11 Device type PLA 33 PLA 33 L PLA 33 CM PLA 33 C Continual U and I measurement PLA 44 CM 2 2 RS485 interface 2 External temperature sensor input Digital input / output / pulseoutput Real-time internal clock USB interface Ethernet interface DIN rail variant Auxiliary supply LCD display 2,55" 2 Internal flash memory Supply powercut events 20 events 20 events 512 MB 230 VAC, 50/60 Hz (+10%,-15%) or 24 VDC 1 GB TFT graphic VGA screen 5,7" EN 50160 class A device Neutral current measurement 1 calculated calculated calculated calculated Range of power line and quality analysers Energy Monitoring And Management Application Multifunction power line analysers PLA 33 and power quality analysers PLA 44 are essential part of systems for energy management and monitoring at industrial areas, office buildings, public service centres such as airports, railways and everywhere the energy flow control is requested. HM 2006 maximum demand controller is special device for load monitoring and control in order to reduce power peaks by disconnection of particular loads. Together with components for power factor correction, BMR offers complete range of power line analysers, quality analysers, maximum demand controllers and accessories for energy management and monitoring systems for various industry applications. PLA range description PLA 33 and PLA 44 are designed for electrical network parameters monitoring and energy management. Both types are fully 4 quadrant devices with continual voltage and current measurement according to norm EN 50160. Basic power line analyser PLA 33 is available in several variants. Simple variant is used for substitution of analogue devices. Variants with communication interface, internal memory and digital inputs and outputs are offered as a measuring point for monitoring and energy management in large SCADA systems. PLA 44 analyser is an advanced power quality analyser which meets specification according to the norm EN 50160 class A. Thanks to powerful 32 bits processor brings many useful features for detailed monitoring and quality analyse of LV and MV networks. Large memory, various communication interfaces, easy setting and usage, suppose PLA 44 be used in SCADA systems or as a sole monitor in island applications. Events recording 4 quadrant measurement Comunication protocol Modbus RTU Asymmetry, unbalance, vector diagram 144 x 144 mm 96 x 96 mm Dimensions 96 x 96 mm 96 x 96 mm 96 x 96 mm Averaging functions of S, P, I Flicker Default feature Optional feature

Upload: others

Post on 04-Nov-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EnergyMonitoringAndManagement · 13 PowerqualityanalyserPLA44 Devicedescription PowerlineanalyserPLA44isdesignedaccordingtothenormEN50160classAfor electricalparametersmonitoringinthree-phaseandsingle

11

Device type PLA 33PLA 33 L PLA 33 CMPLA 33 C

Continual U and I measurement

PLA 44 CM

2 2

RS485 interface

2

External temperature sensor input

Digital input / output / pulseoutput

Real-time internal clock

USB interface

Ethernet interface

DIN rail variant

Auxiliary supply

LCD display 2,55"

2

Internal flash memory

Supply powercut events 20 events 20 events

512 MB

230 VAC, 50/60 Hz (+10%,-15%) or 24 VDC

1 GB

TFT graphic VGA screen 5,7"

EN 50160 class A device

Neutral current measurement

1

calculated calculated calculatedcalculated

Range of power line and quality analysers

Energy Monitoring And ManagementApplicationMultifunction power line analysers PLA 33 and power quality analysers PLA 44 are essential part of systems for energy managementand monitoring at industrial areas, office buildings, public service centres such as airports, railways and everywhere the energy flowcontrol is requested.

HM 2006 maximum demand controller is special device for load monitoring and control in order to reduce power peaks bydisconnection of particular loads.

Together with components for power factor correction, BMR offers complete range of power line analysers, quality analysers,maximum demand controllers and accessories for energy management and monitoring systems for various industry applications.

PLA range descriptionPLA 33 and PLA 44 are designed for electrical network parameters monitoring and energy management. Both types are fully 4quadrant devices with continual voltage and current measurement according to norm EN 50160.

Basic power line analyser PLA 33 is available in several variants. Simple variant is used for substitution of analogue devices. Variantswith communication interface, internal memory and digital inputs and outputs are offered as a measuring point for monitoring andenergy management in large SCADA systems.

PLA 44 analyser is an advanced power quality analyser which meets specification according to the norm EN 50160 class A. Thanks topowerful 32 bits processor brings many useful features for detailed monitoring and quality analyse of LV and MV networks. Largememory, various communication interfaces, easy setting and usage, suppose PLA 44 be used in SCADA systems or as a sole monitorin island applications.

