developing a smoke alarm program for colerain township

Upload: the-world-fire-safety-foundation

Post on 01-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    1/87

    Smoke Alarm Program 1

    Running head: DEVELOPING A SMOKE ALARM PROGRAM FOR COLERAIN

    Developing a Smoke Alarm Program for Colerain Township

    Darian E. Edwards

    Colerain Township Department of Fire And Emergency Medical Services

    Colerain Township, Ohio

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    2/87

    Smoke Alarm Program 2

    CERTIFICATION STATEMENT

    I hereby certify that this paper constitutes my own product, that where the language of

    others is set forth, quotation marks so indicate, and that appropriate credit is given where

    I have used the language, ideas, expressions, or writings of another.

    Signed: _______________________________________

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    3/87

    Smoke Alarm Program 3

    ABSTRACT

    The problem was that Colerain Township Fire Department did not have a smoke alarm

     program, thus subjected residents, according to data, to a higher incident of injuries and deaths

    due to fires.

    The purpose was to develop and or implement a smoke alarm program for Colerain

    Township to reduce injuries or deaths. 1. What were the associated risks of not having smoke

    alarms. 2. Of the two common smoke alarms sensors, ionization and photoelectric, what did

    Colerain Township recommend? 3. What area, within each of the five fire districts, had a high

    risk of fire injuries or death?

    This research project was to utilize an action research method and approach. There was

    an extensive amount of literature review, questionnaires, observations and interviews to assist in

    the pursuit of this research project.

    Multiple studies shows that about 70% of all fire fatalities occur in residences that have

    no functioning smoke alarms. Yet, 95% of the homes in the U.S. have smoke alarms. Of the two

    smoke alarm sensors, the photoelectric smoke alarm is much more dependable for a quicker

    response to smoke with a lesser degree of false alarms. In Colerain Township there are 29

    distinct fire response zones. Of the 29 fire response zones, two zones accounts for 57% of all

    civilian fire casualties.

    It is this authors recommendation that an ordinance be passed that mandates the use of

     photoelectric smoke alarms in new construction and phased into existing buildings. Along with

    the ordinance there must be a well organized public education plan. The highest fire casualty

    zones must be addressed with active fire department interventions such as smoke alarm

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    4/87

    Smoke Alarm Program 4

    installation programs. Revisiting these residences at set intervals must be accomplished to

    collect data for the programs longevity and continued support.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    5/87

    Smoke Alarm Program 5

    TABLE OF CONTENTS

    Certification Statement 2

    Abstract 3

    Table of Contents 5

    Introduction 6

    Background and Significance 7

    Literature Review 10

    Procedures 20

    Results 22

    Discussion 33

    Recommendations 36

    Reference List 40

    Appendix A 42

    Appendix B 47

    Appendix C 65

    Appendix D 67

    Appendix E 69

    Appendix F 71

    Appendix G 73

    Appendix H 75

    Appendix I 79

    Appendix J 81

    Appendix K 83

    Appendix L 86

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    6/87

    Smoke Alarm Program 6

    INTRODUCTION

    The problem was that Colerain Township Fire Department did not have a smoke alarm

     program, thus subjecting residents, according to data, to a higher incident of injuries and deaths

    due to fires.

    The purpose was to develop and or implement a smoke alarm program for Colerain

    Township to reduce injuries or deaths. For decades it has been standard that homes will have

    smoke detectors. For the last four decades the fire service has been preaching that smoke

    detectors save lives.

    1. What were the associated risks of not having smoke alarms. 2. Of the two common

    smoke alarms sensors, ionization and photoelectric, what did Colerain Township recommend? 3.

    What area, within each of the five fire districts, had a high risk of fire injuries or death?

    This research project is to utilize an action research method and approach in order to take

    immediate action to our problem by creating a concrete solution. There will be an extensive

    amount of literature review, questionnaires, observations and interviews to assist in the pursuit of

    this research project. While the overall research was that of an action method, question #1

    utilized the historical method of research by analyzing data from many sources such as National

    Fire Incident Reporting System, NFIRS, United States Fire Administration, USFA, multiple

    reports and data collections. The evaluative method of research was utilized to assess and

    analyze data and make a decision for question #2. Question #3 also used the evaluative method

    of research to identify five distinct areas of high risk associated with injuries and deaths from

    fires.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    7/87

    Smoke Alarm Program 7

    BACKGROUND AND SIGNIFICANCE 

    Colerain Township is the largest unincorporated jurisdiction in the state of Ohio. It is

    located ten miles to the northwest of the city of Cincinnati. The northern boundary of Colerain

    Township is that of Butler County, Ohio. According to the 2010 U.S. Census, the Township has

    a population of 58,499 residents occupying 43.5 sq.ml. (Census) Colerain Township is only

    surpassed by that of West Chester Township in Butler County with regards to population of

    townships in the state of Ohio. West Chester boasts a population of 60,958. (Census) The

    residents of Colerain Township are very diverse. We have a myriad of socioeconomics and

    lifestyles with homes of the affluent to low-income and subsidized housing. The land use is that

    of agricultural, light industry, and a large portion of retail. The Colerain Township Department

    of Fire and Emergency Medical Services (Colerain Fire Department) has a rating of a Class two

    from the Insurance Services Office.

    Smoke alarms were not commercially available until the 1960’s. In 1965 the “single

    station”, also referred to as “stand alone” smoke alarm was produced. At that time the use of

    smoke alarms in the United States, U.S., was at less than 1%. In 1969 the battery operated

    smoke alarm was made available to the public at a price of about $100 each. By 1975 General

    Electric was producing smoke alarms for less than $40 each. (Bukowksi, et al., 2007) By the

    year 2000, the price of smoke alarms had drastically dropped which allowed over 95% of

    residences to have smoke alarms.

    If in the U.S. today, we have approximately 95% compliance with the use of smoke

    alarms in residence, and an even higher percentage of smoke alarms used in commercial settings,

    then the question would be why do we still have a significant amount of injuries and fatalities

    due to fires? In 1977 the U.S. had 7395 civilian fire deaths. In 2007 the U.S. had 3430 civilian

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    8/87

    Smoke Alarm Program 8

    fire deaths. Most would say that we have cut civilian fire deaths in half, the smoke alarms

    worked and have saved lives. However in 1977 there were 3,264,000 structure fires. Again

    looking at the amount of structure fires in the U.S., in 2007 there were a reported 1,557,500 fires.

    (Burn Survior Throughout The World Inc., N.D.) The civilian fire deaths have decreased in

    direct relationship to the decreased amount of structure fires in the U.S.

    The vast majority of smoke alarms in residential occupancies have the ionization sensor

    technology. The ionization technology has been in use since the inception of alarms being mass

     produced for the general public. The price of ionization smoke alarms is between 25% to 50% of

    the price of a photoelectric sensor smoke alarm.

    The American Red Cross provided Colerain Township Fire Department with hundreds of

    ionization smoke alarms. For years the fire department would give the alarms to the residents at

    no charge. The American Red Cross program was abandoned by Colerain Township Fire

    Department approximately 4 years ago. Why would any organization stopped given away life

    saving devices? The reason was simply because there was growing concern and studies being

    made available as to the uncertainty and unreliability of the ionization technology in the smoke

    alarms. Colerain Township Fire Department took a strong stand that they would not provide a

    less than reliable, less than safe device to anyone, regardless of the price or who was backing the

     program. Colerain would not give an inferior product to their residents, thus leaving them with a

    false sense of security and protection to their families. Unfortunately without a strong smoke

    alarm educational program, their will be a higher incident rate for injuries and or fatalities.

    What justification did Colerain Township Fire Department have in refusing to give away

    free smoke alarms? Much of the fire service has become aware of scientific studies being

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    9/87

    Smoke Alarm Program 9

    conducted with regards to the ionization and photoelectric smoke alarms. In 1995 Texas A&M

    University published results of their three year study. They concluded that

    “in the smoldering stage of fire the ionization alarm had a 55.8% failure

    rate to the photoelectric alarms 4.06% failure rate. Note: ‘failure rate’ is

    calculated from statistics showing one or more people died in a house fire. In the 

    flaming stage of fire compared , where the ionization alarm is claimed to have a

    few seconds advantage, it had a 19.8% failure rate, to the photoelectric alarms

    3.99% failure rate.” (Grosse, DeJong, & Murphy, 2011)

    The applied research project will have an established link to the Executive Analysis of

    Community Risk Reduction course taught at the National Fire Academy. This ARP will

    empower the Colerain Township Fire Department and the residents of Colerain Township with

    the ability to prevent, reduce, and mitigate the increase risk of injury or deaths due to a lack of a

    smoke alarm plan. This ARP is to address education of the residents and fire personnel of the

    smoke alarm concern. By doing proper research, we will have identified the best engineered

    smoke alarm for increased safety. A proper plan will be developed for enforcement of any codes

    or standards. There will also be an increase in the emergency response by the fire department

    due to early notification of fire incidences in the homes.

