flat spray sprinkler
TRANSCRIPT
-
7/30/2019 Flat Spray Sprinkler
1/10
GeneralDescriptionThe Model TY-FRFS, TY-FS Special,and TY-FS, Upright and Pendent, Flat
Spray Sprinklers described in this datasheet are intended for installation inaccordance with CEA 4001 SprinklerSystems Planning and Installation orEN12845 Automatic Sprinkler Sys-tems - Design, Installation and Mainte-nance, as applicable. They produce aflatter spray pattern than standardspray sprinklers enabling them to beused with lower clearance above thesuspended open ceilings and in racks.
As necessary the 80K and 115K, FlatSpray Sprinklers may be outfitted withguards, shie lds, or guards wi thshields. The guards may be used inareas that make thesprinklers suscep-tible to mechanical or physical dam-age, whereas the shields may be usedto help prevent the sprinklers from be-ing wetted (cold soldered) from waterspray of higher elevation sprinklers.Table A provides a detailed matrix ofthe allowable combinations.
The Model TY-FRFS with its 3 mmdiameter heat sensitive bulb elementis rated quick response, the Model TY-FS Special with its 4 mm diameter heatsensitive bulb element is rated specialresponse, and the Model TY-FS withits 5 mm diameter heat sensitive bulb
element is rated standard responseA.
CEA 4001 Sprinkler Systems Plan-ning and Installation and EN12845Automatic Sprinkler Systems - De-sign, Installation and Maintenance
permits flat spray sprinklers to be usedin concealed spaces, suspended openceilings, and in racks.
WARNINGSModel TY-FRFS, TY-FS Special, andT Y- FS S pr in kl er s, a s w el l a s guard/shield accessories, describedherein must be installed and main-tained in compliance with this docu-ment, as well as with the applicablestandards recognized by the Approvalagency, in addition to the standards ofany other authorities having jurisdic-tion. Failure to do so may impair theperformance of these devices.
The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.
Model TY-FRFS
Model TY-FS Special
Model TY-FS
Model TY-FRFS, TY-FS Special, and TY-FSFlat Spray Sprinkle rs, Guards, a nd ShieldsUpright a nd Pendent 57 , 80 , and 1 15 K-factor
Pa ge 1 of 1 0 T FP6 3 5M A Y , 2 0 0 6
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
IMPORTANTAlways refer t o Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.
-
7/30/2019 Flat Spray Sprinkler
2/10
Model/SprinklerIdentificationNumbersModel FRFS (3 mm Bulb)TY1136 - Upright 57KTY1236 - Pendent 57KTY3136 - Upright 80KTY3236 - Pendent 80KTY4136 - Upright 115K
TY4236- Pendent 115KModel FS Special (4 mm Bulb)TY1146 - Upright 57KTY1246 - Pendent 57KTY3146 - Upright 80KTY3246 - Pendent 80KTY4146 - Upright 115KTY4246- Pendent 115K
Model FS (5 mm Bulb)TY1156 - Upright 57KTY1256 - Pendent 57KTY3156 - Upright 80KTY3256 - Pendent 80KTY4156 - Upright 115KTY4256- Pendent 115K
OperationThe glass bulb contains a fluid whichexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass bulb, allowing the sprinkler toactivate and water to flow.
Technical DataApprovalsThe Flat Spay Sprinklers are VdS Ap-proved for installation per CEA 4001Sprinkler Systems Planning and In-stallation or EN12845 AutomaticSprinkler Systems - Design, Installa-tion and Maintenance.
The Guards, Shields, and Guards withShields are VdS Approved with thecombinations of product shown in Ta-ble A.
For details contact Tyco Fire & Build-ing Products, Enschede, Netherlands:Tel. 31-53-428-4444Fax 31-53-428-3377
Maximum Working Pressure12,1 bar
Discharge CoefficientK = 57 LPM/bar1/2
K = 80 LPM/bar1/2
K = 115 LPM/bar1/2
Temperature Ratings in C57, 68, 79, 93, and 141
FinishesSprinklers: Natural BrassGuards: Red Painted / Zinc ChromateShields: Zinc Chromate
Physical CharacteristicsFrame . . . . . . . . . . . . . BronzeButton . . . . . . . . . . . . CopperSealing Assembly . . . . . . . . . . .. . . . . . Beryllium Nickel w/Teflon*
Bulb . . . . . . . . . . . . . . GlassCompression Screw . . . . . BronzeDeflector . . . . . . . . . . . Copper
Guard . . . . Welded Carbon steelShield . . . . . . . . . Carbon SteelShield Spring . . . . . Carbon Steel
* Registered trademark of DuPont
DesignCriteriaThe Model TY-FRFS, TY-FS Special,
and TY-FS Flat Spray Sprinklers areonly intended for installation per CEA4001 Sprinkler Systems Planning andInstallation or EN12845 AutomaticSprinkler Systems - Design, Installa-t ion and Maintenance where flatspray sprinklers are permitted.
