  • 7/30/2019 Flat Spray Sprinkler

    1/10

    GeneralDescriptionThe Model TY-FRFS, TY-FS Special,and TY-FS, Upright and Pendent, Flat

    Spray Sprinklers described in this datasheet are intended for installation inaccordance with CEA 4001 SprinklerSystems Planning and Installation orEN12845 Automatic Sprinkler Sys-tems - Design, Installation and Mainte-nance, as applicable. They produce aflatter spray pattern than standardspray sprinklers enabling them to beused with lower clearance above thesuspended open ceilings and in racks.

    As necessary the 80K and 115K, FlatSpray Sprinklers may be outfitted withguards, shie lds, or guards wi thshields. The guards may be used inareas that make thesprinklers suscep-tible to mechanical or physical dam-age, whereas the shields may be usedto help prevent the sprinklers from be-ing wetted (cold soldered) from waterspray of higher elevation sprinklers.Table A provides a detailed matrix ofthe allowable combinations.

    The Model TY-FRFS with its 3 mmdiameter heat sensitive bulb elementis rated quick response, the Model TY-FS Special with its 4 mm diameter heatsensitive bulb element is rated specialresponse, and the Model TY-FS withits 5 mm diameter heat sensitive bulb

    element is rated standard responseA.

    CEA 4001 Sprinkler Systems Plan-ning and Installation and EN12845Automatic Sprinkler Systems - De-sign, Installation and Maintenance

    permits flat spray sprinklers to be usedin concealed spaces, suspended openceilings, and in racks.

    WARNINGSModel TY-FRFS, TY-FS Special, andT Y- FS S pr in kl er s, a s w el l a s guard/shield accessories, describedherein must be installed and main-tained in compliance with this docu-ment, as well as with the applicablestandards recognized by the Approvalagency, in addition to the standards ofany other authorities having jurisdic-tion. Failure to do so may impair theperformance of these devices.

    The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or sprinklermanufacturer should be contactedwith any questions.

    Model TY-FRFS

    Model TY-FS Special

    Model TY-FS

    Model TY-FRFS, TY-FS Special, and TY-FSFlat Spray Sprinkle rs, Guards, a nd ShieldsUpright a nd Pendent 57 , 80 , and 1 15 K-factor

    Pa ge 1 of 1 0 T FP6 3 5M A Y , 2 0 0 6

    Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

    IMPORTANTAlways refer t o Technical DataSheet TFP700 for the INSTALLERWARNING that provides cautionswith respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damagea sprinkler system or its compo-nents and cause the sprinkler to failto operate in a fire situation or causeit to operate prematurely.

  • 7/30/2019 Flat Spray Sprinkler

    2/10

    Model/SprinklerIdentificationNumbersModel FRFS (3 mm Bulb)TY1136 - Upright 57KTY1236 - Pendent 57KTY3136 - Upright 80KTY3236 - Pendent 80KTY4136 - Upright 115K

    TY4236- Pendent 115KModel FS Special (4 mm Bulb)TY1146 - Upright 57KTY1246 - Pendent 57KTY3146 - Upright 80KTY3246 - Pendent 80KTY4146 - Upright 115KTY4246- Pendent 115K

    Model FS (5 mm Bulb)TY1156 - Upright 57KTY1256 - Pendent 57KTY3156 - Upright 80KTY3256 - Pendent 80KTY4156 - Upright 115KTY4256- Pendent 115K

    OperationThe glass bulb contains a fluid whichexpands when exposed to heat. Whenthe rated temperature is reached, thefluid expands sufficiently to shatter theglass bulb, allowing the sprinkler toactivate and water to flow.

    Technical DataApprovalsThe Flat Spay Sprinklers are VdS Ap-proved for installation per CEA 4001Sprinkler Systems Planning and In-stallation or EN12845 AutomaticSprinkler Systems - Design, Installa-tion and Maintenance.

    The Guards, Shields, and Guards withShields are VdS Approved with thecombinations of product shown in Ta-ble A.

