engineering guide radiant products - amca - air … guide - radiant products when to use radiant...
TRANSCRIPT
Please refer to the Price Engineer’s HVAC Handbook for more information on Radiant Heating and Cooling
S E C T I O N H
Engineering GuideRadiant Products
H-2 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
RadiantProductsEngineering Guide
Introduction To Radiant Heating and Cooling
Radiantheatingandcoolingsystemsofferanenergyefficientalternativetoall-airsystems.Inmost cases, the supply air volume oftheairhandlingsystem is limited in sizeto satisfy only the ventilation and latentloads,withtheradiantsystemmakingupthe balance of the heating and coolingloads.Thiscomfortablemethodofheatingandcoolingmaysaveenergy,spaceandbuildingmaintenancecosts.Thefollowingpagesofferanintroductiontotheproducts,systemsanddesignmethodology,aswellastheadvantagesandlimitationsofradiantheatingandcooling.
Managementofheat loadscangenerallybeclassified into twodifferent types:all-air systems or hybrid systems. All-airsystems have been themost prominentinNorthAmericaduringthe20thcenturyandhavebeeninusesincetheadventofairconditioning.Thesesystemsuseairto
serviceboththeventilationrequirementaswellasthebuildingcoolingload.Ingeneral,thesesystemshaveacentralairhandlingunit(orrooftopunit)thatdeliversenoughcoolorwarmairtosatisfythebuildingload.Diffusersmountedinthezonedeliverthisairinsuchawayastopromotecomfortandevenlydistributetheair.Inmanycases,theamountofairrequiredtocoolorwarmthespace or the fluctuations of loadsmakedesigninginaccordancetotheseprinciplesdifficult.Draftisnotuncommon,andsomeceilingdiffusershavebeenknownto“dump”atlowcapacities.
Hybridsystemshavetwocomponents:anair-sideventilationsystemandahydronic(orwater-side)radiantsystem.Theair-sideisdesigned tomeetallof theventilationrequirements for thebuilding,aswell assatisfyalllatentloads.Itisa100%outsideairsystemandbecausetheprimaryfunction
of thesupplyair system isventilationasopposed tocooling, itcanbesuppliedathighersupplyairtemperaturesthanistypicalofoverheadairdistributionsystems.Thewater-sideisdesignedtomeetthebalanceofthesensiblecoolingandheatingloads.These loads may be handled by water based products, such as radiant panels, whichtransfer heat mainly by thermal radiation, andchilledsails,whichtransferheatusinga combination of thermal radiation and naturalconvection. RadiantpanelshavebeenusedforsensibleheatingandcoolinginNorthAmericanbuildingsforoverhalfacentury,andareawidelyrecognizedand well-establishedtechnology. Chilledsailswere originally developed in Europe inthe late 1990s, and are a relatively newtechnologyinNorthAmerica.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-3
RadiantProductsEngineering Guide
Figure 1: Examplesofradiantheatingandcooling
Radiant heating and cooling systemsprovideaneffectivemethodforsatisfyingtheheatingand/orcoolingloadsofaspacewhilepromotingahighlevelofoccupantcomfortandenergyefficiency.
Hydronicsystemshavebeensuccessfullyused in several applications havingdramatically different characteristics. Someexamplesofareaswhere radiantsystemshavebeenappliedinclude:
• GreenBuildings • Hospitals• BurnCenters • IsolationRooms• Schools • DataCenters• OfficeBuildings • Airports• Cafeterias • TelevisionStudios• Theaters • Casinos
Benefits of Air-Water SystemsTherearemanybenefits toheatingandcoolingusingradiantpanelsandchilledsails. Advantagesofthesewaterbasedheatingandcoolingsystemsoverothermechanicalsystemsinclude:• Energyandsystemefficiency• Reducedsystemhorsepower• Indoorenvironmentalquality• Improvedindoorairquality• Increasedthermalcomfort• Reducedmechanicalfootprint• Lowermaintenancecosts• Improvedsystemhygiene
Radiantsystemsareagoodchoicewhere:• Thermalcomfortisamajordesign
consideration• Areashavehighsensibleloads• Areas require a high indoor air quality
(100%outdoorairsystem)• EnergyconservationisdesiredEnergy EfficiencyTheheattransfercapacityofwaterallowsforareductionintheenergyusedtotransportanequivalentamountofheatasanall-airsystem(Stetiu,1998).Thesereductionscanbe found primarily through reduced fanenergy.
The higher chilledwater supply (CHWS)temperaturesusedwithactiveandpassivebeam systems, typically around 58 °F[14.5°C],providemanyopportunitiesforareductioninenergyuse,includingincreasedwater-sideeconomizeruse.ThisincreasedCHWS temperature also allows formorewater-sideeconomizerhoursthanwouldbepossiblewithothersystemswhereCHWStemperaturesaretypically~45°F[7°C].
Concepts and Benefits
Indoor Air QualityDepending on the application, undermaximum load, only ~15 to 40% of thecoolingairflowinatypicalspaceisoutdoorairand is requiredbycode tosatisfy theventilation requirements.The balance ofthesupplyairflowisrecirculatedairwhich,whennottreated,cantransportpollutantsthrough the building. Radiant systemstransferheatdirectlyto/fromthezoneandare often used with a 100% outdoor airsystemwhichexhaustspollutedairdirectlyto the outside, reducing the opportunityforVOCsandillnesstotravelbetweenairdistribution zones.
NoiseRadiant systems do not usually havefan powered devices near the zone.Thistypicallyresultsinlowerzonenoiselevelsthanwhatisachievedwithall-airsystems.Insituationswherepassivebeamsareusedinconjunctionwithaquietairsystem,suchasdisplacementventilation,theopportunitiesfor noise reduction increase further.
Reduced Mechanical FootprintThe increased cooling capacity of waterallowsthetransportsystemtobereducedinsize.Itisgenerallynotunusualtobeabletoreplace~60ft²[6m²]ofairshaftwitha 6in. [150mm]waterriser, increasingtheamountoffloorspaceavailableforuseorlease.Duetothesimplicityofthesystems(i.e.reductioninthenumberofmovingpartsand the elimination of zone filters, drainpans,condensatepumps,andmechanicalcomponents),theretendstobelessspacerequiredintheinterstitialspacetosupporttheHVACsystem.
Lower Maintenance CostsWithnoterminalunitorfancoilfiltersormotorstoreplace,asimplecleaningisallthat is required in order tomaintain theproduct.
H-4 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
When To Use Radiant Systems
Hygienic SystemWith the elimination of the majority of filtersanddrainpans, there isa reducedriskofmoldorbacteriagrowthintheentiremechanical system.
Radiant systems such as radiant panelsand chilled sails arewell-suited to someapplications and less so to others. As aresult,eachapplicationmustbereviewedforpotentialbenefitsaswellasthesuitabilityofthesetypesofsystems.Oneconsiderationwhichcanassistinthedecisiontoemployhydronicsystemsasopposedtoanall-airsystem, is the air-side load fraction—orthepercentageofthetotalairsupplythatmust be delivered to the zone to satisfycodeanddehumidification requirements.Table1showstheloadfractionforseveralspaces.Inthetablethebestapplicationsforhydronic systems are those with the lowest air-sideloadfractionastheyaretheonesthatwillbenefitthemostfromtheefficienciesofhydronicsystems.Anotherfactorwhichshouldbe examined is the sensibleheatratioorthepercentageofthecoolingloadthat issensibleasopposed to latent.Thelatent loadsmustbesatisfiedwithanairsystemandoffersomesensiblecoolingatthesametimebecauseofthetemperatureofdehumidifiedair.Ifthetotalsensiblecoolingloadissignificantlyhigherthanthecapacityoftheairsuppliedtosatisfythelatentloads,aradiantsystemmightbeagoodchoice.
Commercial Office BuildingsInanofficebuildinghydronicheatingandcoolingsystemsprovideseveralbenefits.Thelowersupplyairvolumeoftheairhandlingsystemprovidessignificantenergysavings.In addition, the smaller infrastructurerequiredtomovethislowerairflowallowsforsmallplenumspaces, translating intoshorterfloor-to-floorconstructionorhigherceilings.Thelowersupplyairvolumeandelimination of fans at or near the spaceoffersasignificantreductioningeneratednoise.Oftenthelowerairflowtranslatestoreheatrequirementsbeingreduced.Inthecaseof100%outsideairsystems,thelightingloadcapturedinthereturnplenumisexhaustedfromthebuilding,loweringtheoverallcoolingload.