Events recording

4 quadrant measurement

Comunication protocol Modbus RTU

Asymmetry, unbalance, vector diagram

144 x 144 mm96 x 96 mmDimensions 96 x 96 mm 96 x 96 mm 96 x 96 mm

Averaging functions of S, P, I

Flicker

Default feature Optional feature

Page 2: EnergyMonitoringAndManagement · 13 PowerqualityanalyserPLA44 Devicedescription PowerlineanalyserPLA44isdesignedaccordingtothenormEN50160classAfor electricalparametersmonitoringinthree-phaseandsingle

12

Power line analyser PLA33Device descriptionMultifunction power line analyser PLA 33 is designed for electrical parameters monitoring inthree-phase and single-phase LV and MV systems. Device is based on 16 bits RISC processorthat provides enough power for real-time measurement and calculation of all parameters.Voltage and current are measured continually according to the norm EN 50160, TRMS valuesare digitalized in all three phases.

• voltage and current measurement according the norm EN 50160• current transformer input ../1A and ../5A• minimums and maximums stored in EEPROM memory• measured data recording to FLASH memory• averaging for current, active and apparent power with set period• bright LCD display 2,55" with or without white backlight

Parameter L2 Measuring rangeL1 SUML3

Phase voltage, L-NPhase-phase voltage, L-LFrequency

CurrentNeutral wire current, NCosPower factor

Voltage harmonic distortion, THDUCurrent harmonic distortion, THDI

Max

Odd voltage harmonics up to 19th

Apparent power, SOdd current harmonics up to 19th

Active power, PReactive power, QApparent power, sum S

Reactive power, sum QActive power, sum P

Ractive energy, inductiveActive energy

Reactive energy, capacitive

Min

0 ... 300 V

Accuracy

0 ... 9.999.999 kVArh

0 ... 999 %

0 ... 999 %

0 ... 999 %

40 ... 70 Hz

0 ... 520 V

0,01 ... 6 A

class 1*

0,01 ... 6 A

0,01 ind ... 0,01 cap

0,01 ind ... 0,01 cap

0 ... 999 %

0 ... 5,4 kVAr

0 ... 5,4 kW

0 ... 9.999.999 kWh

0 ... 5,4 kVA

0 ... 1,8 kVAr

0 ... 1,8 kW

0 ... 9.999.999 kVArh

0 ... 1,8 kVA

0 ... 9.999.999 kVArh

0 ... 312 kV

0 ... 9.999.999 kVArh

0 ... 999 %

0,01 ind ... 0,01 cap

0,01 ind ... 0,01 cap

0 ... 7,5 kA

0 ... 7,5 kA

40 ... 70 Hz

0 ... 999 MVA

0 ... 648 MW

0 ... 999 %

0 ... 999 %

0 ... 999 %

0 ... 999 MVAr

0 ... 9.999.999 kWh

0 ... 648 MVAr

0 ... 648 MVA

0 ... 999 MW

Displayed range

0 ... 180 kV

class 1*class 1*

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±0,5 % MV

±0,5 % MV

±1,5 % MR

±0,5 % MR

±0,2 % MV

±0,5 % MR

±0,5 % MR

Internal flash memoryPLA 33CM variant is equipped with internal flash memory. Up to 10measured parameters can be recorded with adjustable sampling rate(200 ms ... 60 minutes). Into the flash memory also load profile canbe stored. Load profile feature is recording 15 minutes energy resultsof all 6 energy meters for 180 days.

Digital inputs and outputsPLA 33 has two digital inputs/outputs which can be configured fordifferent purposes. Digital input is used for status indication by PCand remote pulse synchronization of power demand counter. Digitaloutput for remote control by PC. Pulse output is related to energymeter and alarm output for indication of alarm event.

Power supply 230 VAC (+10%,-15%)

50 Hz / 60 HzSystem frequency

Current measuring range 0,01 ... 6 A

max. 1,5 VAPower consumption

2 programmableNumber of output/input

0 ... 300 VAC

optical insulated transistorOutput type

Voltage measuring range L-N

±0,5 % MRMeasuring accuracy of U and I

Output maximum load

Input type optical insulated free potential

RS485 (Modbus RTU)Communication interface

9,6 / 19,2 / 38,4 / 57,6 kBd

-30°C ... +70°C

50 mmSite depth

92 x 92 mmCutout dimensions

0,5 kgWeight

IP20 rear, IP54 front panelProtection degree

Working temperature

Communication speed

24 VDC / 100 mA

Input load capability 24 VDC / 10 mA

Measuring transformer ratio of U and I 1 ... 1500

96 x 96 mmFront panel dimensions

Technical features

Measured parameters

* for ideal sinusodial curve of voltage and current

Page 3: EnergyMonitoringAndManagement · 13 PowerqualityanalyserPLA44 Devicedescription PowerlineanalyserPLA44isdesignedaccordingtothenormEN50160classAfor electricalparametersmonitoringinthree-phaseandsingle

13

Power quality analyser PLA44Device descriptionPower line analyser PLA 44 is designed according to the norm EN 50160 class A forelectrical parameters monitoring in three-phase and single-phase LV and MV systems.Device is based on 32 bits RISC processor that provides enough power for real-timemeasurement and calculation of all parameters. Voltage and current are measuredcontinually according to norm definition and assure high accuracy of all measured andcalculated parameters. PLA 44 is solution for application everywhere the quality of energyis important.

