Page 1: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 1

on behalf of

Differential Impacts of Additional Consumers in DH Systems

Analysis for Absorption Chillers 11 September 2018

Felix Panitz, Vera Volmer

Technische Universität Dresden

Page 2: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 2

on behalf of

Impacts of Absorption Chiller (ACh)

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

subject matter:

• new generation of ACh (return temperatures 60…70 °C)

• field installations in several district heating systems

• Effects in DH system / relevance of return temp. are discussed but not quantified

Page 3: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 3

on behalf of

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Impacts of Absorption Chiller (ACh)

Goal: estimation of all effects of ACh in DH system total primary energy effort of ACh

Approach: all additional efforts are allocated to the ACh DH system is not changed (no pipes enlarged, no additional CHP-unit)

Page 4: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 4

on behalf of

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Impacts of Absorption Chiller (ACh)

Goal: estimation of all effects of ACh in DH system total primary energy effort of ACh

Approach: all additional efforts are allocated to the ACh DH system is not changed (no pipes enlarged, no additional CHP-unit)

Page 5: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 5

on behalf of

Network simulations

• Network simulations have been conducted for DH-network Hannover (SIR 3S)

• Simulations without and with additional ACh

• 5 representative load situations

CHP 1

ACh • 175 kW • 77 °C/ 68 °C return temp.

CHP 2

Supply Station / ambient temperature CHP1+2 / -14°C CHP1+2 / +1°C CHP1 / +15°C CHP1 / +30°C CHP2 / +30°C

Supply temperature at heat generator 120 °C 92 °C 92 °C 92 °C 92 °C

Return temperature at heat generator 60 °C 58 °C 60 °C 64 °C 64 °C

Thermal load 637 MW 394 MW 105 MW 39 MW 38 MW

Nominal th. Load : 637 MW Length of pipelines : 315 km

Page 6: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 6

on behalf of

• Additional heat loss is small compared to overall heat loss therefore: specific values are used!

• Specific heat loss of ACh is lower than average specific overall heat loss with ACh are slightly lower (44.3 %)

Summer load case (CHP2 / +30°C)

Folie 6

Results of simulation

Heat loss without ACh 11,573 kW

Heat loss with ACh 11,594 kW

Difference 𝚫𝚫�̇�𝐐L 21 kW

Relative increase of heat loss +0.18 % ACh • 175 kW heat consumption • 77 °C return temp.

CHP 2

Nominal th. Load : 637 MW Length of pipelines : 315 km

Specific loss average consumer (without ACh):

= 44.5 %

Specific loss ACh:

= 12.1 % 𝜑𝜑L,ACh = Δ�̇�𝑄L�̇�𝑄Con,ACh

= 21 kW175 kW

𝜑𝜑L,avg = �̇�𝑄L∑�̇�𝑄Con,𝑖𝑖

= 11,573kW26,021kW

Page 7: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 7

on behalf of

0%

10%

20%

30%

40%

50%

-20 -10 0 10 20 30 40ta / °C

avgACh: 77°C

𝑞 L

CHP1CHP2

CH

P1+2

/ -1

4

CH

P1+2

/ +1

CH

P1 /

+15

CH

P1 /

+30

CH

P2 /

+30

Effects on thermal losses

Specific heat losses caused by ACh are smaller than those of average consumer! (despite high ACh return temperature)

possible reason: ACh keeps nearby pipes warm

𝜑𝜑L,avg =�̇�𝑄L

∑�̇�𝑄Con,𝑖𝑖

𝜑𝜑L,ACh =Δ�̇�𝑄L

�̇�𝑄Con,ACh 𝜑𝜑

L

Page 8: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 8

on behalf of

0%

10%

20%

30%

40%

50%

-20 -10 0 10 20 30 40ta / °C

avgACh: 77 °CACh: 68 °C

CHP1CHP2

CH

P1+2

/ -1

4

CH

P1+2

/ +1

CH

P1 /

+15

CH

P1 /

+30

CH

P2 /

+30

𝑞 LEffects on thermal losses

New ACh generation can reduce specific heat losses especially in spring and summer!

𝜑𝜑L

𝜑𝜑L,avg =�̇�𝑄L

∑�̇�𝑄Con,𝑖𝑖

𝜑𝜑L,ACh =Δ�̇�𝑄L

�̇�𝑄Con,ACh

Page 9: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 9

on behalf of

0.00

0.01

0.02

0.03

0.04

0.05

0.06

-20 -10 0 10 20 30 40ta / °C

avgACh: 77 °C

CH

P1+2

/ -1

4

CH

P1+2

/ +1

CH

P1 /

+15

CH

P1 /

+30

CH

P2 /

+30

Effects on pumping electricity

• Specific pumping electricity of ACh is higher than network average

• Hydraulic effects can not be neglected!

different results for CHP1 & CHP2: Location of heat generator & ACh has big influence!

