radiant products engineering guide

Upload: swapnilupgade

Post on 06-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 Radiant Products Engineering Guide

    1/43

    Please refer to the Price Engineer’s HVAC Handbook

    for more information on Radiant Heating and Cooling

    S E C T I O N H

    Engineering GuideRadiant Products

  • 8/18/2019 Radiant Products Engineering Guide

    2/43H-2All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Radiant Products

    Engineering Guide

    Introduction To Radiant Heating and Cooling

    Radiant heating and cooling systems offer anenergy efcient alternative to all-air systems.In most cases, the supply air volume ofthe air handling system is limited in sizeto satisfy only the ventilation and latentloads, with the radiant system making upthe balance of the heating and coolingloads. This comfortable method of heatingand cooling may save energy, space andbuilding maintenance costs. The followingpages offer an introduction to the products,systems and design methodology, as wellas the advantages and limitations of radiantheating and cooling.

    Management of heat loads can generallybe classied into two different types: all-

    air systems or hybrid systems. All-airsystems have been the most prominentin North America during the 20th centuryand have been in use since the advent ofair conditioning. These systems use air to

    service both the ventilation requirement aswell as the building cooling load. In general,these systems have a central air handlingunit (or rooftop unit) that delivers enoughcool or warm air to satisfy the building load.Diffusers mounted in the zone deliver thisair in such a way as to promote comfort andevenly distribute the air. In many cases, theamount of air required to cool or warm thespace or the uctuations of loads makedesigning in accordance to these principlesdifcult. Draft is not uncommon, and someceiling diffusers have been known to “dump”at low capacities.

    Hybrid systems have two components: anair-side ventilation system and a hydronic

    (or water-side) radiant system. The air-sideis designed to meet all of the ventilationrequirements for the building, as well assatisfy all latent loads. It is a 100% outsideair system and because the primary function

    of the supply air system is ventilation asopposed to cooling, it can be supplied athigher supply air temperatures than is typicalof overhead air distribution systems. Thewater-side is designed to meet the balanceof the sensible cooling and heating loads.These loads may be handled by water basedproducts, such as radiant panels, whichtransfer heat mainly by thermal radiation,and chilled sails, which transfer heat usinga combination of thermal radiation andnatural convection. Radiant panels havebeen used for sensible heating and coolingin North American buildings for over half acentury, and are a widely recognized andwell-established technology. Chilled sails

    were originally developed in Europe inthe late 1990s, and are a relatively newtechnology in North America.

  • 8/18/2019 Radiant Products Engineering Guide

    3/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-3

    Radiant ProductsEngineering Guide

    Figure 1: Examples of radiant heating and cooling

    Radiant heating and cooling systemsprovide an effective method for satisfyingthe heating and/or cooling loads of a spacewhile promoting a high level of occupantcomfort and energy efciency.

    Hydronic systems have been successfullyused in several applications havingdramatically different characteristics.Some examples of areas where radiantsystems have been applied include:

     • Green Buildings • Hospitals

     • Burn Centers • Isolation Rooms

     • Schools • Data Centers

     • Ofce Buildings • Airports

     • Cafeterias • Television Studios

     • Theaters • Casinos

    Benefits of Air-Water Systems

    There are many benets to heating andcooling using radiant panels and chilledsails. Advantages of these water basedheating and cooling systems over othermechanical systems include:

     • Energy and system efciency

     • Reduced system horse power

     • Indoor environmental quality

     • Improved indoor air quality

     • Increased thermal comfort

     • Reduced mechanical footprint

     • Lower maintenance costs

     • Improved system hygiene

    Radiant systems are a good choice where:

     • Thermal comfort is a major designconsideration

     • Areas have high sensible loads

     • Areas require a high indoor air quality(100% outdoor air system)

     • Energy conservation is desired

    Energy Efficiency

    The heat transfer capacity of water allows fora reduction in the energy used to transportan equivalent amount of heat as an all-airsystem (Stetiu, 1998). These reductions canbe found primarily through reduced fanenergy.

    The higher chilled water supply (CHWS)temperatures used with active and passivebeam systems, typically around 58 °F[14.5 °C], provide many opportunities for areduction in energy use, including increasedwater-side economizer use. This increasedCHWS temperature also allows for morewater-side economizer hours than would bepossible with other systems where CHWStemperatures are typically ~45 °F [7 °C].

    Concepts and Benefits

    Indoor Air Quality

    Depending on the application, under

    maximum load, only ~15 to 40% of thecooling air ow in a typical space is outdoorair and is required by code to satisfy theventilation requirements. The balance ofthe supply air ow is recirculated air which,when not treated, can transport pollutantsthrough the building. Radiant systemstransfer heat directly to/from the zone andare often used with a 100% outdoor airsystem which exhausts polluted air directlyto the outside, reducing the opportunityfor VOCs and illness to travel between airdistribution zones.

    Noise

    Radiant systems do not usually havefan powered devices near the zone. This

    typically results in lower zone noise levelsthan what is achieved with all-air systems. Insituations where passive beams are used inconjunction with a quiet air system, such asdisplacement ventilation, the opportunitiesfor noise reduction increase further.

    Reduced Mechanical Footprint

    The increased cooling capacity of wate

    allows the transport system to be reducedin size. It is generally not unusual to be ableto replace ~60 ft² [6 m²] of air shaft with a6 in. [150 mm] water riser, increasing theamount of oor space available for use olease. Due to the simplicity of the systems(i.e. reduction in the number of moving partsand the elimination of zone lters, drainpans, condensate pumps, and mechanicacomponents), there tends to be less spacerequired in the interstitial space to supporthe HVAC system.

    Lower Maintenance Costs

    With no terminal unit or fan coil lters omotors to replace, a simple cleaning is althat is required in order to maintain the

    product.

  • 8/18/2019 Radiant Products Engineering Guide

    4/43H-4All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    When To Use Radiant Systems

    Hygienic System

    With the elimination of the majority oflters and drain pans, there is a reducedrisk of mold or bacteria growth in the entiremechanical system.

    Radiant systems such as radiant panelsand chilled sails are well-suited to someapplications and less so to others. As aresult, each application must be reviewedfor potential benets as well as the suitabilityof these types of systems. One considerationwhich can assist in the decision to employhydronic systems as opposed to an all-airsystem, is the air-side load fraction—orthe percentage of the total air supply thatmust be delivered to the zone to satisfycode and dehumidication requirements.Table 1 shows the load fraction for severalspaces. In the table the best applications forhydronic systems are those with the lowestair-side load fraction as they are the ones thatwill benet the most from the efcienciesof hydronic systems. Another factor whichshould be examined is the sensible heatratio or the percentage of the cooling loadthat is sensible as opposed to latent. Thelatent loads must be satised with an airsystem and offer some sensible cooling atthe same time because of the temperature ofdehumidied air. If the total sensible coolingload is signicantly higher than the capacityof the air supplied to satisfy the latent loads,a radiant system might be a good choice.

    Commercial Office Buildings

    In an ofce building hydronic heating andcooling systems provide several benets. Thelower supply air volume of the air handlingsystem provides signicant energy savings.In addition, the smaller infrastructurerequired to move this lower air ow allowsfor small plenum spaces, translating intoshorter oor-to-oor construction or higherceilings. The lower supply air volume andelimination of fans at or near the spaceoffers a signicant reduction in generatednoise. Often the lower air ow translatesto reheat requirements being reduced. Inthe case of 100% outside air systems, thelighting load captured in the return plenum

    is exhausted from the building, lowering theoverall cooling load.