SchoolsSchools are another application that canbenefitgreatlyfromradiantpanelsandchilledsailssystems.Similartoofficebuildings,thebenefitsofalowersupplyairvolumetothespacearelowerfanpower,shorterplenumheight, reduced reheat requirement, andlowernoise levels (oftenacriticaldesignparameterofschools).
Hospital Patient RoomsHospitals are unique applications in thatthe supply air volume required by localcodesforeachspaceisoftengreaterthantherequirementofthecoolingandheatingload.Insomecasesthestandardorcoderequires thesehigherair-changerates forall-air systems only. In these cases thetotalair-changeraterequiredisreducedifsupplementalheatingor cooling isused.This allows for a significant reduction insystemairvolumeandyieldsenergysavingsandotherbenefits.
Furthermore, because these systems aregenerally constant air volume with thepotentialtoreducetheprimaryair-changerates,reheatandthecoolingenergydiscardedaspartofthereheatprocessisasignificantenergysavingsopportunity.Dependingontheapplication,a100%outsideairsystemmay be used. These systems utilize no returnairandnomixingofreturnbetweenpatientrooms,potentiallyloweringtheriskofhospitalassociatedinfections.
Hotels / Dorms Hotels,motels,dormitories,andsimilartypebuildings can also benefit fromhydronicsystems. Fanpowersavingsoftencomefrom the elimination of fan coil units located intheoccupiedspace.Theenergysavingsassociatedwiththese“local”fansissimilarinmagnitudetothatoflargerairhandlingsystems.Italsoallowsfortheeliminationof the electrical service required for theinstallation of fan coil units as well as a reduction in the maintenance of the drain andfiltersystems. The removalof thesefansfromtheoccupiedspacealsoprovideslowernoiselevels,whichcanbeasignificantbenefitinthesleepareas.
ApplicationTotal Air Volume (Typ.)
Ventilation Requirement (Typ.)
Air-Side Load Fraction
Office 1cfm/ft2[5L/sm2] 0.15cfm/ft2[0.75L/sm2] 0.15
School 1.5cfm/ft2[7.5L/sm2] 0.5cfm/ft2[2.5L/sm2] 0.33
Lobby 2cfm/ft2[10L/sm2] 1cfm/ft2[5L/sm2] 0.5
PatientRoom 6 ach 2 ach 0.33
Load-drivenLab 20 ach 6 ach 0.3
Table 1: TypicalloadfractionsforseveralspacesintheUnitedStates
LimitationsThereareseveralareasinabuildingwherehumidity canbedifficult to control, suchas lobby areas and locations of egress.These areasmay see a significant shortterm humidity load if the entrances are not isolated insomeway(revolvingdoorsorvestibules). In theseareas,achoiceofacomplimentarytechnologysuchasfancoilunitsordisplacementventilationisideal.
Otherapplicationsmayhavehighairflow/ventilationrequirements,suchasanexhaustdriven lab. The majority of the benefitprovidedbythehydronicsystemislinkedtothereductioninsupplyairflow.Assuch,theseapplicationsmaynot seesufficientbenefittojustifytheadditionofthehydroniccirculationsystem,makingthemnotlikelytobeagoodcandidateforthistechnology.
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-5
Products - Radiant Panels
OperationRadiantpanelsmainlyusethermalradiationtohandletheheatingorcoolingloadsofaspace.ThermalradiationheatexchangeisbasedondifferencesinsurfacetemperaturesasdiscussedinChapter3—IntroductiontoHeatTransfer from the Price Engineer'sHandbook.Radiantpanelsaddenergytoorremoveitfromaroommainlyusingradiationwith surfaces in the room, but also directly tooccupants(Figure 2).Toalesserextent,thepanelsalsoheatorcoolaroomthroughconvectionoftheroomairasitisheatedorcooledbythepanelsurface.
Because radiant panels can handle thesensibleportionofabuildingloadtheymustbepairedwithanairsystemforventilationand latent load removal. In heating, forexample,heatfromwarmwateristransferredtothepanelsurfaceviaconduction.Theheatpasses through the tubing, themountingextrusion(the‘fin’),andthepanelitself,tothepanelsurface.Atthesurface,heatisbothradiated to other surfaces in the room and transferredtoroomairvianaturalconvection.
Theheattransferthrougharadiantpanelcaneasily be modeled with a thermal resistance circuit, as in Figure 3. The resistance circuit represents the actual components of aradiantpanel.Thenodesrepresentvarioustemperatures of the panel componentsurfaces,andthe‘resistors’representtheheatconductionthroughthepanelcomponentsandtothesurroundingroom.The t̅w node representsthemeanwatertemperaturethattransfersthroughthecoppertubingtotheactualpanel components. Toachieve themaximum possible surface temperatureof thepanel,Tsurf, the conduction from the pipe to the fin to the panel surfacemustbemaximized,or,inversely,theresistancemustbeminimized.Thiscanbeachievedbyusingmaterialsthatarehighlyconductivesuchascoppertubingandaluminumforthefinandpanel.Evensurfacecontactbetweenthe water tubing and the fins decreasesresistance,alongwiththermalpastewhichcanbeappliedbetweenthefinandthepanelsurface tohelpspreadheatevenly to thepanelsurface(Figure 4)
RADIATION
Figure 2: Radiationpathways
Rconv,s
Tair, ceiling
Tpanel, outer insulation
Rinsulation
AUST,ceiling
Rrad,s
Rconv,room
Tair, room
Fin
SurfaceAUST, room
Tsurf, panel
Rrad,room
Rfin
T fin, ave
Rpanel surface Copper tubing with
Towards slab
Towards room and occupants
AUST = Area-weighted temperature of all indoor surfaces of walls, ceiling, floor, windows, doors, etc.
Figure 3:Thermalresistancecircuitdiagramofamodularradiantpanel
Without Thermal Paste
With Thermal Paste
Figure 4: Surfacetemperaturedistributionofaradiantpanel
RadiantProductsEngineering Guide
H-6 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Interconnect
Return
The amount of thermal energy that istransferredtotheroomsurfacesviaradiationisdependentontheviewfactorsfromthepaneltothevariousroomsurfaces,alongwiththeemissivityofthepanelsurface.Alargertemperaturegradientresultsingreaterthermalradiation.Also,theviewfactorsfromthepaneltotheroom,aswellastheemissivityofthepanelsurfaceaffectthetemperatureofthereceivingsurface.RefertoChapter3—IntroductiontoHeatTransferoftheEngineer'sHandbookforfurtherdetailsonthetheoryofradiantheattransfer.Insulationonthebackofthepanelhelpsdecreasetheamountofheatthattravelsbyradiationorconvectiontotheceiling.
ApplicationsRadiantpanelscanbeappliedtovirtuallyany space, especially areas with highsensible loads,areas that requireahighindoorairquality,orareaswherethermalcomfortandenergyconservationaremajordesignconsiderations.Typicalapplicationsofhydronicradiantpanelsarehospitals—includingpatientrooms,isolationrooms,andburncenters—schools,datacenters,officebuildings,andairports.
1. Linear Radiant Panels Linearradiantpanelsareconstructedofaseriesof integratedaluminumheatsinksand copper tubing. Multiple heat sinksformthevisiblefaceofthepanelandarejoinedviatongue-and-grooveconnections.Insulatedbackinghelpskeep the radiantexchangelimitedtotheoccupiedspace.Thecomponentsoflinearradiantpanelscanbeseen in Figure 5.
2. Modular Radiant PanelsModular radiant panels are designed tobe integrated intooralongsidestandardsuspendedceilingsystemsortosuspendfromtheceilinginanexposedapplication.Thevisiblesideofthemodularradiantpanelis a formed steel or aluminum sheet to whichthealuminumheatsinksareattached.Coppertubingrunsthroughtheheatsinks,andinsulatedbackinghelpskeeptheradiantexchangelimitedtotheoccupiedspace.Thecomponentsofmodularradiantpanelscanbe seen in Figure 6.
Connecting Radiant PanelsBothlinearandmodularradiantpanelscanbe connected in series, as shown below. The panelsaresuppliedwithstraight tubing,using180°returnconnectionsforendpanelsandinterconnectsbetweenpanels.Atypicalseriesapplicationofpanelsisaperimeterlayoutwiththepanelsrunningfromwalltowallwhereaneventemperaturedistributionacrossseveralpanelsisdesired.Thelooseconnectionpiecesallowthepanelstobetrimmedinordertofit.Intheseapplications,thefinalconnectionsaredoneinthefield(Figure 7).