𝑒𝑒 Pu

𝑒𝑒Pu,avg =𝑃𝑃Pu

∑�̇�𝑄Con,𝑖𝑖

𝑒𝑒Pu,ACh =Δ𝑃𝑃Pu

�̇�𝑄Con,ACh

Page 10: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 10

on behalf of

0.00

0.01

0.02

0.03

0.04

0.05

0.06

-20 -10 0 10 20 30 40ta / °C

avgACh: 77 °CACh: 68 °C

CH

P1+2

/ -1

4

CH

P1+2

/ +1

CH

P1 /

+15

CH

P1 /

+30

CH

P2 /

+30

Effects on pumping electricity

• New ACh generation with lower return temperatures can reduce pumping electricity especially in transitional season

𝑒𝑒 Pu

𝑒𝑒Pu,avg =𝑃𝑃Pu

∑�̇�𝑄Con,𝑖𝑖

𝑒𝑒Pu,ACh =Δ𝑃𝑃Pu

�̇�𝑄Con,ACh

Page 11: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 11

on behalf of

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Conclusion: network effects

• Additional heat losses are low, Additional pumping electricity is relevant

• Drop of return temp. (77 68 °C) strongly reduces heat and electricity demand

• Do equal simulations for long-term strategy DH temperatures!

Page 12: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 12

on behalf of

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Impact on heat generation

• CHP and boiler: estimate additional power generation and fuel demand

• key figures to characterize additional heat generation needed:

Diff. CHP share:

𝑥𝑥CHP,ACh =Δ𝑄𝑄CHP

Δ𝑄𝑄CHP + Δ𝑄𝑄Boiler 𝜎𝜎CHP,ACh =

Δ𝑊𝑊CHPΔ𝑄𝑄CHP

Diff. CHP coefficient:

Page 13: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 13

on behalf of

Heat generator set-up

• Mode of operation has high impact on key figures!

• How to create realistic operation sequence?

Optimization of generator operation: minimize total operating costs

A: Simulation without ACh B: Simulation with ACh, 175 kW

time series of prices for gas, electricity, CO2

gas tax CHP bonus

CHP plant Heat storage gas boiler Financial parameters

16.25 MWth,nominal

part load 38..100 % Switch-on costs 80 €

65 MWth,nominal

𝜂𝜂 = 90 % part load 0..100 %

50 MWh losses: 0,02 %/h

65 MWth,nominal

DH load profile

Network

year: 2016

Effects of ACh = difference B - A !

Construed example (data security reasons):

simulation sequence: one week (7x24 time steps) MILP problem CPLEX solver used

Page 14: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 14

on behalf of

Simulation periods: 4 x 1 week

winter I winter II spring summer

Week 2 8 20 27

𝑡𝑡a̅ -1.6 °C 2.3 °C 14.1 °C 21.5 °C

�̇�𝑄�Gen 39.7 MW 33.2 MW 15.4 MW 7.5 MW

Load percentage 61.1 % 51.1 % 23.7 % 11.6 %

year: 2016

Page 15: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 15

on behalf of

Characteristic key figures

CHP share CHP coefficient 𝑥𝑥CHP = σCHP =

0%

20%

40%

60%

80%

100%

winter I winter II spring summer

CH

P sh

are

avgACh

CHP heatCHP heat + Boiler heat

CHP ElectricityCHP Heat

00.20.40.60.8

11.21.4

winter I winter II spring summer

CH

P co

effic

ient

avgACh

Page 16: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 16

on behalf of

Characteristic key figures

CHP share

Winter: Additional heat generation provided only by gas boiler

CHP coefficient 𝑥𝑥CHP = σCHP =

Spring: 37 % operation of gas boiler for ACh

0%

20%

40%

60%

80%

100%

winter I winter II spring summer

CH

P sh

are

avgACh

CHP heatCHP heat + Boiler heat

CHP ElectricityCHP Heat

00.20.40.60.8

11.21.4

winter I winter II spring summer

CH

P co

effic

ient

avgACh

Page 17: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 17

on behalf of

Characteristic key figures

CHP share

Winter: Additional heat generation provided only by gas boiler

CHP coefficient 𝑥𝑥CHP = σCHP =

Spring: 37 % operation of gas boiler for ACh

Spring and summer: operation of CHP gets less efficient with additional ACh

0%

20%

40%

60%

80%

100%

winter I winter II spring summer

CH

P sh

are

avgACh

CHP heatCHP heat + Boiler heat

CHP ElectricityCHP Heat

00.20.40.60.8

11.21.4

winter I winter II spring summer

CH

P co

effic

ient

avgACh

Page 18: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 18

on behalf of

-1.0

-0.5

0.0

0.5

1.0

1.5

winter I winter II spring summer

f P,G

en

avgACh

Primary energy: generated heat

Primary energy factor of ACh is higher than average consumer’s value

ACh increases primary energy factor of network

Results may vary widely with different heat generation and heat load constellations!