    Schools

    Schools are another application that canbenet greatly from radiant panels and chilledsails systems. Similar to ofce buildings, thebenets of a lower supply air volume to thespace are lower fan power, shorter plenumheight, reduced reheat requirement, andlower noise levels (often a critical designparameter of schools).

    Hospital Patient Rooms

    Hospitals are unique applications in thatthe supply air volume required by localcodes for each space is often greater thanthe requirement of the cooling and heatingload. In some cases the standard or coderequires these higher air-change rates forall-air systems only. In these cases thetotal air-change rate required is reduced ifsupplemental heating or cooling is used.This allows for a signicant reduction insystem air volume and yields energy savingsand other benets.

    Furthermore, because these systems aregenerally constant air volume with thepotential to reduce the primary air-changerates, reheat and the cooling energy discardedas part of the reheat process is a signicantenergy savings opportunity. Depending onthe application, a 100% outside air systemmay be used. These systems utilize noreturn air and no mixing of return betweenpatient rooms, potentially lowering the riskof hospital associated infections.

    Hotels / Dorms

    Hotels, motels, dormitories, and similar typebuildings can also benet from hydronicsystems. Fan power savings often comefrom the elimination of fan coil units locatedin the occupied space. The energy savings

    associated with these “local” fans is similarin magnitude to that of larger air handlingsystems. It also allows for the eliminationof the electrical service required for theinstallation of fan coil units as well as areduction in the maintenance of the drainand lter systems. The removal of thesefans from the occupied space also provideslower noise levels, which can be a signicantbenet in the sleep areas.

    ApplicationTotal AirVolume (Typ.)

    VentilationRequirement (Typ.)

    Air-SideLoadFraction

    Ofce 1 cfm/ft2 [5 L/s m2] 0.15 cfm/ft2 [0.75 L/s m2] 0.15

    School   1.5 cfm/ft2 [7.5 L/s m2] 0.5 cfm/ft2 [2.5 L/s m2] 0.33

    Lobby 2 cfm/ft2 [10 L/s m2] 1 cfm/ft2 [5 L/s m2] 0.5

    Patient Room 6 ach 2 ach   0.33

    Load-driven Lab 20 ach 6 ach   0.3

    Table 1: Typical load fractions for several spaces in the United States

    Limitations

    There are several areas in a building wherehumidity can be difcult to control, suchas lobby areas and locations of egress.These areas may see a signicant shortterm humidity load if the entrances are notisolated in some way (revolving doors orvestibules). In these areas, a choice of acomplimentary technology such as fan coilunits or displacement ventilation is ideal.

    Other applications may have high air ow/ ventilation requirements, such as an exhaustdriven lab. The majority of the benefitprovided by the hydronic system is linkedto the reduction in supply air ow. As such,these applications may not see sufcientbenet to justify the addition of the hydroniccirculation system, making them not likelyto be a good candidate for this technology.

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    5/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-5

    Products - Radiant Panels

    Operation

    Radiant panels mainly use thermal radiationto handle the heating or cooling loads of aspace. Thermal radiation heat exchange isbased on differences in surface temperaturesas discussed in Chapter 3—Introduction toHeat Transfer from the Price Engineer'sHandbook. Radiant panels add energy to orremove it from a room mainly using radiationwith surfaces in the room, but also directlyto occupants (Figure 2). To a lesser extent,the panels also heat or cool a room throughconvection of the room air as it is heated orcooled by the panel surface.

    Because radiant panels can handle thesensible portion of a building load they mustbe paired with an air system for ventilationand latent load removal. In heating, forexample, heat from warm water is transferredto the panel surface via conduction. The heatpasses through the tubing, the mountingextrusion (the ‘n’), and the panel itself, tothe panel surface. At the surface, heat is bothradiated to other surfaces in the room andtransferred to room air via natural convection.

    The heat transfer through a radiant panel caneasily be modeled with a thermal resistancecircuit, as in Figure 3. The resistance circuitrepresents the actual components of aradiant panel. The nodes represent varioustemperatures of the panel componentsurfaces, and the ‘resistors’ represent the heat

    conduction through the panel componentsand to the surrounding room. The t w noderepresents the mean water temperature thattransfers through the copper tubing to theactual panel components. To achieve themaximum possible surface temperatureof the panel, T surf , the conduction from thepipe to the n to the panel surface mustbe maximized, or, inversely, the resistancemust be minimized. This can be achieved byusing materials that are highly conductivesuch as copper tubing and aluminum for then and panel. Even surface contact betweenthe water tubing and the ns decreasesresistance, along with thermal paste whichcan be applied between the n and the panelsurface to help spread heat evenly to the

    panel surface (Figure 4)

    RADIATION

    Figure 2: Radiation pathways

     Rconv,s

    T air, ceiling

    T  panel, outer insulation

     Rinsulation

     AUST,ceiling

     Rrad,s

     Rconv,room

    T air, room

    Fin

    Surface AUST, room

    T surf, panel

     Rrad,room

     R fin

    T  fin, ave

     R panel surface Copper tubing with

    Towards slab

    Towards room and occupants

     AUST = Area-weighted temperature

    of all indoor surfaces of walls, ceiling,

    floor, windows, doors, etc.

    Figure 3: Thermal resistance circuit diagram of a modular radiant panel

    Without ThermalPaste With Thermal Paste

    Figure 4: Surface temperature distribution of a radiant panel

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    6/43

  • 8/18/2019 Radiant Products Engineering Guide

    7/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-7

    Products - Chilled Sails

    Operation

    Chilled sails provide a functional andunique alternative to conventional radiantpanels. Sails couple the radiant coolingeffects of standard radiant panels with aconvective component. In cooling mode,chilled sails create natural convection bycooling the surrounding air as it passes overthe surface facing the plenum. As the airfalls into the occupied zone, where warmair is pulled over the sail, the convectivecooling capacity of the sail is coupled withthe radiant capacity of the cool sail surface,resulting in a cooling capacity greater thanthat of standard radiant panels. In cooling,the approximate breakdown of heat mode

    transfer of chilled sails is 30% by thermalradiation and 70% by natural convection.

    A general air ow diagram of an exposedchilled sail in heating and cooling mode canbe seen in Figure 8. In certain applications,sails can also be used for heating. In heatingmode, the sails use radiation only to heatthe zone below. Because sails have noinsulation on their reverse side, heat isradiated not only towards the room, butalso towards the building structure. As theslab warms, it in turn helps heat the roomto a small extent by thermal radiation andnatural convection.

    Like radiant panels, chilled sails can alsobe analyzed using a thermal resistance

    circuit diagram, as seen in Figure 9. Theresistance circuit represents the actualcomponents of a chilled sail. The nodesrepresent various temperatures of the sailcomponent surfaces or the conditions of theroom, and the ‘resistors’ represent the heatconduction through the panel componentsor heat transfer between the sail and theroom. The mean water temperature, t  ̅ w, noderepresents the mean water temperature thattransfers through the copper tubing to theactual sail. Most chilled sails are one singleextrusion, which means that the ‘n’ and‘sail’ are one solid piece of aluminum. Tomaximize heat transfer through the sail,or, conversely, to minimize resistance, amaterial with high thermal conductivity,

    such as aluminum, is typically used.As seen in Figure 10, a chilled sail transfersheat to a room with a combination ofradiation and natural convection. Becausechilled sails have no insulation on theirreverse sides, heat is transferred from thecopper tubing/n to the slab and plenum.

    The heat transfer from the sail to the roomhas three components: natural convectionwith the room air, thermal radiation with theroom surfaces, and thermal radiation fromthe top of the sail with either the suspendedceiling or the xed ceiling, depending on thedesign details.

