800 500 27 25 2212 3.3 10 -518 0.771 369 0.821 500 1.002 629 17 16 1912 3.3 20 -519 1.022 701 1.072 890 1.253 1055 17 16 1912 3.3 24 -572 1.133 861 1.183 1167 1.364 1468 15 14 1912 3.3 37 -520 1.293 1262 1.343 1467 1.524 1677 13 12 16

Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance

Flexible Control Cable – Multi-Conductor

Oil & Gas Cables

Ordering Gexol-HF CablesExample:

• Multi-Conductor control cable• 0.6/1kV• #12 AWG• bronze armored & sheathed

AmerCable Gexol-HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

3377––110033 –– 551199 BBSS

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 33: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame Retardant Shielded Pairs Instrumentation CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 31

GEXOL® is a registered trademark of AmerCable Incorporated

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Aluminum or tinnedcopper available by request.

PairsEach pair is twisted with a bare tinned drain wire.Each pair is shielded withpolyester-backed aluminum foil tape toafford 100% coverage.Pair-to-pair isolation plusoverall shield is provided.Pair color code:Black-White

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSXof IEEE 1580 and TypeX110 of UL 1309/CSA 245.

Sheath (Optional)A black low smokeHalogen-Free flame retardant polyolefin,meeting IEEE 1580 andUL 1309/CSA 245. Cable available with

blue stripe to signify intrinsically safe circuit.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 34: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

32

GEXOL® is a registered trademark of AmerCable Incorporated

37-103Gexol®-HF Flame Retardant Shielded Pairs Instrumentation CableLow Smoke Halogen-FreeExtremely Flexible • 0.6/1kV • Rated 110°C

Cable diameters shown asnominal are subject to a ±5%manufacturing tolerance

Flexible Instrumentation Cable – Individually Shielded Pairs

#18 PairsCapacitance = 33 nF/1000 ft.Inductance = 0.22 mH/1000 ft.Resistance = 7.21 ohms/1000 ft.

#16 PairsCapacitance = 37 nF/1000 ft.Inductance = 0.20 mH/1000 ft.Resistance = 4.52 ohms/1000 ft.

#14 PairsCapacitance = 43 nF/1000 ft.Inductance = 0.19 mH/1000 ft.Resistance = 2.85 ohms/1000 ft.

Ordering Gexol-HF CablesExample:

• Instrumentation cable• 0.6/1kV• #14 AWG, 1 pair• bronze armored & sheathed

AmerCable Gexol-HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

Oil & Gas Cables

3377––110033 –– 662200 BBSS

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG mm2 Pairs 37-103 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)

18 1.0 1 -601 0.360 63 0.410 123 0.549 17618 1.0 2 -602 0.551 131 0.601 204 0.740 33518 1.0 3 -603 0.581 163 0.631 265 0.770 34318 1.0 4 -604 0.630 195 0.680 317 0.809 41018 1.0 5 -605 0.685 243 0.735 395 0.908 51118 1.0 7 -606 0.742 340 0.792 457 0.965 57518 1.0 8 -607 0.800 388 0.850 521 1.023 75218 1.0 10 -608 0.976 495 1.026 699 1.207 87418 1.0 12 -609 1.011 581 1.061 780 1.242 98218 1.0 16 -645 1.121 748 1.171 833 1.352 118218 1.0 18 -641 1.181 824 1.231 1050 1.412 130018 1.0 24 -646 1.382 1069 1.432 1151 1.613 172016 1.3 1 -610 0.388 77 0.438 120 0.577 20316 1.3 2 -611 0.565 160 0.615 249 0.759 37716 1.3 3 -612 0.617 200 0.667 311 0.793 41016 1.3 4 -613 0.671 239 0.721 389 0.894 56916 1.3 5 -614 0.730 297 0.780 483 0.953 60916 1.3 7 -615 0.792 416 0.842 559 1.015 70316 1.3 8 -616 0.896 475 0.946 638 1.127 80316 1.3 10 -617 1.047 606 1.097 787 1.278 109816 1.3 12 -618 1.081 711 1.131 923 1.312 113816 1.3 16 -619 1.207 948 1.257 1231 1.430 151716 1.3 18 -626 1.265 1100 1.315 1260 1.496 157016 1.3 20 -688 1.327 1215 1.377 1476 1.560 189416 1.3 24 -699 1.482 1510 1.532 1625 1.775 206514 2.1 1 -620 0.410 97 0.460 151 0.598 19914 2.1 2 -621 0.621 202 0.671 315 0.810 48114 2.1 3 -622 0.658 251 0.708 391 0.889 51514 2.1 4 -623 0.721 301 0.771 469 0.952 63314 2.1 5 -624 0.791 374 0.841 608 1.021 78714 2.1 7 -625 0.905 524 0.955 704 1.136 88614 2.1 8 -629 0.979 498 1.029 803 1.210 101114 2.1 10 -627 1.148 747 1.198 1003 1.379 119614 2.1 12 -628 1.186 896 1.236 1203 1.417 1434