NOTEIn all cases, CEA 4001 Sprinkler Sys-tems Planning and Installation orEN12845 Automatic Sprinkler Sys-tems - Design, Installation and Mainte-nance must be referenced and fol-l ow ed t o e ns ur e a n e ffe ct iv e installation. The Flat Spay Sprinklers
have significantly different water distri-bution characteristics from that of con-ventional and spray pattern sprinklersthat has enabled the Flat Spray Sprin-klers to be used in conformance withCEA 4001 Sprinkler Systems Plan-ning and Installation or EN12845Automatic Sprinkler Systems - De-sign, Installation and Maintenance.
P a g e 2 o f 1 0 TFP6 3 5
TABLE A
ALLOWABLE COMBINATIONS OF GUARDS, SHIELDS, AND GUARDS WITH SHIELDS
Series Bulb Size Orifice Position SIN Guard Shield Guard/Shield
TY-FRFS 3 mm TY1136 N/A N/A N/A
TY-FS Special 4 mm TY1146 N/A N/A N/A
TY-FS 5 mm TY1156 N/A N/A N/A
TY-FRFS 3 mm TY1236 N/A N/A N/A
TY-FS Special 4 mm TY1246 N/A N/A N/A
TY-FS 5 mm TY1256 N/A N/A N/ATY-FRFS 3 mm TY3136 G1 N/A N/A
TY-FS Special 4 mm TY3146 G1 N/A N/A
TY-FS 5 mm TY3156 G1 N/A N/A
TY-FRFS 3 mm TY3236 G1 H1or H2 G1/H1 or G1/H2
TY-FS Special 4 mm TY3246 G1 H1or H2 G1/H1 or G1/H2
TY-FS 5 mm TY3256 G1 H1or H2 G1/H1 or G1/H2
TY-FRFS 3 mm TY4136 G1 N/A N/A
TY-FS Special 4 mm TY4146 G1 N/A N/A
TY-FS 5 mm TY4156 G1 N/A N/A
TY-FRFS 3 mm TY4236 G1 H1 or H2 G1/H1 or G1/H2
TY-FS Special 4 mm TY4246 G1 H1 or H2 G1/H1 or G1/H2
TY-FS 5 mm TY4256 G1 H1 or H2 G1/H1 or G1/H2
115K, 20 mm
Upright
Pendent
Pendent
57K, 10 mm
80K, 15 mm
Upright
Upright
Pendent
-
7/30/2019 Flat Spray Sprinkler
3/10
TFP6 3 5 P a g e 3 o f 1 0
FIGURE 1
57 K-FACTOR, ISO 7/1-R 3/8UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS
FIGURE 280 K-FACTOR, 1/2 INCH NPT
UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS
Components:
55 mm
MAKE-INNOMINAL
10 mm
WRENCHFLATS
UPRIGHT
MAKE-INNOMINAL
PENDENT
40 mm
55 mm
10 mm
*CROSS SECTION
2
6
45
3
1
*
Frame
Button
Bulb (See table above)Compression Screw
Deflector
Sealing Assembly--
-
--
- *2
1
3
5
4
6
Temperature rating is indicated onDeflector or adjacent to orifice seat
*
on frame.
*DEFLECTOR
DEFLECTOR
BULB
SIZEMODEL
SIN
UPRIGHT
TY11363 mmTY-FRFS
TY-FS SPECIAL 4 mm TY1146
TY-FS 5 mm TY1156
PENDENT
TY1236
TY1256
TY1246
7/1-R 3/8
ISO
7/1-R 3/8
ISO
Components:
57 mm
MAKE-INNOMINAL
11 mm
WRENCHFLATS
UPRIGHT
MAKE-INNOMINAL
PENDENT
40 mm
57 mm
11 mm
*CROSS SECTION
2
6
45
3
1
*
Frame
Button
Bulb (See table above)Compression ScrewDeflector
Sealing Assembly-
-
---
-
*
2
1
3
5
4
6
THREADRELIEF
Temperature rating is indicated onDeflector or adjacent to orifice seat
*can be provided on special request.Pipe thread connections per ISO 7/1**
on frame.