    The problem was that Colerain Township Fire Department did not have a smoke alarm

     program, thus subjected residents, according to data, to a higher incident of injuries and deaths

    due to fires. By developing and or implementing a smoke alarm program for Colerain Township,

    there is a direct correlation to two of the goals in the strategic plan of the United States Fire

    Administration (USFA). The first goal of the USFA, reduce risk at the local level through

     prevention and mitigation, would be addressed. In addition, by the implementation of a risk

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    10/87

    Smoke Alarm Program 10

    reduction program, we would be able to improve the fire and emergency services’ professional

    status to our local community and possibly served as a mentor for other fire services that have

    had similar dilemmas.

    LITERATURE REVIEW

    The purpose was to gather and review relevant information in the development and or

    implementation of a smoke alarm program for Colerain Township for the reduction of injuries

    or deaths in residential occupancies. The use of smoke alarms in the U.S. has become common

     practices in all occupancies. The use of smoke alarms has risen from less than 5% in the early

    1970’s to over 95% today. Building and fire codes have incorporated mandatory smoke alarms

    in virtually all occupancies. Fire department life safety inspectors perform inspections of retail,

    industry, places of assembly, apartment complexes, hotels, motels, etc.. Where the life safety

    inspections fall short are single and two family residential occupancies. The concern of this ARP

    is the residential occupancies of single family residences regardless of construction type.

    In April 2006, the Public/Private Fire Safety Council published the WHITE PAPER

     HOME SMOKE ALARMS AND OTHER FIRE DETECTION AND ALARM EQUIPMENT  (White

    Paper Alarms).  The White Paper had 18 various private and public organizations represented

    with their members as contributors to the research The organizations represented included

    groups such as, USAF, Federal Emergency Management Agency, Consumer Product Safety

    Commission, Underwriters Laboratories Inc., and the International Fire Chiefs Association.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    11/87

    Smoke Alarm Program 11

    Research Question #1

    What are the associated risks of not having smoke alarms? Smoke alarms are designed to

    activate when smoke conditions are present, thus giving occupants adequate warning and time to

    exit a potentially toxic and fatal environment.

    In the Smoke Alarm Response and Tenability report produced by Hughes Associates, Inc.,

    they discuss several environmental factors inside a structure fire that affects the abilities of

    individuals to exit the unsafe conditions. In the Tenability Analysis section it states “visibility

    through smoke is not actually a measure of a life threatening tenability criterion. Reduce

    visibility if often considered as a mechanism that slows occupants egress”. In the Tenability

    Analysis it also states that “Many studies have used smoke concentration (or visibility) as a

    criterion for which an occupant may stop attempting to egress”. The Smoke Alarm Response and

    Tenability report does include thermal conditions as a measurable untenable condition. When

    the temperature of a room reaches 120 degrees Celsius (248 Fahrenheit), at five foot from the

    floor, occupants have a reported tolerance of seven minutes. (Christopher Mealy, 2011)

    Being away from home does not remove a person from the dangers associated with fires.

    Andrew K. Pantelis authored a research paper titled The Impact of Alcohol Consumption on Fire

     Egress Behavior  for the Executive Fire Officer (EFO) program. On page five of his introduction

    he states, “The United States Fire Administration (USFA) has recorded that approximately fifty

     percent of university-related fire fatalities nationwide involved people who were under the

    influence of alcohol at the time of the incident”. (Pantelis, 2008) On page 30 of the Results

    section of The Impact of Alcohol Consumption on Fire Egress Behavior , Pantelis explains that at

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    12/87

    Smoke Alarm Program 12

    a blood alcohol level of 0.03% there is a mean increase in egress time of 11.20% and a mean

    increase in egress time of 70.58% when the blood alcohol level of 0.12%.

    Information contained on page 4, Executive Summary, of the White Paper Alarms states

    that 96% of the residential occupancies have smoke detectors, 4% of the homes do not have

    smoke detectors at all. There is also an additional 20% of the homes that have smoke detectors,

    yet they are not working due to batteries either being missing or dead. Page 11 of the White

    Paper Alarms references a report titled U.S. experience with smoke alarms, this report was

    authored by Marty Ahrens. The reference states that homes with working smoke alarms

    represents 30% of fire fatalities. The 4% of homes without smoke alarms account for 39% of all

    fire fatalities. If you add the category of smoke alarms present, but inoperable, then the

     percentage increases to 70% of the fire fatalities. (Council, 2006)

    Marty Ahrens has done extensive research for the National Fire Protection Association

    (NFPA). In a report titled  Smoke Alarm Presence and Performance in U.S. Home Fires,  Ahrens

    states that “No smoke alarms were present at all in 40% of the home fire deaths. Alarms were

     present but did not operate in 23% of the fatalities (Ahrens, ND).” This gives the total of fire

    fatalities due to an absence of functional smoke alarms, regardless of structural occupancy

    classification, similar to residential settings of 63%-70%.

    Research Question #2 

    Of the two common smoke alarms sensors, ionization and photoelectric, what does

    Colerain Township recommend for their residences? Smoke alarms that are for sale to the

    residential consumers contain an ionization sensor or photoelectric sensor. Some detectors do

    have both sensors present in the alarm. On any given day you can find the smoke alarms in the

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    13/87

    Smoke Alarm Program 13

     big box stores such as Lowes, Home Depot, Wal-mart, etc. The prices vary from five dollars

    each to over 30 dollars a piece. Does the type of sensor in the smoke alarm make a difference?

    This ARP will show that it does.

    Both of the smoke alarms reviewed in the ARP, ionization and photoelectric, can be

    electrically powered by an a/c house current or battery power supply. The ionization smoke

    alarm has a sensor that contains a small amount of radioactive material, americium, within the

    ionization chamber. The americium is encased within a gold and americium ingots foil matrix.

    The americium/gold source produces alpha particles. These particles then pass in between two

    metal plates. One of the plates has a positive electrical charge while the second has a negative

    electrical charge. The radioactive alpha particles move through the air, consisting of oxygen and

    nitrogen, and displace electrons from the oxygen/nitrogen mixture. The electrons then become

    either; positively charged and move towards the negatively charged metal plate, the negatively

    charged electron move towards the positively charged metal plate. This moving of electrons to

    the charged plates keep a small electrical current in the sensing chambers. If smoke particles or

    other gases enter into the chamber, they disrupt the flow of electricity between the metal plates

    which then activates the alarm. (EPA, Ionization Technology, 2012)

    The photoelectric smoke alarm has a “T” shaped sensing chamber. The top of the

    chamber, the horizontal bar, has a light emitting diode also known as an LED. The LED sends a

    light from one end of the horizontal chamber to the other end. If smoke particles enter into the

    sensing chamber, the light beam is then interrupted causing the light beam to have some

    deflection of light. There is a photocell at the bottom of the “T” or the vertical beam. When

    light hits the photocell it generates an electrical current. This electrical current then activates the

    alarm. (EPA, Photoelectric Technology, 2012)

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    14/87

    Smoke Alarm Program 14

    Are the two smoke alarm sensors equal? Should the fire service, more specifically

    Colerain Township, recommend a particular sensor to their residents? When you do a simple

    internet search “ionization versus photoelectric smoke alarms”, it returns 287,000 results. Many

    of the reputable organizations that have researched which smoke alarm is better referred to a

    common thread for their research. The Texas A&M University published a report in August of

    1995. While this report may seem outdated for this ARP, much of its findings have found their

    way into new smoke alarm research.

    “Researchers at Texas A&M University, along with support from the

    University of Colorado and Iowa, completed a three year smoke alarm study in

    the August 1995. They were concerned that Underwriters Laboratories testing of

    smoke alarms, by putting a smoke detector in a wooden box and then by blowing

    hot smoke into it, was did not representative of real-world fire conditions.

    Texas A&M’s testing was a fault-tree-analysis model designed by Bell

    Laboratories for the United States military. After three years research they

    concluded: - In the smoldering stage of fire the ionization alarm had a 55.8%

    failure rate to the photoelectric alarms 4.06% failure rate.

    (Note: ‘failure rate’ is calculated from statistics showing one or more people died

    in a house fire. In the flaming stage of fire compared , where the ionization

    alarm is claimed to have a few seconds advantage, it had a 19.8% failure rate, to

    the photoelectric alarms 3.99% failure rate.” (Texas A&M University Study,

    2011)

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    15/87

    Smoke Alarm Program 15

    In the original research performed by Texas A&M University, the ionization smoke

    detector had a higher failure rate than that of the photoelectric detector, regardless of type of fire

    scenario being tested. A failure rate of any product between 20% to 56% would be unacceptable

     by most consumers. To put this another way, compare the failure rates of the two smoke alarms

    to that of two vehicles you were looking at purchasing for your family. One vehicle would break

    down, depending upon road conditions, at a rate of 20% to 56%. The second vehicle would

     break down on the same road conditions at a rate of 4%. Which vehicle would you get for your

    family? When we look at the results of the Texas A&M University studies, we see that the

     photoelectric smoke alarm is much more reliable than that of the ionization smoke alarm.