    Figure 8: Air ow pattern of an exposed chilled sail in cooling and heating mode

    Cooling

    Heating

    Sail

    Sail

    Figure 9: Thermal resistance circuit diagram of a chilled sail

    Figure 10: Typical chilled sail

    Radiant ProductsEngineering Guide

    Towards slab

    Towards room and occupants

    T air, room AUST, room

    Rrad, room

    Rrad, ceiling

    Tair,ceiling

    Rconv, ceiling

    Rconv, room

    R fin/sail

    AUST, ceiling

    Tsurface, fin/soil Sail/Fin

    Copper tubing with

    Top Bottom

  • 8/18/2019 Radiant Products Engineering Guide

    8/43

  • 8/18/2019 Radiant Products Engineering Guide

    9/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-9

    0

    75

    80

    90

    100

    10 20 30 40 50 60 70

        C   a   p   a   c    i   t   y   o    f    S   a    i    l ,

        %

    Free Area as a Percentage of Sail Area

    Figure 16: Typical piping of a sail with an odd number of passes

    Figure 17: Typical even number of passes

    Figure 14: Free area vs. active area of sail Figure 15: Clearance between chilled sail and slab

    0

    0 1 2 3 4 5 6

    20

    40

    60

    80

    100

    0 50 100 150

        E    f    f   e

       c   t    i   v   e    C   a   p   a   c    i   t   y   o    f    S   a    i    l ,

        %

    Clearance Between Chilled Sail and Slab, in.

    Clearance Between Chilled Sail and Slab, mm

    Water Supply

    Sail 1 Sail 2 Sail 3

    Water Return

    Flex HoseFlex Hose

    Water Supply

    Flex Hose

    Products - Chilled Sails

    The amount of free area vs. active area of sail will affect the performance of the sail system according to Figure 14. In all cases, theamount of space between the back of the sail and the structural slab will affect the level of circulation, and thereby the convective coolingcomponent. This capacity is affected according to Figure 15.

    Radiant ProductsEngineering Guide

    Connecting Chilled Sails

    Depending on the width of the unit, the sailsmay have connection locations on oppositeends. Sails with an odd number of sectionswill have connections on opposite ends,and even number of sections will haveconnections on the same ends, as seen

    in Figures 16 and 17 below. Flex hose isgenerally used to connect the water owbetween the units.

  • 8/18/2019 Radiant Products Engineering Guide

    10/43H-10All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    1. Determine the ventilation requirement

    The ventilation requirement should be calculated to meet ventilatiown codes. For example, using ASHRAE Standard 62-2004 to determinethe minimum fresh air ow rate:

    L1

      where

      Qoz = minimum fresh air ow rate, cfm [L/s]

       R p  = outdoor air ow rate per person, cfm/person [L/s(person)]

      P z  = zone population or maximum number of occupants in zone

       Ra  = outdoor air ow rate per unit area, cfm/ft2 [L/sm2]

       A Z   = zone oor area or net occupied area of the zone, ft2 [m2]

    2. Determine required supply air dew-point temperature to remove the latent load

    L2

      where

    q L  = latent load, Btu/h [W]

      Qs  = supply air ow rate, cfm [L/s]

       ΔW  = difference in humidity ratio between the supply air and the room condition,

    lbm,w /lbm,DA or gr/lbm,DA [kgw /kgDA or gw /kgDA]

    Typically, the moisture content of the ventilation air will be sufciently low in the heating season to offset the internal gains.

    3. Determine the occupied zone humidity ratio if there is excessive latent cooling

    From equation L2:

    L3

      where  W oz  = humidity ratio of the room condition, lbm,w /lbm,DA or gr/lbm,DA [kgw /kgDA or gw /kgDA]

      W SA = humidity ratio of the supply air, lbm,w /lbm,DA or gr/lbm,DA [kgw /kgDA or gw /kgDA]

    If W oz is determined to be too low for comfort, humidication of the ventilation air should be considered.

    4. Determine the supply air volume

    The supply air volume is the maximum volume required by code for ventilation, and the volume required for controlling the latent load:

    L4

      where

      Q L  = air ow rate required for controlling the latent load, cfm [L/s]

    5. Determine the heating capacity of the supply airIP L5

    SI L5

      where

      qs,air  = heating capacity of the supply air, Btu/h [W]

       ρ  = uid density, lbm/ft3 [kg/m3]

      c p  = specic heat at constant pressure Btu/hlb°F [kJ/(kgK)]

      Qair   = supply air ow rate, cfm [L/s]

       Δt air  = air temperature change (t return - t supply), °F [K]

    Design Procedure – Heating

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    11/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-11

    6. Determine the heating required from the water side

    L6

      where

      qs, hydronic = heating capacity of the water side, Btu/h [W]

      qt   = total sensible heating capacity, Btu/h [W]

    7. Determine an appropriate temperature loss through the panels

    Specify a panel surface temperature, then nd the related mean water temperature, t  ̅ w.

    Design Procedure – Heating

    Radiant ProductsEngineering Guide

    Figure 18: Connection between mean water temperature and panel surface temperature or,  t  panel - t room = 0.74 (t  ̅ w - t room)

    0   10 120

    0   10 20 30 40 50 60

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0

    5

    35

    45

    50

       t  w  -   t  r  o  o  m      [

         R     ]

       t  w  -   t  r  o  o  m      [

         K     ]

    20 30 40 50 60 70 80 90 100 110

    10

    15

    20

    25

    30

    40

     t panel  - t room [K]

     t panel  - t room [R]

    8. Determine the heat transfer coefficients for the radiant panels

    The natural convection coefcient is:

    IP L7

    SI L7 

    Where

      hc,natural = natural convection coefcient, Btu/hft2°F [W/m2K]

      t a  = room temperature, °F [K]

      t  panel = panel temperature, °F [K]

       Dh  = hydraulic diameter, ft [m]

     Dh = 4A panels / P panels   L8

      Where

     A panels = surface area of active panels, ft2 [m2]

    P panels = the pipe internal perimeter, ft [m]

  • 8/18/2019 Radiant Products Engineering Guide

    12/43H-12All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Design Procedure – Heating

    Radiant ProductsEngineering Guide

    The forced convection coefcient is:

    IP L9

    SI L9

      Where

      hc,forced  = forced convection coefcient, Btu/hft2°F [W/m2K]

      ach  = air change rate, cfm/ft2 [m3 /hm2]

     

    The total convection coefcient is:

    L10

      Where

      hc,total = total convection coefcient, Btu/hft2°F [W/m2K]

    9. Determine the specific capacity of the radiant panels

    The convective heat transfer per square foot to the panel is determined:

    L11

      where

      q ̋ c  = convective heat ux or convective rate per cross sectional area, Btu/hft2 [W/m2]

      qc  = convective heat transfer rate, Btu/h [W]

       A  = surface area of the medium, ft2 [m2]

    Assuming that the wall temperature is equal to the air temperature, the radiant heat exchange with the panel is determined:

    IP L12

    SI L12

     

    where

      q”r   = radiant heat ux, Btu/hft2 [W/m2]

       AUST  = area-weighted temperature of all indoor surfaces of walls, ceiling,oor, windows, doors, etc. (excluding active panel surfaces), °F [°C]

    The total heat transfer per unit of face area is

    L13

      where

      q ̋ o = total heat ux, Btu/hft2 [W/m2]

    10. Determine the area of panels required

    L14

      where

       A panels = area of panels, ft2 [m2]

  • 8/18/2019 Radiant Products Engineering Guide

    13/43

  • 8/18/2019 Radiant Products Engineering Guide

    14/43H-14All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 1 - Patient Room (IP)

    In this case, the supply air is a mix of the return air and the ventilation air. This mixture of outdoor air (at the outdoor conditions, assumingsaturated air at 15 °F with a humidity ratio of 12.5 gr/lb) and return air (assuming that it is at the design conditions of 75 °F, 40% RH – 52.5gr/lb), will have more than enough capacity to handle the latent load. In applications where humidity is critical, further analysis may bedone to determine the requirement of humidication. For more information refer to Chapter 5—Introduction to Psychrometrics of thePrice Engineer's Handbook.