*DEFLECTORPLATE SEATINGESCUTCHEON
SURFACE
SHIELD AND
1/2" NPT
DEFLECTOR1/2" NPT **
**
BULB
SIZEMODEL
SIN
UPRIGHT
TY31363 mmTY-FRFS
TY-FS SPECIAL 4 mm TY3146
TY-FS 5 mm TY3156
PENDENT
TY3256
TY3246
TY3236
-
7/30/2019 Flat Spray Sprinkler
4/10
P a g e 4 o f 1 0 TFP6 3 5
FIGURE 3
115 K-FACTOR, 3/4 INCH NPTUPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS
FIGURE 4MODEL G1 GUARD
TYPICAL INSTALLATION ON UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS
Components:
60 mm
MAKE-IN
NOMINAL13 mm
WRENCHFLATS
UPRIGHT
MAKE-INNOMINAL
PENDENT
46 mm
60 mm
13 mm
*CROSS SECTION
BULBSIZE
MODELSIN
UPRIGHT
TY41363 mmTY-FRFS
TY-FS SPECIAL 4 mm TY4146
TY-FS 5 mm TY4156
PENDENT
TY4256
TY4246
TY4236
2
6
45
3
1
*
Frame
ButtonBulb (See table above)Compression ScrewDeflector
Sealing Assembly--
---
- *2
1
3
5
4
6
THREADRELIEF
Temperature rating is indicated onDeflector or adjacent to orifice seat
*can be provided on special request.Pipe thread connections per ISO 7/1**
on frame.
*DEFLECTORPLATE SEATINGESCUTCHEON
SURFACE
SHIELD AND
3/4" NPT
DEFLECTOR3/4" NPT **
**
73 mm DIA.
60 mm
UPRIGHT
BAR
(ENGAGED)GUARD CLIP
SPRINKLER
GUARD
MODEL G1
PLATE
THREAD RELIEF
PENDENT
BASE
PENDENT
SPRINKLER
FLAT SPRAY
UPRIGHT or
15 or 20 mm
ENGAGED BY
BASE PLATE
-
7/30/2019 Flat Spray Sprinkler
5/10
TFP6 3 5 P a g e 5 o f 1 0
FIGURE 5K80 PENDENT FLAT SPRAY SPRINKLERS
WITHMODEL H1 SHIELD
ORMODEL H1 SHIELD AND MODEL G1 GUARD
GUARD
MODEL G1
SHIELD
MODEL H1
SEATING
SHIELD
SURFACE
8 mm
100 mm DIA.
FLAT SPRAY
SPRINKLER
PENDENT15 mm
SHIELDMODEL H1
SURFACE
SEATING
SHIELD
ATTACHMENT
SPRING
15 mm
FLAT SPRAY
SPRINKLER
PENDENT
FIGURE 6K80 PENDENT FLAT SPRAY SPRINKLERSWITH
MODEL H2 SHIELDOR
MODEL H2 SHIELD AND MODEL G1 GUARD
FLAT SPRAYSPRINKLER
GUARDMODEL G1
SHIELDMODEL H2
PENDENT
SEATING
SHIELD
SURFACE
15 mmPENDENT
SPRINKLERFLAT SPRAY
15 mmMODEL H2SHIELD
160 mm DIA.
32 mm
SEATING
SHIELD
SURFACEATTACHMENTSPRING
-
7/30/2019 Flat Spray Sprinkler
6/10
P a g e 6 o f 1 0 TFP6 3 5
FIGURE 7K115 PENDENT FLAT SPRAY SPRINKLERS
WITHMODEL H1 SHIELD
ORMODEL H1 SHIELD AND MODEL G1 GUARD
SEATING
SHIELD
SURFACEATTACHMENT
SPRING
8 mm
SURFACE
SEATING
SHIELD
ATTACHMENT
SPRING
GUARD
MODEL G1
SHIELD
MODEL H1
FLAT SPRAY
SPRINKLER
PENDENT
20 mm
SHIELD
MODEL H1
20 mm
FLAT SPRAY
SPRINKLER
PENDENT
100 mm DIA.