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 35: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-103Gexol®-HF Flame RetardantShielded Triads Instrumentation CableLow Smoke Halogen-Free Extremely Flexible • 0.6/1kV • Rated 110°C

v2.08.1 33

GEXOL® is a registered trademark of AmerCable Incorporated

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

E111461 � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

ApplicationSmoke, with its toxic and corrosive effects, isbecoming more clearly recognized as the realculprit in fire fatalities. And there is increasingconcern about smoke evolution in confinedspaces or areas of limited egress. Low smoke,Halogen-Free, Gexol-HF should be used in theliving quarters area to insure safe egress ofpersonnel during a fire. Gexol-HF does notproduce corrosive gases during a fire that might damage expensive electronic equipment,making it ideal for use in control rooms thathouse this equipment.

Features� Flame retardant: IEC 332-3 Category A

and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make thisproduct more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higherampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Aluminum or tinnedcopper available by request.

TriadsEach triad is twistedwith a bare tinned drainwire. Each triad isshielded with polyester-backed aluminum foiltape to afford 100%coverage. Triad-to-triadisolation plus overallshielding is provided.Triad color code:Black-White-Red

JacketA black low smokeHalogen-Free flameretardant polyolefin, meeting IEEE 1580 and UL 1309/CSA 245.

InsulationGEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.

Sheath (Optional)A black low smoke Halogen-Free flameretardant polyolefin, meeting IEEE 1580 and UL 1309/CSA 245.

Cable available with blue jacket or stripe to signify

intrinsically safe circuit.

HawkeGland Types Unarmored Armored & Sheathed

Industrial & Safe Area (IP68) 121 153-XIncreased Safety

501/421 501/453/U“EExe”Explosion Proof 710 753

Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2

Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)

ICG 653/U(2 liter or > enclosures)

Zone 1 & 2

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 36: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

34

GEXOL® is a registered trademark of AmerCable Incorporated

37-103Gexol®-HF Flame RetardantShielded Triads Instrumentation CableLow Smoke Halogen-Free Extremely Flexible • 0.6/1kV • Rated 110°C

Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance

Flexible Instrumentation Cable – Individually Shielded Triads

#18 TriadsCapacitance = 33 nF/1000 ft.Inductance = 0.22 mH/1000 ft.Resistance = 7.21 ohms/1000 ft.

#16 TriadsCapacitance = 37 nF/1000 ft.Inductance = 0.20 mH/1000 ft.Resistance = 4.52 ohms/1000 ft.

Ordering Gexol-HF CablesExample:

• Instrumentation cable• 0.6/1kV• #18 AWG, 4 triad• bronze armored & sheathed

AmerCable Gexol-HF Prefix

Specific Cable Number(from table)

Armor RequirementBS – armored &

sheathedBlank – no armor

Oil & Gas Cables

3377––110033 –– 668822 BBSS

Armored andUnarmored Armored (B) Sheath (BS)

Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG mm2 Triads 37-103 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)