    Determine the heating capacity of the supply air

    Using equation L5:

     

    Determine the heating required from the water side

     

    Determine an appropriate temperature loss through the panels

    Using a mean water temperature of:

     

    Determine the heat transfer coefficients for the radiant panels

    Using equation L7 and the relation for  Dh from equation L8, the natural convection coefcient is determined:

    Due to the conguration of the room, it can be assumed as a rst estimation that the panels will be arranged at the perimeter where theload is, and run the width of the exposure (10 ft). Assuming also a 2 ft width of panel:

     

    Using equation L9, the forced convection coefcient is determined:

     

    Using equation L10, the total convection coefcient is determined:

     

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    15/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-15

    Radiant ProductsEngineering Guide

    Example 1 - Patient Room (IP)

    Determine the specific capacity of the radiant panels

    Using equation L11, the convective heat transfer per square foot to the panel is determined:

     

    The outside air temperature has a signicant impact on the inside surface temperatures of exterior walls. The exterior wall temperatureis determined with an h value, convective heat transfer coefcient of a vertical wall, of 1.46 Btu/(hft2°F) and a U value, overall heat transfecoefcient, of 0.315 Btu/(hft2°F):

     

    The average unheated surface temperature is:

    t  

    Calculating the radiant heat exchange:

     

    From equation L13, the total heat transfer per unit of face area is:

     

    Determine the area of panels required

    Using equation L14:

     

  • 8/18/2019 Radiant Products Engineering Guide

    16/43H-16All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 1 - Patient Room (IP)

    Therefore, the assumption of panel size (20 ft2) used to calculate the hydraulic diameter is appropriate.

    The ow rate required to manage the load with a panel ΔT of 10 °F is:

    For simplicity, a 2 ft × 10 ft Price RPL linear radiant panel is selected.

    This panel with 0.41 gpm will have a pipe velocity of 0.55 fps, which corresponds to a Reynolds number of 1900, which is in the laminar

    range. For a better selection, the ow rate is increased to 1.3 gpm, which corresponds with a Reynolds number of 6400, which is in theturbulent region. From the performance chart, this also increases the pressure drop from 0.31 ft to 3.7 ft, which will allow better owcontrol of the panel.

    Recalculating the temperature loss in the panel as well as the capacity:

    This increase in capacity will result in only requiring 15.7 ft2, though it is more practical to stay with the original size in order to maintainaesthetics (the panel will run the length of the perimeter) as well as a standard module size (24 in. wide). Panels can be designed tohave both active and inactive sections to maintain aesthetics.

    When running the entire length of the room, the trim and series option will allow the panel to be trimmed on site if the room size variesslightly during construction.

    PATIENT ROOM

    Corridor

    Panel

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    17/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-17

    Radiant ProductsEngineering Guide

    Consider the patient room shown in the gure below. The patient room includes a television, monitoring equipment and overheadlighting. The temperature set-point is 24 °C with a minimum relative humidity of 40%. The room is 3 m wide, 6 m long, and has a 3m ceiling. There is one exterior wall and window. The supply air temperature in heating mode is reset to 35 °C and the heating watetemperature is 72 °C.

    PATIENT ROOM

    Corridor

    3 m

    6 m

    1.75 m

    2.25 m

    Determine

    The water ow rate and pressure drop for the heating panels required to handle the heating load, assuming -10 °C outdoor air temperature

    Overnight in winter, the envelope loss is 1400 W and the internal gains at that time are limited to the patient load:

    Design Considerations

    Patient 50 W

    Medical Staff/Visitors 0

    Television 0

    Medical Equipment 0

    Overhead Lighting 0

    Envelope   -1400 W

    Total   -1350 W

    Patient latent load   45 W

    Determine the Ventilation Requirement

    For this example, local code refers to ASHRAE Standard 170-2008 for the HVAC system. According to ASHRAE Standard 170-2008,patient rooms with auxiliary heating require 4 ach of supply air, of which two are outdoor air.

    Determine the required supply air dew-point temperature to remove the latent load

    From equation L2:

    Using the ventilation rate:

    Example 1 - Patient Room (SI)

  • 8/18/2019 Radiant Products Engineering Guide

    18/43H-18All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    In this case, the supply air is a mix of the return air and the ventilation air. This mixture of outdoor air (at the outdoor conditions, assumingsaturated air at -10 °C with a humidity ratio of 1.8 g/kg) and return air (assuming that it is at the design conditions of 24 °C, 40% RH – 7.4g/kg), will have more than enough capacity to handle the latent load. In applications where humidity is critical, further analysis may bedone to determine the requirement of humidication. For more information refer to Chapter 5—Introduction to Psychrometrics of thePrice Engineer's Handbook.

    Determine the heating capacity of the supply air

    Using equation L5:

     

    Determine the heating required from the water side

     

    Determine an appropriate temperature loss through the panels

    Using a mean water temperature of:

     

    Determine the heat transfer coefcients for the radiant panels

    Using equation L.7 and the relation for Dh from equation L.8, the natural convection coefcient is determined:

    Due to the conguration of the room, it can be assumed as a rst estimation that the panels will be arranged at the perimeter where theload is, and run the width of the exposure (3 m). Assuming also a 600 mm width of panel:

     

    Using equation L9, the forced convection coefcient is determined:

     

    Using equation L10, the total convection coefcient is determined:

     

    Example 1 - Patient Room (SI)

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    19/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-19

    Radiant ProductsEngineering Guide

    Example 1 - Patient Room (SI)

    Determine the specific capacity of the radiant panels

    Using equation L11, the convective heat transfer per square foot to the panel is determined:

     

    The outside air temperature has a signicant impact on the inside surface temperatures of exterior walls. The exterior wall temperatureis determined with an h value, convective heat transfer coefcient of a vertical wall, of 8.29 W/(m 2K) and a U value, overall heat transfecoefcient, of 0.055 W/(m2K):

     

    The average unheated surface temperature is:

     

    Calculating the radiant heat exchange:

     

    From equation L13, the total heat transfer per unit of face area is:

     

    Determine the area of panels required

    Using equation L14:

     

  • 8/18/2019 Radiant Products Engineering Guide

    20/43H-20All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 1 - Patient Room (SI)

    Therefore, the assumption of panel size (1.8 m2) used to calculate the hydraulic diameter is appropriate.

    The ow rate required to manage the load with a panel ΔT of 5 K is:

    For simplicity, a 600 mm × 3000 mm RPL linear radiant panel is selected.

    This panel with 0.027 kg/s will have a pipe velocity of 0.24 m/s, which corresponds to a Reynolds number of 4300 with a pressure drop

    of 1.2 kPa, which is a good selection.When running the entire length of the room, the trim and series option will allow the panel to be trimmed on site if the room size variesslightly during construction.

    PATIENT ROOM

    Corridor

    Panel

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    21/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-21

    Radiant ProductsEngineering Guide

    Design Procedure – Cooling

    1. Determine the ventilation requirement

    The ventilation requirement should be calculated to meet ventilation codes. For example, using ASHRAE Standard 62-2004 to determinethe minimum fresh air ow rate:

    L1

    2. Determine required supply air dew-point temperature to remove the latent load

    L2

    If the required humidity ratio is not practical, recalculate the supply air volume required with the desired humidity ratio.