Products - Radiant Panels
Figure 5:Componentsofalinearradiantpanelwithoutinsulation
Figure 6:Componentsofamodularradiantpanelwithoutinsulation
Figure 7:Seriesconnectiondetailsforlinearradiantpanels
DESIGN TIPLinearandmodularradiantpanelscanbeconnectedinseriesina‘cloud’configuration,providedthepanelsurfacetemperaturesdonotvarysignificantlyandwater-sidepressuredropismaintainedatacceptablelevels.Agroupingof4to6modularpanelsat2ft[600mm]wideand4ft[1200mm]longiscommonasthepanelsurfacetemperaturewilltypicallybewithin2to4°F[1to2°C]acrossthegroupingincoolingor10to20°F[6to12°C]inheating.
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-7
Products - Chilled Sails
OperationChilled sails provide a functional anduniquealternativetoconventionalradiantpanels. Sails couple the radiant coolingeffectsofstandard radiantpanelswithaconvectivecomponent. Incoolingmode,chilledsailscreatenaturalconvectionbycoolingthesurroundingairasitpassesoverthesurfacefacingtheplenum.Astheairfallsintotheoccupiedzone,wherewarmair ispulledover thesail, theconvectivecoolingcapacityofthesailiscoupledwiththeradiantcapacityofthecoolsailsurface,resultinginacoolingcapacitygreaterthanthatofstandardradiantpanels.Incooling,theapproximatebreakdownofheatmodetransferofchilledsailsis30%bythermalradiationand70%bynaturalconvection.
Ageneralairflowdiagramofanexposedchilledsailinheatingandcoolingmodecanbe seen in Figure 8.Incertainapplications,sailscanalsobeusedforheating.Inheatingmode, the sails use radiation only to heat the zone below. Because sails have noinsulation on their reverse side, heat isradiated not only towards the room, but alsotowardsthebuildingstructure.Astheslabwarms,itinturnhelpsheattheroomtoasmallextentbythermalradiationandnaturalconvection.
Likeradiantpanels,chilledsailscanalsobe analyzed using a thermal resistancecircuitdiagram,asseeninFigure 9. The resistance circuit represents the actualcomponentsofachilledsail. Thenodesrepresentvarioustemperaturesofthesailcomponentsurfacesortheconditionsoftheroom,andthe‘resistors’representtheheatconductionthroughthepanelcomponentsor heat transfer between the sail and the room.Themeanwatertemperature,t̅w, node representsthemeanwatertemperaturethattransfersthroughthecoppertubingtotheactualsail.Mostchilledsailsareonesingleextrusion,whichmeansthatthe‘fin’and‘sail’areonesolidpieceofaluminum.Tomaximize heat transfer through the sail,or, conversely, tominimize resistance, amaterialwith high thermal conductivity,suchasaluminum,istypicallyused.
AsseeninFigure 10, a chilled sail transfers heat to a room with a combination of radiationandnaturalconvection.Becausechilled sails have no insulation on theirreversesides,heatistransferredfromthecoppertubing/fintotheslabandplenum.
The heat transfer from the sail to the room hasthreecomponents:naturalconvectionwith the room air, thermal radiation with the room surfaces, and thermal radiation from thetopofthesailwitheitherthesuspendedceilingorthefixedceiling,dependingonthedesigndetails.
Figure 8: Airflowpatternofanexposedchilledsailincoolingandheatingmode
Cooling
Heating
Sail
Sail
Figure 9: Thermalresistancecircuitdiagramofachilledsail
Figure 10: Typicalchilledsail
RadiantProductsEngineering Guide
Towards slab
Towards room and occupants
Tair, room AUST,room
Rrad, room
Rrad, ceiling
Tair,ceiling
Rconv, ceiling
Rconv, room
R fin/sail
AUST,ceiling
Tsurface, fin/soil Sail/Fin
Copper tubing with
Top Bottom
H-8 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Products - Chilled Sails
Incoolingmode,themajorityoftheheattransferoccursbynatural convectionaswarm air rises due to natural buoyancy forces,passesoverthechilledsails,cools,and then sinks down into the occupiedzone.Inheatingmode,heatistransferredmainlythroughthermalradiationwithroomsurfaces,where it increases theaverageunheatedsurfacetemperatureoftheroom(AUST).Aswarmairrisespasttheheatedsails, natural convection occurs, whichresults in warmer return air. Because sails arewater-onlysystems,theycanonlyhandlethesensibleportionofabuildingloadandmustbepairedwithafreshairsystemforventilationandlatentloadremoval.
ApplicationsTheircoolingcapacityanduniquedesignmakechilledsailsanexcellentalternativetopanelsystems,particularlyinapplicationsthathaveanarchitectural focus. Typicalapplicationsofchilledsailsincludeoffices,meeting/conference rooms, theaters,studios,lobbies/foyers,waitingareas,oranyareaswereradiantpaneluseisappropriate.Chilledsailsaredesignedforarchitecturalappealandaretypically installedinT-barceilinggridsorfreelysuspended.
Figure 11:Exposedchilledsails
Figure 13: Activeandinactivesections
Figure 12: Continuous chilled sail sections
RadiantProductsEngineering Guide
ComponentsChilledsailsaretypicallyconstructedfromcopper piping and aluminumextrusionsdesigned to optimize capacity, as wellas for architectural appeal (Figure 11).Exposedchilledsailsareofteninstalledasthefinishedceilingbyeitherinstallingasacloud, as shown in Figure 11,orcombiningactiveandinactivesectionsforacontinuouslook,asseeninFigure 12.
Chilledsailsaredesignedtobe installedeitheropentotheroomorbeloworbehind
aperforatedceiling,andmaybeinstalledinlargeordiscretesections.Ineithercase,theoperationofthechilledsailrequiresthataportionoftheceilingisopentoallowaircirculationtotherearoftheassembly.Forinstallationsbehindaperforatedceilingorinstalledasacloudinanopenceiling,thisisgenerallynotanissue.Forinstallationswhere the sails are installed in a ceilingsystem,thisisoftenaccomplishedbyusingnon-activesectionsofsail toallowairtopassuptotheareaabovetheceiling,asshow in Figure 13.
Passive Elements for Return Passive Elements for Return
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-9
075
80
90
100
10 20 30 40 50 60 70
Capa
city
of S
ail,
%
Free Area as a Percentage of Sail Area
Figure 16:Typicalpipingofasailwithanoddnumberofpasses
Figure 17:Typicalevennumberofpasses
Figure 14:Freeareavs.activeareaofsail Figure 15: Clearance between chilled sail and slab
00 1 2 3 4 5 6
20
40
60
80
1000 50 100 150
Effe
ctiv
e Ca
paci
ty o
f Sai
l, %
Clearance Between Chilled Sail and Slab, in.
Clearance Between Chilled Sail and Slab, mm
Water Supply
Sail 1 Sail 2 Sail 3
Water Return
Flex HoseFlex Hose
Water Supply
Flex Hose
Products - Chilled Sails
Theamountoffreeareavs.activeareaofsailwillaffecttheperformanceofthesailsystemaccordingtoFigure 14.Inallcases,theamountofspacebetweenthebackofthesailandthestructuralslabwillaffectthelevelofcirculation,andtherebytheconvectivecoolingcomponent.ThiscapacityisaffectedaccordingtoFigure 15.
RadiantProductsEngineering Guide
Connecting Chilled SailsDependingonthewidthoftheunit,thesailsmayhaveconnectionlocationsonoppositeends. Sails with an odd number of sections willhave connectionsonoppositeends,and even number of sections will haveconnections on the same ends, as seen inFigures16and17below.Flexhoseisgenerallyusedtoconnectthewaterflowbetween the units.
H-10 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
1. Determine the ventilation requirementTheventilationrequirementshouldbecalculatedtomeetventilatiowncodes.Forexample,usingASHRAEStandard62-2004todeterminetheminimumfreshairflowrate:
L1
where Qoz= minimumfreshairflowrate,cfm[L/s] Rp = outdoorairflowrateperperson,cfm/person[L/s(person)] Pz = zonepopulationormaximumnumberofoccupantsinzone Ra = outdoorairflowrateperunitarea,cfm/ft2[L/sm2] AZ = zonefloorareaornetoccupiedareaofthezone,ft2[m2]
2. Determine required supply air dew-point temperature to remove the latent load
L2
where qL = latentload,Btu/h[W] Qs = supplyairflowrate,cfm[L/s] ΔW= differenceinhumidityratiobetweenthesupplyairandtheroomcondition, lbm,w/lbm,DAorgr/lbm,DA[kgw/kgDAorgw/kgDA]
Typically,themoisturecontentoftheventilationairwillbesufficientlylowintheheatingseasontooffsettheinternalgains.