Parameter L2

0 ... 600 V

L1 SUML3

Phase voltage, L-NPhase-phase voltage, L-LFrequency

Current

Neutral wire current, NCos

Power factorVoltage harmonic distortion, THDUCurrent harmonic distortion, THDI

Max

Odd voltage harmonics up to 50th

Apparent power, SOdd current harmonics up to 50th

Active power, PReactive power, QApparent power, sum S

Reactive power, sum QActive power, sum P

Ractive energy, inductiveActive energy

Reactive energy, capacitive 0 ... 9.999.999 kVArh class 1*0 ... 9.999.999 kVArh

Min Measuring range Accuracy

0 ... 999 %

0 ... 999 %

0 ... 999 %

40 ... 70 Hz

0 ... 1000 V

0,01 ... 6 A

0,01 ... 6 A

0,01 ind ... 0,01 cap

0,01 ind ... 0,01 cap

0 ... 999 %

0 ... 10,8 kVAr

0 ... 10,8 kW

0 ... 9.999.999 kWh

0 ... 10,8 kVA

0 ... 3,6 kVAr

0 ... 3,6 kW

0 ... 9.999.999 kVArh

0 ... 3,6 kVA

0 ... 900 kV

0 ... 9.999.999 kVArh

0 ... 999 %

0,01 ind ... 0,01 cap

0,01 ind ... 0,01 cap

0 ... 7,5 kA

0 ... 7,5 kA

40 ... 70 Hz

0 ... 999 MVA

0 ... 999 MW

0 ... 999 %

0 ... 999 %

0 ... 999 %

0 ... 999 MVAr

0 ... 9.999.999 kWh

0 ... 999 MVAr

0 ... 999 MVA

0 ... 999 MW

Displayed range

0 ... 900 kV

class 1*class 1*

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±1,0 % MR

±0,5 % MV

±0,5 % MV

±1,5 % MR

±0,5 % MR

±0,2 % MV

±0,5 % MR

±0,5 % MR

Measured parameters

Phase sequence a–a a–aa–a

Phase asymmetry 0 ... 100 % ±0,5 % MR0 ... 100 %

Flicker a–a a–aa–a

• voltage and current measurement according the norm EN 50160• current transformer input ../1A and ../5A• minimums and maximums stored in EEPROM memory• measured data recording to FLASH memory• averaging for current, active and apparent power with set period• 5,7" TFT VGA (640 x 480) display• voltage and current harmonic measurement up 50th harmonic• neutral current measurement• three and four wire connection and measurement• load profile recording up to 512 days• asymmetry, phase sequence, rotation• flicker• RS485, LAN, USB interfaces

Main characteristics

* for ideal sinusodial curve of voltage and current

NEWPRODUCT

Specification is just

informative

Will be released during 2011

Page 4: EnergyMonitoringAndManagement · 13 PowerqualityanalyserPLA44 Devicedescription PowerlineanalyserPLA44isdesignedaccordingtothenormEN50160classAfor electricalparametersmonitoringinthree-phaseandsingle

14

Power supply 230 VAC (+10%,-15%)

50 Hz / 60 HzSystem frequency

Current measuring range 0,01 ... 6 A

max. 15 VAPower consumption

2 programmableNumber of output/input

0 ... 600 VAC

optical insulated transistorOutput type

Voltage measuring range L-N

±0,5 % MRMeasuring accuracy of U and I

Output maximum load

Temperature input NTC 3k3

RS485, LAN, USBCommunication interface

9,6 ... 57,6 kBd

-30°C ... +70°C

55 mmSite depth

138 x 138 mmCutout dimensions

1 kgWeight

5,7" TFT VGADisplay

Working temperature

RS485 communication speed

24 VDC / 100 mA

Input load capability 24 VDC / 10 mA

Measuring transformer ratio of U and I 1 ... 1500

144 x 144 mmFront panel dimensions

Technical features

Input type optical insulated free potential

Modbus RTUCommunication protocol

EN 50160, class ARelated standards

IP20 rear, IP54 front panelProtection degree

Load profileIn the device memory there is reserved space for load profile storingof all energy meters. Load profile has adjustable recording period of15, 30 and 60 minutes. For set recording period of 15 minutes therewill be stored load profile stored for 180 days with FIFO dataorganization.