    3. Determine the supply air volume

    The supply air volume is the maximum volume required by code for ventilation and the volume required for controlling the latent load

    L4

    4. Determine the sensible cooling capacity of the supply air

    IP L5

    SI L5

    5. Determine the sensible cooling required from the water side

    L6

    6. Determine an appropriate temperature rise through the panels

    A panel temperature correction is unnecessary because the temperature differential between the water and air is small in cooling modeFor panels and sails that are designed well, the surface temperature can be approximated to be the mean water temperature:

    L15

      where

      t w  = mean water temperature, °F [K]

      t CHWS  = chilled water supply temperature, °F [K]

      t out   = chilled water return temperature, °F [K]

    7. Determine the heat transfer coefficients for the radiant panels

    The natural convection coefcient is:

    IP L16

    SI L16

  • 8/18/2019 Radiant Products Engineering Guide

    22/43H-22All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Design Procedure – Cooling

    The forced convection coefcient is:

    IP L9

    SI L9

     

    The total convection coefcient is:

    L10

    8. Determine the specific capacity of the radiant panels

    The convective heat transfer per square foot to the panel is determined:

    L11

     

    Assuming that the wall temperature is equal to the air temperature, the radiant heat exchange with the panel is determined:

    IP L12

    SI L12

     

    The total heat transfer per unit of face area is:

    L13 

    9. Determine the area of panels required

    L14

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    23/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-23

    Radiant ProductsEngineering Guide

    Example 2 - Small Office (IP)

    Consider a small ofce with a southern exposure. The space is designed for two occupants, a computer with LCD monitor, T8 orescenlighting, and has a temperature set-point of 75 °F. The room is 10 ft wide, 12 ft long, and 9 ft from oor to ceiling. The owner expressedinterest in using radiant panels.

    12 ft

    9 ft10 ft

    SMALL OFFICE

    Window

    Space Considerations

    One of the primary considerations when using a radiant heating and cooling system is humidity control. As previously discussed, it isimportant to consider both the ventilation requirements and the latent load when designing the air-side of the system.

    The assumptions made for the example are as follows:

     • Load/person is 250 Btu/h sensible and 155 Btu/h latent

     • Lighting load in the space is 6.875 Btu/h/ft²

     • Computer load is 300 Btu/h (CPU and LCD Monitor)

     • Total skin load is 1450 Btu/h

     • Specic heat and density of the air are 0.24 Btu/lb°F and 0.075 lb/ft³ respectively • Design conditions are 75 °F, with 50% relative humidity

     • Design dew point is 55 °F

    Design Considerations

    Occupants 2

    Set-Point 75 °F

    Floor Area 120 ft²

    Exterior Wall 108 ft²

    Volume 1080 ft³

    qoz   800 Btu/h

    ql   825 Btu/h

    qex   1450 Btu/hqT   3075 Btu/h

    Determine

    a) The ventilation requirement.

    b) The suitable supply air and supply water temperatures.

    c) The total convective heat transfer coefcient for radiant panels.

  • 8/18/2019 Radiant Products Engineering Guide

    24/43H-24All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Solution

    a) Determine the ventilation requirement

    The ventilation requirement should be calculated to meet ventilation codes. For example, using ASHRAE Standard 62-2004 to determinethe minimum fresh air ow rate for a typical ofce space:

    b) Determine required supply air dew-point temperature to remove the latent load

    From equation L2:

    Using the ventilation rate:

     At the design conditions (75 °F, 50% RH), the humidity ratio is 65 gr/lb, requiring a difference in humidity ratio between the supply androom air of:

    From the gure below, the dew point corresponding to the humidity ratio is 40 °F, which is too cool for standard equipment.

    Evaluating the humidity ratio at several temperatures led to the selection of a dew point of 50 °F in order to use less expensive commonequipment while also minimizing the supply air volume required to control humidity.

    Humidity Ratio

    Dew Point lb/lb gr/lb

    40 0.00543 38

    45 0.0065   46

    50   0.0075 53

    55 0.0095   67

    0.000

    0.002

    0.004

    0.006

    0.010

    0.012

    0.014

    0.016

    0.018

    0.020

    0.022

    0.024

    0.026

    0.028

    0.030

    35 40

    1      2      . 5      

    1      3      . 0      

    1     3      . 5        1 0 %

     2  0  %

      3  0  %

     4  0  %  5  0  %

      6  0  %

       7  0  %  8

      0  %   9   0   %

    1      4      . 0      

    1      4      . 5      

    1      5      . 0      

    45 55 60 65 70 80 85 90 95 100 105 110 115 120

    65

    Dry Bulb Temperature, ºF

       E  n   t   h  a   l  p   y

       -    B   t

      u   /   l   b

       o   f    D

      r   y    A   i  r

    H  u mi    d  

    i    t   y R  a  t  i    o  ,l    b  w /   l    b  D A 

    70

    75

    80

    85

    1   5   

    2    0   

    2    5   

    3    0   

    3    5   

    4   0   

    4   5   

    5   0   

    6    0      6    5   

    Volume - ft3 /lb of Dry Air

    Saturation Temperature, ºF

    Relative Humidity

    40

    45

    50

    55

    60

    35

    0.0075

    50

    Example 2 - Small Office (IP)

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    25/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-25

    Radiant ProductsEngineering Guide

    The required air volume to satisfy the latent load is:

    The supply air volume to the ofce is the maximum volume required by code for ventilation and the volume required for controllingthe latent load:

    c) Determine the heat transfer coefficients for the radiant panels

    For panels and sails that are designed well, the surface temperature can be approximated to be the mean water temperatureAssuming a chilled water supply temperature 2 °F above the dew point in order to minimize the potential for condensation and a

    temperature rise of 4 °F through the panel leads to a mean water temperature of:

    Using equation L16, the natural convection coefcient is determined:

    Using equation L9, the forced convection coefcient is determined:

     

    Using equation L10, the total convection coefcient is determined:

     

    Example 2 - Small Office (IP)

  • 8/18/2019 Radiant Products Engineering Guide

    26/43H-26All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 2 - Small Office (SI)

    Consider a small ofce with a southern exposure. The space is designed for two occupants, a computer with LCD monitor, T8 orescentlighting, and has a design temperature set-point of 24 °C. The room is 3 m wide, 4 m long, and 3 m from oor to ceiling. The ownerexpressed interest in using radiant panels.

    Space Considerations

    One of the primary considerations when using a radiant heating and cooling system is humidity control. As previously discussed, it isimportant to consider both the ventilation requirements and the latent load when designing the air-side of the system.

    The assumptions made for the example are as follows:

     • Load/person is 65 W sensible and 55 W latent

     • Lighting load in the space is 25 W/m²

     • Computer load is 80 W (CPU and LCD Monitor)

     • Total skin load is 425 W

     • Specic heat and density of the air are 1.007 kJ/kgK and 1.3 kg/m³ respectively

     • Design conditions are 24 °C, with 50% relative humidity

     • Design dew point is 13 °C

    Design Considerations

    Occupants 2

    Set-Point   24 °C

    Floor Area 12 m²

    Exterior Wall 12 m²

    Volume 36 m³

    qoz   210 W

    ql   300 W

    qex

      425 WqT   935 W

    Determine

    a) The ventilation requirement.

    b) The suitable supply air and supply water temperatures.

    c) The total convective heat transfer coefcient for radiant panels.

