fire dampers & smoke dampers -...

22
Series HFS, IBD, IBD - FS & LR. HFS Fire and Leakage Rated Smoke Damper. 322 - 325H Multileaf Blade Design. Range of Electrical On/Off, Spring Return and Pneumatic Actuators. IBD Interlocking Curtain Blade Fire Damper. 307 - 321H HFS & IBD Vertical and Horizontal Mounting. IBD - FS ‘Fire Seal’ Fire and Leakage Rated Damper. 329 - 340H HFS, IBD & IBD - FS. Roll Formed Blades and Frame. HFS, IBD & IBD - FS. Universal Mounting Sleeve and Angles. 314 - 317, 323, 334 - 336H IBD & IBD - FS. ‘Safe Test’ Test Latch Fitted as Standard IBD & IBD - FS. Electro Thermal Resettable Link Option, (Allows remote activation via Smoke Detectors, or Alarm System). LR Low Heat Radiation Fire/Smoke/Control Damper. 326 - 328H Innovative Low Radiation, Low Leakage, Insulated Single Damper Blade. Mounting Flanges, Pre-Insulated Sleeve and Air Balancing Damper. IBD - FS & LR. Vertical (Wall Mounting Only). All Products 4 Hour Fire Rated, (subject to wall/floor thickness and construction). 71 Degrees C Fusible Link (Standard). Ordering Key and Specification 321, 325, 328 & 340H H Fire & Smoke Dampers Fire Dampers & Smoke Dampers 307H

Upload: others

Post on 28-Jul-2020

56 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Series HFS, IBD, IBD - FS & LR. HFS Fire and Leakage Rated Smoke Damper. 322 - 325H Multileaf Blade Design. Range of Electrical On/Off, Spring Return and Pneumatic Actuators.

IBD Interlocking Curtain Blade Fire Damper. 307 - 321H HFS & IBD Vertical and Horizontal Mounting.

IBD - FS ‘Fire Seal’ Fire and Leakage Rated Damper. 329 - 340H HFS, IBD & IBD - FS. Roll Formed Blades and Frame.

HFS, IBD & IBD - FS. Universal Mounting Sleeve and Angles. 314 - 317, 323, 334 - 336H

IBD & IBD - FS. ‘Safe Test’ Test Latch Fitted as Standard

IBD & IBD - FS. Electro Thermal Resettable Link Option, (Allows remote activation via Smoke Detectors,

or Alarm System).

LR Low Heat Radiation Fire/Smoke/Control Damper. 326 - 328H Innovative Low Radiation, Low Leakage, Insulated Single Damper Blade. Mounting Flanges, Pre-Insulated Sleeve and Air Balancing Damper. IBD - FS & LR. Vertical (Wall Mounting Only).

All Products 4 Hour Fire Rated, (subject to wall/floor thickness and construction).

71 Degrees C Fusible Link (Standard).

Ordering Key and Specification 321, 325, 328 & 340H

H

Fire

& S

mok

e Da

mpe

rs

Fire Dampers &Smoke Dampers

307H

Page 2: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers

308H

Fire

& S

mok

e Da

mpe

rs

Holyoake Curtain-type fire dampers are designed to maintain theintegrity of the fire resistance of a wall, or floor, in which a hole hasbeen formed to permit the passage of air, ducted or otherwise, toenable an air distribution system to function. The arrangement ofinterlocking blades mounted in a guide channel frame, minimizesspace requirements and facilitates ease of installation in ductwork.Fire Rating:All Holyoake Series IBD units carry up to a 4 HOUR rating toAS 1530.4 as determined by the following testing Authority.For the purposes of the Australian and New Zealand Building Code they have an FRL/FRR of – / 240 / – .

BRANZ Assessment Report Certificate No.1 IBD Damper mounted in a concrete wall, or floor. (Certified for 240 minute fire rating).

BRANZ Fire Test Certificate No. FTC 392 IBD Damper mounted in a plasterboard wall. (Certified for 30 or 60 minute fire rating). (Certificates are available upon request).

Standard Construction

Frame: 110 mm x 1.2 mm galvanised steel, roll formed guide channel.

Blades: 70 mm x 1.0 mm galvanised steel, roll formed inter-locking profile.

Springs: Blade End: stainless steel. Retraction: stainless steel. Note: Horizontal dampers with a duct ‘B’ dimension of less than 180 mm have all blades fitted with end springs only. Above 180 mm constant force springs only are fitted. All vertical dampers have the bottom blade only fitted with end springs.

Fusible Links: ‘Safe Test’ Test latch Model IBD-TL fitted as standard, complete with 71º C Fusible Link. See page 318H for more details. (Other ratings available on request). Please contact your local Holyoake branch.

Mounting: Vertical or horizontal, but in all cases the blades must be horizontal.

Alternate Electro-Thermal Resettable LinkActivation: This device can be activated by smoke detectors of

compatible design, (Supply and fit by others). By definition, a fire damper provides an effective

barrier to the passage of fire and products of combustion, but when its operation is initiated by the detection of smoke, or other products of combustion it may then be termed “smoke damper”.

The difference between a fire damper and a smoke damper is not a physical one, but is in the method of initiating the operation. (AS 1682.1-1990).

Mounting Sleeves: Series IBD fire dampers must be installed in sleeves

(refer to Pages 313H - 317H). These sleeve assemblies are available, please consult the sales office.

Stainless Steel: Construction in stainless steel is available for both

IBD and mounting sleeves.

Model IBD-B-V Illustrated.

Mounting Sleeve Omitted for Clarity,

refer to Pages 313H - 317H for details.

Horizontal

Mounting Sleeves omitted for clarity.

Vertical

A AA + 64 D + 64

A + 64

BB

(Duct)B(Duct)

B(Duct)

A(Duct)

B(Duct)

A(Duct)

HHH

H

Style-A Style-B Style-C Style-CR Style-CO

Notes1. In specifying a fire damper the width should always be stated first and the height second.

2. Nominal dimensions are opening sizes and allow clearance for insertion into mounting sleeve:

6 mm Duct Connection Style A & B. 3 mm Duct Connection Style C, CR & CO.

Where this allowance is not required specify “exact size”.

Duct Connection

Single Section Maximum Dimensions

DUCT CONNECTION STYLE A B C CO

A B A B A B A BAlternative Max.

Dimension Combinations

Vertical

Horizontal

838 1828 838 1600 774 1568

1219 762 1219 654 1155 622

838 965 838 835 774 803

1016 762 1016 654 952 622

CR

B

774

774 1568

1155 622

774 803

952 622

Page 3: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Fire Dampers – Series IBD

309H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-A-V

Interlocking blade, vertical (wall) mounting damper, gravity operated, spring loaded initial movement, blade stack located within air stream.

Minimum size A 100 x B 63 mm.

Maximum size combinations:A 838 x B 1828, or A 1219 x B 762 mm (Single Section).

Model: IBD-B-V

Interlocking blade, vertical (wall) mounting damper, gravity operated, spring loaded initial movement, blade stack located out of air stream.

Minimum size A 100 x B 83 mm.

Maximum size combinations:A 838 x B 1600, or A 1219 x B 654 mm (Single Section).

Model: IBD-A-V (multiple)

See above for details on individual IBD-A-V dampers

Model: IBD-B-V (multiple)

* Minimum of 85 mm when fitted with IBD - ETR, refer to Page 318H.