    In July 2009, the NFPA issued a follow up report, original report February 22, 2008,

    addressing the significance of the two smoke alarm sensor technologies. Appendix D, page 130,

    addressed “nuisance alarms” of the two smoke alarm technologies. The report includes

    information gathered from a study performed in Washington State From June 1, 2000 to July

    31, 2002, 757 homes had either the ionization or photoelectric smoke alarms installed. The

    same homes were visited nine months and 15 months later. At the nine month follow up visit,

    20% of the ionization smoke alarms and 5% of the photoelectric smoke alarms were found to be

    non-functional. The 15 month follow up had similar results. When questioned about the alarms,

    the occupants common reason was that the alarms were disabled because of “nuisance” alarms.

    Most of the nuisance alarms occurred from cooking, thus the occupants removed the batteries or

    the entire smoke alarm. (Committee, 2009) Previously in this ARP it was noted that 23% of all

    fire fatalities occurred in homes with smoke alarms that were disabled or non-functional.

    There is one additional option that many organizations are advocating. The dual sensor

    smoke alarm is equipped with both the ionization and the photoelectric sensing technology. In

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    16/87

    Smoke Alarm Program 16

    theory if a smoke alarm has both sensors in the same unit, then there would be optimum

     protection against both the smoldering and flaming fire. Unfortunately the dual technology still

     produces the nuisance alarms, mainly from cooking, that leads to removal of batteries or

    detectors thus increasing the risk of fire fatalities. For nine months the Consumer Product Safety

    Commission conducted studies of homes in the Washington D.C. area testing the nuisance

    alarms in the kitchens of residential homes.

    “Results For smoke alarms 5 feet from the stove, nuisance alarms occurred

    during 8.7% (41/469) of cooking events for ionization, 11.3% (53/469) for dual-

    sensor, and 3.0% (14/469) for photoelectric smoke alarms. At 10 ft. from the

    stove, nuisance alarms occurred during 4.9% (23/469) of cooking events for

    ionization, 8.7% (41/469) for dual-sensor, and 6.0% (28/469) for photoelectric

    smoke alarms. At 20 feet from the stove, nuisance alarms occurred during 1.1%

    (5/469) of cooking events for ionization, 1.1% (5/469) for dual-sensor, and 0.9%

    (4/469) for photoelectric smoke alarms.” (intern), ND)

    Research Question #3 

    What area, within each of the five fire districts, had a high risk of fire injuries or death?

    The information retrieved during the research of question three was obtained from the Firehouse

    Software that is utilized for our departments National Fire Incident Reporting System (NFIRS).

    The current edition utilized was Firehouse Software 7.2. The parameters of the searches were

    limited to those of structure fires, interior fires. The searches were further filtered by requesting

    information with regards to the incidents street location, assigned fire zone, and status of smoke

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    17/87

    Smoke Alarm Program 17

    alarm in the area of the fire. A ten year search, January 1, 2003 through January 1, 2013, was

     performed with regards to civilian injuries.

    Five additional searches were performed for years, 2012, 2011, 2010, 2009, and 2008.

    Theses searches were similar to the ten year search, with the exception of casualties. This

    individual years of data were collected on all building fires, with interior fires.

    It should be noted that the Firehouse Software search was original research conducted by

    this author. All search result, as they relate to question three, were forwarded to Captain Mark

    Walsh for his review. Captain Walsh is in charge of the Life Safety Bureau in Colerain

    Township. Captain Walsh has extensive knowledge of the topic of this ARP. Captain Walsh can

     be contacted through his direct office line of 513-245-6505.

    During the time from January 1, 2003 through January 1, 2013 there were 87 civilian

    injuries that resulted from 69 building fires. (Edwards, 2013) Of the 87 listed injuries, one

    resulted in the death of a civilian. The results of the reports were categorized by the function of

    the smoke alarms. The smoke alarm categories were; failed, none present, operated, too small of

    a fire to activate, and undetermined. The category of undetermined includes both unknown

    function and undocumented on the NFIRS.

    Of the 68 fire incidents that resulted in 87 civilian casualties, 21 of those incidents had

    smoke alarms either failed or were not present. This represents 31% of the total incidents where

    the occupants did not have functioning fire alarms. (Edwards, 2013) Colerain has five fire

    stations protecting its 58,499 residents occupying 43.5 sq.ml. Fire districts 102 and 103 did not

    have fire casualties in the last ten years. District 25, Zone A represented 33% of the fire

    casualties. District 26, Zone E represented 23.8% . District 109, Zones B and C each

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    18/87

    Smoke Alarm Program 18

    represented 9.5% of the fire casualties which resulted in the last ten years in Colerain Township

    Ohio.

    From the year 2008 until 2013, there were 228 fires in Colerain Township that

    were classified as being “interior” building fires. Of the 228 building fires reviewed, 32% of

    these incidents had either an absence of smoke detectors or a failure of a present smoke detector,

    a failure rate was usually between 30%-50% of detectors that were not present. (Edwards, Yearly

    Fire Incidents Report, 2013) Colerain Township is divided into five districts. These five

    districts are broken down into 29 separate zones. The results of the five year, building fire,

    search shows that the following fire zones, of the five districts, have the highest incident rates of

    the 228 building fires: District 102, Zone A has 2%; District 103, Zone A has 4%; District 109,

    Zone B has 6%; District 25, Zone A has 19%; District 26, Zone E has 12% of the total fire

    incidents (Edwards, Yearly Fire Incidents Report, 2013).

    When comparing the incidents of casualties along with the incidents of interior

     building fires, there are common factors. District 25 Zone A, District 26 Zone E, and District

    109 Zone B had higher incidents of casualties and interior building fires. These three fire zones

    have a high risk of fire and or casualty.

    District 25 Zone A coincides with the Census Bureau as being census tracts 207.41 and

    207.42. The area can be geographically defined as the neighborhood within Colerain Ave,

    Springdale Rd, Pippin Rd, and Compton Rd,. The population of this zone is 7469. The average

    household income is $47,500. (American FactFinder, 2010) Most of the adults in this area are

    high school graduates without further formal education. This area can be considered working

    class families with limited resources and funding.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    19/87

    Smoke Alarm Program 19

    District 26 Zone E coincides with the Census Bureau as being census tracts207.05 and

    207.62. The area can be geographically defined as the neighborhood, south of District 25 Zone

    A, Colerain Ave, Compton Rd, Pippin Rd, and Banning Rd. The population of this zone is 6211.

    The average household income is $53,500. The educated majority is that of a high school

    graduate. This area can be considered working class families with limited resources and funding

    similarly found in District 25 Zone A.

    Districts 102 Zone A and 103 Zone A are very similar in make up. They each represent a

     population of about 1500. The average household incomes are $73,000 to $95,000. The

    majority are high school graduates, yet the percentage of college graduates increase slightly.

    Data shows that there were no casualties in these areas in the last ten years. Also these two

    zones only represent a combined total of 6% of the building fires.

    District 109 Zone B is the furthest most northern part of Colerain Township. It has a

     population of about 3,000 people. The average household income is $63,000. The education is

     primarily that of high school graduates. (American FactFinder, 2010)

    In summary, it can be argued that the values of a smoke alarm are so obvious that we

    routinely have discussions with our elementary schools. Smoke alarms save lives and reduce

     property damage due to early notification to the occupant and then fire departments. The

    contrary to that statement can also be said. In the absence of “working” smoke alarm, the risks

    of injuries and fatalities due to a fire is substantially higher when compared to occupancies with

    functioning alarms. The majority of homes have functioning smoke alarms, yet about 70% of

    fatalities occur in homes without functioning smoke alarms.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    20/87

    Smoke Alarm Program 20

    Statistically, the ionization and photoelectric smoke alarms are the only two types that are

    used in residential occupancies. The Ionization is most often the alarm of choice to be installed

    in homes, it is after all the most inexpensive. Research shows two major areas of concern with

    the ionization detector. First, it has a high failure rate in a smoldering fire. Second, the

    increased number of a nuisance alarms create an environment where occupants disable or

    remove the alarm, placing themselves into an elevated likelihood of casualty or death due to

    fires. The photoelectric, while is more expensive, is more reliable in a smoky environment and

    does have a lower nuisance alarm rate. Cheaper is not always better, photoelectric should be

    recommended by Colerain Township.

    After analyzing our firehouse software and NFIRS, it was determined that our two major

    high hazard areas were District 25 Zone A and District 26 Zone E. These two districts have the

    majority of structure fire incidents along with the higher percentage of nonfunctional smoke

    alarms. The census bureau shows that these two districts also coincide with being the least

    amount of formal education and lower family income when compared to the other districts and

    zones within Colerain Township.

