data centers - bonneville power administration...data centers in the pnw pnw population avg. it load...
TRANSCRIPT
![Page 1: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/1.jpg)
Data Centers Presented on the Momentum Savings Monthly Call
May 3rd & June 7th
![Page 2: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/2.jpg)
Why should we
CARE?
![Page 3: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/3.jpg)
350-450 aMW 7th Plan
Embedded Data Center Load
![Page 4: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/4.jpg)
55aMW Savings Potential
With no program in place to capture it
7th Plan Potential, 2016-2021
![Page 5: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/5.jpg)
So what is a data center?
![Page 6: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/6.jpg)
Closets
![Page 7: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/7.jpg)
Server Room
![Page 8: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/8.jpg)
Localized Data Centers
![Page 9: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/9.jpg)
Mid-Tier Data Centers
![Page 10: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/10.jpg)
Co-Location, ‘Colos’
![Page 11: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/11.jpg)
Enterprise
![Page 12: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/12.jpg)
![Page 13: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/13.jpg)
![Page 14: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/14.jpg)
What they all have in common
![Page 15: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/15.jpg)
Priorities
Security
Reliability thereafter, efficiency
![Page 16: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/16.jpg)
IT Equipment
– Servers
– Storage
– Networking (communications)
HVAC and Infrastructure
– Cooling
– Power management
![Page 17: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/17.jpg)
IT Equipment
– Servers
– Storage
– Networking (communications)
HVAC and Infrastructure
– Cooling
– Power management
Computer Wattage BTUs
![Page 18: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/18.jpg)
IT Equipment
– Servers
– Storage
– Networking (communications)
HVAC and Infrastructure
– Cooling
– Power management
Computer Wattage BTUs
![Page 19: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/19.jpg)
IT Equipment
– Servers
– Storage
– Networking (communications)
HVAC and Infrastructure
– Cooling
– Power management
Computer Wattage BTUs
![Page 20: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/20.jpg)
IT and Infrastructure
![Page 21: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/21.jpg)
Consumption Nationally
Berkeley National Lab
![Page 22: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/22.jpg)
Data Centers in the PNW
Enterprise ???
Mid-Tier 500
Localized 700
Server Rooms 20,000
Server Closet 16,233
CBSA
![Page 23: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/23.jpg)
Trend to Enterprise DCs
Berkeley National Lab
![Page 24: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/24.jpg)
Getting EE into the DC
![Page 25: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/25.jpg)
EE savings from embedded
DCs only
– Assumption: enterprise
DCs high-efficient facilities
Criticism for being overly
optimistic/aggressive
– Input from Cadmus study
and CBSA
7th Plan Scope
![Page 26: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/26.jpg)
Savings Potential
– 55 aMW 5-year potential
– 750 aMW 20-year potential
Load Forecast
– 405 aMW in 2017
– 637 aMW in 2030
Avg. 2.7% annual growth
7th Plan Scope
![Page 27: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/27.jpg)
0
100
200
300
400
500
600
700
2016 2021 2026 2031
Load Forecast
Savings Potential
LF - Savings
aMW
![Page 28: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/28.jpg)
0
10
20
30
40
50
60
70
2016 2021 2026 2031
Savings Potential
aMW
![Page 29: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/29.jpg)
Practices v. Widgets
![Page 30: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/30.jpg)
Practices
Virtualization (43%*)
– Running the workload of multiple
servers on one physical host
server – creates “virtual”
servers
Decommissioning servers
(9.5%*)
ASHRAE HVAC guidelines
And the cloud… more later
* 7th Plan Potential
![Page 31: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/31.jpg)
Widgets
Efficient servers (11%*) – An ENERGY STAR qualified server uses 30% less energy
than a conventional server
– Most energy intensive component
Efficient storage (10%*) – Far second in energy intensiveness
Efficient network equipment (3.6%*) – Distant 3rd in energy intensiveness
Efficient UPS (6%*) – Uninterruptible Power Supply
* 7th Plan Potential
![Page 32: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/32.jpg)
% ENERGY STAR Servers % Virtualization
Enterprise ??? ???
Mid-Tier 71% 33%
Localized 44% 27%
Server Rooms 31% 30%
Server Closet 38% 8%
CBSA *CBSA pop. ¼ of national estimates
**does not include HVAC
Top Practice & Widget in Use
![Page 33: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/33.jpg)
Market Analysis
![Page 34: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/34.jpg)
Market Analysis
DCs in our region
Supply Chain
Market Actors
![Page 35: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/35.jpg)
PNW Population Avg. IT Load kW**
Enterprise ??? ?????