3. Determine the occupied zone humidity ratio if there is excessive latent coolingFromequationL2:
L3
where Woz = humidity ratio of the room condition, lbm,w/lbm,DAorgr/lbm,DA[kgw/kgDAorgw/kgDA] WSA=humidityratioofthesupplyair,lbm,w/lbm,DAorgr/lbm,DA[kgw/kgDAorgw/kgDA]
IfWozisdeterminedtobetoolowforcomfort,humidificationoftheventilationairshouldbeconsidered.
4. Determine the supply air volumeThesupplyairvolumeisthemaximumvolumerequiredbycodeforventilation,andthevolumerequiredforcontrollingthelatentload:
L4
where QL = airflowraterequiredforcontrollingthelatentload,cfm[L/s]
5. Determine the heating capacity of the supply air
IP L5
SI L5
where qs,air=heatingcapacityofthesupplyair,Btu/h[W] ρ =fluiddensity,lbm/ft3[kg/m3] cp =specificheatatconstantpressureBtu/hlb°F[kJ/(kgK)] Qair=supplyairflowrate,cfm[L/s] Δtair=airtemperaturechange(treturn - tsupply),°F[K]
Design Procedure – Heating
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-11
6. Determine the heating required from the water side
L6
where qs, hydronic=heatingcapacityofthewaterside,Btu/h[W] qt =totalsensibleheatingcapacity,Btu/h[W]
7. Determine an appropriate temperature loss through the panels Specifyapanelsurfacetemperature,thenfindtherelatedmeanwatertemperature,t̅w.
Design Procedure – Heating
RadiantProductsEngineering Guide
Figure 18: Connectionbetweenmeanwatertemperatureandpanelsurfacetemperatureor, tpanel-troom=0.74(t̅w - troom)
0 10 120
0 10 20 30 40 50 60
0
10
20
30
40
50
60
70
80
90
0
5
35
45
50
t w - t
room
[R]
t w - t
room
[K]
20 30 40 50 60 70 80 90 100 110
10
15
20
25
30
40
tpanel - troom [K]
tpanel - troom [R]
8. Determine the heat transfer coefficients for the radiant panelsThenaturalconvectioncoefficientis:
IP L7
SI L7
Where hc,natural=naturalconvectioncoefficient,Btu/hft2°F[W/m2K] ta =roomtemperature,°F[K] tpanel=paneltemperature,°F[K] Dh =hydraulicdiameter,ft[m]
Dh = 4Apanels / Ppanels L8
Where Apanels=surfaceareaofactivepanels,ft2[m2] Ppanels=thepipeinternalperimeter,ft[m]
H-12 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Design Procedure – Heating
RadiantProductsEngineering Guide
Theforcedconvectioncoefficientis:
IP L9
SI L9
Where hc,forced=forcedconvectioncoefficient,Btu/hft2°F[W/m2K] ach =airchangerate,cfm/ft2[m3/hm2]
Thetotalconvectioncoefficientis:
L10
Where hc,total=totalconvectioncoefficient,Btu/hft2°F[W/m2K]
9. Determine the specific capacity of the radiant panelsTheconvectiveheattransferpersquarefoottothepanelisdetermined:
L11
where q̋c =convectiveheatfluxorconvectiveratepercrosssectionalarea,Btu/hft2[W/m2] qc=convectiveheattransferrate,Btu/h[W] A = surface area of the medium, ft2[m2]
Assumingthatthewalltemperatureisequaltotheairtemperature,theradiantheatexchangewiththepanelisdetermined:
IP L12
SI L12
where q”r =radiantheatflux,Btu/hft2[W/m2] AUST=area-weightedtemperatureofallindoorsurfacesofwalls,ceiling,
floor,windows,doors,etc.(excludingactivepanelsurfaces),°F[°C]
Thetotalheattransferperunitoffaceareais
L13
where q̋o=totalheatflux,Btu/hft2[W/m2]
10. Determine the area of panels required
L14
where Apanels =areaofpanels,ft2[m2]
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-13
RadiantProductsEngineering Guide
Example 1 - Patient Room (IP)
Considerthepatientroomshowninthefigurebelow.Thepatientroomincludesatelevision,monitoringequipmentandoverheadlighting.Thetemperatureset-pointis75°Fwithaminimumrelativehumidityof40%.Theroomis10ftwideand20ftlong,witha9ftceiling.Theattachedtoiletroomis5ftwideand7ftlong,withan8ftceiling.Thereisoneexteriorwallandwindow.Thesupplyairtemperatureinheatingmodeisresetto95°F,withtheheatingwatertemperatureat175°F.
DetermineThewaterflowrateandpressuredropfortheheatingpanelsrequiredtohandletheheatingload,assuming15°Foutdoorairtemperature
Overnightinwinter,theenvelopelossis4800Btu/handtheinternalgainsatthattimearelimitedtothepatientload:
Design Considerations
Patient 160Btu/h
Medical Staff/Visitors 0
Television 0
Medical Equipment 0
Overhead Lighting 0
Envelope -4800Btu/h
Total -4640Btu/h
Patient latent load 155Btu/h
Determine the Ventilation RequirementForthisexample,localcodereferstoASHRAEStandard170-2008fortheHVACsystem.AccordingtoASHRAEStandard170-2008,patientroomswithauxiliaryheatingrequire4achofsupplyair,ofwhichtwoareoutdoorair.
Determine the required supply air dew-point temperature to remove the latent loadFromequationL2:
Usingtheventilationrate:
PATIENT ROOM
Corridor
10 ft
20 ft
5 ft
7 ft
H-14 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 1 - Patient Room (IP)
Inthiscase,thesupplyairisamixofthereturnairandtheventilationair.Thismixtureofoutdoorair(attheoutdoorconditions,assumingsaturatedairat15°Fwithahumidityratioof12.5gr/lb)andreturnair(assumingthatitisatthedesignconditionsof75°F,40%RH–52.5gr/lb),willhavemorethanenoughcapacitytohandlethelatentload.Inapplicationswherehumidityiscritical,furtheranalysismaybedonetodeterminetherequirementofhumidification.FormoreinformationrefertoChapter5—IntroductiontoPsychrometricsofthePriceEngineer'sHandbook.
Determine the heating capacity of the supply airUsingequationL5:
Determine the heating required from the water side
Determine an appropriate temperature loss through the panelsUsingameanwatertemperatureof:
Determine the heat transfer coefficients for the radiant panelsUsingequationL7andtherelationforDhfromequationL8,thenaturalconvectioncoefficientisdetermined:
Duetotheconfigurationoftheroom,itcanbeassumedasafirstestimationthatthepanelswillbearrangedattheperimeterwheretheloadis,andrunthewidthoftheexposure(10ft).Assumingalsoa2ftwidthofpanel:
UsingequationL9,theforcedconvectioncoefficientisdetermined:
UsingequationL10,thetotalconvectioncoefficientisdetermined:
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-15
RadiantProductsEngineering Guide
Example 1 - Patient Room (IP)
Determine the specific capacity of the radiant panelsUsingequationL11,theconvectiveheattransferpersquarefoottothepanelisdetermined:
Theoutsideairtemperaturehasasignificantimpactontheinsidesurfacetemperaturesofexteriorwalls.Theexteriorwalltemperatureisdeterminedwithanhvalue,convectiveheattransfercoefficientofaverticalwall,of1.46Btu/(hft2°F)andaUvalue,overallheattransfercoefficient,of0.315Btu/(hft2°F):
Theaverageunheatedsurfacetemperatureis:
t
Calculatingtheradiantheatexchange:
FromequationL13,thetotalheattransferperunitoffaceareais:
Determine the area of panels requiredUsingequationL14:
H-16 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 1 - Patient Room (IP)
Therefore,theassumptionofpanelsize(20ft2)usedtocalculatethehydraulicdiameterisappropriate.
TheflowraterequiredtomanagetheloadwithapanelΔTof10°Fis:
Forsimplicity,a2ft×10ftPriceRPLlinearradiantpanelisselected.
Thispanelwith0.41gpmwillhaveapipevelocityof0.55fps,whichcorrespondstoaReynoldsnumberof1900,whichisinthelaminarrange.Forabetterselection,theflowrateisincreasedto1.3gpm,whichcorrespondswithaReynoldsnumberof6400,whichisintheturbulentregion.Fromtheperformancechart,thisalsoincreasesthepressuredropfrom0.31ftto3.7ft,whichwillallowbetterflowcontrolofthepanel.
Recalculatingthetemperaturelossinthepanelaswellasthecapacity:
Thisincreaseincapacitywillresultinonlyrequiring15.7ft2,thoughitismorepracticaltostaywiththeoriginalsizeinordertomaintainaesthetics(thepanelwillrunthelengthoftheperimeter)aswellasastandardmodulesize(24in.wide).Panelscanbedesignedtohavebothactiveandinactivesectionstomaintainaesthetics.
