31
A brand of the l FP100 ® Performance Standards > 450/750 V and 600/1000 V > BS 6387:1994 Cat C (950±40°C for 180 mins) > BS 6387:1994 Cat W (650±40°C for 30 mins) > BS 6387:1994 Cat Z (950±40°C for 15 mins) > EN 50267-2-2:1999 > EN 61034-2:2005 > IEC 60331-21:1999 > Use in screwed steel conduit to achieve f ire rating > LPCB Approved > Low smoke, zero halogen, flame retardant Core identification o red o brown o black o yellow o orange o grey o blue green/yellow Other core colours available on request Conductor Plain annealed copper stranded (class 2) conductor. Insulation Mineral ceramic (Mica/Glass) fire resistant tape. 90°C high performance cross linked mineral filled insulation. Key Applications > Essential safety circuits where the cable is protected by metal conduit. > May be used for emergency lighting, fire alarm systems not requiring a twisted cable or other essential services. Ref:FP100/12/2017 THE FIRE RESISTANT SOLUTION FOR STEEL CONDUIT Certificate No 077c, 077p CABLE DESCRIPTION Tempreture Range -25 to +90°C Bending Radius up to 8mm diameter r=4D above 9mm diameter r=6D Mechanical impact Requires rotection Fire performance BS EN 60332-1-2 Flexibility Semi-flexible Halogen Free BS EN 50267-2-1 Low Smoke Emissions BS EN 61034-2 Fire Resistant IEC 60331-21 BS 6387 Category CWZ EN50200 PH120*

Upload: donhan

Post on 11-May-2018

235 views

Category:

Documents


5 download

TRANSCRIPT

A brand of the

l

FP100®

Performance Standards

> 450/750 V and 600/1000 V> BS 6387:1994 Cat C (950±40°C for 180 mins)> BS 6387:1994 Cat W (650±40°C for 30 mins)> BS 6387:1994 Cat Z (950±40°C for 15 mins)> EN 50267-2-2:1999> EN 61034-2:2005> IEC 60331-21:1999> Use in screwed steel conduit to achieve f ire rating> LPCB Approved> Low smoke, zero halogen, flame retardant

Core identification o red o brown o black o yellow o orangeo grey o blue green/yellow

Other core colours available on request

Conductor Plain annealed copper stranded (class 2) conductor.

InsulationMineral ceramic (Mica/Glass) fire resistant tape. 90°C high performance cross linked mineral filled insulation.

Key Applications > Essential safety circuits where the cable is protected by metal conduit.> May be used for emergency lighting, fire alarm systems not requiring a twisted cable or other essential services.

Ref

:FP1

00/1

2/20

17

THE FIRE RESISTANT SOLUTION FOR STEEL CONDUIT

Certificate No 077c, 077p

CABLE DESCRIPTION

FIRE RESISTANT CABLES LOW VOLTAGE

600/1000 V *

FP100®

Temperature Range-25 to +90ºC≠

Bending Radiusup to 8mm diameter r=4D above 8mm diameter r=6D

Mechanical impactRequires protection

Fire PerformanceBSEN60332-1-2

FlexibilitySemi-flexible

Halogen FreeBSEN50267-2-1

Low Smoke EmissionsBSEN61034-2

Fire ResistantIEC 60331-21

BS6387 Category CW Z*EN50200 PH120*BS8434-2 120min**W hen tested in Steel Conduit

Tempreture Range-25 to +90°C

Bending Radiusup to 8mm diameter r=4Dabove 9mm diameter r=6D

Mechanical impactRequires rotection

Fire performanceBS EN 60332-1-2

FlexibilitySemi-flexible

Halogen FreeBS EN 50267-2-1

Low Smoke EmissionsBS EN 61034-2

Fire ResistantIEC 60331-21

BS 6387 Category CWZEN50200 PH120*

> * Sizes 1.5 - 10mm2 are rated at 450/750V.> Installation methods for current rating “Enclosed in conduit on a wall or in trunking” in accordance with BS7671/IEE Wiring Regulations. > Minimum recommended installation temperature -5°C.> The tabulated ratings are based upon a 30°C ambient temperature at 90°C operating temperature.> For other ambient temperatures or where several circuits are grouped together, the following rating factors should be applied.

Notes to table

Temperature ratings factor

Rating Factors for Groupings

Overseas sales enquiriesTel: +44 (0) 23 8029 5481Fax: +44 (0) 23 8029 5465

Overseas technicalTel: +44 (0) 23 8029 5481Fax: +44 (0) 23 8029 5002

Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 5437

Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465

UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002

Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireSO50 6YUUnited Kingdomwww.prysmiangroup.co.uk

Ref

: FP1

00/1

2/20

17For further information pleasesee our dedicated FP Cables website:www.fpcables.co.uk

A brand of the

Nominal cross

sectional area

mm2

Approximate cable

weight

kg/km

Maximum conductor resistance

at 20°C

Ω/km

Current rating

DC or single phase AC

Amps

Current rating Three

phase AC

Amps

Volt drop DC

mV/A/m

Approximate overall

diameter

mm

Short circuit rating(1 sec)