DUCT CONNECTION STYLE ‘B’ (Single Section)

Dimension ‘B’From - 84 144 179 239 299 359 394 454 514 574 609 669 729 789

To 83 143 178 238 298 358 393 453 513 573 608 668 728 788 823

Dimension ‘H’ = B + 29* 29* 54* 54* 54* 54* 79* 79* 79* 79* 104 104 104 104 129

Dimension ‘B’From 824 884 944 1004 1039 1099 1159 1219 1254 1314 1374 1434 1469 1529 1589

To 883 943 1003 1038 1098 1158 1218 1253 1313 1373 1433 1468 1528 1588 1600

Dimension ‘H’ = B + 129 129 129 154 154 154 154 179 179 179 179 204 204 204 204

DUCT CONNECTION STYLE ‘A’ (Single Section)

Dimension ‘B’From - 64 184 304 424 544 664 784 904 1024 1144 1264 1384 1504 1624 1744

To 63 183 303 423 543 663 783 903 1023 1143 1263 1383 1503 1623 1743 1828

Dimension ‘X’ 15* 30* 42* 54* 66* 78* 90 102 114 126 138 150 162 174 186 198

Assembly and Dimensional Information(A & B Dimensions allow 6 mm clearance for mounting sleeve of nominated size)

Where opening is larger than maximum single section size, an assembly of equal size single section dampers is used. Style ‘B’ assemblies where more than one unit high, would consist of ‘B’ type units in the top row only and ‘A’ type elsewhere. Multiple assemblies are shipped in sections for field assembly. Adequate fire rated bracing must be provided by the installer to prevent collapse of multiple unit assemblies when closed, even under relatively low pressure differential conditions.

Maximum multiple unit module for vertical dampers is 3 wide by 2 high single sections as shown.

A

A11077

H

B

B

X

AirFlow

EitherWay

AirFlow

EitherWay

Mounting Sleeve omitted for clarity - refer to Pages 313H - 317H for details.

77110

IBD-A-V

IBD-B-V

150189

Model IBD-B-V (Multiple)

A

HB

Model IBD-A-V (Multiple)

A

B

X

Mounting Sleeve omitted for clarity - refer to Pages 313H - 317H for details.

IBD-A-V

IBD-A-V IBD-A-V

IBD-A-V IBD-A-V

IBD-A-V

IBD-A-V IBD-A-V IBD-A-V

IBD-B-V IBD-B-V IBD-B-V

Page 4: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers

310H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-A-H

Interlocking blade, horizontal (floor) mounting fire damper, spring loaded for complete travel, blade stack located within air stream.

*Where dimension ‘B’ exceeds 180 mm, two constant force springs anchored to the frame and attached to the last blade draw the blade curtain closed. Where dimension ‘B’ is less than 180 mm, all blades are fitted with “omega” springs at blade ends, which drive the curtain to the closed position.

Minimum size A 100 x B 70 mm.

Maximum size combinations:-A 838 x B 965, or A 1016 x B 762 mm (Single Section).

Model: IBD-B-H

Interlocking blade, horizontal (floor) mounting fire damper, spring loaded for complete travel, blade stack located out of air stream.

Spring arrangement similar to IBD-A-H.

Minimum size A 100 x B 35 mm.

Maximum size combinations:-A 838 x B 835, or A 1016 x B 654 mm (Single Section).

Model: IBD-A-H (multiple)

Model: IBD-B-H (multiple)

(A & B Dimensions allow 6mm clearance for duct of nominated size).

Where opening is larger than maximum single section size, an assembly of equal size single section dampers is used. Blade stacks for assemblies two sections across the ‘B’ dimension are normally installed as illustrated, with blade stacks outermost, thus improving access and minimising air flow interference. Multiple assemblies are shipped in sections for field assembly.

Maximum multiple unit module for horizontal dampers is 2 wide and 2 high single sections as shown.

DUCT CONNECTION STYLE ‘B’ (Single Section)

Dimension ‘B’From - 36 86 111 161 181 239 299 359 394 454 514 574 609 669 729 789 824

To 35 85 110 160 180 238 298 358 393 453 513 573 608 668 728 788 823 835

Dimension ‘H’ = B + 54* 54* 54* 54* 54* 54* 54* 54* 79* 79* 79* 79* 104 104 104 104 129 129

DUCT CONNECTION STYLE ‘A’ (Single Section)

Dimension ‘B’From - 71 101 151 181 244 364 484 604 724 844

To 70 100 150 180 243 363 483 603 723 843 965

Dimension ‘X’ 26* 42* 56* 70* 40* 52* 64* 76* 88 100 112

Model IBD-A-H (Multiple) Model IBD-B-H (Multiple)

AA

B B

IBD-A-H

IBD-A-H IBD-A-H

IBD-A-H IBD-B-H

IBD-B-H IBD-B-H

IBD-B-H

Assembly and Dimensional Information

*

*

X

77110 77110

B B

H

A A

189

AirFlow

EitherWay

AirFlow

EitherWay

IBD-A-H IBD-B-H

150

* Minimum of 85 mm when fitted with IBD - ETR, refer to Page 318H.

Mounting Sleeve omitted for clarity, refer to Pages 313H - 317H for details.

Mounting Sleeve omitted for clarity, refer to Pages 313H - 317H for details.

Page 5: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Fire Dampers – Series IBD

311H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-C-V

Interlocking blade located out of airstream, vertical (wall) mounting damper, gravity operated, spring loaded initial movement, fitted with enclosure plates and square, or rectangular spigots to suit duct connections.

Model: IBD-CR-V

Interlocking blade located out of airstream, vertical (wall) mounting damper, gravity operated, spring loaded initial movement, fitted with enclosure plates and round spigots to suit duct connections.

Model: IBD-CO-V

Interlocking blade located out of airstream, vertical (wall) mounting damper, gravity operated, spring loaded initial movement, fitted with enclosure plates and oval spigots to suit duct connections.

Typical Multiple Assembly

Assembly and Dimensional Information

Where opening is larger than maximum single section size, an assembly of equal size single section dampers is used. Where ‘H’ requires more than one section, the blade stack for the lower section will be in the air stream. The extent of this obstruction may be determined by dimension ‘X’ on Model IBD-A-V, of the appropriate size.

DUCT CONNECTION STYLE C, CR & CO (Single Section)

Dimension ‘B’ From - 52 112 147 207 267 327 362 422 482 542 577 637 697 757

To 51 111 146 206 266 326 361 421 481 541 576 636 696 756 791

Dimension ‘H’ = B + 61* 61* 86* 86* 86* 86* 111 111 111 111 136 136 136 136 161

Dimension ‘B’From 792 852 912 972 1007 1067 1127 1187 1222 1282 1342 1402 1437 1497 1557

To 851 911 971 1006 1066 1126 1186 1221 1281 1341 1401 1436 1496 1556 1568

Dimension ‘H’ = B + 161 161 161 186 186 186 186 211 211 211 211 236 236 236 236

A & B Dimensions allow 3 mm clearance for duct of nominated size

A + 64

A (Duct)

B + 64

A + 64

A (Duct)

32

32

32

1104040

77

HB

(Duct)

H

B(Duct)

H

B(Duct)

Air FlowEither Way

1105050

77

1105050

77

Air FlowEither Way

A or B(Duct)

A or B+ 64

32

32

32

HB

(Duct)

IBD-C-V

IBD-CR-V

IBD-CO-V

IBD-CR-VMULTIPLEASSEMBLY

Air FlowEither Way

* Minimum head height with IBD - ETR is 85 mm, refer to Page 318H.

Mounting Sleeves omitted for clarity, refer to Pages 313H - 317H for details.

Page 6: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers

312H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-C-H

Interlocking blade located out of airstream, horizontal (floor) mounting fire damper, *spring loaded for complete travel, fitted with enclosure plates and square, or rectangular spigots to suit duct connections.

Model: IBD-CR-H

Interlocking blade located out of airstream, horizontal (floor) mounting fire damper, *spring loaded for complete travel, fitted with enclosure plates and round spigots to suit duct connections.