    PROCEDURES

    The purpose of the applied research project was to develop and or implement a smoke

    alarm program for Colerain Township to reduce injuries or deaths from fires in the residential

    occupancies. The research methods utilized were historical and evaluative research for the

    research questions. The overall research associated with this ARP was an action research

    method.

    The development of this project began while in preparation for the Executive Analysis of

    Community Risk Reduction course taught at the National Fire Academy in March of 2013. This

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    21/87

    Smoke Alarm Program 21

    author analyzed demographics as they related to the community of Colerain Township, Hamilton

    County Ohio. The primary source of research materials for community make-up was found on-

    line at the United States Census Bureau. An advanced search of data such as population,

    education, household income, was performed on the American Factfinder portion of the Census

    Bureau web site.

    Discussions with Captain Mark Walsh, fire safety inspector with Colerain Township,

     provided additional insight into the current controversy of smoke alarm technologies and the

    varied research and endorsements. The recent actions, taken by Chief Bruce Smith of Colerain

    Township Fire Department, to cease in the participation of the distribution of smoke alarms to

    the residents, caused concern of increased risk of injuries and or death due to the lack of a smoke

    alarm safety program.

    A subsequent literature review was conducted at the request of this author to Captain

    Mark Walsh in March of 2013. Articles and research from fire service trade associations and fire

    service research and education establishments were presented. An online search of organizations

    such as the National Fire Protection Association, Environmental Protection Agency, and general

    online searches using Google were preformed to access current and relevant material as they

    relate to residential smoke alarms.

    The National Fire Incident Reporting System and Firehouse Software programs were

    accessed and searched to analyze fire injuries, deaths, and smoke alarm information as they

    relate to interior building fires within Colerain Township. Most of the research in this area came

    from the Firehouse Software version 7.2. To duplicate the data, one would open the software,

    click onto the “reports” tab, click onto the “NFIRS incident reports”, followed by clicking onto

    the highlighted “NFIRS incident reports”. The data was filtered by four subcategories: time

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    22/87

    Smoke Alarm Program 22

    frame of incident, basic page 1, NFIRS 3 structure fire report, and NFIRS 4 civilian casualties

    report.

    The criteria and focus of the materials reviewed were pertinent to the Colerain Township

    geographic area along with being relevant and focused to the research as it relates to this ARP.

    The materials also needed to be as relevant as possible. While it can not be argued that having a

    lower number of injuries and fatalities from fire incidents is a goal of the fire service, it does

    create limitations to the amount of data that can be extracted and analyzed for this authors ARP.

    RESULTS

    Research Question #1 

    What were the associated risks of not having smoke alarms? Not having functional

    smoke detectors can contribute to a decrease in the amount of time a person has from the

    discovery of the fire until the interior conditions are beyond that of a survivable environment.

    According to the report, Smoke Alarm Response and Tenability, “The primary goal of a smoke

    alarm is to provide adequate warning to occupants before conditions become untenable in a fire”.

    In theory when smoke goes across the sensor of a smoke alarm, the alarm then activates giving a

    warning to occupants to vacate the building. In the absence of a smoke alarm, smoke is allowed

    to continue to build up in the confined environment of a structure. This smoke build up creates a

    situation where “reduced visibility is often considered as a mechanism that slows occupant

    egress…for which an occupant may stop attempting to egress”. (Christopher Mealy, 2011)

    Smoke alarms also give early notification of fires to allow occupants time to escape the heat that

    increases in a structure. Imagine if you were asleep while a fire is developing a floor below you.

    The heat would rise to your level and possibly block your path of egress. On page 3 of Smoke

     Alarm Response and Tenability it states that 120 degrees Celsius is the threshold for tenability.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    23/87

    Smoke Alarm Program 23

    At 120 degrees Celsius, 428 degrees Fahrenheit, a person can tolerate this exposure for 7

    minutes.

    The increased risk of death due to residential fires was remarkable in comparison to the

     percentage homes without smoke alarms. It is astonishing that 39% of all fire fatalities are

    related to the 4% of homes that do not have smoke alarms. The value of a working smoke alarm

    can also be seen in the fact that another 30% of fire fatalities occur in 20% of the homes that

    have some non-functional smoke alarms. (Ahrens, ND) The totality of the smoke alarm issue is

    that people are approximately 300% more likely to die in a residential house fire without

    working smoke alarms than of a home with a functioning smoke alarm.

    Research Question #2 

    Of the two common smoke alarms sensors, ionization and photoelectric, what does

    Colerain Township recommend for their residences? Much of the research work performed by

    Texas A&M University has been referenced and duplicated throughout the United States in

    recent years. Marty Ahrens has also contributed a significant amount of research and effort in

    the assessment of ionization versus photoelectric smoke alarms. Colerain Township

    recommends the use of photoelectric smoke alarms. While the smoke alarms are marketed for

    different types of fires, smoldering and flaming fires, on average the photoelectric outperforms

    the ionization smoke alarm. In many studies it was shown that during a smoldering fire, the

     photoelectric smoke alarm could activate 12-30 minutes faster than the ionization smoke alarms.

    The ionization smoke alarms are marketed for the flaming fire, yet it has been shown to activate

     just seconds before the photoelectric smoke alarm. When comparing the seconds versus minutes

    faster, the photoelectric smoke alarms seem to give the residents much more advanced warning

    of potentially deadly environments in the home. The ionization sensing technology has a higher

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    24/87

    Smoke Alarm Program 24

    incidence of false, nuisance, alarms than the photoelectric. The occurrence of nuisance alarms

    was the main reason for people to remove the batteries from smoke alarms, or removing the

    smoke alarm altogether, thus making the resident more susceptible to death in a residential fire.

    Colerain Township recommends the photoelectric smoke alarms be utilized in residential

    occupancies.

    On October 1, 2012, this author attended a presentation by Kidde. Kidde is one of the

    larger smoke alarm manufacturers. Ms. Carmel Leek, Regional Sales Manager of Kidde Fire &

    Security, gave a presentation on the newer ten year lithium battery smoke and carbon monoxide

    alarms. The Kidde company, realizing the dangers of battery removal in alarms, is marketing

    their “hassle free” smoke alarm. Ms. Leek confirmed that none of the newer “hassle free” alarms

    have an ionization sensor, they are all photoelectric. During the presentation Ms. Leek was

    quoted as saying: “these eliminate nuisance alarms” and “wants to see a push for photoelectric

    alarms”. During discussions of ordinances requiring photoelectric alarms, she stated that these

    ordinances were “very commendable”. (Leeks, 2013)

    Research Question #3 

    What area, within each of the five fire districts, had a high risk of fire injuries or

    death? During the time from January 1, 2003 through January 1, 2013 there were 87 civilian

    injuries that resulted from 69 building fires. (Edwards, Civilian Casualties by Incident, 2013) Of

    the 87 listed injuries, one resulted in the death of a civilian. The results of the reports were

    categorized by the function of the smoke alarms. The smoke alarm categories were; failed, none

     present, operated, too small of a fire to activate, and undetermined. The category of

    undetermined includes both unknown function and undocumented on the NFIRS.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    25/87

    Smoke Alarm Program 25

    Of the 68 fire incidents that resulted in 87 civilian casualties, 21 of those incidents had

    smoke alarms either failed or were not present. This represents 31% of the total incidents, where

    the occupants did not have functioning smoke alarms. (Edwards, Civilian Casualties by Incident,

    2013)

    Colerain has five fire stations protecting its 58,499 residents occupying 43.5 sq.ml. Fire

    districts 102 and 103 did not have civilian fire casualties in the last ten years. District 25, Zone

    A represented 33% of the fire casualties. District 26, Zone E represented 23.8% . District 109,

    Zones B and C each represented 9.5% of the fire casualties which resulted in the last ten years in

    Colerain Township Ohio.

    From the years 2008 through 2012, there were 228 fires in Colerain Township that were

    classified as being “interior” building fires. Of the 228 building fires reviewed, 23% of the

     building fire incidents did not have a smoke alarm present. During the same five year period,

    9% of the building fire incidents had a failure in the smoke alarm. This resulted in 32% of these

    incidents where the occupants did not have an early warning of a deadly environment. (Edwards,

    Yearly Fire Incidents Report, 2013) The results of the five year, building fire, search shows that

    the following fire zones, of the five districts, have the highest incident rates of the 228 building

    fires: District 102, Zone A has 2%; District 103, Zone A has 4%; District 109, Zone B has 6%;

    District 25, Zone A has 19%; District 26, Zone E has 12% of the total fire incidents (Edwards,

    Yearly Fire Incidents Report, 2013).

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    26/87

    Smoke Alarm Program 26

    2008-2012 Smoke Alarm Activation

    The total of fire incidents, during the five year period, that had smoke alarms fail in

    addition to the incidents where there was an absence of smoke alarms represents 32% or 73 of

    the fire incidents.