Amps

Volt drop Single

phase AC

mV/A/m

Volt drop Three

phase AC

mV/A/m

Single Core1 .5* 3.5 26 12.1 215 23 20 31 31 27

2.5* 4.1 38 7.41 360 31 28 19 19 16

4* 4.6 54 4.61 570 42 37 12 12 10

6* 5.2 75 3.08 860 54 48 7.9 7.9 6.8

10* 6.6 120 1.83 1425 75 66 4.7 4.7 4

16 7.7 180 1.15 2275 100 88 2.9 2.9 2.5

25 9.0 270 0.727 3375 133 117 1.85 1.9 1.65

35 10.0 360 0.524 5000 164 144 1.35 1.35 1.15

50 11.7 490 0.387 7150 198 175 0.99 1.05 0.9

70 13.2 680 0.268 10000 253 222 0.68 0.75 0.65

95 15.3 940 0.193 13575 306 269 0.49 0.58 0.5

120 16.8 1160 0.153 17150 354 312 0.39 0.48 0.42

150 18.7 1440 0.124 21450 393 342 0.32 0.43 0.37

185 20.8 1800 0.0991 26450 449 384 0.25 0.37 0.32

240 23.5 2350 0.0754 34325 528 450 0.19 0.33 0.29

300 27.3 3000 0.0601 42925 603 514 0.155 0.31 0.27

400 32.5 3970 0.0470 57225 683 584 0.120 0.29 0.25

500 36.0 4980 0.0366 71525 783 666 0.093 0.28 0.24

630 40.0 6340 0.0283 90125 900 764 0.072 0.27 0.23

Ambient Temperature°C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Number of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

3rd

June, 2009

TO WHOM IT MAY CONCERN

Dear Customers,

Approval for Single Core Fire Resistant Cable – BS6387 C,W,Z

(FP100, FP300)

This letter is to advise you that our single core fire resistant cable, FP100 (insulated only)

and FP300 (insulated and sheathed) is accredited to BS6387 C,W,Z with LPCB certificate

077c and 077e respectively. This is also recognised by the Hong Kong Fire Services

Department.

Since single core fire resistant cable is not published with BS standard, both FP100 and

FP300 could not be type tested with BASEC. Therefore, there is no BASEC product

certificate available for single core fire resistant cable.

Both of the FP100 and FP300 are under the guarantee policy of Prysmian.

Yours sincerely,

Stephen Lam

Area Manager

Prysmian Hong Kong Holding Limited

Room 1010-11, Lu Plaza T (852) 2311 1554

2 Wing Yip Street F (852) 2366 1227

Kwun Tong

HONG KONG

BF1345 Rev. 0.2 Page 1 of 3 © BRE Global Ltd, 2014

This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).

To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.

LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

Certificate of Product Approval Certificate Number: 077p Issue: 04

PRYSMIAN CABLE & SYSTEMS LIMITED

Chickenhall Lane Bishopstoke Eastleigh Hants SO50 6YU United Kingdom

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix having complied with the requirements of the standard(s) detailed below:

Product(s) Standard(s) (see Appendix for details) Cable Types as listed below: FP100 LSOH

See Certificate Appendix for details

BS 6387:2013 (Category CWZ) EN 50267-2-1:1999 EN 61034-2:2005 IEC 60331-21:1999

BF1345 Rev. 0.2 Page 2 of 3 © BRE Global Ltd, 2014

Appendix to Certificate No: 077p Issue: 04 PRYSMIAN CABLE & SYSTEMS LIMITED

This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).

To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.

LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

Product name LPCB Ref. No.

FP100 LSOH 077p/01

Nominal csa of conductor (mm2) Core Construction BS 6387 EN 50267-2-1 EN 61034-2 IEC 60331-21

1.5 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

2.5 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

4.0 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

6.0 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

10 One(1) C,W,Z(2,3) <0.5% HCI >60% Complies(4)

Uo/U 600/1000 V

Notes: 1. Stranded conductor only. 2. Where a single cable is fitted in a conduit, only phase to earth voltage was applied. 3. To satisfy the requirements of BS 6387:2013, for Categories C,W,Z testing was conducted using a 20mm

stainless steel conduit as the other metallic element. 4. The FP100 LSOH cables met the requirements of IEC 60331-21:1999 when tested at a temperature of 950ºC

for a duration of 90mins + 15mins cool down, at a voltage rating of 600V.

Cross-Listed products and alternative branding are detailed on page 3.

BF1345 Rev. 0.2 Page 3 of 3 © BRE Global Ltd, 2014

Appendix to Certificate No: 077p Issue: 04 PRYSMIAN CABLE & SYSTEMS LIMITED

This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.

David Hoare 16 September 2014 13 May 2013 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue

This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).

To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.

LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]

LPCB Ref No. Model No. Alternative Model No. Labelled Distributors Cert/Ref No.

077p/01 FP100 LSOH

1.5mm2 - 10mm2

FT SIFER 950i OHLS

1.5mm2 - 10mm2 Draka UK Ltd 1134g/01

TO WHOM IT MAY CONCERN For FP100 077p issue we received the response letter by FSD, we could use on-line certificate to convince FSD officer.     http://www.redbooklive.com/search/displaycompany.jsp?sectiontype=1&companyid=352&productgroupid=3074&sectionid=24&searchgrouptypeid=13&searchgroupid=0&id=677