Model: IBD-CO-H

Interlocking blade located out of airstream, horizontal (floor) mounting fire damper, *spring loaded for complete travel, fitted with enclosure plates and oval spigots to suit duct connections.

* Where B, or D dimension exceeds 148 mm, two constant force springs anchored to the frame and attached to the last blade draw the blade curtain closed. Where B, or D are less than 148 mm, all blades are fitted with “omega” springs at blade ends, which drive the curtain to the closed position.

Typical Multiple Assembly

Assembly and Dimensional Information

Where opening is larger than maximum single section size, an assembly of equal size single section dampers is used. Where ‘H’ requires two sections, the blade stacks are located out of the air stream on opposite sides of the opening.

A & B Dimensions allow 3 mm clearance for duct of nominated size.

Dimension ‘B’ +From - 54 79 129 149 207 267 327 362 422 482 542 577 637 697 757 792

To 53 78 128 148 206 266 326 361 421 481 541 576 636+ 696 756 791* 803*

Dimension ‘H’ = B + 86 86 86 86 86 86 86 111 111 111 111 136 136 136 136 161 161

Typical Section Styles C, CR & CO, Horizontal.

40*

40*

Air FlowEither Way

77110

A + 64A

(Duct)

32

H

32

32

B (Duct)

B+ 64

HB (Duct)

H

B (Duct)

A or B+ 64

A or B(Duct)

A + 64A

(Duct)

HB (Duct)

IBD-C-H

IBD-CR-H

IBD-CR-H

MULTIPLE

ASSEMBLY

IBD-C-H

IBD-CO-H

Duct Connection Style ‘C, CR, & CO’ (Single Section)

* Maximum Single Section for DuctConnection Style CR is 774 mm Diameter.

+ Dimension B is a Maximum of 622 mm if Dimension A = 774 - 952 mm.

*50 mm for IBD-CR-H or IBD-CO-H.

Page 7: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

313H

Fire

& S

mok

e Da

mpe

rs

The following installation method and diagrams (shown on the next page) are presented as the method by which Holyoake fire dampers must be installed.

It draws upon SMACNA fire, smoke and radiation damper installation guide for HVAC systems, third edition, 1986, and is intended to meet the requirements of Australian Standard 1682, Part 2, 1990.

(I) The casing shall completely penetrate the fire barrier and be retained:

(a) on both sides by means of mounting flanges in such a manner that it can expand in a fire without distorting the blades in a closed position; or

(b) on the accessible side by means of one mounting flange only, which can be fixed to the fire damper and to the fire barrier through oversized holes and penny washers. Fixings should be finger tight (to allow movement for thermal expansion), but locked, i.e. with double nut (lock nut).

Mounting flanges 5, 6, 7 shall be butted against the face of the fire barrier and fixed to the fire damper casing. The width of the angle section of the flange shall be not less than twice the clearance between the fire damper body and the penetration.

(II) The fire damper shall be installed so that the airflow2 does not impede its closure, and air velocities3 do not exceed the damper’s limit (10 m/s).

(III) The method of attachment of ductwork to the fire damper must be such that any deformation, or collapse of the ductwork in a fire, does not dislodge the fire damper, or affect its performance. This is best achieved by the use of breakaway joints which will allow damaged ductwork to fall away. e.g. Slip Joints, Proprietary Duct Flange Systems, etc.

(IV) Clearance between sleeve and penetration should be packed with compressible, non-combustable4 materials and generally be such that the hole size may be no less than overall sleeve size + 1% + 10 mm, both width and height. However, in no case should total clearance be less than the tested prototype (12 x 2 = 24), or exceed 50% of the flange face width.

(V) Access doors, or removable pressed panels, must be provided for duct entry, to test and reset release mechanisms and for inspection.

(VI) When installed and closed, the blade and pivots must be fully contained within the penetrated element and within the casing (AS 1682.2 - 1990).

(VII) Fire dampers may not be used as control dampers. i.e. They must be installed fully open.

(VIII) All Holyoake IBD type fire dampers must be sleeve mounted.5,6,7

See details on following pages.

(IX) Series IBD vertical (wall) mounted fire dampers must not be installed either with blades vertical (on end), with the blade stack below the opening, or horizontally.

(X) Ensure damper is square and free from racking, that there are no obstructions in the centre track, and that it is installed in accordance with the “this way up” arrow on every damper, both vertical and horizontal.

(XI) For Special Applications and Installation Methods, please contact your local Holyoake Branch.

Notes

1 AS 1682.1 - 1990 requires the casing to be no less than 1.6 mm in thickness.

Australian Standards Association allow that the combination of casing and

sleeve in this case satisfies this requirement. In keeping with SMACNA

recommendations, minimum sleeve thickness is 0.45mm which augments

the roll-formed section to provide a total of 1.6 mm for the smallest duct

size, and greater for larger sizes. Holyoake sleeves are a minimum thickness

of 0.55 mm.

2 Air flow may be from either direction for Holyoake Series IBD.

3 While damper size influences acceptable velocities (i.e. the larger the

damper the lower the velocity), Holyoake Industries suggests a maximum of

10 m/s on vertical gravity dampers. If velocities are expected to exceed this,

it is suggested that spring closure (type H) dampers be specified, even for

vertical mounting. Pressure differential across the closed damper should

not exceed 750 Pa.

4 Material capable of resisting high temperatures, fusing at not less than

1000ºC, such as high temperature mineral wool, may be accepted for this

purpose. Prototypes were tested with a High Temperature Loose Wool.

5 SMACNA requires the damper and retaining flanges to be secured to the

sleeve, with 6 mm bolts and nuts, 12 mm welds, 4.7 mm steel rivets, or

No. 10 steel screws. (Optional fixing screws can be provided).

6 Retaining flanges must be of minimum thickness 2.5 mm for face area

> 2 m2, or 2.0 mm for face area < 2 m2 (AS 1682.1 - 1990).

They are mandatory on all four sides, but need not be welded to form a frame.

7 Materials for sleeves and retaining flanges must comply with

AS 1682.1 - 1990, which allows galvanised steel with a coating class not

less than Z275.

Fire Damper Installation

Fire Dampers – Series IBD

Vertical in wall

Vertical in wall

This is the correct position

Vertical in wall

Page 8: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers

314H

Fire Damper Installation

Installation in a Masonry Wall, (refer to notes on previous page).

Installation in a Plasterboard Wall, (refer to notes on previous page).

* = Wall opening to be lined with the same quantity and thickness of plasterboard, as per wall lining. Plasterboard packer not required if double layer wall linings used.

Joining of multiple sections.

Fire

& S

mok

e Da

mpe

rs Duct ConnectionsStyle CR & CO.

Duct ConnectionsStyle ‘B’.

Fixing (Note 7 on page 313H).Clearance & Packing (IV on page 313H).

Duct ConnectionsStyle ‘C’.

Duct ConnectionsStyle ‘A’.

Mounting Angles& Fixing.

‘S’ Cleat - Typical Breakaway Joint (III on page 313H).

Sleeve (VIII on page 313H).

Keep track clearof fastenings and other obstructions.

Typical Fire Damper Installation Various Styles

Joining ofMultiple Sections.

300 Typ.300 Typ.

50 Typ.50 Typ.

Plasterboard Wall.Plasterboard as perwall lining. Attachedto stud*.

Steel retaining anglesnot fixed to wall.

Fire rated masticsealant.

Duct.

‘S’ Cleat (III on page 313H).

Timber or Steel stud framing the opening all round, screwed at the corners and to the vertical studs.

Keep track clear of fastenings andother obstructions.

Plasterboard packer all round (as per wall lining), attached to wall.

Fixing to sleeve(Note 5 on page 313H).