    For details contact Tyco Fire & Build-ing Products, Enschede, Netherlands:Tel. 31-53-428-4444Fax 31-53-428-3377

    Maximum Working Pressure12,1 bar

    Discharge CoefficientK = 57 LPM/bar1/2

    K = 80 LPM/bar1/2

    K = 115 LPM/bar1/2

    Temperature Ratings in C57, 68, 79, 93, and 141

    FinishesSprinklers: Natural BrassGuards: Red Painted / Zinc ChromateShields: Zinc Chromate

    Physical CharacteristicsFrame . . . . . . . . . . . . . BronzeButton . . . . . . . . . . . . CopperSealing Assembly . . . . . . . . . . .. . . . . . Beryllium Nickel w/Teflon*

    Bulb . . . . . . . . . . . . . . GlassCompression Screw . . . . . BronzeDeflector . . . . . . . . . . . Copper

    Guard . . . . Welded Carbon steelShield . . . . . . . . . Carbon SteelShield Spring . . . . . Carbon Steel

    * Registered trademark of DuPont

    DesignCriteriaThe Model TY-FRFS, TY-FS Special,

    and TY-FS Flat Spray Sprinklers areonly intended for installation per CEA4001 Sprinkler Systems Planning andInstallation or EN12845 AutomaticSprinkler Systems - Design, Installa-t ion and Maintenance where flatspray sprinklers are permitted.

    NOTEIn all cases, CEA 4001 Sprinkler Sys-tems Planning and Installation orEN12845 Automatic Sprinkler Sys-tems - Design, Installation and Mainte-nance must be referenced and fol-l ow ed t o e ns ur e a n e ffe ct iv e installation. The Flat Spay Sprinklers

    have significantly different water distri-bution characteristics from that of con-ventional and spray pattern sprinklersthat has enabled the Flat Spray Sprin-klers to be used in conformance withCEA 4001 Sprinkler Systems Plan-ning and Installation or EN12845Automatic Sprinkler Systems - De-sign, Installation and Maintenance.

    P a g e 2 o f 1 0 TFP6 3 5

    TABLE A

    ALLOWABLE COMBINATIONS OF GUARDS, SHIELDS, AND GUARDS WITH SHIELDS

    Series Bulb Size Orifice Position SIN Guard Shield Guard/Shield

    TY-FRFS 3 mm TY1136 N/A N/A N/A

    TY-FS Special 4 mm TY1146 N/A N/A N/A

    TY-FS 5 mm TY1156 N/A N/A N/A

    TY-FRFS 3 mm TY1236 N/A N/A N/A

    TY-FS Special 4 mm TY1246 N/A N/A N/A

    TY-FS 5 mm TY1256 N/A N/A N/ATY-FRFS 3 mm TY3136 G1 N/A N/A

    TY-FS Special 4 mm TY3146 G1 N/A N/A

    TY-FS 5 mm TY3156 G1 N/A N/A

    TY-FRFS 3 mm TY3236 G1 H1or H2 G1/H1 or G1/H2

    TY-FS Special 4 mm TY3246 G1 H1or H2 G1/H1 or G1/H2

    TY-FS 5 mm TY3256 G1 H1or H2 G1/H1 or G1/H2

    TY-FRFS 3 mm TY4136 G1 N/A N/A

    TY-FS Special 4 mm TY4146 G1 N/A N/A

    TY-FS 5 mm TY4156 G1 N/A N/A

    TY-FRFS 3 mm TY4236 G1 H1 or H2 G1/H1 or G1/H2

    TY-FS Special 4 mm TY4246 G1 H1 or H2 G1/H1 or G1/H2

    TY-FS 5 mm TY4256 G1 H1 or H2 G1/H1 or G1/H2

    115K, 20 mm

    Upright

    Pendent

    Pendent

    57K, 10 mm

    80K, 15 mm

    Upright

    Upright

    Pendent

  • 7/30/2019 Flat Spray Sprinkler

    3/10

    TFP6 3 5 P a g e 3 o f 1 0

    FIGURE 1

    57 K-FACTOR, ISO 7/1-R 3/8UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS

    FIGURE 280 K-FACTOR, 1/2 INCH NPT

    UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS

    Components:

    55 mm

    MAKE-INNOMINAL

    10 mm

    WRENCHFLATS

    UPRIGHT

    MAKE-INNOMINAL

    PENDENT

    40 mm

    55 mm

    10 mm

    *CROSS SECTION

    2

    6

    45

    3

    1

    *

    Frame

    Button

    Bulb (See table above)Compression Screw

    Deflector

    Sealing Assembly--

    -

    --

    - *2

    1

    3

    5

    4

    6

    Temperature rating is indicated onDeflector or adjacent to orifice seat

    *

    on frame.