    The total of fire incidents, during the five year period, that were large enough, where

    smoke alarms activated represented 34% or 77 of the fire incidents.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    27/87

    Smoke Alarm Program 27

    The total of fire incidents in 2012 that had smoke alarms fail in addition to the incidents

    where there was an absence of smoke alarms represents 42% or 21 of the fire incidents.

    The total of fire incidents, that were large enough, where smoke alarms activated

    represented 22% or 11 of the fire incidents.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    28/87

    Smoke Alarm Program 28

    The total of fire incidents in 2011 that had smoke alarms fail in addition to the incidents

    where there was an absence of smoke alarms represents 22% or 7 of the fire incidents.

    The total of fire incidents, that were large enough, where smoke alarms activated

    represented 44% or 14 of the fire incidents.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    29/87

    Smoke Alarm Program 29

    The total of fire incidents in 2010 that had smoke alarms fail in addition to the incidents

    where there was an absence of smoke alarms represents 32% or 13 of the fire incidents.

    The total of fire incidents, that were large enough, where smoke alarms activated

    represented 39% or 16 of the fire incidents.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    30/87

    Smoke Alarm Program 30

    The total of fire incidents in 2009 that had smoke alarms fail in addition to the incidents

    where there was an absence of smoke alarms represents 26% or 15 of the fire incidents.

    The total of fire incidents, that were large enough, where smoke alarms activated

    represented 43% or 25 of the fire incidents.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    31/87

    Smoke Alarm Program 31

    The total of fire incidents in 2008 that had smoke alarms fail in addition to the incidents

    where there was an absence of smoke alarms represents 37% or 17 of the fire incidents. The total

    of fire incidents, that were large enough, where smoke alarms activated represented 23% or 11 of

    the fire incidents.

    As the fire companies canvass the high risk targeted areas of District 25 Zone A

    and District 26 Zone E, Those with older ionization smoke alarms will have them replaced with

    the photoelectric smoke alarms provided by the fire department. With the limited resources of

    the department, we are not able to replace or install smoke alarms in every room of every

    residence. When we encounter a home that has either a missing smoke alarm or an ionization

    alarm, we shall install one photoelectric smoke alarm on each floor. The occasion will be used

    as an educational opportunity for the occupants. In order to further assist the occupants, we shall

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    32/87

    Smoke Alarm Program 32

     provide them with coupons for smoke alarms purchases at Lowes and Home Depot home

    improvement stores.

    There is a great need for proper documentation of smoke alarms distributed. The crews

    installing the alarms shall document data such as; address of home, location of installed detector,

    and date of installation. The Washington State Study showed that 20% of installed ionization

    smoke alarms were inoperable within months due to nuisance alarms. Only 5% of photoelectric

    alarms were disabled by the residents. (Committee, 2009) A time of no less than six months

    should pass after the installation of a photoelectric smoke alarm, at that time a inspection should

    occur at the residence. The data collected from the follow up inspection should produce data

    showing how many, or what percent, of the photoelectric smoke alarms were disabled and why.

    Those residences that already have photoelectric smoke alarms installed should have

     positive reinforcements. For those that are providing their families with the utmost in fire alarms

    should be rewarded. Coupons redeemable for local restaurants and other establishments that

    sponsor this program can be disseminated to the public. Many of the local businesses support

    Colerain Township public safety educational programs. A few of these businesses offering

    rewarding coupons for food and or services would be; Firehouse Subs, Larosa’s Pizza, Gold Star

    Chili, and Quaker Steak and Lube. When people are rewarded for their positive safety, they will

    get positive reinforcements. This will assist in our marketing of the educational program.

    Along with educating the public so that individuals can make a positive change. We are

    also making positive changes in our local fire codes. We have been educating our elected

    officials with the need for photoelectric smoke alarms. We have drafted code changes that

    require all newly built occupancies to have photoelectric smoke alarms. The newly drafted fire

    code will also require all rental properties to change to photoelectric smoke alarms. Colerain

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    33/87

    Smoke Alarm Program 33

    Township is not the only jurisdiction in Ohio to address the problem with code changes. Other

     jurisdictions in Ohio have adopted single station photoelectric smoke alarms. These cities or

    townships are Shaker Heights, Chagrin Falls, Brooklyn, Mayfield Village, Mooreland Hills,

    Lynhurst and the City of Cincinnati for all rental properties. (Dean, 2013)

    The public information officers within Colerain Township Fire Department will keep the

    general public informed of our smoke alarm program. Various photos of our fire fighters

    canvassing the neighborhoods will be posted on social media sites that the fire department

    utilizes such as Facebook, Twitter, and fire department website. The local media outlets will be

    informed and updated through news releases. The Northwest Press, a local publication, will

    have informational guest columns written for dissemination to the public. Correspondences with

    the owners of rental property within Colerain Township will be in the form of mailed

    documentation explaining the requirements of landlords.

    DISCUSSION / IMPLICATION

    There is very little discussion needed on the associated risks of not having a smoke alarm

    in the home. Both the White Paper Home Smoke Alarms and Other Fire Detection and Alarm

     Equipment  and the Smoke Alarm Presence and Performance in U.S. Home Fires, both indicate

    that the absence of a working smoke alarm accounts for almost 70% of all fire fatalities.

    The results of this ARP is very similar to other studies. It was determined that in the

    analysis of building fires from 2008 through 2012, Colerain encountered a 9% failure rate of

    smoke alarms. The same study showed that 23% of the incidents had no smoke alarms present.

    If we look at the Abstract of Smoke Alarm Presence and Performance in U.S. Home Fires it was

    reported that nationally “smoke alarms were present but failed to operate in 9% of the reported

    fires” (Ahrens, ND) It was also reported that 31% of the reported fires had no smoke alarms

     present. While it is reported that nationally there was a higher percentage of fires without smoke

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    34/87

    Smoke Alarm Program 34

    alarms present, it is worth noting that the five year analysis had 24% of building fires where the

    smoke alarms were listed as “undetermined”. The undetermined category could account for a

    slight change in the percentage of smoke alarm presence and or activation.

    On page seven of the Smoke Alarm Presence and Performance in U.S. Home Fires, it

    states that two-thirds of fire deaths in the residential occupancies occurred without the protection

    of a working smoke alarm. The ten year analysis of civilian casualties for Colerain show that

    there was a single fatality, there was no working smoke alarm present. It is noted that a true and

    fair comparison can not be done with data showing a single event. However, it is also worth

    asking the question of “had there been a working smoke alarm”, could this single fatality have

     been prevented?

    When we mention that people need an early warning for fire incidents, many times we do

    not take into account of “all” people. People in general need as much advanced warning of

    smoke and or fire. Consider the reaction and escape time of those that are slower due to age,

    younger and older. There are many people that may have some disabilities, be it mental or

     physical. The disabled in residential occupancies are common. To put their unique situation in

     perspective when compared to a healthy adults reaction and escape time, keep in mind that

    Andrew K. Pantelis’s research paper, titled The Impact of Alcohol Consumption on Fire Egress

     Behavior, showed that being under the influence of alcohol can substantially increase the amount

    of time for a person to react to smoke alarms. Could one not draw an inference of an intoxicated

     persons reaction time with that of a person that has slowed perception or physical abilities due to

    age or disabilities? The presence of smoke alarms will give “all” people advanced notification

    and alarm of fire conditions. Thus giving them the increase in time from the discovery of fire

    conditions to that of exiting the building.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    35/87

    Smoke Alarm Program 35

    In the same study produced by Marty Ahrens, it states on page eight that in 62% of the

    fires in which battery operated smoke alarms were present, yet did not operate, it was because

    the batteries were missing or disconnected. When questioned about why occupants removed or

    disabled the batteries, the common reason given was due to “nuisance” alarms, or false alarms.

    In the July 2009 NFPA report, the nuisance alarm was addressed. In the Washington State study

    of 757 homes, the rate of ionization smoke alarms being disabled was 4 to 1 in comparison to

     photoelectric smoke alarms. Unfortunately in my study I was unable to conduct an interview to

    ascertain the reasons for disabled alarms in Colerain.

    Why not recommend a dual sensor smoke alarm, thus protecting against a flaming fire

    and from a smoldering fire? When we review the Pilot Study For Nuisance Alarms, it is

    discovered that the combination sensor smoke alarm has occurrences of a false, or nuisance,

    alarm at an even higher percentage that the ionization smoke alarm technology. (intern), ND)

    The implications of this ARP is that smoke alarms must be in all occupancies to give the

     best chance of survival through an early warning of fire conditions. As important as it is to

    ensure smoke alarms for everyone, it must be the proper alarms. It is apparent that smoke alarms

    with the ionization sensors are the least reliable. They have a higher incident of false or nuisance

    alarms. They are prone to delayed responses in smoldering fires, by as much as 15-30 minutes

    after photoelectric alarms activate. In general they give a false sense of security to occupants.

    The refusal to participate in the Red Cross’s smoke alarm program is the appropriate one.