Sleeve (VIII on page 313H).

Clearance & Packing (IV on page 313H).

‘SafeTest’ Test latch.

Damper.

Page 9: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Notes1. Above details are intended as a guide for field installation of sleeves.

2. Refer to Pages 313H - 317H for full sleeve information.

Installation Details and Sleeve Mounting Dimensions

For ‘H’ dimension refer to table, page 309H.

Fire Dampers – Series IBD

315H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-A-V

Model: IBD-A-H

B (x A)

B (x A)

150 Max 6 150 Max 6

150 Max 6

150 Max 6

Model: IBD-B -V

Model: IBD-B -H

B (x A)

H (x A)

B (x A)H (x A)

150 Max 6 150 Max 6

150 Max 6

150 Max 6

Sleeve

Duct Sealer

Duct attachment method for the IBD Type ‘B’ in Sleeve

Connecting Duct

‘S’ Cleat

NC

NO

C

NC

NO

C

Top Switch

Brown

Green

Blue

Damper Open

(Blades Stacked)

Damper Closed

(Blades Released)

(Blade Stack)

NC

C

NO

1

2

3

Bottom Switch

Brown

Green

Blue

NC

C

NO

1

4

5

Top Switch

Brown

Green

Blue

(Blade Stack)

NC

C

NO

1

2

3

Bottom Switch

Brown

Green

Blue

NC

C

NO

1

4

5

EE

Reset and Release MicroswitchesOptional Release and/or Reset Microswitches are available, factory fitted. Contact your local Holyoake branch for details.

Note Standard Switches are not fire rated.

Page 10: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers

316H

Fire

& S

mok

e Da

mpe

rs

Notes1. Above details are intended as a guide for field installation of sleeves.

2. Refer to Pages 313H - 317H for full sleeve information.

For ‘H’ dimension refer to table on page 311H.

Installation Details and Sleeve Mounting Dimensions

D

H (x D + 64)

Model: IBD-CR-V

(IBD-CO-V Similar)

Model: IBD-CR-H

(IBD-CO-H Similar)

B H (x B + 64)

B

B

150 Max 6 150 Max 6

150 Max 6

150 Max 6

Model: IBD-C-V

Model: IBD-C-H

B

H (x A + 64)

B H (x A + 64)

150 Max 6 150 Max 6

150 Max 6

150 Max 6

Guide Product Weights

IBD Curtain Fire Dampers

IBD-A-V 200 x 200

IBD-A-V 600 x 400 (Inc Sleeve)

IBD-B-V 250 x 250

IBD-B-V 206 x 500

IBD-B-V 760 x 560

IBD-B-V 1050 x 700

IBD-B-V 350 x 350 (Inc Sleeve)

IBD-B-V 400 x 375 (Inc Sleeve)

IBD-B-V 500 x 350 (Inc Sleeve)

IBD-CR-V 150 Diameter

IBD-CR-V 200 Diameter

IBD-CR-V 250 Diameter

IBD-CR-V 450 Diameter

IBD-CR-V 400 Diameter (Inc Sleeve)

IBD-A-H 580 x 480

IBD-A-H 1000 x 680

IBD-B-H 600 x 600

IBD-CR-H 150 Diameter

IBD-CR-H 200 Diameter

IBD-CR-H 300 Diameter

IBD-CR-H 350 Diameter

Approximate Weight in Kg

2

16.4

3.5

4.5

12.7

11.5

16

16.26

19.64

3.1

4.08

5.12

10.45

23.62

8.03

16.22

11.5

3.7

4.43

6.54

8.02

Page 11: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Selection Data – Series IBD

317H

Fire

& S

mok

e Da

mpe

rs

Holyoake Fire Damper Sleeves Model IBD-MSU fire damper mounting sleeves are constructed to meet the requirements of AS 1682, Parts 1 & 2 - 1990 (refer also page 313H, Damper Installation and Notes). They are of a standard length (450 mm), sufficient for all wall thicknesses up to 290 mm. However, optional extended length sleeves are available upon request. Mounting angles are supplied. One set is fixed on one end of the sleeve and the other set is supplied loose, for final fixing of these to the sleeve, on site, by others.

(Note: Both sets may be provided loose, due to handling and transport considerations).

All factory sleeves are supplied fixed to the appropriate fire damper.

Minimum Wall, Or Floor Thickness: Standard Sleeve 100 mm. Optional Extended Sleeve 291 mm.

Maximum Wall, Or Floor Thickness: Standard Sleeve 290 mm. Optional Extended Sleeve 690 mm

Material: Galvanised Steel Type Z275.

Maximum Dimensions per Side Sleeve Thickness 0 - 300 0.55 301 - 762 0.55 763 - 1371 0.75 1372 - 1828 0.95

Flanges 40 x 60 x 2 mm galvanised steel angle. (x4 per side, x 2)

Universal Mounting Sleeve IBD-MSU(Factory Furnished)

H (ID)

450*

60

W (ID)

LooseRetainingFlanges

Factory FixedRetaining Flanges+

* Standard length. Specify alternative if required.+ May be supplied loose due to handling considerations.

40

60

Typical IBD Installation

Construction: Sleeves are corner lapped and spot-welded, then attached to the damper frame on all four sides, to form a rigid assembly.

All damper sleeves come with raw edges.

Optional ‘S’ cleats on all edges (Typical Breakaway Joint).

Optional 25, or 35 mm Breakaway flange on all edges. Do NOT use bolts, or ‘no bolt corner clips’ for Fire Damper Breakaway Joints, (Optional PVC cleats are available). (Typical Breakaway Joint – refer to Section K Accessories).

Type ‘B’ damper sleeves are fitted with a duct bridging piece.

An extended damper sleeve is available for wall depths 291 – 690 mm, (specify length required when ordering). Supplied only as part of a complete unit.

Casing sleeve may only be extended 150 mm from the face of the wall on each side, if slip joint or ‘S’ cleat is used; or 80 mm each side if ‘Breakaway’ flange is fitted.

Standard, or Extended Sleeve

Style A B C CR CO

Width A - 3 A - 3 A + 67 B + 67 A + 67

Height B - 3 H + 3 H + 3 H + 3 H + 3

If in excess of these dimensions sleeve should be trimmed back to the appropriate lengths. This then complies with AS 1682, Parts 1 & 2, 1990.

Note: Factory Fitted Mounting Angles are positioned 150 mm from the end of the sleeve, unless specified at 80 mm.

290 Max.Wall orFloor

450

60

40

150Max.Factory

FittedAngles+

Field FixedAngles

Typical Assembly - Standard Damper Sleeve(B Type Damper Illustrated)

4 4

Packing Material. See Installation (IV on page 313H).

1

6

28

2

*

80Max.

100 Min.Wall orFloor

6

*This area

withinwall, or

floor depth.

3

Typical Assembly - Optional Extended Damper Sleeve(A Type Damper Illustrated)

690 Max.Wall orFloor

Factory FittedAngles+

Field FixedAngles

5

1

2

291 Min.Wall orFloor

*

150Max.

6

80Max.

6

Packing Material. See Installation(IV on page 313H).

60

40

28

850 Max

3

*This area

withinwall, or

floor depth.

Page 12: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers - Testing

318H

Fire

& S

mok

e Da

mpe

rs

Safe and Simple Testing Method. Test and Reset in minutes. AS 1851 - 2012 (Section 13) requires that you annually test Fire

Dampers. To ensure the Life and Property saving function for which they are

designed, all fire dampers should be drop tested after installation. All IBD dampers are fitted with ‘Safe Test’ Test Latch links.