    *DEFLECTOR

    DEFLECTOR

    BULB

    SIZEMODEL

    SIN

    UPRIGHT

    TY11363 mmTY-FRFS

    TY-FS SPECIAL 4 mm TY1146

    TY-FS 5 mm TY1156

    PENDENT

    TY1236

    TY1256

    TY1246

    7/1-R 3/8

    ISO

    7/1-R 3/8

    ISO

    Components:

    57 mm

    MAKE-INNOMINAL

    11 mm

    WRENCHFLATS

    UPRIGHT

    MAKE-INNOMINAL

    PENDENT

    40 mm

    57 mm

    11 mm

    *CROSS SECTION

    2

    6

    45

    3

    1

    *

    Frame

    Button

    Bulb (See table above)Compression ScrewDeflector

    Sealing Assembly-

    -

    ---

    -

    *

    2

    1

    3

    5

    4

    6

    THREADRELIEF

    Temperature rating is indicated onDeflector or adjacent to orifice seat

    *can be provided on special request.Pipe thread connections per ISO 7/1**

    on frame.

    *DEFLECTORPLATE SEATINGESCUTCHEON

    SURFACE

    SHIELD AND

    1/2" NPT

    DEFLECTOR1/2" NPT **

    **

    BULB

    SIZEMODEL

    SIN

    UPRIGHT

    TY31363 mmTY-FRFS

    TY-FS SPECIAL 4 mm TY3146

    TY-FS 5 mm TY3156

    PENDENT

    TY3256

    TY3246

    TY3236

  • 7/30/2019 Flat Spray Sprinkler

    4/10

    P a g e 4 o f 1 0 TFP6 3 5

    FIGURE 3

    115 K-FACTOR, 3/4 INCH NPTUPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS

    FIGURE 4MODEL G1 GUARD

    TYPICAL INSTALLATION ON UPRIGHT AND PENDENT FLAT SPRAY SPRINKLERS

    Components:

    60 mm

    MAKE-IN

    NOMINAL13 mm

    WRENCHFLATS

    UPRIGHT

    MAKE-INNOMINAL

    PENDENT

    46 mm

    60 mm

    13 mm

    *CROSS SECTION

    BULBSIZE

    MODELSIN

    UPRIGHT

    TY41363 mmTY-FRFS

    TY-FS SPECIAL 4 mm TY4146

    TY-FS 5 mm TY4156

    PENDENT

    TY4256

    TY4246

    TY4236

    2

    6

    45

    3

    1

    *

    Frame

    ButtonBulb (See table above)Compression ScrewDeflector

    Sealing Assembly--

    ---

    - *2

    1

    3

    5

    4

    6

    THREADRELIEF

    Temperature rating is indicated onDeflector or adjacent to orifice seat

    *can be provided on special request.Pipe thread connections per ISO 7/1**

    on frame.

    *DEFLECTORPLATE SEATINGESCUTCHEON

    SURFACE

    SHIELD AND

    3/4" NPT

    DEFLECTOR3/4" NPT **

    **

    73 mm DIA.

    60 mm

    UPRIGHT

    BAR

    (ENGAGED)GUARD CLIP

    SPRINKLER

    GUARD

    MODEL G1

    PLATE

    THREAD RELIEF

    PENDENT

    BASE

    PENDENT

    SPRINKLER

    FLAT SPRAY

    UPRIGHT or

    15 or 20 mm

    ENGAGED BY

    BASE PLATE

  • 7/30/2019 Flat Spray Sprinkler

    5/10

    TFP6 3 5 P a g e 5 o f 1 0

    FIGURE 5K80 PENDENT FLAT SPRAY SPRINKLERS

    WITHMODEL H1 SHIELD

    ORMODEL H1 SHIELD AND MODEL G1 GUARD

    GUARD

    MODEL G1

    SHIELD

    MODEL H1

    SEATING

    SHIELD

    SURFACE

    8 mm

    100 mm DIA.