18 1.0 1 -647 0.380 75 0.430 144 0.569 19918 1.0 2 -681 0.649 183 0.699 290 0.880 38018 1.0 3 -648 0.688 190 0.738 305 0.919 39318 1.0 4 -682 0.755 281 0.805 408 0.986 55118 1.0 5 -649 0.871 286 0.921 419 1.102 56118 1.0 7 -650 0.947 409 0.997 565 1.178 72418 1.0 8 -683 1.026 515 1.076 680 1.257 87018 1.0 12 -640 1.244 766 1.294 965 1.475 119516 1.3 1 -668 0.399 86 0.449 155 0.588 21316 1.3 3 -669 0.735 218 0.785 338 0.966 46616 1.3 4 -698 0.807 410 0.857 530 1.038 70016 1.3 6 -676 1.012 630 1.062 750 1.243 95516 1.3 7 -670 1.012 630 1.062 750 1.243 105016 1.3 8 -677 1.090 729 1.140 876 1.338 1103

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 37: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

v2.08.1 35

37-103VFDType VFD Power CableGexol®-HF InsulatedLow Smoke Halogen-Free Three Conductor • 2kV • Rated 110°C

ApplicationA flexible, braid and foil shielded, 2kV powercable specifically engineered for use in variablefrequency AC motor drive (VFD) applications.

Features� Low Smoke and Halogen-Free.

� Specially engineered cable design produces a longer cable life in VFD applications.

� Overall braid and foil shield provides 100%coverage containing VFD EMI emissions.

� Symmetrical insulated ground conductorsreduce induced voltage imbalances and carry common mode noise back to the drive.

� High strand count conductors and braid shield design is much more flexible and easier than IEC 60092-350 series cables to install.

� Gexol-HF’s lower dielectric constant (standardHFXLPE, HFEPR insulation materials havehigher dielectric constants) reduces reflectedwave peak voltage magnitudes. This allows forlonger output cable distances and minimizesthe effect of high frequency noise induced into the plant ground system.

� 2kV insulation thickness resists the repetitive2x voltage spikes from 600V VFDs andreduces drive over current trip problems due to cable charging current.

� Dual certified IEEE 1580 Type LSX and UL 1309/CSA 245 Type X110.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Flame retardant: IEC 332-3 Category A and IEEE 1202.

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

� Optional braid armor of bronze, aluminum or tinned copper.

Insulation (2kV)GEXOL®-HF low smokeHalogen-Free flame retardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.

Color: Gray with printed phase I.D.(Black-White-Red) Jacket

A black low smoke Halogen-Free flameretardant polyolefin, meeting IEEE 1580 and UL 1309/CSA 245.

Power Conductors (x3)Soft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

Ground Conductors (x3)Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.Gexol®-HF insulated andsized per UL 1277.Color: Green

Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinned copper availableby request.

ShieldOverall tinned copperbraid plus aluminum/polyester tape providing100% coverage.

Sheath (Optional)A black low smoke Halogen-Free flame retardant polyolefin, meeting IEEE 1580 and UL 1309/CSA 245.

Ratings & Approvals� 110˚C Temperature Rating

� American Bureau of Shipping (ABS): 99-BT5905-X

� UL Listed as Marine Shipboard Cable: (E111461)

� Transport Canada: pending

� Det Norske Veritas (DNV): pending

� Lloyd’s Register of Shipping pending

� Germanischer Lloyd (GL): pendingOther certifications pending

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 38: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

36

37-103VFDType VFD Power CableGexol®-HF InsulatedLow Smoke Halogen-Free Three Conductor • 2kV • Rated 110°C

GEXOL® is a registered trademark of AmerCable Incorporated

Size Nominal Weight Nominal Weight Nominal WeightAWG/ Part No. Diameter Per Part No. Diameter Per Part No. Diameter Perkcmil 37-103 Inches* 1000 Ft. 37-103 Inches* 1000 Ft. 37-103 Inches* 1000 Ft. Size (AWG) 110˚C 90˚C 75˚C