Each Holyoake Series IBD Fire Damper is mechanically tested before it is allowed to leave the factory. In the event of damage occurring during transit, on site, or during installation, rendering any fire damper ineffective, failure to function will reveal any warping, track obstruction, or spring failure that may have occurred. This will require rectification, cleaning and removal of the obstacle, prior to retesting and handover.

The Holyoake ‘Safe Test’ IBD-TL Test Latch, is a latching device with a specially made fusible link, which, when the latch is released, swings clear and allows the curtain to close as if the link had parted under the influence of flame. After testing, the curtain can be re-stacked and the same link clipped back into the latch, where it is again ready to be released in the event of a fire.

To Operate IBD Dampers1. Remove the duct access door (refer to Section K accessories section of this manual).2. Using this access, reach in and remove the locking pin from the nearest latch.3. Check that the locking pin is still in place on the other latch, so that the fusible link is retained by it, when released.4. Check that the track is clear of any obstruction and keep hands clear.5. Lift the latch lever, and the curtain will rapidly close.6. Reload the curtain and swing the fusible link back into place in the latch.7. Replace the locking pin in the latch.8. Replace the duct access door.

To Operate IBD Dampers below minimum heights shown.1. Remove the duct access door (refer to Section K accessories section of this manual).2. Remove locking pin from both sides.3. Check that the track is clear of any obstruction and keep hands clear.4. Support the blade pack, lift both latch levers and remove fusible link.5. Release the blade pack and the curtain will rapidly close.6. Reload the curtain and support the blade pack, whilst replacing the fusible link locating pins into both latches.7. Replace both locking pins.8. Replace the duct access door.

‘Safe Test’ - Test Latch Model IBD-TL

Minimum Duct Height for dampers fitted with Electro Thermal Resettable Links

Duct Connection Style Minimum Duct Height

A 210

B 150

C 150

CR 150

CO 150

For testing purposes, all dampers below these heights will require removal of link and blades dropped manually.

All Holyoake IBD type fire dampers, are available with optional Electro Thermal Resettable Link mechanisms. (subject to minimum duct heights, see table below).Contact your local Holyoake branch for details. 24 V AC or DC Supply Electro Thermal Resettable Release.Max 30 Sec Release and 60 Sec Reset, with integral 71 Degrees C Thermal Resettable Release.

Electro Thermal Resettable Links Model: IBD-ETR

Locking Pin

IBD-TLFusibleLink 71°C

IBD-TL2Latch Assy(Galvanised Steel)

IBD-TL

Note: Take suitable safety precautions for Hand and Eye Protection.

100

MIN 85

Combined Electro/Thermal Release

Blade Support/Locating Bar

Type ‘B’

Type ‘A’

Combined Electro/Thermal Release

Blade Support/Locating Bar

Page 13: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Fire Dampers, Performance Data – Series IBD

1

3

109

8

7

6

5

4

20

30

40

50

60

70

8090

100

150

200

125

0.1 .2 .3 .4 .5 .6 .8 1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0 8.0 10 15 20 30 40 50 70 100

Static

Pressure

(Pa)

30CV

25CV

20CV

15CV

10CV

7.5CV

5.0CV

3.5CV

Area Factor (From Table)

Notes1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.

2. Ratings are based on dampers installed in accordance with details in this catalogue, with ductwork upstream and downstream.

For pressure drop through an open IBD-A-V, or IBD-A-H fire damper use the

following procedure:

1. Find the Area Factor from the above table – enter duct height and width.

2. Determine Conversion Velocity (CV) by multiplying Area Factor by flow in

m3/s (CV = Area Factor x m3/s).

3. Enter pressure drop chart with Area Factor and establish intersection

with Conversion Velocity (CV) line just determined. Read pressure drop

on left hand side of the chart.

Note: Interpolations while not precise, are adequate for most calculations.

EXAMPLE:

Find the pressure drop across a 900 wide x 1504 high model IBD-A-V fire

damper, passing 11 m3/s.

1. From the table using interpolation, the Area Factor is 0.9.

2. CV = 11 x 0.9 = 10.

3. From pressure drop chart, pressure drop is 9 Pa.

(All dimensions include 6 mm clearance total between outside of damper frame and inside of duct).

AREA FACTOR TABLE – DUCT CONNECTION - STYLE A

Dim. ‘B’ Dimension ‘A’ Width (mm)

(mm) 100 200 300 400 500 600 700 800 900 1000 1100 1200

184 55.90 33.90 24.30 19.00 15.60 13.20 11.40 10.10 9.00 8.18 7.47

304 82.70 29.00 17.60 12.60 9.83 8.06 6.83 5.92 5.23 4.68 4.24 3.87

424 55.80 19.60 11.90 8.51 6.63 5.44 4.61 3.99 3.53 3.16 2.86 2.61

544 42.10 14.80 8.95 6.42 5.01 4.10 3.48 3.01 2.66 2.38 2.16 1.97

664 33.80 11.80 7.18 5.15 4.02 3.29 2.79 2.42 2.14 1.91 1.73 1.58

784 28.20 9.90 6.00 4.31 3.36 2.75 2.33 2.02 1.79 1.60 1.45 1.32

904 24.20 8.50 5.15 3.70 2.88 2.36 2.00 1.74 1.53 1.37 1.24 1.13

1024 21.20 7.45 4.51 3.24 2.53 2.07 1.75 1.52 1.34 1.20 1.09 0.99

1144 18.90 6.63 4.02 2.88 2.25 1.84 1.56 1.35 1.19 1.07 0.97 0.88

1264 17.00 5.97 3.62 2.60 2.02 1.66 1.41 1.22 1.08 0.96 0.87 0.80

1384 15.50 5.43 3.29 2.36 1.84 1.51 1.28 1.11 0.98 0.88 0.79 0.72

1504 14.20 4.98 3.02 2.17 1.69 1.38 1.17 1.02 0.90 0.80 0.73 0.66

1624 13.10 4.60 2.79 2.00 1.56 1.28 1.08 0.94 0.83 0.74 0.67 0.61

1744 12.20 4.27 2.59 1.86 1.45 1.19 1.01 0.87 0.77 0.69 0.62 0.57

319H

Fire

& S

mok

e Da

mpe

rs

Model: IBD-A-V, or H

Page 14: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series IBD – Fire Dampers, Performance Data

320H

Fire

& S

mok

e Da

mpe

rs

1

3

109

8

7

6

5

4

20

30

40

50

60

70

8090

100

150

200

125

0.1 .2 .3 .4 .5 .6 .8 1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0 8.0 10 15 20 30 40 50 70 100

Static

Pressure

(Pa)

30CV

25CV

20CV

15CV

10CV

7.5CV

5.0CV

3.5CV

Area Factor (From Table)

For pressure drop through an open IBD-B-V or IBD-B-H fire damper use the

following procedure:

1. Find the Area Factor from the above table – enter duct height and width.

2. Determine Conversion Velocity (CV) by multiplying Area Factor by flow in

m3/s (CV = Area Factor x m3/s).

3. Enter pressure drop chart with Area Factor and establish intersection

with Conversion Velocity (CV) line just determined. Read pressure drop

on left hand side of the chart.

Note: Interpolations while not precise, are adequate for most calculations.

EXAMPLE:

Find the pressure drop across a 500 wide x 514 high model IBD-B-V fire

damper, passing 2.2 m3/s.

1. From the table using interpolation, the Area Factor is 4.51.

2. CV = 2.2 x 4.5 = 10.

3. From pressure drop chart, pressure drop is 8 Pa.

(All dimensions include 6 mm clearance total between outside of damper frame and inside of duct).