    3 m

    4 m

    3 m

    SMALL OFFICE

    Window

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    27/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-27

    Radiant ProductsEngineering Guide

    Example 2 - Small Office (SI)

    Solution

    a) Determine the ventilation requirement

    The ventilation requirement should be calculated to meet ventilation codes. For example, using ASHRAE Standard 62-2004 to determinethe minimum fresh air ow rate for a typical ofce space:

    b) Determine required supply air dew-point temperature to remove the latent load

    From equation L2:

    Using the ventilation rate:

     At the design conditions (24 °C, 50% RH), the humidity ratio is 9.5 g/kg of dry air, requiring a difference in humidity ratio between thesupply and room air of:

    From the gure below the dew point corresponding to the humidity ratio is 5 °C, which is too cool for standard equipment.

    Evaluating the humidity ratio at several temperatures led to the selection of a dewpoint of 10 °C in order to use less expensive equipmenwhile also minimizing the supply air volume required to control humidity.

    Humidity Ratio

    Dew Point g/kg

    5 5.5

    7.5 6.75

    10 8

    12.5 9.25

    Dry-Bulb Temperature, ºC

        E   n   t    h   a    l

       p   y    -     k   J

       /    k  g    o    f

         D   r   y 

        A    i   r

    30

    25

    20

    15

    10

    5

    0

    50454035302520151050

    0

    4  5  

    4  0  

    3  5  

    3  0  

    2  5  

    2  0  

    1 5  

    5  0  

    5  5  

    6  0  

    6  5  

    7  0  

    7  5  

    8  5  

    9  0  

    9  5  

    1 0  0  

    1 0  5  

    1 0  5  

    1 1 0     1 1 5     1 2  0     1 2  5  

    Volume - m3 /kg of Dry Air

    Saturation Temperature, ºC

    Relative Humidity

    H  u mi    d  i    t   y R  a  t  i    o  , g w /   k   g D A 

    30

    10

    5

    15

    20

    0      . 7      8      

    0      . 8      0      

    0      . 8      2      

    0      . 8      4      

    0      . 8      6      

    0      . 9      0      

    0      

    . 9      2      

    0      . 9      4      

    0      . 9      6      

     1  0  %

      2  0  %

      3  0  %

      4  0  %

       5  0   %

       6   0   %

       7   0   %  8

       0   %   9   0   %

    25

    8

  • 8/18/2019 Radiant Products Engineering Guide

    28/43H-28All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 2 - Small Office (SI)

    The required air volume to satisfy the latent load is:

    The supply air volume to the ofce is the maximum volume required by code for ventilation and the volume required for controllingthe latent load:

    c) Determine the heat transfer coefficients for the radiant panels

    For panels and sails that are designed well, the surface temperature can be approximated to be the mean water temperature. Assuminga chilled water supply temperature 1 K above the dew point in order to minimize the potential for condensation and a temperature riseof 2 K through the panel leads to a mean water temperature of:

    Using equation L16, the natural convection coefcient is determined:

    Using equation L9, the forced convection coefcient is determined:

     

    Using equation L10, the total convection coefcient is determined:

     

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    29/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-29

    Radiant ProductsEngineering Guide

    Performance

    Radiant panels performance depends onseveral factors:

     • The difference in surface temperaturesbetween the panel and the surroundingsurfaces

     • The mean water temperature and thepanel thermal resistance

     • View factor of the panel to the surfacesto be cooled/heated

     • Water ow rate

     • Emissivity and absorption of affectedsurfaces

    The water ow rate in the coil affects

    two performance factors. First, the heattransfer between the water and the panel isdependent on whether the ow is laminar(poor), transitional (inconsistent) orturbulent (good). Secondly, it also affectsthe mean water temperature.

    The higher the ow rate, the closer thedischarge temperature will be to theinlet, thereby changing the average watertemperature imposed on the panel. Asthe separation between the mean watertemperature and the surrounding roomtemperature (ΔT) increases, so does thecapacity. In heating, the ΔT is limited bythermal comfort. In cooling, the ΔT is alsolimited by two factors, thermal comfort andcondensation prevention. Good practice

    for panel selection in cooling avoidscondensation by limiting the enteringwater temperature to the room’s dewpoint + 2 °F [1 K]. The most commondesign condition for spaces in cooling is75 °F [24 °C] at 50% RH, producing a dewpoint of 55 °F [13 °C] and limiting enteringwater temperature to a minimum of 57 °F[14 °C].

    Figure 19 shows the effect on the owrate, indicated by Reynolds number, onthe capacity of a typical radiant panel. Asindicated on the chart, increasing the owrate into the transitional range (Re > 2300,shown in blue on the graph) increases theoutput of the panel.

    Product Selection

    Figure 19: Radiant panel capacity vs. water ow

    40

    0 2000 4000 6000 8000 10000 12000

    50

    60

    70

    80

    90

    100

         C   a   p   a   c    i   t   y ,

        %

    Re

    The water ow rate is largely dependent on thepressure drop and return water temperaturesacceptable to the designer. In most casesthe water ow rate should be selected tobe fully turbulent (Re > 4000) under designconditions. The difference between the meanwater temperature is dened as:

    L17

    and the room/surrounding surfacetemperatures are the primary driverof panel performance. The larger thisdifference is, the greater the radiant andconvective transfer rates are. As noted inequation L12, the radiant energy exchangebetween two surfaces is based on theabsolute temperature to the fourth power.Conversely, a lower temperature differencewill reduce the amount of potential energyexchange, and thereby capacity. As a result,it is desirable from a capacity standpointto select entry water temperatures as lowas possible in cooling, while maintaining itabove the dew point in the room to ensuresensible cooling only.

    The location of radiant panels relative toloads in the space inuences their capacityand is greatly dependent on the view factoof the panel to the objects that are to beconditioned. When used in spaces withhigh solar gain, such as perimeter zonesthe capacity increases as the surroundingsurface temperature increases. As surfacetemperatures change throughout theday, panel capacity changes accordinglyFurthermore, as the distance between thepanel and the affected surface increases, theview factor diminishes, thus reducing direcradiant exchange between the two surfacesPanel placement is based on a combinationof surface temperature and distance to theoccupant in order to ensure an effectiveoperative temperature is achieved. Locatingpanels along glass perimeters without lowemissivity coatings may have a negativeeffect on energy use as some energy will belost to the outdoors through the glass.

  • 8/18/2019 Radiant Products Engineering Guide

    30/43H-30All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 3 - Small Office Panel Selection (IP)

    Design Considerations

    Occupants 2

    Set-Point 75 °F

    Floor Area 120 ft²

    Exterior Wall 108 ft²

    Volume 1080 ft³

    qoz 800 Btu/h

    ql   825 Btu/h

    qex 1450 Btu/h

    qT 3075 Btu/h

    hc, total 0.823 Btu/hft°F

    Qs   38 cfm

    Ts   50 °F

    tCHWS   57 °F

    tpanel   59 °F

    Determine

    a) The area of panels required.

    b) The area of panels required assuming 95 °F outdoor air temperature.

    c) The ow rate for the panels from (b).

    d) A practical layout and piping arrangement for the panels from (b).

    12 ft

    9 ft10 ft

    SMALL OFFICE

    Window

    Consider the small ofce presented in the previous example.

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    31/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-31

    Radiant ProductsEngineering Guide

    Solution

    a) Determine the sensible cooling capacity of the supply air

    Using equation L5:

    Determine the sensible cooling required from the water-side

     

    Determine the specific capacity of the radiant panelsUsing equation L11, the convective heat transfer to the panel is determined:

    Using equation L12 and assuming that the wall temperature is equal to the room air set-point temperature, the radiant heat exchangewith the panel is determined:

     

    From equation L13, the total heat transfer per unit of face area is:

    Determine the area of panels required

    Using equation L14:

    Using multiples of 4 ft2, which is a standard ceiling tile sized at 2 ft × 2 ft, the total area required is 76 ft2.