    FLAT SPRAY

    SPRINKLER

    PENDENT15 mm

    SHIELDMODEL H1

    SURFACE

    SEATING

    SHIELD

    ATTACHMENT

    SPRING

    15 mm

    FLAT SPRAY

    SPRINKLER

    PENDENT

    FIGURE 6K80 PENDENT FLAT SPRAY SPRINKLERSWITH

    MODEL H2 SHIELDOR

    MODEL H2 SHIELD AND MODEL G1 GUARD

    FLAT SPRAYSPRINKLER

    GUARDMODEL G1

    SHIELDMODEL H2

    PENDENT

    SEATING

    SHIELD

    SURFACE

    15 mmPENDENT

    SPRINKLERFLAT SPRAY

    15 mmMODEL H2SHIELD

    160 mm DIA.

    32 mm

    SEATING

    SHIELD

    SURFACEATTACHMENTSPRING

  • 7/30/2019 Flat Spray Sprinkler

    6/10

    P a g e 6 o f 1 0 TFP6 3 5

    FIGURE 7K115 PENDENT FLAT SPRAY SPRINKLERS

    WITHMODEL H1 SHIELD

    ORMODEL H1 SHIELD AND MODEL G1 GUARD

    SEATING

    SHIELD

    SURFACEATTACHMENT

    SPRING

    8 mm

    SURFACE

    SEATING

    SHIELD

    ATTACHMENT

    SPRING

    GUARD

    MODEL G1

    SHIELD

    MODEL H1

    FLAT SPRAY

    SPRINKLER

    PENDENT

    20 mm

    SHIELD

    MODEL H1

    20 mm

    FLAT SPRAY

    SPRINKLER

    PENDENT

    100 mm DIA.

    FIGURE 8K115 PENDENT FLAT SPRAY SPRINKLERS

    WITHMODEL H2 SHIELD

    ORMODEL H2 SHIELD AND MODEL G1 GUARD

    160 mm DIA.

    32 mm

    SEATINGSHIELD

    SURFACEATTACHMENTSPRING

    FLAT SPRAYSPRINKLER

    GUARDMODEL G1

    SHIELDMODEL H2

    PENDENT

    SEATINGSHIELD

    SURFACEATTACHMENTSPRING

    20 mmPENDENT

    20 mm

    SPRINKLERFLAT SPRAY

    MODEL H2SHIELD

  • 7/30/2019 Flat Spray Sprinkler

    7/10

    InstallationInstallation instructions are provided inthe following subsections:

    Sprinkler Only

    Sprinkler With Guard

    Sprinkler With Shield

    Sprinklers With Guard & Shield

    SPRINKLER ONLY

    The Model TY-FRFS, TY-FS Special,and TY-FS Sprinklers must be in-stalled in accordance with the follow-ing instructions:

    NOTESDo not install any bulb type sprinkler ifthe bulb is cracked or there is a loss ofliquid from the bulb. With the sprinklerheld horizontally, a small air bubbleshould be present. The diameter of theair bubble is approximately 1/16 inch(1,6 mm) for the 135F/57C to 3/32inch (2,4 mm) for the 360F/182Ctemperature ratings.

    A leak tight 1/2 inch NPT sprinkler jointshould be obtained with a torque of 7to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-mum of 21 ft. lbs. (28,5 Nm) of torquemay be used to install sprinklers with1/2 NPT connections. A leak tight 3/4inch NPT sprinkler joint should be ob-tained with a torque of 10 to 20 ft.lbs.(13,4 to 26,8 Nm). A maximum of 30ft.lbs. (40,7 Nm) of torque is to be used

    to install sprinklers with 3/4 NPT con-nections. Higher levels of torque maydistort the sprinkler inlet and causeleakage or impairment of the sprinkler.

    Do not attempt to make-up for insuffi-cient adjustment in the escutcheonplate by under- or over-tightening thesprinkler. Readjust the position of thesprinkler fitting to suit.

    Step 1. Pendent sprinklers are to beinstalled in the pendent position, andupright sprinklers are to be installed inthe upright position.