Model: IBD-B-V, or H

AREA FACTOR TABLE– DUCT CONNECTION - STYLE B

Dim. ‘B’ Dimension ‘A’ Width (mm)

(mm) 100 200 300 400 500 600 700 800 900 1000 1100 1200

84 67.90 48.70 38.00 31.10 26.40 22.90 20.20 18.10 16.40 14.90

179 42.40 25.70 18.50 14.40 11.80 9.99 8.67 7.65 6.85 6.20 5.66

299 67.80 23.80 14.40 10.40 8.07 6.61 5.60 4.86 4.29 3.84 3.48 3.17

394 50.30 17.60 10.70 7.68 5.99 4.91 4.16 3.60 3.18 2.85 2.58 2.35

514 37.90 13.30 8.07 5.79 4.51 3.70 3.13 2.72 2.40 2.15 1.94 1.78

609 31.80 11.10 6.75 4.85 3.78 3.10 2.62 2.27 2.01 1.80 1.63 1.49

729 26.30 9.24 5.60 4.02 3.13 2.57 2.18 1.89 1.67 1.49 1.35 1.23

824 23.20 8.14 4.93 3.54 2.76 2.26 1.92 1.66 1.47 1.31 1.19 1.09

944 20.20 7.07 4.29 3.08 2.40 1.97 1.67 1.44 1.28 1.14 1.03 0.94

1039 18.30 6.41 3.89 2.79 2.17 1.78 1.51 1.31 1.16 1.03 0.94 0.86

1159 16.30 5.73 3.47 2.49 1.94 1.59 1.35 1.17 1.03 0.93 0.84 0.76

1254 15.10 5.29 3.21 2.30 1.79 1.47 1.25 1.08 0.95 0.85 0.77 0.71

1374 13.80 4.82 2.92 2.10 1.63 1.34 1.13 0.98 0.87 0.78 0.70 0.64

1469 12.80 4.50 2.73 1.96 1.53 1.25 1.06 0.92 0.81 0.73 0.66 0.60

1589 11.80 4.15 2.52 1.81 1.41 1.15 0.98 0.85 0.75 0.67 0.61 0.55

Notes1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.

2. Ratings are based on dampers installed in accordance with details in this catalogue, with ductwork upstream and downstream.

Page 15: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Interlocking Blade Fire Damper - Series IBD

321H

Product Ordering Key and Suggested Specifications

Fire

& S

mok

e Da

mpe

rs

Vertical,

or

Horizontal

Mounting.

Nominal

Duct Size,

(‘A’ Width

Dimension

First).

TL = Test Latch with

71º C Link,

ETR = Electro Thermal

Resettable Link.

Single Pole

Micro Switch

(For Release Position).

2 x Single Pole

Micro Switch

(For Reset And

Release Position).

Extended Damper Sleeve,

(Specify Wall Thickness).

Fire dampers shall be interlocking blade, curtain type, conforming to the requirements of the Australian and N.Z. Building Code and shall be built to comply with construction details proven by prototype tests conducted in accordance with AS 30, AS 1682, or UL 555, to withstand exposure to controlled flame for no less than 4 hours before failure of the assembly as a whole, or any of its components and shall qualify for a 4 hour fire resistance rating, in terms of Australian Standard AS 1530, Part 4, fire resistance test of structures.

Fire dampers shall be equipped for either vertical, or horizontal mounting and shall close by release of a fusible link at a temperature of 71ºC, or by means of an Electro Thermal Resettable Release device incorporating a 71º C Thermal Resettable Release.

“Safe Test” Test latches and access doors shall be provided for all fire dampers, so that they may be test operated at any time after installation without destroying fusible links and annually in accordance with AS 1851 - 2012 ( Section 13 ), Routine service of fire protection systems and equipment.

Fire dampers shall be installed in wall, or floor openings utilizing factory fitted galvanised steel mounting sleeves and angles, other materials and practices required to satisfy the Australian and N.Z. Building Code and AS 1682 Parts I & II and as shown in the manufacturers installation instructions.

Fire dampers shall be Holyoake Series IBD, with sleeves Holyoake Model IBD-MSU, all as manufactured and supplied by Holyoake.

IBD – A – V – WIDTH (A)mm – TL – MSU – SPECIAL B H x ETR OPTIONS C HEIGHT (B) mm CR CO

Universal

Mounting

Sleeve

Interlocking

Curtain Blade

Fire Damper

Duct

Connection

Style

Page 16: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series HFS – Fire & Leakage Rated Smoke Damper

322H

Model: HFS-R-146

Fire

& S

mok

e Da

mpe

rs

Latch: Stainless steel with 71ºC fusible link.

Axles: 84 mm long hex, M.S. bright zinc-plated pins, mechanically locked and welded to half hex blade channel.

Cranks: 6 mm M.S. bright zinc-plated, force fitted to hex pin and S.S. link bar pin.

Blade Rotation: Parallel only.

Finish: Mill.Maximum Velocity: 10m/s

Frame Bracing: Diagonal corner braces on all dampers above 300 x300.

Handing: Standard left hand as illustrated. Alternative right hand is available, specify when ordering.

Remote Indication: All units are fitted with a normally open single pole limit

switch activated by the blade. Standard is set to close circuit on damper closure. Alternative (close circuit on damper opening) is available, specify when ordering.

Sleeve Material: Galvanised Steel Type Z275. Maximum Dimensions

Per Side mm Sleeve Thickness mm 0-300 0.45 301-762 0.55 763-1113 0.75

Mounting Angles: 40 x 60 x 2 mm galvanised steel angle, (x4 per side, x2).

Installation: HFS-R-146 dampers must not be installed with the axles vertical. They may be used in either vertical, or horizontal planes, with air flow and fire exposure from either direction.

Dampers must be fixed square and free from racking.

Duct Connection: Mounting Sleeves are supplied raw edged. Duct Joints

to the damper must be “Break-away” type e.g. ‘S’ cleat.

The Holyoake HFS-R-146 is a fire and leakage rated multi-leaf steel damper, for the prevention of the spread of fire and/or smoke through ducted air systems, or between plenums. Self contained as a fire damper and externally operable by electric, or pneumatic actuator; constructed to comply with AS 1668.1, 1998 and AS 1682.1, 1990.

Fire Rating: Tested in accordance with AS 1530.4,1990, integrity was maintained for a minimum of 4 hours. For purposes of the Australian and New Zealand Building Code they have a F.R.L./F.R.R. of – / 240 / –

Tests: BRANZ Fire Test Certificate No. FTC 390, HFS-R-146 mounted in a concrete wall, or floor. (Certified for 240 minute fire rating).

BRANZ Fire Test Certificate No. FTC 391, HFS-R-146 mounted in a plasterboard wall. (Certified for 30 and 60 minute fire rating).

(Certificates are available upon request).

Mounting: Sleeve mount in accordance with AS 1682 - 1990, Part 2, and generally as described on pages 313H - 317H and 323H, with blade axles located within the fire partition. Sleeves and mounting angles are furnished as standard. Holes through walls, or floors must be sized to provide room for expansion in accordance with AS 1682.1 - 1990. HFS-R-146 requires a 12 mm tolerance gap on all four sides.

Actuators: Because of critical fitting requirements, actuators must be factory fitted. Factory supplied make may vary from time to time.

Specify: (a) Make. (b) Voltage (if electric).

(c) Pressure range (if pneumatic). (d) Spring, or non-spring return (if electric).

(e) Fail open, or closed (if spring). (f) Temperature rating.

Standard Construction

Dimensions: Nominal Size is sleeve ID, always stated as W x H, in that order

Note: Add 6 mm to Nominal W (Width) and Nominal H (Height) for Internal Duct size

Minimum Nominal Size: 200 mm Wide x 230 mm High.

Maximum Nominal Size: 900 mm Wide x 1113 mm High.

Frame: Mild steel grade G250 galvanised to Z275, 167 x 23 x 1.15 mm roll formed hat section, with machine notched joints and corner gussets.