Digital inputs and outputsPLA 44 has two digital inputs/outputs which can be configured forseveral purposes. Digital input is used for status indication by PC andremote pulse synchronization of power demand counter. Digitaloutput can be used for remote control by PC. Pulse output is relatedto energy meter and alarm output is used for indication of alarmevents.

EN50160 class A devicePLA 44 is device according to standard EN50160 class A. Voltageand current are measured continually with high sampling rate toprovide all parameter calculations defined by the norm.

Communication interfacesAnalyser PLA 44 has built-in RS485 communication interface to beimplemented into existing RS485 networks. It offers also Ethernetinterface for direct connection to LAN. For easy and fast reading ofstored data, load profiles, events and configuration can be connecteddirectly to PC via USB port.

External temperature sensorPLA 44 has separate input for external temperature sensor which canbe used for temperature monitoring at various locations.

Fully graphic TFT displayPLA 44 has 5,7" big colour TFT display with VGA resolution 640 x480 dots. Measured values and stored data are shown in numeric andgraphic form for easy and precise understanding.

NEWPRODUCT

Specification is just

informative

Will be released during 2011

Internal flash memoryPLA 44 is equipped by internal 1GB flash memory for measuredparameters recording. Sampling period is adjustable from 200ms to60 minutes.

Measured parameters can be read from the memory over devicecommunication interfaces by program PMS.

Page 5: EnergyMonitoringAndManagement · 13 PowerqualityanalyserPLA44 Devicedescription PowerlineanalyserPLA44isdesignedaccordingtothenormEN50160classAfor electricalparametersmonitoringinthree-phaseandsingle

15

DescriptionHM 2006 device is designed for electrical power demand regulation of bigger consumers.Regulation is optimized according to defined curve and set regulation or technical maximum.If trend of average demand verges to exceed the set demand value, particular stages of

electrical loads are being disconnected. In the casethat the trend verges under the set level, controller isreconnecting disconnected circuits.

Controller has 5 inputs, which are used for energymeter pulses of +P, +Q, -P, -Q and synchronizationimpulse. One input can be used for tariff indication.Controller is normally connected to the energy meterpulse outputs via separation unit. Controller outputs

are realized by 6 changeover contacts 3A/250VAC which control mechanical contactorcircuits of defined electrical loads.

Operation principleHM 2006 controller regulates demand according to set maximal value of average hour demand in kW. This value is periodically compared withmeasured power demand during the quarter-hour and in the case of fast power demand increase over the defined neutral zone, controller starts todisconnect appropriate loads.

If the power demand decreases under the certain level and power demand reserve appears,controller starts to connect appropriate loads back to the system.

Device shows, during quarter-hour period, calculation of the average hour power demandin kW according to the real power demand. After incoming of the pulse for the newquarter-hour beginning, this value is being erased. All disconnected loads will beconnected back and new regulation cycle will start.

Maximum reached quarter-hour value of power, date and time of this event for every tariffseparately are recorded into internal memory. Those maximal values are accessible on thedevice display. History of every power demand curve during quarter-hour is saved to theinternal memory with capacity for 40 days of recording.

max. 1,5 VA

Number of controlled outputs

Internal power supply 24 VDC

Power consumption

3 A / 250 VACSwitching power of relay outputs

Supply voltage 230 VAC (+10%,-15%)

System frequency

6 changeover contacts

Number of pulse inputs 5 (+P, -P, +Q, -Q, synchr.)

50 / 60 Hz

0°C ... +70°C

IEC 60715 (DIN 35 mm)Mounting

6 DIN rail modulesDimensions

700 gWeight

48 hoursReal-time clock backup

Working temperature

RS485Communication interface

IP20Protection degree

Technical features

Maximum demand controller HM2006

Schematic diagram

Internal load profile memoryIn the HM 2006 there is built-in FIFO memory for load profile andoutputs status with capacity for 40 days recording. Once the memoryis full the newest data overwrites the oldest one.

Internal synchronization pulseHM 2006 has internal real time clock with 48 hours backup. 1/4period can be synchronized by external signal or internal clock.

Internal power supplyDevice is equipped with metallically separated internal power supply12 VDC for supplying energy meter pulse outputs or separation unitOP105.

SW for HM2006HM 2006 uses special software HM 2006PC for its monitoring andconfiguration. HM 2006PC software is ready to be used with all typeof BMR RS485 converters.

Internal load profile memory 40 days (FIFO type)

BMRCommunication protocol