Whenrunningtheentirelengthoftheroom,thetrimandseriesoptionwillallowthepaneltobetrimmedonsiteiftheroomsizevariesslightlyduringconstruction.
PATIENT ROOM
Corridor
Panel
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-17
RadiantProductsEngineering Guide
Considerthepatientroomshowninthefigurebelow.Thepatientroomincludesatelevision,monitoringequipmentandoverheadlighting.Thetemperatureset-pointis24°Cwithaminimumrelativehumidityof40%.Theroomis3mwide,6mlong,andhasa3mceiling.Thereisoneexteriorwallandwindow.Thesupplyairtemperatureinheatingmodeisresetto35°Candtheheatingwatertemperatureis72°C.
PATIENT ROOM
Corridor
3 m
6 m
1.75 m
2.25 m
DetermineThewaterflowrateandpressuredropfortheheatingpanelsrequiredtohandletheheatingload,assuming-10°Coutdoorairtemperature.
Overnightinwinter,theenvelopelossis1400Wandtheinternalgainsatthattimearelimitedtothepatientload:
Design Considerations
Patient 50 W
Medical Staff/Visitors 0
Television 0
Medical Equipment 0
Overhead Lighting 0
Envelope -1400W
Total -1350W
Patient latent load 45W
Determine the Ventilation RequirementForthisexample,localcodereferstoASHRAEStandard170-2008fortheHVACsystem.AccordingtoASHRAEStandard170-2008, patientroomswithauxiliaryheatingrequire4achofsupplyair,ofwhichtwoareoutdoorair.
Determine the required supply air dew-point temperature to remove the latent loadFromequationL2:
Usingtheventilationrate:
Example 1 - Patient Room (SI)
H-18 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Inthiscase,thesupplyairisamixofthereturnairandtheventilationair.Thismixtureofoutdoorair(attheoutdoorconditions,assumingsaturatedairat-10°Cwithahumidityratioof1.8g/kg)andreturnair(assumingthatitisatthedesignconditionsof24°C,40%RH–7.4g/kg),willhavemorethanenoughcapacitytohandlethelatentload.Inapplicationswherehumidityiscritical,furtheranalysismaybedonetodeterminetherequirementofhumidification.FormoreinformationrefertoChapter5—IntroductiontoPsychrometricsofthePriceEngineer'sHandbook.
Determine the heating capacity of the supply airUsingequationL5:
Determine the heating required from the water side
Determine an appropriate temperature loss through the panelsUsingameanwatertemperatureof:
Determinetheheattransfercoefficientsfortheradiantpanels
UsingequationL.7andtherelationforDhfromequationL.8,thenaturalconvectioncoefficientisdetermined:
Duetotheconfigurationoftheroom,itcanbeassumedasafirstestimationthatthepanelswillbearrangedattheperimeterwheretheloadis,andrunthewidthoftheexposure(3m).Assumingalsoa600mmwidthofpanel:
UsingequationL9,theforcedconvectioncoefficientisdetermined:
UsingequationL10,thetotalconvectioncoefficientisdetermined:
Example 1 - Patient Room (SI)
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-19
RadiantProductsEngineering Guide
Example 1 - Patient Room (SI)
Determine the specific capacity of the radiant panelsUsingequationL11,theconvectiveheattransferpersquarefoottothepanelisdetermined:
Theoutsideairtemperaturehasasignificantimpactontheinsidesurfacetemperaturesofexteriorwalls.Theexteriorwalltemperatureisdeterminedwithanhvalue,convectiveheattransfercoefficientofaverticalwall,of8.29W/(m2K)andaUvalue,overallheattransfercoefficient,of0.055W/(m2K):
Theaverageunheatedsurfacetemperatureis:
Calculatingtheradiantheatexchange:
FromequationL13,thetotalheattransferperunitoffaceareais:
Determine the area of panels requiredUsingequationL14:
H-20 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 1 - Patient Room (SI)
Therefore,theassumptionofpanelsize(1.8m2)usedtocalculatethehydraulicdiameterisappropriate.
TheflowraterequiredtomanagetheloadwithapanelΔTof5Kis:
Forsimplicity,a600mm×3000mmRPLlinearradiantpanelisselected.
Thispanelwith0.027kg/swillhaveapipevelocityof0.24m/s,whichcorrespondstoaReynoldsnumberof4300withapressuredropof1.2kPa,whichisagoodselection.
Whenrunningtheentirelengthoftheroom,thetrimandseriesoptionwillallowthepaneltobetrimmedonsiteiftheroomsizevariesslightlyduringconstruction.
PATIENT ROOM
Corridor
Panel
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-21
RadiantProductsEngineering Guide
Design Procedure – Cooling
1. Determine the ventilation requirementTheventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminetheminimumfreshairflowrate:
L1
2. Determine required supply air dew-point temperature to remove the latent load
L2
Iftherequiredhumidityratioisnotpractical,recalculatethesupplyairvolumerequiredwiththedesiredhumidityratio.
3. Determine the supply air volumeThesupplyairvolumeisthemaximumvolumerequiredbycodeforventilationandthevolumerequiredforcontrollingthelatentload:
L4
4. Determine the sensible cooling capacity of the supply air
IP L5
SI L5
5. Determine the sensible cooling required from the water side
L6
6. Determine an appropriate temperature rise through the panels Apaneltemperaturecorrectionisunnecessarybecausethetemperaturedifferentialbetweenthewaterandairissmallincoolingmode.Forpanelsandsailsthataredesignedwell,thesurfacetemperaturecanbeapproximatedtobethemeanwatertemperature:
L15
where tw =meanwatertemperature,°F[K] tCHWS=chilledwatersupplytemperature,°F[K] tout =chilledwaterreturntemperature,°F[K]
7. Determine the heat transfer coefficients for the radiant panelsThenaturalconvectioncoefficientis:
IP L16
SI L16
H-22 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Design Procedure – Cooling
Theforcedconvectioncoefficientis:
IP L9
SI L9
Thetotalconvectioncoefficientis:
L10
8. Determine the specific capacity of the radiant panelsTheconvectiveheattransferpersquarefoottothepanelisdetermined:
L11
Assumingthatthewalltemperatureisequaltotheairtemperature,theradiantheatexchangewiththepanelisdetermined:
IP L12
SI L12
Thetotalheattransferperunitoffaceareais:
L13
9. Determine the area of panels required
L14
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-23
RadiantProductsEngineering Guide
Example 2 - Small Office (IP)
Considerasmallofficewithasouthernexposure.Thespaceisdesignedfortwooccupants,acomputerwithLCDmonitor,T8florescentlighting,andhasatemperatureset-pointof75°F.Theroomis10ftwide,12ftlong,and9ftfromfloortoceiling.Theownerexpressedinterestinusingradiantpanels.
12 ft
9 ft 10 ft
SMALL OFFICE
Window
Space ConsiderationsOneoftheprimaryconsiderationswhenusingaradiantheatingandcoolingsystemishumiditycontrol.Aspreviouslydiscussed,itisimportanttoconsiderboththeventilationrequirementsandthelatentloadwhendesigningtheair-sideofthesystem.
Theassumptionsmadefortheexampleareasfollows:
• Load/personis250Btu/hsensibleand155Btu/hlatent• Lightingloadinthespaceis6.875Btu/h/ft²• Computerloadis300Btu/h(CPUandLCDMonitor)• Totalskinloadis1450Btu/h• Specificheatanddensityoftheairare0.24Btu/lb°Fand0.075lb/ft³respectively• Designconditionsare75°F,with50%relativehumidity• Designdewpointis55°F
Design Considerations
Occupants 2
Set-Point 75°F
FloorArea 120ft²
ExteriorWall 108ft²
Volume 1080ft³
qoz 800Btu/h
ql 825Btu/h
qex 1450Btu/h
qT 3075Btu/h
Determinea)Theventilationrequirement.b)Thesuitablesupplyairandsupplywatertemperatures.c)Thetotalconvectiveheattransfercoefficientforradiantpanels.
H-24 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Solutiona) Determine the ventilation requirementTheventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminetheminimumfreshairflowrateforatypicalofficespace:
b) Determine required supply air dew-point temperature to remove the latent loadFromequationL2:
Usingtheventilationrate:
Atthedesignconditions(75°F,50%RH),thehumidityratiois65gr/lb,requiringadifferenceinhumidityratiobetweenthesupplyandroomairof:
Fromthefigurebelow,thedewpointcorrespondingtothehumidityratiois40°F,whichistoocoolforstandardequipment.Evaluatingthehumidityratioatseveraltemperaturesledtotheselectionofadewpointof50°Finordertouselessexpensivecommonequipmentwhilealsominimizingthesupplyairvolumerequiredtocontrolhumidity.