    Step 2. With pipe thread sealant ap-plied to the pipe threads, hand tighten

    the sprinkler into the sprinkler fitting.

    Step 3. Tighten the sprinkler into thesprinkler fitting using only the W-Type6 Sprinkler Wrench (Ref. Figure 10).With reference to Figures 1, 2, and 3the W-Type 6 Sprinkler Wrench is tobe applied to the wrench flats.

    SPRINKLER WITH GUARD

    With reference to Figure 4, the ModelG1 Guard must be installed as follows:

    S t e p 1 . The G1 Guard i s to be

    mounted on the sprinkler after thesprinkler has been installed in accord-ance with the Sprinklers Only sub-section.

    Step 2. With the Clips loose, firstspread the two halves of the SprinklerGuard just enough to pass by thesprinkler deflector from the side. Then,once again spread the two halves ofthe Sprinkler Guard just enough topass over the sprinkler thread reliefportion of the sprinkler. (Refer to Fig-ures 2 and 3.)

    Step 3. With the Sprinkler Guard posi-tioned on the thread relief portion ofthe sprinkler, as applicable, engagethe Clips and then slide the Clips untilthey seat against the Base to completethe installation as shown in Figure 4.

    To help assist with the sliding of theClips, the Guard Installation Tool maybe used as shown in Figure 9. In addi-

    tion, pliers can be used to facilitate thefinal seating of he Clips.

    NOTESThe Clips must seat against the Basein order to be considered fully seated

    and in order to complete the installa-tion.

    The G1 may be located in any positionrelative to the sprinkler frame arms.

    SPRINKLER WITH SHIELD

    With reference to Figures 5, 6, 7, or 8,the Model H1 or Model H2 Shield mustbe installed as follows:

    Step 1. Pendent sprinklers are to beinstalled in the pendent position.

    Step 2. With pipe thread sealant ap-

    FIGURE 9MODEL G-1 GUARD INSTALLATION PROCEDURE

    WITH INSTALLATION TOOL APPLIED OVER

    TOWARD BASE PLATES UNTIL FULLY ENGAGED

    ADJACENT BARS, PRESS SECOND CLIP

    SWIVEL CLIPS OVER

    INSTALLED, CAREFULLY

    AND FIT ONTO SPRINKLER

    TOWARD BASE PLATES

    ADJACENT BARS AND SLIDE

    SPREAD BASE PLATES APART

    PLATESBASE

    FIRST

    CLIP INSTALLATIONTOOL (SHIPPED WITH

    GUARDS)

    CLIP FULLYENGAGED

    SLOTBAR

    CLIP FULLYENGAGED

    SECOND

    A PLIER

    USEDMAY BE

    INSTALLATIONTOOL

    CLIP

    CLIP

    TOOLINSTALLATION

    CLIP

    CLIP

    WITH SPRINKLER PROPERLY

    THREAD RELIEF

    UNTIL SNUG

    MODEL G1GUARD

    FLAT SPRAYSPRINKLER

    FIGURE 10W-TYPE 6 SPRINKLER

    WRENCH

    WRENCH RECESS(END "A" USED FOR

    ISO 7/1-R 3/8 &

    WRENCH RECESS(END "B" USED FOR

    3/4" NPT MODELS)

    1/2" NPT MODELS)

    FIGURE 11W-TYPE 7 SPRINKLER

    WRENCH

    RECESSWRENCH

    WITH SPRINKLERENGAGEMENTIN TO ENSURE

    WRENCHINGAREA

    PUSH WRENCH

    TFP6 3 5 P a g e 7 o f 1 0

  • 7/30/2019 Flat Spray Sprinkler

    8/10

    plied to the pipe threads, install theShield over the sprinkler threads.

    Step 3. Install the Attachment Springover the sprinkler threads until it seatsagainst the Shield.

    Step 4. Hand tighten the sprinkler intothe sprinkler fitting.

    Step 5. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Sprinkler Wrench (Ref. Figure 11).The wrench is to be applied to thesprinkler wrenching area shown in Fig-ures 2 or 3, as applicable.

    NOTEWhen installed correctly, the Attach-ment Spring wi l l be sl ightly com-pressed and the Shield will be heldfirmly in place.