Blades: Mild steel grade G250 galvanised to Z275, 157 x 1.15 mm roll formed “double vee and hex, on 146 mm shaft centres.

Blade Seals: Silicon seal on blade edge.

Side Seals: Stainless steel type 301.

Blade Linkage: External in frame, concealed between frame and mounting sleeve.

Bearings: 12.5 mm I.D. x 28 mm O.D. grease-packed ball races, pressed into frame.

Control Shaft: 12.5 mm O.D. x 1.2 mm wall 304 stainless steel tube.

Control Linkage: 71ºC fusible link driven crank type, with integral constant force return spring.

HFS-R-146

With Sleeve

and Actuator.

Page 17: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Model: HFS-R-146

For maximum open free area, select exact modular height. Exact modular height is where H = H Min.

For non modular height use the following: Determine number of blades from Table 1, then:

W (Max.900)

HFS-R-146

(Mounting Sleeveand ActuatorOmitted for Clarity).

SS 304Tubular Shaft.

Grease Packed& Sealed BallBearings.

Blade Edge Seals.

71°CFusible Link.

SS 301Side Seal.

Latch WithFusible Link.

Limit Switch.

W (Max 900 Nom).

TABLE 1 - NOMINAL DIMENSIONS

No. of Blades 1 2 3 4 5 6 7

H Min 230 376 522 668 814 960 1106

H Max 375 521 667 813 959 1105 1113

A Min 115 115 115 115 115 115 115

B Min 33 33 33 33 33 33 33

C Min 175 175 175 321 467 613 759

40

55

B

146

A

A

H(Max 1113

Nominal)

C

167

22

15

B

A = H - H Min + A Min 2

C = H - H Min + C Min

A 300 = 300 - 230 = 35 + 115 = 150

2

2

B 300 = 300 - 230 = 35 + 33 = 682

C 300 = 300 - 230 = 35 + 175 = 2102

B = H - H Min + B Min 2

Jack Shaft Centre From Top of Casing

Top + Bottom Blade Centres Blade Stop Heights

e.g. 300 Height

323H

Fire

& S

mok

e Da

mpe

rs

Note: Add 6 mm to Nominal W (Width) and Nominal H (Height) for Internal Duct Size.

Dimensional Data – Series HFS

Notes1 Standard sleeve length of 450 mm will accommodate walls 80 - 200 mm thick. For other wall depths, specify special length.

2 Limit switch tails.

3 Typical actuator. For smallest damper, fits within overall damper and mounting angle height.

4 M6 galvanised bolts (* Refer to page 313H ‘Fire Damper Installation Notes’).

5 Packing in the expansion gap, High Temperature Mineral Wool, (Supply and fit by others ).

6 Multiple assemblies need to be individually operated and separated by a minimum of 200 mm of structural support,

(in either width, or height); of the same fire rating and structural integrity as the surrounding wall.

Illustration details an example of arrangement to be supplied and is as tested.

Trim sleeves as per note 6 on page 317H, to comply with AS 1682, Part 2, 1990.

55

60 x 40 x 2 GMSFixed MTG Angle

60 x 40 x 2 GMS2

3

1450

165

Min

125

200 Max80Min

5

6

6

4

W (Nominal)100

146

C

H

60

Slotted For M6 Bolts*.

4

H(Nominal)

8

7

Page 18: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

Series HFS – Performance Data

324H

Fire

& S

mok

e Da

mpe

rs

1000

100

200

300

400

500

10

20

30

40

50

1

2

3

4

5

1 2 3 4 5 6 7 8 20 30 40 50 60 70 8010 100

25CV

15CV

10CV

7.5CV

5CV

4CV

Static

Pressure

(Pa)

Area Factor (From Table)

Use the table and chart to determine the pressure drop through

HFS – R– 146 Fire / Smoke Dampers.

1. Determine area factor for damper by entering the area factor table with

duct width and height.

2. Find conversion velocity (CV) by multiplying area factor for selected size

damper by flow rate in m3/s. CV = Area Factor x m3/s.

3. Enter pressure drop chart with area factor and proceed up to the

appropriate conversion velocity (CV) line.

Read the pressure drop (Pa) on the left hand side of the chart.

EXAMPLE:

Find the pressure drop across a 350 wide x 814 high model HFS-R-146

Fire/Smoke Damper handling 1.3 m3/s.

1. From the table the area factor is 5.25.

2. CV = 1.3 x 5.25 = 6.825.

3. From pressure drop chart, Pressure Drop is 12Pa.

(Note: Interpolations while not precise, are adequate for most calculations).

Notes

AREA FACTOR TABLE

Nom Ht. No. of Nominal Width (mm)

(mm) Blades 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900

230 1 66.56 48.91 38.66 31.97 27.24 23.74 21.03 18.88 17.13 15.67 14.45 13.40 12.49 11.70 11.00

376 2 29.31 21.54 17.02 14.07 12.00 10.45 9.26 8.31 7.54 6.90 6.36 5.90 5.50 5.15 4.84

522 3 18.79 13.81 10.91 9.02 7.69 6.70 5.94 5.33 4.84 4.42 4.08 3.78 3.53 3.30 3.11

668 4 13.83 10.16 8.03 6.64 5.66 4.93 4.37 3.92 3.56 3.26 3.00 2.78 2.59 2.43 2.29

814 5 10.94 8.04 6.35 5.25 4.48 3.90 3.46 3.10 2.81 2.58 2.37 2.20 2.05 1.92 1.81

960 6 9.05 6.65 5.26 4.35 3.70 3.23 2.86 2.57 2.33 2.13 1.96 1.82 1.70 1.59 1.50

1106 7 7.72 5.67 4.48 3.71 3.16 2.75 2.44 2.19 1.99 1.82 1.67 1.55 1.45 1.36 1.28

Note: Add 6 mm to Nominal W (Width) and Nominal H (Height) for Internal Duct Size.

Model: HFS-R-146

1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.

2. Pressure drop data is for dampers tested with ductwork on both the up and downstream sides.These values need to be suitably increased where dampers

are mounted with ductwork on one side only, or when mounted onto plenum walls. (Refer to SMACNA, or ASHRAE System Design Guides).

3. Data is for the specific sizes listed in the Area Factor table. For other sizes use the next size down and make a proportional adjustment based on the

approximate increase in free area.

Notes

Page 19: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

325H

Fire

& S

mok

e Da

mpe

rs

Fire & Leakage Rated Smoke Damper – Series HFS

Fire and Leakage Rated Smoke dampers shall be multi-leaf dampers, constructed to comply with details proven by prototype tests conducted in accordance with AS 1530.4.

To withstand exposure to controlled flame for no less than 4 hours before failure of the assembly, or any of its components.

Fire and Smoke dampers shall be equipped for either vertical, or horizontal mounting, are complete with a suitable electric, or pneumatic actuator and shall release by a fusible link at a temperature of 71ºC.

Alternatively the fire/smoke damper can be activated by a remote signal from a fire alarm panel (supply and fit by others).

Fire and Smoke dampers should be annually, or biannually tested as determined by AS 1851 - 2012 ( Section 13 ), Routine service of fire protection systems and equipment; in accordance with their design failure position. Fire and Leakage Rated Smoke dampers, shall be Holyoake series HFS-R-146 with Sleeves, Holyoake Model HFSR146 - MSU and shall be as manufactured and supplied by Holyoake.

HFS-R-146 – WIDTH (W)mm – MSU – OPTIONS – ACTUATORS x HEIGHT (H)mm

Fire and Leakage RatedSmoke Damper.

Reverse Handing (Right Hand).Reverse Switching

(Close Circuit onDamper Opening).

Extended Damper Sleeve(Specify Wall/Slab

Thickness).