Humidity Ratio
Dew Point lb/lb gr/lb
40 0.00543 38
45 0.0065 46
50 0.0075 53
55 0.0095 67
0.000
0.002
0.004
0.006
0.010
0.012
0.014
0.016
0.018
0.020
0.022
0.024
0.026
0.028
0.030
35 40
12.5
13.0
13.5 10%
20%
30%40%
50%60%70%80%90
%
14.0
14.5
15.0
45 55 60 65 70 80 85 90 95 100 105 110 115 120
65
Dry Bulb Temperature, ºF
Enthalpy - Btu/lb
of Dry
Air
Hum
idity Ratio, lbw /lb
DA
70
75
80
85
15
20
25
30
35
40
45
50
60 65
Volume - ft3/lb of Dry Air
Saturation Temperature, ºF
Relative Humidity
40
45
50
55
60
35
0.0075
50
Example 2 - Small Office (IP)
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-25
RadiantProductsEngineering Guide
Therequiredairvolumetosatisfythelatentloadis:
Thesupplyairvolumetotheofficeisthemaximumvolumerequiredbycodeforventilationandthevolumerequiredforcontrollingthelatentload:
c) Determine the heat transfer coefficients for the radiant panelsForpanels and sails that aredesignedwell, the surface temperature canbe approximated tobe themeanwater temperature. Assumingachilledwatersupplytemperature2°Fabovethedewpointinordertominimizethepotentialforcondensationandatemperatureriseof4°Fthroughthepanelleadstoameanwatertemperatureof:
UsingequationL16,thenaturalconvectioncoefficientisdetermined:
UsingequationL9,theforcedconvectioncoefficientisdetermined:
UsingequationL10,thetotalconvectioncoefficientisdetermined:
Example 2 - Small Office (IP)
H-26 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 2 - Small Office (SI)
Considerasmallofficewithasouthernexposure.Thespaceisdesignedfortwooccupants,acomputerwithLCDmonitor,T8florescentlighting,andhasadesigntemperatureset-pointof24°C.Theroomis3mwide,4mlong,and3mfromfloortoceiling.Theownerexpressedinterestinusingradiantpanels.
Space ConsiderationsOneoftheprimaryconsiderationswhenusingaradiantheatingandcoolingsystemishumiditycontrol.Aspreviouslydiscussed,itisimportanttoconsiderboththeventilationrequirementsandthelatentloadwhendesigningtheair-sideofthesystem.
Theassumptionsmadefortheexampleareasfollows:
• Load/personis65Wsensibleand55Wlatent• Lightingloadinthespaceis25W/m²• Computerloadis80W(CPUandLCDMonitor)• Totalskinloadis425W• Specificheatanddensityoftheairare1.007kJ/kgKand1.3kg/m³respectively• Designconditionsare24°C,with50%relativehumidity• Designdewpointis13°C
Design Considerations
Occupants 2
Set-Point 24°C
FloorArea 12m²
ExteriorWall 12m²
Volume 36m³
qoz 210W
ql 300W
qex 425W
qT 935W
Determinea)Theventilationrequirement.b)Thesuitablesupplyairandsupplywatertemperatures.c)Thetotalconvectiveheattransfercoefficientforradiantpanels.
3 m
4 m
3 m
SMALL OFFICE
Window
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-27
RadiantProductsEngineering Guide
Example 2 - Small Office (SI)
Solutiona) Determine the ventilation requirementTheventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminetheminimumfreshairflowrateforatypicalofficespace:
b) Determine required supply air dew-point temperature to remove the latent loadFromequationL2:
Usingtheventilationrate:
Atthedesignconditions(24°C,50%RH),thehumidityratiois9.5g/kgofdryair,requiringadifferenceinhumidityratiobetweenthesupplyandroomairof:
Fromthefigurebelowthedewpointcorrespondingtothehumidityratiois5°C,whichistoocoolforstandardequipment.
Evaluatingthehumidityratioatseveraltemperaturesledtotheselectionofadewpointof10°Cinordertouselessexpensiveequipmentwhilealsominimizingthesupplyairvolumerequiredtocontrolhumidity.
Humidity Ratio
DewPoint g/kg
5 5.5
7.5 6.75
10 8
12.5 9.25
Dry-Bulb Temperature, ºC
Entha
lpy - k
J/kg o
f Dry
Air
30
25
20
15
10
5
050454035302520151050
0
45
40
35
30
25
20
15
50
55
60
65
70
75
85
90
95
100
105
105110 115 120 125
Volume - m3/kg of Dry Air
Saturation Temperature, ºC
Relative Humidity
Hum
idity Ratio, gw /kg
DA
30
10
5
15
20
0.78
0.80
0.82
0.84
0.86
0.90
0.92
0.94
0.96
10%
20%
30%40%
50%60
%70%80
%90%
25
8
H-28 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 2 - Small Office (SI)
Therequiredairvolumetosatisfythelatentloadis:
Thesupplyairvolumetotheofficeisthemaximumvolumerequiredbycodeforventilationandthevolumerequiredforcontrollingthelatentload:
c) Determine the heat transfer coefficients for the radiant panelsForpanelsandsailsthataredesignedwell,thesurfacetemperaturecanbeapproximatedtobethemeanwatertemperature.Assumingachilledwatersupplytemperature1Kabovethedewpointinordertominimizethepotentialforcondensationandatemperatureriseof2Kthroughthepanelleadstoameanwatertemperatureof:
UsingequationL16,thenaturalconvectioncoefficientisdetermined:
UsingequationL9,theforcedconvectioncoefficientisdetermined:
UsingequationL10,thetotalconvectioncoefficientisdetermined:
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-29
RadiantProductsEngineering Guide
PerformanceRadiantpanelsperformancedependsonseveralfactors:
• Thedifferenceinsurfacetemperaturesbetweenthepanelandthesurroundingsurfaces
• Themeanwatertemperatureandthepanelthermalresistance
• Viewfactorofthepaneltothesurfacestobecooled/heated
• Waterflowrate• Emissivityandabsorptionofaffected
surfacesThe water flow rate in the coil affectstwoperformancefactors.First,theheattransferbetweenthewaterandthepanelisdependentonwhethertheflowislaminar(poor), transitional (inconsistent) orturbulent(good).Secondly,italsoaffectsthemeanwatertemperature.
Thehigher the flow rate, the closer thedischarge temperature will be to theinlet,therebychangingtheaveragewatertemperature imposed on the panel. Astheseparationbetween themeanwatertemperature and the surrounding roomtemperature (ΔT) increases,sodoes thecapacity.Inheating,theΔTislimitedbythermalcomfort.Incooling,theΔTisalsolimited by two factors, thermal comfort and condensationprevention.Goodpracticefor panel selection in cooling avoidscondensation by limiting the enteringwater temperature to the room’s dewpoint + 2 °F [1 K]. The most commondesignconditionforspacesincoolingis 75°F[24°C]at50%RH,producingadewpointof55°F[13°C]andlimitingenteringwatertemperaturetoaminimumof57°F[14°C].
Figure 19 shows the effect on the flowrate, indicated byReynolds number, onthecapacityofatypicalradiantpanel.Asindicatedonthechart,increasingtheflowrateintothetransitionalrange(Re>2300,showninblueonthegraph)increasestheoutputofthepanel.
Product Selection
Figure 19: Radiantpanelcapacityvs.waterflow
400 2000 4000 6000 8000 10000 12000
50
60
70
80
90
100
Cap
acity
, %
Re
Thewaterflowrateislargelydependentonthepressuredropandreturnwatertemperaturesacceptable to thedesigner. Inmostcasesthewaterflowrateshouldbeselected tobefullyturbulent(Re>4000)underdesignconditions. The difference between the mean watertemperatureisdefinedas:
L17
and the room/surrounding surfacetemperatures are the primary driverof panel performance.The larger thisdifferenceis,thegreatertheradiantandconvectivetransferratesare.AsnotedinequationL12,theradiantenergyexchangebetween two surfaces is based on the absolutetemperaturetothefourthpower.Conversely,alowertemperaturedifferencewillreducetheamountofpotentialenergyexchange,andtherebycapacity.Asaresult,itisdesirablefromacapacitystandpointtoselectentrywatertemperaturesaslowaspossibleincooling,whilemaintainingitabovethedewpointintheroomtoensuresensiblecoolingonly.