    Example 3 - Small Office Panel Selection (IP)

  • 8/18/2019 Radiant Products Engineering Guide

    32/43H-32All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 3 - Small Office Panel Selection (IP)

    b) The area of panels required assuming 95 °F outdoor air temperature

    The exterior wall temperature is determined with an h value, convective heat transfer coefcient, of 1.46 Btu/(hft2°F) and a U value, overallheat transfer coefcient, of 0.693 Btu/(hft2°F):

     

    The average unheated surface temperature is:

    Recalculating the radiant heat exchange and total heat transfer from (a):

     Determine the area of panels required

    Using equation L14:

     

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    33/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-33

    Example 3 - Small Office Panel Selection (IP)

    Radiant ProductsEngineering Guide

    SMALL OFFICE

    Light

    Panel

    PanelPanel

    Panel Panel

    SMALL OFFICE

    Panel Panel

    Panel

    Panel

    Light

    c) The flow rate for the panels from (b)

    d) A practical layout and piping arrangement for the panels from (b)

    In order to t the panels from (b) in a lay-in ceiling, a 48 in. × 24 in. RPM modular panel is selected. Referring to the product datasheet, a ow rate of 1.02 (~1 gpm) has a water pressure drop of 0.17 ft.

    Using these panels would require a quantity of:

     

    If these panels are connected in series, the total loop pressure drop would be:

  • 8/18/2019 Radiant Products Engineering Guide

    34/43H-34All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 3 - Small Office Panel Selection (SI)

    Design Considerations

    Occupants 2

    Set-Point 24 °C

    Floor Area 12 m²

    Exterior Wall 12 m²

    Volume 36 m³

    qoz 210 W

    ql   300W

    qex 425 W

    qT 935 W

    hc, total 4.71 W/m2K

    Qs   22.5 L/s

    Ts   10 °C

    tCHWS   14 °C

    tpanel   15 °C

    Determine

    a) The area of panels required.

    b) The area of panels required assuming 35 °C outdoor air temperature.

    c) The ow rate for the panels from (b).

    d) A practical layout and piping arrangement for the panels from (b).

    Consider the small ofce presented in the previous example.

    3 m

    4 m

    3 m

    SMALL OFFICE

    Window

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    35/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-35

    Example 3 - Small Office Panel Selection (SI)

    Solution

    a) Determine the sensible cooling capacity of the supply air

    Using equation L5:

    Determine the sensible cooling required from the water-side

     

    Determine the specific capacity of the radiant panelsUsing equation L11, the convective heat transfer to the panel is determined:

    Using equation L12 and assuming that the wall temperature is equal to the room air set-point temperature, the radiant heat exchangewith the panel is determined:

     

    From equation L13, the total heat transfer per unit of face area is:

     

    Determine the area of panels required

    Using equation L14:

    Using multiples of 0.36 m2, which is a standard ceiling tile sized at 600 mm × 600 mm, the total area required is 6.48 m 2.

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    36/43H-36All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 3 - Small Office Panel Selection (SI)

    b)The area of panels required assuming 35 °C outdoor air temperature

    The exterior wall temperature is determined with an h value, convective heat transfer coefcient, of 0.255 W/(m2K) and a U value, overallheat transfer coefcient, of 0.121 W/(m2K):

     

    The average unheated surface temperature is:

    Recalculating the radiant heat exchange and total heat transfer from (a):

     Determine the area of panels required

    Using equation L14:

     

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    37/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-37

    Radiant ProductsEngineering Guide

    Example 3 - Small Office Panel Selection (SI)

    SMALL OFFICE

    Light

    Panel

    PanelPanel

    Panel Panel

    SMALL OFFICE

    Panel Panel

    Panel

    Panel

    Light

    c) The flow rate for the panels from (b)

    d) A practical layout and piping arrangement for the panels from (b)

    In order to t the panels from (b) in a lay-in ceiling, a 1200 mm x 600 mm RPM modular panel is selected. Referring to the product datasheet, a ow rate of 0.07 (~0.075 kg/s) has a water pressure drop of 0.69 kPa.

    Using these panels would require a quantity of:

     

    If these panels are connected in series, the total loop pressure drop would be:

  • 8/18/2019 Radiant Products Engineering Guide

    38/43H-38All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 4 - Small Office Chilled Sail Selection (IP)

    Consider the small ofce presented in the previous example.

    Design Considerations

    Occupants 2

    Set-Point 75 °F

    Floor Area 120 ft²

    Exterior Wall 108 ft²

    Volume 1080 ft³

    qoz 800 Btu/h

    ql   825 Btu/h

    qex 1450 Btu/h

    qT 3075 Btu/h

    Cooling Capacity of Hydronic System 2049 Btu/h

    tCHWS   57 °F

    tpanel   59 °F

    Determine

    The required area and possible location of chilled sails.

    Solution

    The difference between the room air temperature and the mean panel temperature is:

    Referring to the product data page, the specic capacity of the chilled sail is determined using this temperature difference:

     

    12 ft

    9 ft10 ft

    SMALL OFFICE

    Window

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    39/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-39

    Radiant ProductsEngineering Guide

    Example 4 - Small Office Chilled Sail Selection (IP)

    Determine the area of sails required

    Using equation L14:

    Selecting a sail that is 10 ft long and 4.5 ft wide provides 45 ft 2 of sail area. From the performance table, this piped-in series will resulin a pressure drop of 2 ft.

    24 in. × 96 in. Price CSA

    (troom - t  ̅ w), °F Capacity, Btu/h Water Flow Rate, gpm Head Loss, ft

    14 635 0.35 0.356

    16 740 0.41 0.488

    18 848 0.47 0.642

    20 959   0.53 0.816

    Based on 4 °F water temperature drop

    SMALL OFFICE

    Sail

  • 8/18/2019 Radiant Products Engineering Guide

    40/43H-40All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Example 4 - Small Office Chilled Sail Selection (SI)

    Consider the small ofce presented in the previous example.

    3 m

    4 m

    3 m

    SMALL OFFICE

    Window

    Design Considerations

    Occupants 2

    Set-Point 24 °C

    Floor Area 12 m²

    Exterior Wall 12 m²

    Volume 36 m³

    qoz 210 W

    ql   300 W

    qex 425 W

    qT 935 W

    Cooling Capacity of Hydronic System 557 W

    tCHWS   14 °C

    tpanel   15 °C

    Determine

    The required area and possible location of chilled sails.

    Solution

    The difference between the room air temperature and the mean panel temperature is:

    Referring to the product data page, the specic capacity of the chilled sail is determined using this temperature difference:

     

    Radiant ProductsEngineering Guide

  • 8/18/2019 Radiant Products Engineering Guide

    41/43

     © Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimetre. H-41

    Radiant ProductsEngineering Guide

    Example 4 - Small Office Chilled Sail Selection (SI)

    Determine the area of sails required

    Using equation L14:

    Selecting a sail that is 3 m long and 1.5 m wide provides 4.5 m2 of sail area. From the performance table, this piped-in series will resulin a pressure drop of 6 kPa.

    600 mm × 2908 mm Price CSA

    (t room - t  ̅w), K Capacity, W Water Flow Rate, kg/h Head Loss, kPa

    8 186 79 1.06

    9   217 93 1.46

    10 249 107 1.92

    11 281 120 2.44

    Based on 4 °C water temperature drop

    SMALL OFFICE

    Sail

  • 8/18/2019 Radiant Products Engineering Guide

    42/43H-42All Metric dimensions ( ) are soft conversion. © Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimetre.