FIGURE 8K115 PENDENT FLAT SPRAY SPRINKLERS
WITHMODEL H2 SHIELD
ORMODEL H2 SHIELD AND MODEL G1 GUARD
160 mm DIA.
32 mm
SEATINGSHIELD
SURFACEATTACHMENTSPRING
FLAT SPRAYSPRINKLER
GUARDMODEL G1
SHIELDMODEL H2
PENDENT
SEATINGSHIELD
SURFACEATTACHMENTSPRING
20 mmPENDENT
20 mm
SPRINKLERFLAT SPRAY
MODEL H2SHIELD
-
7/30/2019 Flat Spray Sprinkler
7/10
InstallationInstallation instructions are provided inthe following subsections:
Sprinkler Only
Sprinkler With Guard
Sprinkler With Shield
Sprinklers With Guard & Shield
SPRINKLER ONLY
The Model TY-FRFS, TY-FS Special,and TY-FS Sprinklers must be in-stalled in accordance with the follow-ing instructions:
NOTESDo not install any bulb type sprinkler ifthe bulb is cracked or there is a loss ofliquid from the bulb. With the sprinklerheld horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135F/57C to 3/32inch (2,4 mm) for the 360F/182Ctemperature ratings.
A leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. A leak tight 3/4inch NPT sprinkler joint should be ob-tained with a torque of 10 to 20 ft.lbs.(13,4 to 26,8 Nm). A maximum of 30ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-nections. Higher levels of torque maydistort the sprinkler inlet and causeleakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-cient adjustment in the escutcheonplate by under- or over-tightening thesprinkler. Readjust the position of thesprinkler fitting to suit.
Step 1. Pendent sprinklers are to beinstalled in the pendent position, andupright sprinklers are to be installed inthe upright position.
Step 2. With pipe thread sealant ap-plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into thesprinkler fitting using only the W-Type6 Sprinkler Wrench (Ref. Figure 10).With reference to Figures 1, 2, and 3the W-Type 6 Sprinkler Wrench is tobe applied to the wrench flats.
SPRINKLER WITH GUARD
With reference to Figure 4, the ModelG1 Guard must be installed as follows:
S t e p 1 . The G1 Guard i s to be
mounted on the sprinkler after thesprinkler has been installed in accord-ance with the Sprinklers Only sub-section.
Step 2. With the Clips loose, firstspread the two halves of the SprinklerGuard just enough to pass by thesprinkler deflector from the side. Then,once again spread the two halves ofthe Sprinkler Guard just enough topass over the sprinkler thread reliefportion of the sprinkler. (Refer to Fig-ures 2 and 3.)
Step 3. With the Sprinkler Guard posi-tioned on the thread relief portion ofthe sprinkler, as applicable, engagethe Clips and then slide the Clips untilthey seat against the Base to completethe installation as shown in Figure 4.
To help assist with the sliding of theClips, the Guard Installation Tool maybe used as shown in Figure 9. In addi-
tion, pliers can be used to facilitate thefinal seating of he Clips.
NOTESThe Clips must seat against the Basein order to be considered fully seated
and in order to complete the installa-tion.
The G1 may be located in any positionrelative to the sprinkler frame arms.
SPRINKLER WITH SHIELD
With reference to Figures 5, 6, 7, or 8,the Model H1 or Model H2 Shield mustbe installed as follows:
Step 1. Pendent sprinklers are to beinstalled in the pendent position.
Step 2. With pipe thread sealant ap-
FIGURE 9MODEL G-1 GUARD INSTALLATION PROCEDURE
WITH INSTALLATION TOOL APPLIED OVER
TOWARD BASE PLATES UNTIL FULLY ENGAGED
ADJACENT BARS, PRESS SECOND CLIP
SWIVEL CLIPS OVER
INSTALLED, CAREFULLY
AND FIT ONTO SPRINKLER
TOWARD BASE PLATES
ADJACENT BARS AND SLIDE
SPREAD BASE PLATES APART
PLATESBASE
FIRST
CLIP INSTALLATIONTOOL (SHIPPED WITH
GUARDS)
CLIP FULLYENGAGED
SLOTBAR
CLIP FULLYENGAGED
SECOND
A PLIER
USEDMAY BE
INSTALLATIONTOOL
CLIP
CLIP
TOOLINSTALLATION
CLIP
CLIP
WITH SPRINKLER PROPERLY
THREAD RELIEF
UNTIL SNUG
MODEL G1GUARD
FLAT SPRAYSPRINKLER
FIGURE 10W-TYPE 6 SPRINKLER
WRENCH
WRENCH RECESS(END "A" USED FOR
ISO 7/1-R 3/8 &
WRENCH RECESS(END "B" USED FOR
3/4" NPT MODELS)
1/2" NPT MODELS)
FIGURE 11W-TYPE 7 SPRINKLER
WRENCH
RECESSWRENCH
WITH SPRINKLERENGAGEMENTIN TO ENSURE
WRENCHINGAREA
PUSH WRENCH
TFP6 3 5 P a g e 7 o f 1 0
-
7/30/2019 Flat Spray Sprinkler
8/10
plied to the pipe threads, install theShield over the sprinkler threads.