The location of radiant panels relative toloadsinthespaceinfluencestheircapacityandisgreatlydependentontheviewfactorof thepanel to theobjects that are tobeconditioned. When used in spaces withhigh solargain, suchasperimeter zones,thecapacity increasesas thesurroundingsurface temperature increases.Assurfacetemperatures change throughout theday, panel capacity changes accordingly.Furthermore,asthedistancebetweenthepanelandtheaffectedsurfaceincreases,theviewfactordiminishes,thusreducingdirectradiantexchangebetweenthetwosurfaces.Panelplacementisbasedonacombinationofsurfacetemperatureanddistancetotheoccupant in order to ensure an effectiveoperativetemperatureisachieved.Locatingpanelsalongglassperimeterswithoutlowemissivity coatingsmay have a negativeeffectonenergyuseassomeenergywillbelosttotheoutdoorsthroughtheglass.
H-30 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 3 - Small Office Panel Selection (IP)
Design Considerations
Occupants 2
Set-Point 75°F
FloorArea 120ft²
ExteriorWall 108ft²
Volume 1080ft³
qoz 800Btu/h
ql 825Btu/h
qex 1450Btu/h
qT 3075Btu/h
hc, total 0.823Btu/hft°F
Qs 38cfm
Ts 50°F
tCHWS 57°F
tpanel 59°F
Determine
a)Theareaofpanelsrequired.b)Theareaofpanelsrequiredassuming95°Foutdoorairtemperature.c)Theflowrateforthepanelsfrom(b).d)Apracticallayoutandpipingarrangementforthepanelsfrom(b).
12 ft
9 ft 10 ft
SMALL OFFICE
Window
Considerthesmallofficepresentedinthepreviousexample.
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-31
RadiantProductsEngineering Guide
Solution
a) Determine the sensible cooling capacity of the supply airUsingequationL5:
Determine the sensible cooling required from the water-side
Determine the specific capacity of the radiant panelsUsingequationL11,theconvectiveheattransfertothepanelisdetermined:
UsingequationL12andassumingthatthewalltemperatureisequaltotheroomairset-pointtemperature,theradiantheatexchangewiththepanelisdetermined:
FromequationL13,thetotalheattransferperunitoffaceareais:
Determine the area of panels requiredUsingequationL14:
Usingmultiplesof4ft2,whichisastandardceilingtilesizedat2ft×2ft,thetotalarearequiredis76ft2.
Example 3 - Small Office Panel Selection (IP)
H-32 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 3 - Small Office Panel Selection (IP)
b)Theareaofpanelsrequiredassuming95°Foutdoorairtemperature
Theexteriorwalltemperatureisdeterminedwithanhvalue,convectiveheattransfercoefficient,of1.46Btu/(hft2°F)andaUvalue,overallheattransfercoefficient,of0.693Btu/(hft2°F):
Theaverageunheatedsurfacetemperatureis:
Recalculatingtheradiantheatexchangeandtotalheattransferfrom(a):
Determine the area of panels requiredUsingequationL14:
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-33
Example 3 - Small Office Panel Selection (IP)
RadiantProductsEngineering Guide
SMALL OFFICE
Light
Panel
PanelPanel
Panel Panel
SMALL OFFICEPanel Panel
Panel
Panel
Light
c) The flow rate for the panels from (b)
d) A practical layout and piping arrangement for the panels from (b) Inordertofitthepanelsfrom(b)inalay-inceiling,a48in.×24in.RPMmodularpanelisselected.Referringtotheproductdatasheet,aflowrateof1.02(~1gpm)hasawaterpressuredropof0.17ft.
Usingthesepanelswouldrequireaquantityof:
Ifthesepanelsareconnectedinseries,thetotallooppressuredropwouldbe:
H-34 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 3 - Small Office Panel Selection (SI)
Design Considerations
Occupants 2
Set-Point 24°C
FloorArea 12m²
ExteriorWall 12m²
Volume 36m³
qoz 210W
ql 300W
qex 425W
qT 935W
hc, total 4.71W/m2K
Qs 22.5L/s
Ts 10°C
tCHWS 14°C
tpanel 15°C
Determinea)Theareaofpanelsrequired.b)Theareaofpanelsrequiredassuming35°Coutdoorairtemperature.c)Theflowrateforthepanelsfrom(b).d)Apracticallayoutandpipingarrangementforthepanelsfrom(b).
Considerthesmallofficepresentedinthepreviousexample.
3 m
4 m
3 m
SMALL OFFICE
Window
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-35
Example 3 - Small Office Panel Selection (SI)
Solution
a) Determine the sensible cooling capacity of the supply airUsingequationL5:
Determine the sensible cooling required from the water-side
Determine the specific capacity of the radiant panelsUsingequationL11,theconvectiveheattransfertothepanelisdetermined:
UsingequationL12andassumingthatthewalltemperatureisequaltotheroomairset-pointtemperature,theradiantheatexchangewiththepanelisdetermined:
FromequationL13,thetotalheattransferperunitoffaceareais:
Determine the area of panels requiredUsingequationL14:
Usingmultiplesof0.36m2,whichisastandardceilingtilesizedat600mm×600mm,thetotalarearequiredis6.48m2.
RadiantProductsEngineering Guide
H-36 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 3 - Small Office Panel Selection (SI)
b)The area of panels required assuming 35 °C outdoor air temperatureTheexteriorwalltemperatureisdeterminedwithanhvalue,convectiveheattransfercoefficient,of0.255W/(m2K)andaUvalue,overallheattransfercoefficient,of0.121W/(m2K):
Theaverageunheatedsurfacetemperatureis:
Recalculatingtheradiantheatexchangeandtotalheattransferfrom(a):
Determine the area of panels requiredUsingequationL14:
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-37
RadiantProductsEngineering Guide
Example 3 - Small Office Panel Selection (SI)
SMALL OFFICE
Light
Panel
PanelPanel
Panel Panel
SMALL OFFICEPanel Panel
Panel
Panel
Light
c) The flow rate for the panels from (b)
d) A practical layout and piping arrangement for the panels from (b) Inordertofitthepanelsfrom(b)inalay-inceiling,a1200mmx600mmRPMmodularpanelisselected.Referringtotheproductdatasheet,aflowrateof0.07(~0.075kg/s)hasawaterpressuredropof0.69kPa.
Usingthesepanelswouldrequireaquantityof:
Ifthesepanelsareconnectedinseries,thetotallooppressuredropwouldbe:
H-38 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 4 - Small Office Chilled Sail Selection (IP)
Considerthesmallofficepresentedinthepreviousexample.
Design Considerations
Occupants 2
Set-Point 75°F
FloorArea 120ft²
ExteriorWall 108ft²
Volume 1080ft³
qoz 800Btu/h
ql 825Btu/h
qex 1450Btu/h
qT 3075Btu/h
CoolingCapacityofHydronicSystem 2049Btu/h
tCHWS 57°F
tpanel 59°F
DetermineTherequiredareaandpossiblelocationofchilledsails.
SolutionThedifferencebetweentheroomairtemperatureandthemeanpaneltemperatureis:
Referringtotheproductdatapage,thespecificcapacityofthechilledsailisdeterminedusingthistemperaturedifference:
12 ft
9 ft 10 ft
SMALL OFFICE
Window
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-39
RadiantProductsEngineering Guide
Example 4 - Small Office Chilled Sail Selection (IP)
Determine the area of sails requiredUsingequationL14:
Selectingasailthatis10ftlongand4.5ftwideprovides45ft2ofsailarea.Fromtheperformancetable,thispiped-inserieswillresultinapressuredropof2ft.
24 in. × 96 in. Price CSA
(troom - t̅w), °F Capacity, Btu/h Water Flow Rate, gpm Head Loss, ft
14 635 0.35 0.356
16 740 0.41 0.488
18 848 0.47 0.642
20 959 0.53 0.816
Basedon4°Fwatertemperaturedrop
SMALL OFFICE
Sail
H-40 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
Example 4 - Small Office Chilled Sail Selection (SI)
Considerthesmallofficepresentedinthepreviousexample.
3 m
4 m
3 m
SMALL OFFICE
Window
Design Considerations
Occupants 2
Set-Point 24°C
FloorArea 12m²
ExteriorWall 12m²
Volume 36m³
qoz 210W
ql 300W
qex 425W
qT 935W
CoolingCapacityofHydronicSystem 557W
tCHWS 14°C
tpanel 15°C
DetermineTherequiredareaandpossiblelocationofchilledsails.