    Colerain Township Fire & EMS should not be part of a program that gives false sense of security

    or faulty equipment to their residents. The Colerain Township

    An additional item noteworthy of discussion would be the words of Kiddie Smoke

    Alarms. In an email received from Adrian Butler, of the World Fire Safety Foundation, Kiddie

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    36/87

    Smoke Alarm Program 36

    describes aspects of their newer “Worry-Free” smoke alarms. A very interesting thing is that in

    their overall product line features, Kiddie states, “Only smoke alarms with a photoelectric smoke

    sensor programmed to reduce nuisance alarms” (Butler, 2013) are sold as the “Worry-Free”

    smoke alarm. Why not an ionization smoke alarm? Can they not make ionization sensor alarms

    that minimize “nuisance” alarms?

    This study presents overwhelming evidence of a need for a smoke alarm program

    targeted specifically at two response zones within Colerain Township. There are two response

    zones, District 25 Zone A, and District 26 Zone E, that represent 58.8% The same two zones, out

    of 29, represents 31% of the total interior building fires within Colerain Township. Any smoke

    alarm project that is undertaking by this author or the Colerain Township Fire & EMS should be

    started within the highest risk area.

    RECOMMENDATIONS

    What is Colerain Township Fire & EMS to do about our dilemma? Our dilemma is not

    handing out less than reliable smoke alarms with the inability to purchase large quantities of

    smoke alarms for citizens. The first step will be public education. Instead of simply

    understanding why people are disabling their smoke alarms, we need to educate the public as to

    why the smoke alarm is activating. It has become apparent to this author that most of the non-

    fire service public do not have the knowledge of the two different types of smoke alarm sensors

    on the market. Public education needs to be an active role in getting people to change to a more

    reliable smoke alarm. Colerain has utilized social media sites such as twitter, facebook, and our

    fire department web site to educate the public to the risks associated with ionization smoke

    alarms and the benefits of the more reliable photoelectric smoke alarms. In addition to social

    media this author has written an article as a guest columnist in the local newspaper and given

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    37/87

    Smoke Alarm Program 37

    interviews with the local television news media. The use of social media has presented us with

    the ability to reach more people while using less of our budget.

    Future endeavors will incorporate mass mailings of public safety announcements.

    Valpak coupons is a local mailing that mass mails coupons to residential homes. Valpak has

    divided their mailing areas into “zones”. Each zone consist of 10,000 residences. At a price of

    $150 per zone, or 10,000 homes, our fire department is able to get our public safety message

     printed and mailed. We will begin with a smoke alarm message. Then a different message will

     be sent out on a quarterly basis. This marketing “partnership” will bring businesses and the fire

    department together while getting vital safety information to the community. It benefits the fire

    department by having thousands of homes delivered tailored safety messages, while providing

    the business sponsor with advertisement at a rate of less than 50% cost of the standard rate.

    One limitation with this marketing program is that is does not deliver to our identified

    high hazard district. 25. This is due to low economy and return on investment for the Valpak

    company. In order to combat this and get equal education for the residents, we will need to

    canvass the area with fire personnel and educational materials. Very simply firefighters going

    door to door with flyers and educational handouts.

    The public service announcements and neighborhood canvassing will be a positive

    change. It will engage our citizens in conversation and allow us feedback about their concerns

    and reintroduce the residents to their fire service.

    Financial limitations prevent the local fire departments from purchasing large quantities

    of photoelectric smoke alarms for distribution to the public. On May 1, 2013 the Colerain

    Township Fire & EMS was given a $1,000 credit to be used at the local Meijer’s store. The

    $1,000 has been appropriated for the smoke alarm program to purchase photoelectric smoke

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    38/87

    Smoke Alarm Program 38

    alarms. These alarms are to be placed on the fire apparatus for disbursement to the public as

    deemed necessary by the emergency response crews. This is the first securing of outside

    donations and funds for the program. Additional sponsors and monies will need to be

    appropriated to continue with an adequate supply of photoelectric smoke alarms.

    A future partner in protection will the International Association of Firefighters Local

    3915, Colerain Career Firefighters. They are willing to contribute monies to worthwhile

    educational programs. Local 3915 has authorized the disbursement of $500 to purchase

    additional photoelectric smoke alarms upon the distribution of the current supply of smoke

    alarms obtained through the Meijer’s original donation. There is potential to increase future

    funding for this project. There are many community based fraternal organizations that are more

    than willing to contribute, these groups are; The Knights of Columbus, The Masonic Lodge,

    Moose Lodge, Citizens Fire Academy, etc.

    How will we follow up to see if this program is beneficial and working? The

    short term goal would be to conduct follow up inspections of homes that have our photoelectric

    smoke alarms installed in them. The follow up inspections should occur at six month and 12

    months post installation. This information will give us insight as to how many alarms have been

    altered by the occupants and why. The long term evaluation would take several years. This

    would be to collect data as to civilian fire injuries and or fatalities. The goal would ultimately be

    to significantly reduce the occurrences of civilian fire injuries, allow time for occupants to exit

    the home during fire conditions while it is still tenable, and to ultimately reduce fire loss with a

    quicker response from the fire department by early notification of the occupants of smoke.

    The final goal of this project would be the passing of an ordinance that requires all newly

     built, or significantly renovated, structures to have photoelectric smoke alarms installed. The

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    39/87

    Smoke Alarm Program 39

    ordinance would also have provisions for multi-family rental units to phase out the less reliable

    ionization smoke alarms for the installation of photoelectric smoke alarms on a sliding time

    scale.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    40/87

    Smoke Alarm Program 40

    REFERENCES

     American FactFinder . (2010). Retrieved March 1, 2013, from United States Census Bureau:

    http://factfinder2.census.gov/faces/nav/jsf/pages/index.xhtml

    Texas A&M University Study . (2011, February 11). Retrieved April 02, 2013, from The World Fire Safety

    Foundation: http://www.theworldfiresafetyfoundation.org/texasaandm.html

    Ahrens, M. (ND, ND ND). Smoke Alarm Presence and Performance in U.S. Home Fires. Retrieved April 1,

    2013, from NFPA.org:

    http://www.nfpa.org/assets/files/PDF/Foundation%20proceedings/Smoke_Alarm_Presence_an

    d_Performance_in_US_Home_Fires-Ahrens.pdf

    Bukowksi, R. W., Peaconk, R. D., Averill, J. D., Cleary, T. G., Bryner, N. P., Walton, W. D., . . . Kuligowski, E.

    D. (2007, December). Performance of Home Smoke Alarms. Retrieved March 26, 2013, from

    National Institute of Standards & Technology:

    http://www.fire.nist.gov/bfrlpubs/fire07/PDF/f07063.pdf

    Burn Survior Throughout The World Inc. (N.D., N.D. N.D.). United States Fire Statistics. Retrieved March

    26, 2013, from Burn Survivor: http://www.burnsurvivorsttw.org/fsafety/usstats.html

    Butler, A. (2013, September 16). Worry-Free.

    Christopher Mealy, A. W. (2011). Smoke Alarm Response and Tenability. Baltimore: Huges Associates,

    Inc.

    Committee, N. 7. (2009, July 01). TASK GROUP ON SMOKE DETECTION FOLLOW-UP REPORT . Retrieved

    April 02, 2013, from NFPA.org:

    http://www.nfpa.org/assets/files//PDF/Research/FinalReportTaskGroupSmokeDetectionFollow

    Up.pdf

    Council, P. F. (2006, April). WHITE PAPER Home Smoke Alarms. Retrieved March 27, 2013, from

    USFA.FEMA: http://www.usfa.fema.gov/downloads/pdf/white-paper-alarms.pdf

    Dean, D. (2013, May 14). (D. Edwards, Interviewer)

    Edwards, D. (2013, April 09). Civilian Casualties by Incident. Colerain Township, Ohio, USA.

    Edwards, D. (2013, April 14). Yearly Fire Incidents Report. Colerain Township, Ohio, USA.

    EPA, U. (2012, June 27). Ionization Technology . Retrieved April 02, 2013, from United States

    Environmental Protection Agency: http://www.epa.gov/radiation/sources/smoke_ion.html

    EPA, U. (2012, June 27). Photoelectric Technology . Retrieved April 02, 2013, from United States

    Environmental Protection Agency: http://www.epa.gov/radiation/sources/smoke_photo.html

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    41/87

    Smoke Alarm Program 41

    Grosse, L., DeJong, J., & Murphy, J. (2011, February 24). Texas A&M Univestity Study . Retrieved March

    27, 2013, from World Fire Safety Foundation:

    http://www.theworldfiresafetyfoundation.org/texasaandm.html

    intern), A. L. (ND, ND ND). PILOT STUDY OF NUISANCE ALARMS. Retrieved April 08, 2013, from

    Consumer Product Safety Commission: http://www.cpsc.gov/PageFiles/98715/smokealarm.pdf

    Leeks, C. (2013, October 01). Kidde Smoke Alarms. Cincinnati, Ohio.