Step 3. Install the Attachment Springover the sprinkler threads until it seatsagainst the Shield.
Step 4. Hand tighten the sprinkler intothe sprinkler fitting.
Step 5. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Sprinkler Wrench (Ref. Figure 11).The wrench is to be applied to thesprinkler wrenching area shown in Fig-ures 2 or 3, as applicable.
NOTEWhen installed correctly, the Attach-ment Spring wi l l be sl ightly com-pressed and the Shield will be heldfirmly in place.
SPRINKL ER WIT H GUARD ANDSHIELD
With reference to Figures 5, 6, 7 or 8,the guard with shield arrangementmust be installed as follows:
Step 1. Pendent sprinklers are to beinstalled in the pendent position.
Step 2. With pipe thread sealant ap-plied to the pipe threads, install theShield over the sprinkler threads.
Step 3. When installing K115 Sprin-klers, Install the Attachment Springover the sprinkler threads until it seatsagainst the Shield.
NOTE
An Attachment Spring is not utilized forK80 Sprinklers with Guard and Shield.
Step 4. Hand tighten the sprinkler intothe sprinkler fitting.
Step 5. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Sprinkler Wrench (Ref. Figure 11).The wrench is to be applied to thesprinkler wrenching area shown in Fig-ures 2 or 3, as applicable.
Step 7. After the sprinkler with shieldis installed into the sprinker pipe fitting,install the guard as described in theSprinkler With Guard sub-section.
Care andMaintenanceThe Model TY-FRFS, TY-FS Special,and TY-FS Sprinklers must be main-tained and serviced in accordance
with the following instructions:
NOTESBefore closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shutdown theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.
Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwisealtered after leaving the factory. Modi-f ied sprinklers must be replaced.Sprinklers that have been exposed tocorrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.
Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed.Also, replace anysprinkler thathas a cracked bulb or that has lostliquid from its bulb. (Ref. InstallationSection).
Proper installation of sprinklers in-stalled with guards, shields, or guardswith shields should be verified duringthe annual visual inspection of thesprinklers.
The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the Approval agency andstandards of any other authorities hav-ing jurisdiction. The installing contrac-tor or sprinkler manufacturershouldbecontacted relative to any questions.
It is recommended that automaticsprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.
LimitedWarrantyProducts manufactured by Tyco Fire &Building Products (TFBP) are war-ranted solely to the original Buyer for
ten (10) years against defects in mate-rial and workmanship when paid forand properly installed and maintainedunder normal use and service. Thiswarranty will expire ten (10) yearsfrom date of shipment by TFBP. Nowarranty is given for products or com-ponents manufactured by companiesnot affiliated by ownership with TFBPor for products and components whichhavebeen subjectto misuse, improperinstallation, corrosion, or which havenot been installed, maintained, modi-fied or repaired in accordance with thestandards recognized by the Approvalagency, as well as the standards of
any other Authorities Having Jurisdic-tion. Materials found by TFBP to bedefective shall be either repaired orreplaced, at TFBPs sole option. TFBPneither assumes, nor authorizes anyperson to assume for it, any other ob-ligation in connection with the sale ofproducts or parts of products. TFBPshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyers representatives.
In no event shall TFBP be liable, incontract, tort, strict liability or underany other legal theory, for incidental,indirect, special or consequential dam-ages, including but not limited to laborcharges, regardless of whether TFBPwas informed about the possibility ofsuch damages, and in no event shallTFBPs liability exceed an amountequal to the sales price.
