comtrol io-link master and ifm kq6001 · test report overview the ifm proximity sensor, kq6001...

22
COMPATIBILITY REPORT IFM KQ6001 Proximity Sensor PLC DCS/HMI/SCADA IO-LINK SENSORS/ACTUATORS

Upload: ngocong

Post on 19-Aug-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

COMPATIBILITY REPORT

IFM KQ6001 Proximity Sensor

PLC

DCS/HMI/SCADA

IO-LINK SENSORS/ACTUATORS

Page 2: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Contents

Contents .................................................................................................................................................................................. 2

Test Report Overview ............................................................................................................................................................. 3

IO-Link Master - IO-Link Diagnostics Page ............................................................................................................................. 3

Configuring IO-Link Settings ................................................................................................................................................... 4

After Configuring Port-Friendly Names ............................................................................................................................... 5

Setting Up Passwords ............................................................................................................................................................. 6

KQ6001 Configuration ............................................................................................................................................................. 7

Loading IODD Files ............................................................................................................................................................. 7

Verifying that the Correct IODD Files Are Loaded .............................................................................................................. 9

Changing Parameters on the KQ6001 with the GUI ......................................................................................................... 10

Changing Parameters Using the ISDU Interface............................................................................................................... 12

Restore Factory Defaults ...................................................................................................................................................... 14

Using the Data Storage Feature ........................................................................................................................................... 15

Automatic Data Storage .................................................................................................................................................... 16

Clearing Data Storage ....................................................................................................................................................... 18

Manual Data Storage ......................................................................................................................................................... 19

Using the Device Validation Feature ..................................................................................................................................... 22

Incompatible Device Attached to Port ............................................................................................................................... 22

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 2

Page 3: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Test Report Overview

The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master. This report contains the following topics:

• IO-Link Master – IO-Link Diagnostics page

• Configuring IO-Link settings

• Setting up passwords

• Configuring the KQ6001 proximity sensor with or without the IODD file

• Restoring the KQ6001 to factory defaults

• Using the Data Storage feature

• Using the Device Validation feature

The sensors were tested using Application Base v1.3.9 on the IO-Link Master 4-EIP (machine mountable IP67). This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration.

IO-Link Master - IO-Link Diagnostics Page

Upon connection to the IO-Link Master, the KQ6001 immediately displays in the IO-Link Diagnostics page without any configuration.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 3

Page 4: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Configuring IO-Link Settings

During IO-Link configuration, the Minimum Cycle Time can be left to the default value, as the IO-Link Master negotiates the required Cycle Time with each sensor.

This example shows configuring a friendly port name. The Data Storage and Device Validation features are discussed later in the report. Implement Data Storage after IO-Link device configuration.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 4

Page 5: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

After Configuring Port-Friendly Names

The IO-Link Diagnostics page now displays friendly Port Names.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 5

Page 6: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Setting Up Passwords

The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 6

Page 7: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

KQ6001 Configuration

You can use the Comtrol IO-Link Master to configure the IO-Link device.

• If an IODD file is loaded on the IO-Link Master, you may want to use the GUI on the top of the IO-Link Device – Port page to change parameter settings.

• If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device – Port page

This section discusses the following topics:

• Loading IODD files

• Verifying that the correct IODD file is loaded

• Changing IO-Link device parameters using the GUI

• Resetting to the IO-Link device to factory defaults

• Changing IO-Link device parameters using the ISDU Interface

Loading IODD Files

IODD file packages must be unzipped and the appropriate files located and rezipped or loaded individually.

1. Click Attached Devices | IODD Files.

2. Click the Browse… button.

3. Select the file set to upload and click Open.

4. Click the UPLOAD button.

5. If there are files in the IODD file set that are not required by the associated xml file, the IO-Link Master does not load the files, and displays an Ignored Files message. Click Ok to close the message.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 7

Page 8: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

6. The IODD Files page now displays the IODD files loaded on the IO-Link Master.

7. If you want to view the xml file, click the corresponding IODD FILENAME in the table.

8. Optionally, click the hyperlink to view the xml file in your browser.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 8

Page 9: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Verifying that the Correct IODD Files Are Loaded

Use the IO-Link Device Configuration Summary page to verify that the correct IODD files for the attached IO-Link devices have been loaded on the IO-Link Master. The correct file is loaded if an xml file name displays in the IODD Name field.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 9

Page 10: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Changing Parameters on the KQ6001 with the GUI

1. The KQ6001 displays as expected in the PORT page.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 10

Page 11: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

2. Click the EDIT button to make parameter changes using the GUI.

3. Click the SAVE button. If there are parameters that change dynamically based on the other parameter changes, you may want to click REFRESH to verify that the changes occurred as expected.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 11

Page 12: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Changing Parameters Using the ISDU Interface

This shows using the IO-Link ISDU Interface to change configuration parameters. Open the IO-Link Device ISDU Interface by clicking the + next the name.