    Pantelis, A. K. (2008). The Impact of Alcohol Consumption on Fire Egress Behavior. Emmittsburg: National

    Fire Academy.

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    42/87

    Smoke Alarm Program 42

    Appendix A

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    43/87

    Smoke Alarm Program 43

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    44/87

    Smoke Alarm Program 44

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    45/87

    Smoke Alarm Program 45

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    46/87

    Smoke Alarm Program 46

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    47/87

    Smoke Alarm Program 47

    Appendix B

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    48/87

    Smoke Alarm Program 48

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    49/87

    Smoke Alarm Program 49

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    50/87

    Smoke Alarm Program 50

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    51/87

    Smoke Alarm Program 51

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    52/87

    Smoke Alarm Program 52

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    53/87

    Smoke Alarm Program 53

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    54/87

    Smoke Alarm Program 54

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    55/87

    Smoke Alarm Program 55

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    56/87

    Smoke Alarm Program 56

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    57/87

    Smoke Alarm Program 57

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    58/87

    Smoke Alarm Program 58

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    59/87

    Smoke Alarm Program 59

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    60/87

    Smoke Alarm Program 60

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    61/87

    Smoke Alarm Program 61

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    62/87

    Smoke Alarm Program 62

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    63/87

    Smoke Alarm Program 63

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    64/87

    Smoke Alarm Program 64

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    65/87

    Smoke Alarm Program 65

    Appendix C

    2012 Smoke Alarm Activation Summary

    Street Zone Detector Function

    Day 102 A None PresentGosling 102 A Operated

    Blue Rock 103 A None Present

    Blue Rock 103 A None Present

    Blue Rock 103 A Undetermined

    Green Springs 109 A Operated

    Kemper 109 B None Present

    Pippin 109 B None Present

    Sudbury 109 B Undetermined

    Hazelcrest 109 B Undetermined

    Waldent Glen 109 C Operated

    Berthbrook 25 A Failed

    Arborwood 25 A None Present

    Springdale 25 A None Present

    Birchway 25 A Not Documented

    Pippin 25 A Operated

    Springdale 25 A Operated

    Colerain 25 A Operated

    Springdale 25 A Too small to activate

    Adair 25 A Undetermined

    Marker 25 A Undetermined

    Bevis 25 D None Present

    October 25 D Operated

    Hanois 25 F None Present

    Wenning 25 G None Present

    Yuba 25 G None Present

    Yuba 25 G Undetermined

    Pindale 25 G Undetermined

    Coogan 25 G Undetermined

    Coogan 25 G Undetermined

    Chippenham 25 H Failed

    Wilson 25 H Undetermined

    Crestland 25 H Undetermined

    Owl Creek 25 J None Present

    Orchardhill 26 A Failed

    Galbraith 26 B Operated

    Fireshade 26 B Too small to activate

    Acre 26 C None Present

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    66/87

    Smoke Alarm Program 66

    Colerain 26 C None Present

    Nandale 26 C Operated

    Cheviot 26 C Undetermined

    Blue Rock 26 C Undetermined

    Blue Acres 26 C Undetermined

    Jonrose 26 E Failed

    Beckys Ridge 26 E None Present

    Pippin 26 E None Present

    Woodhill 26 E None Present

    Regal 26 E Operated

    Planet 26 F Operated

    Planet 26 F Undetermined

    Total Function Total Zone

    4 Failed 2 102 A

    17 None present 3 103 A

    11 Operated 1 109 A

    2 Too small 4 109 B

    16 Undetermined 1 109 C

    10 25 A

    2 25 D

    1 25 F

    6 25 G

    3 25 H

    1 25 J1 26 A

    2 26 B

    6 26 C

    5 26 E

    2 26 F

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    67/87

    Smoke Alarm Program 67

    Appendix D

    2011 Smoke Alarm Activation Summary

    Street Zone Detector Function

    Dunlap 102 C None PresentPoole 103 A Undetermined

    East Miami River 103 B None Present

    Swissvale 109 A Operated

    Overdale 109 A Undetermined

    Pippin 109 B Operated

    Haverknoll 109 B Operated

    Spaulding 109 B Too small

    Walden Glen 109 C Operated

    Walden Glen 109 C Operated

    Walden Glen 109 C Operated

    Walden Glen 109 C Undetermined

    Walden Glen 109 C Undetermined

    Springdale 25 A None Present

    Colerain 25 A Operated

    Arborwood 25 A Operated

    Darbi Dew 25 A Undetermined

    Amberway 25 A Undetermined

    Pippin 25 A Undetermined

    Thimbleglen 25 B Undetermined

    Colerain 25 B Undetermined

    Niagara 25 D None Present

    Wuest 26 A Operated

    Rocker 26 C Operated

    Colerain 26 C Operated

    Colerain 26 C Operated

    Colerain 26 C Operated

    Cheviot 26 D Operated

    Compton 26 E Failed

    Galbraith 26 E Failed

    Jonrose 26 E None Present

    Sheldon 26 E Undetermined

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    68/87

    Smoke Alarm Program 68

    Total Function Total Zone

    2 Failed 1 102 C

    5 None Present 1 103 A

    14 Operated 1 103 B1 Too Small 2 109 A

    10 Undetermined 3 109 B

    5 109 C

    6 25 A

    2 25 B

    1 25 D

    1 26 A

    4 26 C

    1 26 D

    4 26 E

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    69/87

    Smoke Alarm Program 69

    Appendix E

    2010 Smoke Alarm Activation Summary

    Street Zone

    Detector

    Activation

    Brehm 103 A Undetermined

    Country Village 103 C Operated

    Springleaf 103 C Too Small

    Springlake 103 D Too Small

    Crest 109 B Operated

    Wincanton 109 B Undetermined

    Amberway 25 A None Present

    Niagara 25 A None Present

    Amberway 25 A Operated

    Amberway 25 A Operated

    Amberway 25 A Undetermined

    Amberway 25 A Undetermined

    Eddystone 25 B Operated

    Chagrin 25 C Operated

    Town Terrace 25 D Failed

    Niagara 25 D Operated

    Storm 25 D Too Small

    Pebble Valley 25 E Operated

    Cornwall 25 G Undetermined

    Roosevelt 25 H None Present

    Galbraith 26 B FailedGalbraith 26 B None Present

    Sandy 26 B None Present

    Galbraith 26 B Operated

    Galbraith 26 B Operated

    Georgianna 26 B Operated

    Rocker 26 C Failed

    Colerain 26 C None Present

    Colerain 26 C None Present

    April 26 C Operated

    Cheviot 26 C OperatedNandale 26 C Undetermined

    Colerain 26 C Undetermined

    Oak Creek 26 D Operated

    Apple Valley 26 D Too Small

    Lookover 26 E None Present

    Lookover 26 E None Present

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    70/87

    Smoke Alarm Program 70

    Tripoli 26 E Too Small

    Blue Lark 26 F None Present

    Uranus 26 F Operated

    Mars 26 F Operated

    Total Function Total Zone

    3 Failed 1 103A

    10 Not Present 2 103 C

    16 Operated 1 103 D

    5 Too Small 2 109 B

    7 Undetermined 6 25 A1 25 B

    1 25 C

    3 25 D

    1 25 E

    1 25 G

    1 25 H

    6 26 B

    7 26 C

    2 26 D

    3 26 E3 26 F

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    71/87

    Smoke Alarm Program 71

    Appendix F 

    2009 Smoke Alarm Activation Summary 

    Street Zone Detector Activation

    Day 102 A UndeterminedGosling 102 A Undetermined

    Dunlap 102 C Undetermined

    Brehm 103 A Too Small to activate

    Springdale 103 C Undetermined

    Springwater 103 D Operated

    Desert Gold 103 D Too Small to activate

    Gravenhurst 109 A Failed

    Chestehill 109 A Operated

    Overdale 109 A Operated

    Pippin 109 A Operated

    Haverknoll 109 B Operated

    Waldon 109 B Operated

    Walden Glen 109 C Operated

    Walden Glen 109 C Operated

    Pippin 25 A Failed

    Colerain 25 A None Present

    Burgess 25 A Operated

    Colerain 25 A Too Small to activate

    Aries 25 A Undetermined

    Red Skin 25 D None Present

    Philknoll 25 D None Present

    Pippin 25 D Operated

    Town Terrace 25 D Operated

    Windswept 25 D Too Small to activate

    Hollis 25 D Undetermined

    Holly Glen 25 D Undetermined

    Redskin 25 D Undetermined

    Colerain 25 E Operated

    Field Glen 25 G Operated

    Trinidad 25 G Operated

    Sacremento 25 G Undetermined

    Sacremento 25 G Undetermined

    Ash hill 26 A Failed

    Galbraith 26 B Failed

    Firshade 26 B Failed

    Cheviot 26 B Operated

    Galbraith 26 B Operated

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    72/87

    Smoke Alarm Program 72

    Blue Acres 26 C None Present

    Banning 26 C Operated

    Rocker 26 C Operated

    Banning 26 C Operated

    Blue Acres 26 C Too Small to activate

    Bay Towne 26 D Operated

    Weiss 26 D Operated

    Regal 26 E Failed

    Pippin 26 E None Present

    Pippin 26 E None Present

    Barthas 26 E None Present

    Clara 26 E None Present

    Pippin 26 E None Present