The foregoing warranty is made in lieuof any and all other warranties, ex-press or implied, including warrantiesof merchantability and fitness for aparticular purpose.
This limited warranty sets forth the ex-clusive remedy for claims based onfailure of or defect in products, materi-als or components, whether the claimis made in contract, tort, strict liabilityor any other legal theory.
This warranty will apply to the full ex-tent permitted by law. The invalidity, inwhole or part, of any portion of thiswarranty will not affect the remainder.
P a g e 8 o f 1 0 TFP6 3 5
-
7/30/2019 Flat Spray Sprinkler
9/10
OrderingProcedureWhen placing an order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.
NOTESprinklers, wrenches, guards, shields,attachment springs, and additional clipinstallation tool are all sold separately
Contact your local distributor for avail-ability.
Sprinklers:Specify: (Specify Model/SIN), (SpecifyStandard Response, Special Re-sponse, or Quick Response, (specifyK-factor), (specify temperature rating),(specify Pendent or Upright) Sprinkler,P/N (specify from Table A).
Sprinkler Wrenches:Specify: W-Type (specify) SprinklerWrench, P/N (specify).
W-6. . . . . . . . . . . . . . . . . . . . . P/N 56-000-6-387W-7. . . . . . . . . . . . . . . . . . . . . P/N 56-850-4-001
Guards:Specify: Model G-1 Guard having
(specify) finish, P/N (specify).
Red Painted . . . . . . . . . . . . . . P/N 56-000-6-387Zinc Chromate . . . . . . . . . . . . P/N 56-850-4-001
Shields:Specify: Model (specify), (specify NPTsize) Shield , P/N (specify).
H1, 1/2" NPT . . . . . . . . . . . . . P/N 22521H1, 3/4" NPT . . . . . . . . . . . . . P/N 22522H2, 1/2" NPT . . . . . . . . . . . . . P/N 22529H2, 3/4" NPT . . . . . . . . . . . . . P/N 22524
Attachment Springs:Specify: (specify NPT size) ShieldSpring, P/N (specify).
1/2" NPT . . . . . . . . . . . . . . . . . P/N 225263/4" NPT . . . . . . . . . . . . . . . . . P/N 22527
Additional* Clip Installation Tools:specify: Clip Installation Tool for G1
Guard, P/N 56-000-8-597.
* The Clip Installation Tool is includedwith guard orders in original cartons.
P/N 51 XXX 1 XXX
68C (Red)155
TEMPERATURE
RATING
(Fluid Color)
57C (Orange)1351
SPRINKLER
MATERIAL
TABLE APART NUMBER SELECTIONFLAT SPRAY SPRINKLERS
79C (Yellow)
286
93C (Green)200
141C (Blue)
175
NATURAL BRASS
MODEL/SIN
391 115K PENDENT, 3/4 INCH NPT
382 57K PENDENT, ISO 7/1-R 3/8
370 80K UPRIGHT, 1/2 INCH NPT
TY-FRFS/TY1236
TY-FRFS/TY3136
TY-FRFS/TY4236
371
390
80K PENDENT, 1/2 INCH NPT
115K UPRIGHT, 3/4 INCH NPT
TY-FRFS/TY3236
TY-FRFS/TY4136
482 57K PENDENT, ISO 7/1-R 3/8TY-FS Special/TY1246
470 80K UPRIGHT, 1/2 INCH NPTTY-FS Special/TY3146
471 80K PENDENT, 1/2 INCH NPTTY-FS Special/TY3246
490 115K UPRIGHT, 3/4 INCH NPTTY-FS Special/TY4146
491 115K PENDENT, 3/4 INCH NPTTY-FS Special/TY4246
582 57K PENDENT, ISO 7/1-R 3/8TY-FS/TY1256
570 80K UPRIGHT, 1/2 INCH NPTTY-FS/TY3156
571 80K PENDENT, 1/2 INCH NPTTY-FS/TY3256
590 115K UPRIGHT, 3/4 INCH NPTTY-FS/TY4156
591 115K PENDENT, 3/4 INCH NPTTY-FS/TY4256
380 TY-FRFS/TY1136 57K UPRIGHT, ISO 7/1-R 3/8
480 TY-FS Special/TY1146 57K UPRIGHT, ISO 7/1-R 3/8
580 TY-FS/TY1156 57K UPRIGHT, ISO 7/1-R 3/8
TFP6 3 5 P a g e 9 o f 1 0
-