    Radiant ProductsEngineering Guide

    References

    ASHRAE (2004a).Standard 55-2004—Thermal environmental conditions for human occupancy . Atlanta, GA: American

    Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc.

    ASHRAE (2004b). Standard 62.1-2004—Ventilation for acceptable indoor air quality . Atlanta, GA: American Society for

    Heating, Refrigerating and Air-Conditioning Engineers.

    ASHRAE (2005). Standard 138-2005—Method of testing for rating ceiling panels for sensible heating and cooling .

    Atlanta, GA: American Society for Heating, Refrigerating and Air-Conditioning Engineers.

    ASHRAE (2007). Humidity control design guide . Atlanta, GA: American Society for Heating, Refrigerating and Air-  

    Conditioning Engineers.

    ASHRAE (2008a). ASHRAE handbook—Applications. Atlanta, GA: American Society for Heating, Refrigerating and

    Air-Conditioning Engineers.

    ASHRAE (2008b). Standard 170-2008—Ventilation of health care facilities . Atlanta, GA: American Society for Heating,

    Refrigerating and Air Conditioning Engineers.

    ASHRAE (2009). ASHRAE handbook—Fundamentals . Atlanta, GA: American Society for Heating, Refrigerating and

    Air-Conditioning Engineers.

    ASHRAE (2010). Standard 55-2010—Thermal environmental conditions for human occupancy. Atlanta, GA: American

    Society for Heating, Refrigerating and Air-Conditioning Engineers.

    Awbi, H.B. & Hatton, A. (1999). Natural convection from heated room surfaces. Energy and Buildings, 30 , 233-244.

    Babiak, J,. Olesen B.W., & Petras, D. (2009). REHVA guidebook no. 7: Low temperature heating and high temperature

    cooling . Brussels, Belgium: Federation of European Heating and Air-conditioning Associations (REHVA).

    Beausoleil-Morrison, I. (2000). The adaptive coupling of heat and air ow modelling within dynamic whole-building

    simulation. PhD Thesis, University of Strathclyde, Glasgow, UK.

    Behne, M. (1999). Indoor air quality in rooms with cooled ceilings, mixing ventilation or rather displacement ventilation.

    Energy and Buildings, 30 , 155 – 166.

    Berglund, L., Rascati, R., & Markel., M.L. (1982). Radiant heating and control for comfort during transient conditions.

    ASHRAE Transactions, 88  (2), 765-775.

    Conroy, C., & Mumma, S.A. (2001). Ceiling radiant cooling panels as a viable distributed parallel sensible cooling

    technology integrated with dedicated outdoor-air systems. ASHRAE Transactions, 107  (1), 571-579.

    CSA (2010). CSA Z317.0-10—Special requirements for heating, ventilation, and air-conditioning (HVAC) systems in

    health care facilities . Mississauga, ON: Canadian Standards Association.

    DIN (2003). Ventilation for buildings—Ceiling-mounted radiant panels supplied with water at a temperature below

    120 °C –Part 2: Test method for thermal output (English version of DIN EN 14037-2) . Berlin, Germany: Bueth

    Verlag GmbH.

    DIN (2004). Ventilation for buildings—Chilled ceilings -Testing and rating (English version of DIN EN 14240) . Berlin,

    Germany: Bueth Verlag GmbH.

    Fisher, D.E. (1995). An experimental investigation of mixed convection heat transfer in a rectangular enclosure. PhD

    Thesis, University of Illinois, Urbana, IL.

    Fitzner, K. (1996). Displacement ventilation and cooled ceilings—Results of laboratory test and practical installations.

    Proceedings from Indoor Air ’96 . Nagoya, Japan.

    Incropera, F.P. & DeWitt, D.P. (1996).Fundamentals of heat and mass transfer(4th ed.). NewYork, NY: John Wiley and Sons.

    ISO (2005). ISO Standard 7730-2005—Ergonomics of the thermal environment–Analytical determination and

    interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria.

    Geneva, Switzerland: International Standards Organization.

  • 8/18/2019 Radiant Products Engineering Guide

    43/43

    Radiant ProductsEngineering Guide

    References

    Jeong J. & Mumma, S. A. (2003). Impact of mixed convection on ceiling radiant cooling panel. HVAC&R Research,

    9  (3), 251-257.

    Kochendörfer, C. (1996). Standard testing of cooling panels and their use in system Planning. ASHRAE Transactions,

    102  (1), 651-658.

    Min,T.C., Schutrum, L.F., Parmelee, G.V., & Vouris, J.D. (1956). Natural convection and radiation in a panel heated room.

    Heating Piping and Air Conditioning (HPAC) , 153 – 160.

    Mumma, S. A. (2002). Chilled ceilings in parallel with dedicated outdoor air systems: Addressing the concerns of

    condensation, capacity and cost. ASHRAE Transactions 2002  (2), 220 – 231.

    Mundt, E. (1990). Convection ows above common heat sources in rooms with displacement ventilation. Proceedings

    from Roomvent 1990 . Oslo, Norway.

    Nickel, J. (2002). 1.3 - Heating and cooling with ceilings. Technical report 87/2002e: Cooling and heating systems .

    Aachen, Germany: Krantz Komponenten.

    Novoselac, A., Burley, B., & Srebric, J. (2006). New convection correlations for cooled ceiling panels in rooms with

    mixed and stratied airow. HVAC&R Research, 12  (N2), 279-294.

    Novoselac, A. & Srebric, J. (2002). A critical review on the performance and design of combined cooling ceiling and

    displacement ventilation systems. Energy and Buildings, 34  (5), 497-509.

    Olesen, B.W., Sliwinska, E., Madsen, T.L., & Fanger, P.O. (1982). Effect of body posture and activity on the thermal

    insulation of clothing: Measurements by a moveable thermal manikin. ASHRAE Transactions, 88  (2), 791-801.

    Price Industries (2011). Price engineer's HVAC handbook—A comprehensive guide to HVAC fundamentals. Winnipeg,

    MB: Price Industries Limited.

    Schiavon, S, Bauman, F., Lee, K.H., & Webster, T. (2010). Development of a simplified cooling load design tool for

    underfloor air distribution systems, final report to CEC PIER program . Berkeley, CA: Center for the Built Environment,

    Center for Environmental Design Research, University of California at Berkeley.

    Stetiu, C. (1998). Radiant cooling in U.S. ofce buildings:Towards eliminating the perception climate imposed barriers.

    Doctorial Dissertation, Energy and Resources Group, University of California at Berkeley, CA.

    Tan, H., Murata, T., Aoki, K., & Kurabuchi, T. (1998). Cooled ceiling/displacement ventilation hybrid air conditioning

    system—Design criteria. Proceedings from Roomvent ’98 . Stockholm, Sweden.

    Virta, M., Butler, D., Gräslund, J., Hogeling, J., Kristiansen, E.L., Reinikainen, M., & Svensson, G. (2004). REHVA

    guidebook no. 5: Chilled beam application guidebook . Brussels, Belgium: Federation of European Heating and

    Air-conditioning Associations (REHVA).

    Yin, Y., Zhang, X., & Chen, Q. (2009). Condensation risk in a room with high latent load and chilled ceiling panel and

    with air supplied from liquid desiccant system. HVAC&R Research, 15  (2), 315-327.

    Zhang, H., Huizenga, C., Arens, E., & Yu, T. (2005). Modeling thermal comfort in stratified environments. Berkeley, CA:

    Center for the Built Environment, University of California.