𝑓𝑓P,Gen,avg =1.1 ⋅ �̇�𝑄fuel − 2.8 ⋅ 𝑃𝑃CHP

�̇�𝑄Gen

𝑓𝑓P,Gen,ACh =1.1 ⋅ Δ�̇�𝑄fuel − 2.8 ⋅ Δ𝑃𝑃CHP

Δ�̇�𝑄Gen

negative 𝑓𝑓P,Gen are permitted for scientific analysis

Page 19: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 19

on behalf of

Impact on heat generation

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Page 20: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 20

on behalf of

…ACh

system

�̇�𝑄L

𝑡𝑡su

𝑡𝑡re𝑡𝑡re,ACh

�̇�𝑄Gen

Δ𝑃𝑃Pu Δ�̇�𝑄L 𝑃𝑃ACh

�̇�𝑄Con,ACh

Heat

ge

nera

tion�̇�𝑄fuel

𝑃𝑃Pu

Evaluation of overall system

Total effort for produced cold �̇�𝑄0

Combination of network effects (load points) and optimization (week simulations)

Page 21: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 21

on behalf of

Evaluation of produced cold

• ACh has better primary energy efficiency than compression chiller in summer

• Effects of lower ACh return temperature look small but primary energy factor can be lowered by about 0.1 to 0.15

COPth COPel

ACh 0.75 10

0.0

0.5

1.0

1.5

2.0

2.5

-20 -10 0 10 20 30 40

f P,0

ta / °C

ACh 77°C

ACh 68°C

compression chiller with annual COPel = 2...5

Page 22: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 22

on behalf of

Conclusion • Method developed for quantifying effects of additional ACh

• In given example:

Add. heat losses are small, add. pumping electricity can not be neglected

Comparison to compression chiller: ACh has better primary energy efficiency (only) in summer

Heat generation set-up and operation have big influence on primary energy efficiency

• Results can not be generalized!

• DH companies can use presented method to evaluate ecological and economic sense of ACh in existing systems

Page 23: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 23

on behalf of

Thank you for your attention!

Contact:

Vera Volmer, Felix Panitz

+49 351 463 34477

[email protected], [email protected]

Technische Universität Dresden

Institute of Power Engineering Chair of Building Energy Systems and Heat Supply

Project: EnEff: Wärme – Feldtest Absorptionskälteanlagen für KWKK-Systeme Research project founded by the Federal Ministry for Economic Affairs and Energy following a resolution of the German Bundestag FKZ: 03ET1171B

Page 24: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 24

on behalf of

Evaluation of add. consumer heat

• ACh values higher than those of average consumer

• Highest primary energy factors in winter to spring

• Combination: Network effects + key figures of heat generation

-1.0

-0.5

0.0

0.5

1.0

1.5

-20 -10 0 10 20 30 40

f P,Co

n

ta / °C

avgACh 77°CACh 68°C

Page 25: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 25

on behalf of

Network effects

0%

5%

10%

15%

20%

25%

65 70 75 80tre,ACh / °C

CHP1+2 / -14CHP1+2 / +1CHP1 / +15CHP1 / +30CHP2 / +30

0,000,010,020,030,040,050,060,070,08

65 70 75 80tre,ACh / °C

CHP1+2 / -14CHP1+2 / +1CHP1 / +15CHP1 / +30CHP2 / +30

For different ACh return temperatures

Page 26: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 26

on behalf of

Network effects For different ACh installations

Page 27: Differential Impacts of Additional Consumers in DH Systems...CHP1+2 / -14 CHP1+2 / +1 CHP1 / +15 CHP1 / +30 CHP2 / +30. Effects on pumping electricity • Specific pumping electricity

THE 16th INTERNATIONAL SYMPOSIUM on District Heating and Cooling Panitz, Volmer | Diff. Impact of Consumers | Slide 27

on behalf of

P-Q-diagram of evaluated CHP plant