SolutionThedifferencebetweentheroomairtemperatureandthemeanpaneltemperatureis:
Referringtotheproductdatapage,thespecificcapacityofthechilledsailisdeterminedusingthistemperaturedifference:
RadiantProductsEngineering Guide
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-41
RadiantProductsEngineering Guide
Example 4 - Small Office Chilled Sail Selection (SI)
Determine the area of sails requiredUsingequationL14:
Selectingasailthatis3mlongand1.5mwideprovides4.5m2ofsailarea.Fromtheperformancetable,thispiped-inserieswillresultinapressuredropof6kPa.
600 mm × 2908 mm Price CSA
(troom - t̅w), K Capacity, W Water Flow Rate, kg/h Head Loss, kPa
8 186 79 1.06
9 217 93 1.46
10 249 107 1.92
11 281 120 2.44
Basedon4°Cwatertemperaturedrop
SMALL OFFICE
Sail
H-42 All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011. Imperial dimensions are converted to metric and rounded to the nearest millimetre.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
RadiantProductsEngineering Guide
References
ASHRAE(2004a).Standard 55-2004—Thermal environmental conditions for human occupancy.Atlanta,GA:American SocietyofHeating,RefrigerationandAir-ConditioningEngineers,Inc.
ASHRAE(2004b).Standard 62.1-2004—Ventilation for acceptable indoor air quality.Atlanta,GA:AmericanSocietyfor Heating,RefrigeratingandAir-ConditioningEngineers.
ASHRAE(2005).Standard 138-2005—Method of testing for rating ceiling panels for sensible heating and cooling. Atlanta,GA:AmericanSocietyforHeating,RefrigeratingandAir-ConditioningEngineers.
ASHRAE(2007).Humidity control design guide.Atlanta,GA:AmericanSocietyforHeating,RefrigeratingandAir- ConditioningEngineers.
ASHRAE(2008a).ASHRAE handbook—Applications.Atlanta,GA:AmericanSocietyforHeating,Refrigeratingand Air-ConditioningEngineers.
ASHRAE(2008b).Standard 170-2008—Ventilation of health care facilities.Atlanta,GA:AmericanSocietyforHeating, RefrigeratingandAirConditioningEngineers.
ASHRAE(2009).ASHRAE handbook—Fundamentals.Atlanta,GA:AmericanSocietyforHeating,Refrigeratingand Air-ConditioningEngineers.
ASHRAE(2010).Standard 55-2010—Thermal environmental conditions for human occupancy.Atlanta,GA:American SocietyforHeating,RefrigeratingandAir-ConditioningEngineers.
Awbi,H.B.&Hatton,A.(1999).Naturalconvectionfromheatedroomsurfaces.Energy and Buildings, 30,233-244.
Babiak,J,.OlesenB.W.,&Petras,D.(2009).REHVA guidebook no. 7: Low temperature heating and high temperature cooling.Brussels,Belgium:FederationofEuropeanHeatingandAir-conditioningAssociations(REHVA).
Beausoleil-Morrison,I.(2000).Theadaptivecouplingofheatandairflowmodellingwithindynamicwhole-building simulation.PhDThesis,UniversityofStrathclyde,Glasgow,UK.
Behne,M.(1999).Indoorairqualityinroomswithcooledceilings,mixingventilationorratherdisplacementventilation. Energy and Buildings, 30,155–166.
Berglund,L.,Rascati,R.,&Markel.,M.L.(1982).Radiantheatingandcontrolforcomfortduringtransientconditions. ASHRAE Transactions, 88(2),765-775.
Conroy,C.,&Mumma,S.A.(2001).Ceilingradiantcoolingpanelsasaviabledistributedparallelsensiblecooling technologyintegratedwithdedicatedoutdoor-airsystems.ASHRAE Transactions, 107(1),571-579.
CSA(2010).CSA Z317.0-10—Special requirements for heating, ventilation, and air-conditioning (HVAC) systems in health care facilities.Mississauga,ON:CanadianStandardsAssociation.
DIN(2003).Ventilationforbuildings—Ceiling-mounted radiant panels supplied with water at a temperature below 120 °C –Part 2: Test method for thermal output (English version of DIN EN 14037-2).Berlin,Germany:Bueth VerlagGmbH.
DIN(2004).Ventilationforbuildings—Chilled ceilings -Testing and rating (English version of DIN EN 14240). Berlin, Germany:BuethVerlagGmbH.
Fisher,D.E.(1995).Anexperimentalinvestigationofmixedconvectionheattransferinarectangularenclosure.PhD Thesis,UniversityofIllinois,Urbana,IL.
Fitzner,K.(1996).Displacementventilationandcooledceilings—Resultsoflaboratorytestandpracticalinstallations. ProceedingsfromIndoor Air ’96.Nagoya,Japan.
Incropera,F.P.&DeWitt,D.P.(1996).Fundamentals of heat and mass transfer (4thed.).NewYork,NY:JohnWileyandSons.
ISO (2005). ISO Standard 7730-2005—Ergonomics of the thermal environment–Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Geneva,Switzerland:InternationalStandardsOrganization.
EN
GIN
EE
RIN
G G
UID
E -
RA
DIA
NT
PR
OD
UC
TS
© Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion. Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-43
RadiantProductsEngineering Guide
References
JeongJ.&Mumma,S.A.(2003).Impactofmixedconvectiononceilingradiantcoolingpanel.HVAC&R Research, 9(3),251-257.
Kochendörfer,C.(1996).StandardtestingofcoolingpanelsandtheiruseinsystemPlanning.ASHRAE Transactions, 102(1),651-658.
Min,T.C.,Schutrum,L.F.,Parmelee,G.V.,&Vouris,J.D.(1956).Naturalconvectionandradiationinapanelheatedroom. Heating Piping and Air Conditioning (HPAC),153–160.
Mumma,S.A.(2002).Chilledceilingsinparallelwithdedicatedoutdoorairsystems:Addressingtheconcernsof condensation,capacityandcost.ASHRAE Transactions 2002(2),220–231.
Mundt,E.(1990).Convectionflowsabovecommonheatsourcesinroomswithdisplacementventilation.Proceedings from Roomvent 1990.Oslo,Norway.
Nickel,J.(2002).1.3-Heatingandcoolingwithceilings.Technical report 87/2002e: Cooling and heating systems. Aachen,Germany:KrantzKomponenten.
Novoselac,A.,Burley,B.,&Srebric,J.(2006).Newconvectioncorrelationsforcooledceilingpanelsinroomswith mixedandstratifiedairflow.HVAC&R Research, 12(N2),279-294.
Novoselac,A.&Srebric,J.(2002).Acriticalreviewontheperformanceanddesignofcombinedcoolingceilingand displacementventilationsystems.Energy and Buildings, 34(5),497-509.
Olesen,B.W.,Sliwinska,E.,Madsen,T.L.,&Fanger,P.O.(1982).Effectofbodypostureandactivityonthethermal insulationofclothing:Measurementsbyamoveablethermalmanikin.ASHRAE Transactions, 88(2),791-801.
PriceIndustries(2011).Price engineer's HVAC handbook—A comprehensive guide to HVAC fundamentals. Winnipeg, MB:PriceIndustriesLimited.
Schiavon,S,Bauman,F.,Lee,K.H.,&Webster,T.(2010).Development of a simplified cooling load design tool for underfloor air distribution systems, final report to CEC PIER program.Berkeley,CA:CenterfortheBuiltEnvironment, CenterforEnvironmentalDesignResearch,UniversityofCaliforniaatBerkeley.
Stetiu,C.(1998).RadiantcoolinginU.S.officebuildings:Towardseliminatingtheperceptionclimateimposedbarriers. DoctorialDissertation,EnergyandResourcesGroup,UniversityofCaliforniaatBerkeley,CA.
Tan,H.,Murata,T.,Aoki,K.,&Kurabuchi,T.(1998).Cooledceiling/displacementventilationhybridairconditioning system—Designcriteria.ProceedingsfromRoomvent ’98.Stockholm,Sweden.
Virta,M.,Butler,D.,Gräslund,J.,Hogeling,J.,Kristiansen,E.L.,Reinikainen,M.,&Svensson,G. (2004).REHVA guidebook no. 5: Chilled beam application guidebook.Brussels,Belgium:FederationofEuropeanHeatingand Air-conditioningAssociations(REHVA).
Yin,Y.,Zhang,X.,&Chen,Q.(2009).Condensationriskinaroomwithhighlatentloadandchilledceilingpaneland withairsuppliedfromliquiddesiccantsystem.HVAC&R Research, 15(2),315-327.
Zhang,H.,Huizenga,C.,Arens,E.,&Yu,T.(2005).Modeling thermal comfort in stratified environments.Berkeley,CA: CenterfortheBuiltEnvironment,UniversityofCalifornia.