Please note:

• You must enter the decimal value for the ISDU Block Index and ISDU Sub-index.

• The following images do not display the complete web page.

• The following screenshots do not illustrate the system responses. The IO-Link Master responds with a command executed notification.

1. If necessary, retrieve the current value of the ISDU Index that you are planning on changing.

2. Change the parameter from 2000 to 1500.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 12

Page 13: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

3. Change the parameter from 2000 to 1500.

4. Click REFRESH to observe that the parameter changes executed.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 13

Page 14: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Restore Factory Defaults

Returning the KQ6001 to factory defaults is easy using the IO-Link Device - Port page.

1. Click the EDIT button and scroll down to the Restore Factory Settings option.

2. This shows that the Restore to Factory command executed.

3. Click the CANCEL button to exit EDIT mode.

4. Click REFRESH to verify that the parameters have reverted to their original values.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 14

Page 15: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Using the Data Storage Feature

The Data Storage feature can be implemented automatically or manually using Application Base v1.2.4 or higher.

The KQ6001 has been configured accordingly before enabling the Automatic Upload Data Storage feature.

• ISDU Index 24 = Proximity#80 (Default = ***)

• ISDU Index 76 = 1500 (Default = 0)

• ISDU Index 78 = 1500 (Default = 0)

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 15

Page 16: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Automatic Data Storage

The following illustrates how the Automatic Data Storage feature works. In this example, both Automatic Upload and Download are enabled, then several parameters will be changed, the KQ6001 is disconnected and reconnected to illustrate that the originally stored parameters are downloaded back to the KQ6001.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click Automatic Upload Enable to On.

4. Click Automatic Download Enable to On.

5. Click the SAVE button. The data storage (sensor configuration) uploads to the IO-Link Master as soon as the SAVE button is clicked.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 16

Page 17: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

6. Notice that the IO-Link Diagnostics page displays that Automatic Data Storage Configuration for uploading and downloading is enabled.

7. Reset the KQ6001 to factory defaults.

8. Verify that the settings have been reset.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 17

Page 18: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

9. Remove the KQ6001 from the IO-Link Master.

10. Reattach the KQ6001 to the IO-Link Master.

11. Verify that the data storage downloads to the KQ6001.

Clearing Data Storage

Clearing Data Storage from a port is easy. Simply click the EDIT button and then the CLEAR button.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 18

Page 19: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Manual Data Storage

The KQ6001 has been configured accordingly:

• ISDU Index 24 = Proximity#80 (Default = ****)

• ISDU Index 76 = 1500 (Default = 0)

• ISDU Index 78 = 1500 (Default = 0)

Data Storage was cleared in the previous discussion. In addition, Automatic upload and download are disabled.

The following illustrates how Manual Data Storage works.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click the UPLOAD button under Data Storage Manual Ops.

4. Click CONTINUE.

5. Click Ok to the DONE message and then SAVE.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 19

Page 20: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

6. Reset the KQ6001 to factory defaults, as displayed in this illustration.

7. Click Configuration | IO-Link Settings and then the EDIT button.

8. Click the DOWNLOAD button and the CONTINUE button.

9. Click Ok to the DONE message.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 20

Page 21: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

10. Observe that the parameters have been downloaded from the IO-Link Master to the KQ6001.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 21

Page 22: Comtrol IO-Link Master and ifm KQ6001 · Test Report Overview The IFM Proximity Sensor, KQ6001 operates properly with the Comtrol IO-Link Master.This report contains the following

Using the Device Validation Feature

The KQ6001 supports Compatible Device Validation. A device serial number is required for Identical Device Validation.

This report does not illustrate Compatible Device Validation with another KQ6001 because a single KQ6001 was available for testing.

Incompatible Device Attached to Port

1. In the IO-Link Configuration page, click EDIT, set Device Validation mode to Compatible.

2. Click the GET ATTACHED button.

3. Click SAVE.

4. Remove the KQ6001 and connect another IO-Link device (not a KQ6001).

5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.

3/30/2015 Comtrol IO-Link Master | IFM KQ6001 Proximity Sensor P a g e | 22