Mid-Tier 500 122
Localized 700 16
Server Rooms 20,000 5
Server Closet 16,233 1.3
CBSA **does not include HVAC
Data Centers in the PNW
![Page 36: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/36.jpg)
PNW Population Avg. IT Load kW** aMW
Enterprise ??? ????? ??????
Mid-Tier 500 122 61
Localized 700 16 11
Server Rooms 20,000 5 100
Server Closet 16,233 1.3 21
CBSA **does not include HVAC
Data Centers in the PNW
![Page 37: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/37.jpg)
Not in the 7th Plan, CBSA – assumed highly efficient
Irony
– All over the news
– Yet, next to no details about what is inside them
Moving to our region
– Cheap energy/temperate climates
– Trans-Pacific telecommunications hub
– Cloud migration
Enterprise Data Centers
![Page 38: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/38.jpg)
… just means using someone else’s computer
![Page 39: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/39.jpg)
Supply Chain Our understanding of the supply chain is very basic
![Page 40: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/40.jpg)
…But that’s about it
– Are there other channels?
• Physical v. Financial
–What are the estimate sizes of each channel?
–What is the difference between branded/unbranded
equipment?
–Where is the influence?
Supply Chain
![Page 41: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/41.jpg)
Supply Chain Market Actors
– Manufacturers, VARs (Value Added Reseller), IT service
providers, System integrators
Data Center Actors
– Facilities Manager
– IT Manager
– CFO
– Good information on decision-making process at DC
Market Actors
![Page 42: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/42.jpg)
Need a lot more information – especially on supply chain
– Most information is technology focused
– Who are they? We have a sense of types of actors, but not much
info on specific market actor profiles
– What is the difference between them?
– What value-add do they contribute?
– What existing relationships does our industry have with these
market actors, if any, that might be leveraged?
Market Actors
![Page 43: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/43.jpg)
Momentum Savings?
Modeling a data center
We have one model for DC energy
consumption, what are its weaknesses
and strengths?
Sales Data Availability
It appears one source of sales data may
exist (IDC), but do any other possibilities
exist out there?
![Page 44: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/44.jpg)
Risks and Barriers Ethan’s Gut Feeling
Collecting sales data could be difficult – if we do that
No EE program – Incentives, relationships, etc.
Broadly speaking, little interest in EE
Secretive market – Market actors, especially large ones (enterprise DCs) may not be open to
sharing market intelligence, qualitatively or quantitatively.
Double counting
– End Use types not unique to DCs, e.g. HVAC
![Page 45: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/45.jpg)
Where next?
Need an ‘IT meets EE’ expert
– Help us understand the market
There’s a lot of niche topics
here – what is noise and what
is substance?
– We only have the 7th Plan to
guide us and it doesn’t seem to
be a very robust analysis
Dig deeper into what we have
– CBSA especially
Get a grasp on enterprise DCs
– How many are there, are they
really super efficient?
– Can we get much info on them?
Or are they black boxes?
![Page 46: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/46.jpg)
Where next?
Need an ‘IT meets EE’ expert perspective
There’s a lot of niche topics here – what is noise and what is substance?
– We only have the 7th Plan to guide us and it doesn’t seem to be a very robust analysis
Dig deeper into what we have – CBSA especially
– Utility Programs
Get a grasp on enterprise DCs – How many are there? Are they
really super efficient?
– Can we get much info on them? Or are they black boxes?
– Should we ignore them?
![Page 47: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/47.jpg)
Where next?
Figure out the
technology/efficiency options
– With lighting, we think:
Incandescent, CFL, LED…
What is the equivalent for data
centers?
End Use v. Building Type
– Is this a study of data centers, or
is it a study of IT equipment?
![Page 48: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/48.jpg)
Sources Cadmus Study
Has worked with PG&E on a couple large DC studies PG&E
Multiple DC studies Berkeley National Laboratory
The lab where data center research is focused – multiple sources Power Council
Workbooks CBSA
Surveyed small to medium DCs NEEA
Embedded DC market actor survey ACEEE
Based on NEEA work, embedded data center
![Page 49: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server](https://reader034.vdocuments.us/reader034/viewer/2022042409/5f2684acd6703c5d3e23fd46/html5/thumbnails/49.jpg)
Questions?