14 -508VFD 0.540 194 -508BVFD 0.590 281 -508BSVFD 0.725 356 18 27 24 1812 -516VFD 0.590 224 -516BVFD 0.646 321 -516BSVFD 0.772 401 18 33 29 2410 -308VFD 0.633 308 -308BVFD 0.694 412 -308BSVFD 0.820 497 14 44 38 338 -309VFD 0.764 441 -309BVFD 0.820 565 -309BSVFD 0.988 702 14 56 48 436 -310VFD 0.865 570 -310BVFD 0.925 708 -310BSVFD 1.090 865 12 75 65 584 -312VFD 1.072 886 -312BVFD 1.125 1061 -312BSVFD 1.295 1243 12 99 83 792 -314VFD 1.215 1421 -314BVFD 1.271 1618 -314BSVFD 1.440 1822 10 131 111 1051 -315VFD 1.340 1517 -315BVFD 1.395 1743 -315BSVFD 1.560 1966 10 153 131 121

1/0 -316VFD 1.443 1803 -316BVFD 1.493 2027 -316BSVFD 1.666 2327 10 176 150 1452/0 -317VFD 1.572 2153 -317BVFD 1.622 2399 -317BSVFD 1.854 2840 10 201 173 1664/0 -319VFD 2.053 3463 -319BVFD 2.103 3785 -319BSVFD 2.335 4347 8 270 232 223262 -320VFD 2.193 4175 -320BVFD 2.243 4522 -320BSVFD 2.475 5120 6 315 273 254313 -321VFD 2.370 4727 -321BVFD 2.420 5104 -321BSVFD 2.652 5747 6 344 298 287373 -322VFD 2.501 5415 -322BVFD 2.551 5809 -322BSVFD 2.845 6674 6 387 332 315444 -323VFD 2.670 6707 -323BVFD 2.721 7141 -323BSVFD 3.014 8059 6 440 382 350535 -324VFD 2.972 7483 -324BVFD 3.022 2966 -324BSVFD 3.316 8981 6 498 407 390646 -326VFD 3.164 8916 -326BVFD 3.214 9428 -326BSVFD 3.508 10504 4 553 474 431777 -327VFD 3.388 10395 -327BVFD 3.438 10940 -327BSVFD 3.732 12088 4 602 516 473

*Cable diameters are subject to a +/- 5% manufacturing tolerance

Green InsulatedGrounding Conductor (x3)

andhas a

low capacitance for superior performance in

VFD applications!

Gexol-HFis

flexible 75°C Ratings Based on Table B.310.1

of the 2005 NEC for cables in raceway and a

30°C ambient.

110°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged

in a single bank per hanger. For those instances where cable must be double banked, the 110°C ampacities

should be multiplied by 0.8.

90°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a

single bank per hanger. For those instances where cable must be double banked, the 90°C ampacities

should be multiplied by 0.8.

VFD CableAmpacity Ratings

Unarmored ArmoredArmored &

Sheathed (BS)

Ampacity

See page 2 for Stranding Profile

Oil & Gas Cables

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 39: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

37-449-812 & 37-449-813Gexol-331HF Fire Resistant Public Address/General Alarm CableLow Smoke Halogen-Free Composite • 0.6/1kV • Rated 110°C

v2.08.1 37

Ratings & Approvals� 110˚C Temperature Rating� American Bureau of Shipping (ABS)

99-BT5905-X� UL Listed as Marine Shipboard Cable

(E111461) � Transport Canada (pending)� Det Norske Veritas (DNV)

(pending)� Lloyd’s Register of Shipping (LRS)

(pending)

JacketA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

InsulationFire resistant tape +GEXOL®-HF low smokeHalogen-Free flameretardant cross-linkedpolyolefin, meeting therequirements for Type LSX of IEEE 1580 and Type X110 of UL 1309/CSA 245.

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.

SheathA black low smokeHalogen-Free flameretardant polyolefin,meeting IEEE 1580 and UL 1309/CSA 245.

ArmorBasket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Aluminum or tinnedcopper available by request.

ApplicationExclusively approved by GAI-Tronics for use asthe system cable for their SmartSeries® publicaddress/general alarm systems. GAI-Tronics’microprocessor-based SmartSeries® systems utilize the latest technology in data communications to significantly improve systemintegrity and functionality. It is critical to personnel safety that the public address/generalalarm system continue to function in an emergency fire condition. For this reason,AmerCable has designed these system cables to be rugged, reliable, fire resistant, and basedon its proven Gexol technology.