    SPRINKL ER WIT H GUARD ANDSHIELD

    With reference to Figures 5, 6, 7 or 8,the guard with shield arrangementmust be installed as follows:

    Step 1. Pendent sprinklers are to beinstalled in the pendent position.

    Step 2. With pipe thread sealant ap-plied to the pipe threads, install theShield over the sprinkler threads.

    Step 3. When installing K115 Sprin-klers, Install the Attachment Springover the sprinkler threads until it seatsagainst the Shield.

    NOTE

    An Attachment Spring is not utilized forK80 Sprinklers with Guard and Shield.

    Step 4. Hand tighten the sprinkler intothe sprinkler fitting.

    Step 5. Tighten the sprinkler into thesprinkler fitting using only the W-Type7 Sprinkler Wrench (Ref. Figure 11).The wrench is to be applied to thesprinkler wrenching area shown in Fig-ures 2 or 3, as applicable.

    Step 7. After the sprinkler with shieldis installed into the sprinker pipe fitting,install the guard as described in theSprinkler With Guard sub-section.

    Care andMaintenanceThe Model TY-FRFS, TY-FS Special,and TY-FS Sprinklers must be main-tained and serviced in accordance

    with the following instructions:

    NOTESBefore closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shutdown theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.

    Sprinklers that are found to be leakingor exhibiting visible signs of corrosionmust be replaced.

    Automatic sprinklers must never be

    painted, plated, coated or otherwisealtered after leaving the factory. Modi-f ied sprinklers must be replaced.Sprinklers that have been exposed tocorrosive products of combustion, buthave not operated, should be replacedif they cannot be completely cleanedby wiping the sprinkler with a cloth orby brushing it with a soft bristle brush.

    Care must be exercised to avoid dam-age to the sprinklers - before, during,and after installation. Sprinklers dam-aged by dropping, striking, wrenchtwist/slippage, or the like, must be re-placed.Also, replace anysprinkler thathas a cracked bulb or that has lostliquid from its bulb. (Ref. InstallationSection).

    Proper installation of sprinklers in-stalled with guards, shields, or guardswith shields should be verified duringthe annual visual inspection of thesprinklers.

    The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the Approval agency andstandards of any other authorities hav-ing jurisdiction. The installing contrac-tor or sprinkler manufacturershouldbecontacted relative to any questions.

    It is recommended that automaticsprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.

    LimitedWarrantyProducts manufactured by Tyco Fire &Building Products (TFBP) are war-ranted solely to the original Buyer for

    ten (10) years against defects in mate-rial and workmanship when paid forand properly installed and maintainedunder normal use and service. Thiswarranty will expire ten (10) yearsfrom date of shipment by TFBP. Nowarranty is given for products or com-ponents manufactured by companiesnot affiliated by ownership with TFBPor for products and components whichhavebeen subjectto misuse, improperinstallation, corrosion, or which havenot been installed, maintained, modi-fied or repaired in accordance with thestandards recognized by the Approvalagency, as well as the standards of

    any other Authorities Having Jurisdic-tion. Materials found by TFBP to bedefective shall be either repaired orreplaced, at TFBPs sole option. TFBPneither assumes, nor authorizes anyperson to assume for it, any other ob-ligation in connection with the sale ofproducts or parts of products. TFBPshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyers representatives.

    In no event shall TFBP be liable, incontract, tort, strict liability or underany other legal theory, for incidental,indirect, special or consequential dam-ages, including but not limited to laborcharges, regardless of whether TFBPwas informed about the possibility ofsuch damages, and in no event shallTFBPs liability exceed an amountequal to the sales price.

    The foregoing warranty is made in lieuof any and all other warranties, ex-press or implied, including warrantiesof merchantability and fitness for aparticular purpose.

    This limited warranty sets forth the ex-clusive remedy for claims based onfailure of or defect in products, materi-als or components, whether the claimis made in contract, tort, strict liabilityor any other legal theory.

    This warranty will apply to the full ex-tent permitted by law. The invalidity, inwhole or part, of any portion of thiswarranty will not affect the remainder.

    P a g e 8 o f 1 0 TFP6 3 5

  • 7/30/2019 Flat Spray Sprinkler

    9/10

    OrderingProcedureWhen placing an order, indicate the fullproduct name. Refer to the Price Listfor complete listing of Part Numbers.