    Galbraith 26 E Operated

    Rock Acre 26 E Operated

    Gila 26 E Operated

    Regal 26 E Operated

    McGill 26 E Undetermined

    Colerain 26 E Undetermined

    Bluelark 26 F Undetermined

    Total Function Total Zone

    6 Failed 2 102 A

    9 Not Present 1 102 C25 Operated 1 103 A

    5 Too Small to Activate 1 103 C

    13 Undetermined 2 103 D

    4 109 A

    2 109 B

    2 109 C

    5 25 A

    8 25 D

    1 25 E

    4 25 G1 26 A

    4 26 B

    5 26 C

    2 26 D

    12 26 E

    1 26 F

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    73/87

    Smoke Alarm Program 73

    Appendix G

    2008 Smoke Alarm Activation Summary 

    Street Zone Detector Activation

    Squirrelsnest 102 C OperatedBlue Rock 103 A Too small to activate

    Country View 103 A Undetermined

    Austin Ridge 103 C Too small to activate

    Daleview 103 C Too small to activate

    Overdale 109 A Undetermined

    Retford 109 B None Present

    Hazelcrest 109 B Operated

    Crest 109 B Undetermined

    Ontario 25 A Failed

    Aries 25 A Failed

    Marino 25 A Failed

    Arborwood 25 A None Present

    Marino 25 A None Present

    Springdale 25 A None Present

    Colerain 25 A None Present

    Niagara 25 A None Present

    Rumford 25 A Operated

    Arborwood 25 A Operated

    Niagara 25 A Operated

    Manhatten 25 A Operated

    Pippin 25 A Too small to activate

    Niagara 25 A Too small to activate

    Springdale 25 A Undetermined

    Niagara 25 A Undetermined

    Colerain 25 B Operated

    October 25 D Failed

    October 25 D Failed

    Jackfrost 25 D Failed

    October 25 D None Present

    Moonflower 25 D Operated

    Bentbrook 25 D Operated

    Seasons 25 D Undetermined

    Capstan 25 D Undetermined

    Pippin 25 F Operated

    Paprika 25 F Too small to activate

    Schon 25 G Too small to activate

    Sacremento 25 G Undetermined

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    74/87

    Smoke Alarm Program 74

    Roppelt 25 J Undetermined

    Banning 26 C None Present

    Grange 26 C Operated

    Hillary 26 C Too small to activate

    Boleyn 26 C Undetermined

    Pippin 26 E None Present

    Windy Way 26 E None Present

    Blanchetta 26 E None Present

    Trelawney 26 E Too small to activate

    Total Function Total Zone

    6 Failed 1 102 C

    11 None Present 2 103 A

    11 Operated 2 103 C

    9 Too small to activate 1 109 A

    10 Undetermined 3 109 B

    16 25 A

    1 25 B

    8 25 D

    2 25F

    2 25 G

    1 25 J

    4 26 C

    4 26 E

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    75/87

    Smoke Alarm Program 75

    Appendix H

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    76/87

    Smoke Alarm Program 76

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    77/87

    Smoke Alarm Program 77

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    78/87

    Smoke Alarm Program 78

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    79/87

    Smoke Alarm Program 79

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    80/87

    Smoke Alarm Program 80

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    81/87

    Smoke Alarm Program 81

    Appendix J 

    Ohio 

    Smoke detectors don't save lives, at least not the most

    commonly used detectors

    By Darian Edwards Correspondent 1st Responder Newspaper Story Number 102710102 Disclaimer: This article is a direct street report from our correspondent and has not been edited by the

    1st Responder newsroom. 

    Smoke detectors don't save lives, at least not the most commonly used detectors.

    In the early 1970's less than 10% of the homes had smoke detectors, back then 8 people died forevery 1,000 fires that occurred. Today 95% of homes have smoke detectors, however 8 people stilldie for every 1,000 fires that occur. 70% of fire-related fatalities, in Hamilton County, are due tosmoke inhalation, not the heat or flames. 75% of fatalities occur during sleeping hours.

    Smoke detectors are built with one of two sensors in them. One sensor, Ionization, is designed torecognize and alarm in the presence of a flaming fire. It detects the small particles that aresuspended in the air (ionized electrons), these particles are so small you may not even be able to seeor smell them. The Ionization detectors utilize a very small amount of a radioactive isotope thatemits Alpha radiation. (Don’t worry, unless you are playing with the detector or inhaling the airdirectly off of it, the radiation is harmless) The second sensor, Photoelectric, is designed to recognizeand alarm in the presence of a smoldering fire. The Photoelectric senses the smoke that is producedfrom smoldering fires or from items such as synthetic materials. The smoke disrupts a light sensorinside the detector and activates the alarm.

    In a flaming fire, such as a kitchen fire, an Ionization detector goes off about 10 seconds prior to aPhotoelectric detector. In a smoldering fire, such as electrical or careless smoking, the Photoelectricdetector can activate 10, 15, 20, even 30 minutes before the Ionization detector goes off, if it evenactivates at all. Studies have been done by the National Institute of Standards and Testing, National

    Fire Protection Association, and Texas A&M University, all of which confirm similar findings thatIonization smoke detectors are failing us. Their test results have been shown on multiple televisionshows and posted on various websites such as Youtube. Many states have banned, or are currentlydebating the banning of, detectors that use Ionization technology. Many of the courts have passed judgment against the detector manufacturers for faulty Ionization detectors.

    The overwhelming majority of the population has Ionization detectors in their home. Why?, because

    it is the cheapest in cost. A Photoelectric detector costs about twice what the Ionization sells for.Therefore the Ionization detector is the cheaper and more economical choice. How do you knowwhich one you have? Look on the back of the detector, if you see an "I" or "radioactive" then its anIonization detector. A Photoelectric detector will have a "P" on it.

    Please provide your family with the proper safety equipment. We buckle our kids into child seats andseat belts; our cars have airbags and bicycle helmets are in common use now. So why not provide

    your family with the proper smoke detector? Replace your ineffective Ionization detectors with thePhotoelectric detectors.

    Call your local fire department for more information.Colerain Township Fire & EMS 513-825-6143

    http://www.1rwn.com/

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    82/87

    Smoke Alarm Program 82

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    83/87

    Smoke Alarm Program 83

    Appendix K 

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    84/87

    Smoke Alarm Program 84

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    85/87

    Smoke Alarm Program 85

  • 8/9/2019 Developing a Smoke Alarm Program for Colerain Township

    86/87

    Smoke Alarm Program 86

    Appendix L

    ORDINANCE PROPOSAL OF PHOTOELECTRIC SMOKE ALARMS AND DEVICES

    FOR HEARING IMPAIRED PERSONS

    Owners of all dwellings shall install a minimum of one smoke alarm in each sleeping area and

    adjacent to a sleeping area in each dwelling unit. At least one additional smoke alarm shall be

    installed on each additional story of the dwelling, including the basement, but excluding any

    crawl space or unfinished attic. In multifamily dwellings and two-family dwellings, smoke

    alarms shall be installed in all stairwells on each level, in all common space and hallways, and

    wherever else the Colerain Township Fire Department deems necessary. Smoke alarms shall be

    listed with an approved testing agency and shall be installed in a manner and location consistent

    with the manufacturer's instructions.

    Where a dwelling is occupied by a person who is deaf or hearing impaired, a smoke

    alarm shall be installed by the owner which provides a visual or vibrating signal sufficient to

    warn the deaf or hearing impaired individual when activated.

    Any newly constructed dwelling shall have hard-wired smoke detectors, with battery

     backup, installed as required by the Ohio Building Code and the Ohio Fire Code. When

    alterations, repairs or additions requiring a building permit occur and the value of such work is

    more than 50% of the assessed valuation or when all or most of the electrical wiring is being

    replaced, hard-wired smoke alarms, with battery backup, shall be installed. Wiring shall be

     permanent and without a disconnection switch, other than those required for over current

     protection.

    Rental properties, be they residential, condominium, townhouse, or apartments shall

    replace the older smoke alarms with new photoelectric smoke alarms. When a rentable unit is

    vacated, prior to renting this unit again, photoelectric smoke alarms must be installed. In

     properties that have 12 or less units, the owner has one year from date of notice of this ordinanceto have all photoelectric smoke alarms. Properties that have more than 12 units have two years

    from notice of ordinance to have all photoelectric smoke alarms.

    Existing single and multi-family dwellings with hard-wired smoke alarms mus