Features� Fire resistant: IEC 60331.

� Flame retardant: IEC 332-3 Category A and IEEE 1202.

� Low smoke and Halogen-Free.

� High strand count conductors make this product more flexible and easier to install than IEC 60092-350 Series cables.

� Higher temperature rating results in higher ampacity ratings.

� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).

� Suitable for use in Class I, Division 1 andZone 1 environments (armored and sheathed).

Exclusively approved by

Oil & Gas Cables

www. amercable.com • e-mail: [email protected]

Page 40: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

38

37-449-812 & 37-449-813Gexol-331HF Fire Resistant Public Address/General Alarm CableLow Smoke Halogen-Free Composite • 0.6/1kV • Rated 110°C

Oil & Gas Cables

AmerCable P/N 37-449-813

(GAI-Tronics P/N 60029-109)

Armored and Sheathed16 Core

Composite CableConsisting of:

� 6 x 18 AWG twisted pairs,

� 1 x 12 AWG twisted pair,

� 1 x 18 AWG orange conductor,

� 1 x 12 AWG green/yellow conductor

AmerCable P/N 37-449-812

(GAI-Tronics P/N 60029-108)

Armored and Sheathed 16 Core

Composite CableConsisting of:

� 6 x 18 AWG twisted pairs,

� 1 x 14 AWG twisted pair,

� 1 x 18 AWG orange conductor,

� 1 x 14 AWG green/yellow conductor.

Exclusively approved by

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 v.2.06.1

Page 41: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

39

Visit our website at

www.amercable.comfor the location of your nearestauthorized distributor or agent

Page 42: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

The Assembly Application ProfessionalsThe Assembly Application Professionals

CableASSEMBLIESCableASSEMBLIES

Precision Engineered

Turn-key cable assembly solutions for hazardous

and industrial environments

Constructions:� 300V – 15kV AC� DC Power� Composite Power

& Control� Instrumentation� Thermocouple� Fiber Optic� Electro-Optic

Applications:� Service Loops� Driller’s Console� Mud Pump Controls� 15kV Bridle Assembly� Tender-to-Platform Bridle� Ship-to-Shore Power� Portable Power

Generation� Zone 1 (EX) Rated

Cable Assemblies

40

Page 43: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

(800) 506-9473

www.amercablesystems.com

Cable Assemblies from AmerCable Systemssave you time & money!

� Fast Delivery� Job-site application evaluation

and consultation� Highly reliable cable assemblies

custom built and tested to spec

Page 44: Gexol®® Low Smoke Halogen-Free Cables - INTOP ... Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size Conductor AWG/kcmil of Strands (inches) Std. Size (mm2)

AmerCable is an ISO 9001 certified cable manufacturer thatcombines leading-edge manufacturing technology, innovative

thinking, and high quality service to deliver thefinest oil & gas cable products available.

AmerCable serves the world from our Oil & GasGroup headquarters in Houston, Texas. Our

professional field engineers and sales force work with you to create innovative, cost effective project solutions.

What can you expect from AmerCable?� Fastest Lead Times in the Industry

(Standard 6 - 8 weeks / Emergency 2 - 4 weeks)

� On Time Delivery (99%+ avg. in the last 36 months)

� Professional Sales, Support and Service

� Strategic Inventory Locations

AmerCable’s manufacturing facility in El Dorado, Arkansas.

OOiill && GGaass CCaabblleess

2/08© 2008, AmerCable Incorporated

10633 West Little York • Building #1 • Suite #100 • Houston, TX 77041 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 • e-mail: [email protected] • www.amercable.com

Gexol® 125 –

World Class Oil & Gaspower, control and instrumentation Cables

NEK606 –

Premium quality IECPower, control and instrumentation cables

CIR® –

Crush and ImpactResistant cables withoutexternal armoring

Low Smoke Halogen-Free –

Fire resistant and flame retardant cableconstructions

OneWorld –

Meets BOTH IEC andIEEE marine shipboardcable standards

MMVMarine MediumVoltage Cables

Cable Assemblies

Turn-key cable assembly solutions for hazardous and industrialenvironments

VFDVariable Frequency

Drive Cables