Nominal Size Sleeve ID (‘W’ Width Dimension First).

UniversalMounting Sleeve.

Specify

(a) Make.

(b) Voltage (if electric).

(c) Pressure range (if pneumatic).

(d) Spring, or non-spring return(if electric).

(e) Fail open, or closed (if spring).

(f) Temperature rating.

Product Ordering Key and Suggested Specifications

Guide Product Weights

Fire & Leakage Rated Smoke Dampers

HFS-R-146 200 x 230 (Inc Sleeve, Angles & Motor)

HFS-R-146 250 x 250 (Inc Sleeve, Angles & Motor)

Approximate Weight in Kg

10.1

11.33

Important NoteHFS dampers must be transported with their blades horizontal, not in the vertical position.

Page 20: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013

The Holyoake Series LR (Low Radiation) Fire Dampers are designedto impede the spread of fire and heat within building compartments, whilst maintaining the walls integrity. The low leakage insulated damper blade assembly with blade tip sealing ring, forms a solid barrier against flame, smoke and hot gases. Complying with AS/NZS 1668.1 - 1998 the LR Fire Damper is certified for a 4 hour rating in a masonry wall and a 2 hour rating in a plasterboard wall.

4 Hour FRL/FRR and Radiation Protection to AS 1530 part 4.The Holyoake LR Fire Smoke damper has been designed to providepremium protection for occupants and building structures in theevent of a fire. The innovative heat radiation blocking damper blade, will snap closed within seconds upon the air temperature reaching 71̊ C, providing rapid temperature response. Furnace testing to AS 1530.4 - 1997 has proven that the damper will stop the passage of fire and smoke through a fire rated wall for at least 4 hours.

The LR Damper integrates both a fire, smoke and control damper intoone easy to install, maintain and test unit. It is supplied complete with external low radiation sleeve and mounting flanges. Fire protection is provided by a fusible link and damper blade that seals the duct shut in the event of a fire. The damper blade is designed to reduce the transfer of heat radiationthrough the firewall, providing induct heat radiation control, while theouter solid insulating sleeve ensures minimal conduction of heat intothe wall cavity.

The unique Series LR damper design ensures that the damper blade always stays within the confines of the wall and provides a cost effective solution.

Features:

Model: LR

Series LR – Low Radiation Fire Damper

326H

Fire

& S

mok

e Da

mpe

rs

Standard Insulated.Sectional View Through Plasterboard Wall.

Blade Tip Sealing Ring

Sliding FlangePermanently Attached Flange

Non - ConductiveSolid InsulatingSleeve

Minimal HeatTransfer IntoWall Cavity

Insulated Damper Blade

Fusible Link

Standard Insulated. For Plasterboard or Masonry Walls.

Optional Un-insulated. Sectional View Through Masonry Wall.

Blade Tip Sealing Ring

Sliding FlangePermanently Attached Flange

Galvanised SteelSleeveInsulated

Damper Blade

Fusible Link

Fire Proof Sealant

Optional Un-insulated. For Masonry Walls Only.

Guide Product Weights

Low Radiation Fire & Smoke Damper

LR 150

Approximate Weight in Kg

4.17 Boxed

Page 21: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

Rating

Masonry Walls Exova WarringtonFire Aus Pty LtdTest Certificate SFC41085.3

FRL/FRR rating: – /240/ – Heat radiation less than 10 kW/m2

Framed Walls*Exova WarringtonFire Aus Pty LtdTest Certificate SFC41084.3

FRL/FRR rating: – /120/ 30 *Heat radiation less than 10 kW/m2

NATA certified testing to AS 1530 part 4, to the requirements of AS 1682 Part 1.

* In accordance with Exova WarringtonFire 45757.1.

Performance Data

Leakage When Damper Shut

327H

Fire

& S

mok

e Da

mpe

rs

Performance and Dimensional Data – Series LR

1. Cut Hole

2. Insert LR Damper

Through Hole in WallFixing

Screw Fix As Provided

Fixing

4. Attach Sliding

Flange & Fix

to Wall

3. Fix attached

flange to wall

Static Pressure Drop When Damper Fully Open

Flow (l/s) ∆Ps (Pa) fully open

10 1

20 2

40 5

60 9

80 16

100 24

120 36

140 47

160 61

180 78

200 94

Installation

1 The LR damper has one flange permanently attached. Installation is simple. A circular hole is made through the wall where the duct is to penetrate.

Cut Size In Wall mm Insulated Un-insulated LR150 Ø180 - Ø185 LR150 Ø155 - Ø160

2 Mount the LR damper through the hole in the wall.

3 Fix the outside flange. 4 On the opposite side of the wall mount the sliding flange over the LR Damper sleeve and fasten to both the damper and wall.

In plasterboard walls the weight of the damper must be supported independently of the wall lining, in accordance with plasterboard manufacturers specifications.

Dimensions:

(* Includes steel and timber framed walls).

LR 150

A 145

B 110

C 95 -170

D 430

E 137

Note: All Dimensions in mm.

Damper Setting

The damper can be used for balancing and set using the attached external handle. The clamp nut on the handle must be tightened to hold the damper blade in place. The handle may also be used to check the functioning of the damper when inspection is due.

Series LR dampers are suitable for Wall Mounting Only.

Pressure Behind Damper (Pa)

Leakage

(l/s)14

12

10

8

6

4

2

0

0 500 1000 1500

Note

Page 22: Fire Dampers & Smoke Dampers - Holyoakeattachments.holyoake.com/products/files_upload/Fire... · Fire Dampers – Series IBD 311H Fire & Smoke Dampers Model: IBD-C-V Interlocking

© Holyoake Air Management Solutions – 2013328H

Fire

& S

mok

e Da

mpe

rs

Holyoake LR Low Radiation Fire Dampers shall have a 4 hour rating in a masonry wall and a 2 hour rating in a steel, or timber framed wall. The rating shall be certified to AS 1530.4 and to the requirements of AS 1682.1. The rating applies to fires on both sides of a fire wall. Heat radiation emitted during testing to AS 1530.4 was less than 10 kW/m2. LR Low Radiation Fire Dampers contain a fusible link that releases and allows the damper to close upon reaching 71ºC. LR Fire Dampers should be annually tested as determined by AS 1851 - 2012 ( Section 13 ). Routine service of fire protection systems and equipment. An external lockable handle is included as standard that can be used to position the damper blade to provide volume control. No additional insulating material will be needed to install the Low Radiation Fire Damper. Low Radiation Fire Dampers shall be Holyoake Series LR Standard (Insulated) and shall be manufactured and supplied by Holyoake.

Patent Pending

LR150

Model

OPTION

Standard

(Insulated)

Product Ordering Key and Suggested Specifications

Holyoake LR Low Radiation Un-insulated Fire Dampers shall have a 4 hour rating in a masonry wall, (not suitable for steel, or timber framed walls). The rating shall be certified to AS 1530.4 and to the requirements of AS 1682.1. The rating applies to fires on both sides of a fire wall. Heat radiation emitted during testing to AS 1530.4 was less than 10 kW/m2. LR Low Radiation Un-insulated Fire Dampers contain a fusible link that releases and allows the damper to close upon reaching 71ºC. LR Fire Dampers should be annually tested as determined by AS 1851 - 2012 ( Section 13 ). Routine service of fire protection systems and equipment. An external lockable handle is included as standard that can be used to position the damper blade to provide volume control. No additional insulating material will be needed to install the Low Radiation Un-insulated Fire Damper. Low Radiation Un-insulated Fire Dampers shall be Holyoake Series LR (Un-insulated) and shall be manufactured and supplied by Holyoake.

LR150

Model

OPTION

Un-insulated

Series LR – Low Radiation Fire Damper