    NOTESprinklers, wrenches, guards, shields,attachment springs, and additional clipinstallation tool are all sold separately

    Contact your local distributor for avail-ability.

    Sprinklers:Specify: (Specify Model/SIN), (SpecifyStandard Response, Special Re-sponse, or Quick Response, (specifyK-factor), (specify temperature rating),(specify Pendent or Upright) Sprinkler,P/N (specify from Table A).

    Sprinkler Wrenches:Specify: W-Type (specify) SprinklerWrench, P/N (specify).

    W-6. . . . . . . . . . . . . . . . . . . . . P/N 56-000-6-387W-7. . . . . . . . . . . . . . . . . . . . . P/N 56-850-4-001

    Guards:Specify: Model G-1 Guard having

    (specify) finish, P/N (specify).

    Red Painted . . . . . . . . . . . . . . P/N 56-000-6-387Zinc Chromate . . . . . . . . . . . . P/N 56-850-4-001

    Shields:Specify: Model (specify), (specify NPTsize) Shield , P/N (specify).

    H1, 1/2" NPT . . . . . . . . . . . . . P/N 22521H1, 3/4" NPT . . . . . . . . . . . . . P/N 22522H2, 1/2" NPT . . . . . . . . . . . . . P/N 22529H2, 3/4" NPT . . . . . . . . . . . . . P/N 22524

    Attachment Springs:Specify: (specify NPT size) ShieldSpring, P/N (specify).

    1/2" NPT . . . . . . . . . . . . . . . . . P/N 225263/4" NPT . . . . . . . . . . . . . . . . . P/N 22527

    Additional* Clip Installation Tools:specify: Clip Installation Tool for G1

    Guard, P/N 56-000-8-597.

    * The Clip Installation Tool is includedwith guard orders in original cartons.

    P/N 51 XXX 1 XXX

    68C (Red)155

    TEMPERATURE

    RATING

    (Fluid Color)

    57C (Orange)1351

    SPRINKLER

    MATERIAL

    TABLE APART NUMBER SELECTIONFLAT SPRAY SPRINKLERS

    79C (Yellow)

    286

    93C (Green)200

    141C (Blue)

    175

    NATURAL BRASS

    MODEL/SIN

    391 115K PENDENT, 3/4 INCH NPT

    382 57K PENDENT, ISO 7/1-R 3/8

    370 80K UPRIGHT, 1/2 INCH NPT

    TY-FRFS/TY1236

    TY-FRFS/TY3136

    TY-FRFS/TY4236

    371

    390

    80K PENDENT, 1/2 INCH NPT

    115K UPRIGHT, 3/4 INCH NPT

    TY-FRFS/TY3236

    TY-FRFS/TY4136

    482 57K PENDENT, ISO 7/1-R 3/8TY-FS Special/TY1246

    470 80K UPRIGHT, 1/2 INCH NPTTY-FS Special/TY3146

    471 80K PENDENT, 1/2 INCH NPTTY-FS Special/TY3246

    490 115K UPRIGHT, 3/4 INCH NPTTY-FS Special/TY4146

    491 115K PENDENT, 3/4 INCH NPTTY-FS Special/TY4246

    582 57K PENDENT, ISO 7/1-R 3/8TY-FS/TY1256

    570 80K UPRIGHT, 1/2 INCH NPTTY-FS/TY3156

    571 80K PENDENT, 1/2 INCH NPTTY-FS/TY3256

    590 115K UPRIGHT, 3/4 INCH NPTTY-FS/TY4156

    591 115K PENDENT, 3/4 INCH NPTTY-FS/TY4256

    380 TY-FRFS/TY1136 57K UPRIGHT, ISO 7/1-R 3/8

    480 TY-FS Special/TY1146 57K UPRIGHT, ISO 7/1-R 3/8

    580 TY-FS/TY1156 57K UPRIGHT, ISO 7/1-R 3/8

    TFP6 3 5 P a g e 9 o f 1 0

  • 7/30/2019 Flat Spray Sprinkler

    10/10

    P a g e 1 0 o f 1 0 TFP6 3 5

    TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446