Compatibility Report Comtrol IO-Link Master ifm O5D100 Optical Distance Sensor

Upload: dothuy

Post on 08-Mar-2018

229 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

Compatibility Report

Comtrol IO-Link Master

ifm O5D100 Optical Distance Sensor

Page 2: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 2

Contents

Contents .................................................................................................................................................................................. 2

Test Report Overview ............................................................................................................................................................. 3

IO-Link Master - IO-Link Diagnostics Page ............................................................................................................................. 3

Configuring IO-Link Settings ................................................................................................................................................... 4

After Configuring Port-Friendly Names ............................................................................................................................... 5

Setting Up Passwords ............................................................................................................................................................. 6

O5D100 Configuration ............................................................................................................................................................ 7

Loading IODD Files ............................................................................................................................................................. 7

Verifying that the Correct IODD Files Are Loaded ............................................................................................................ 10

Changing Parameters on the O5D100 with the GUI ......................................................................................................... 11

Changing Parameters Using the ISDU Interface............................................................................................................... 14

Restore Factory Defaults ...................................................................................................................................................... 16

Using the Data Storage Feature ........................................................................................................................................... 19

Automatic Data Storage - Upload ...................................................................................................................................... 20

Automatic Data Storage - Download ................................................................................................................................. 23

Clearing Data Storage ....................................................................................................................................................... 25

Manual Data Storage ......................................................................................................................................................... 26

Using the Device Validation Feature ..................................................................................................................................... 29

Incompatible Device Attached to Port ............................................................................................................................... 29

Page 3: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 3

Test Report Overview

The ifm Optical Distance sensor, O5D100 operates properly with the Comtrol IO-Link Master. This report contains these topics:

• IO-Link Master – IO-Link Diagnostics page

• Configuring IO-Link settings

• Setting up passwords

• Configuring the O5D100 with or without the IODD file

• Restoring the O5D100 to factory defaults

• Using the Data Storage feature

• Using the Device Validation feature

The IO-Link devices were tested using Application Base v1.4.13 on the IO-Link Master 4-EIP (machine mountable IP67). This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration.

IO-Link Master - IO-Link Diagnostics Page

Upon connection to the IO-Link Master, the O5D100 immediately displays in the IO-Link Diagnostics page without any configuration.

Page 4: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 4

Configuring IO-Link Settings

During IO-Link configuration, the Minimum Cycle Time can be left to the default value, as the IO-Link Master negotiates the required Cycle Time with each IO-Link device.

This example shows configuring a friendly port name. The Data Storage and Device Validation features are discussed later in the report. Data Storage is typically implemented after IO-Link device configuration unless you want to save the default configuration.

Page 5: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 5

After Configuring Port-Friendly Names

The IO-Link Diagnostics page now displays friendly Port Names.

Page 6: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 6

Setting Up Passwords

The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

Page 7: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 7

O5D100 Configuration

You can use the Comtrol IO-Link Master to configure the IO-Link device.

• If an IODD file is loaded on the IO-Link Master, you may want to use the GUI on the top of the IO-Link Device – Port page to change parameter settings.

• If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device – Port page

This section discusses the following topics:

• Loading IODD files

• Verifying that the correct IODD file is loaded

• Changing IO-Link device parameters using the GUI

• Resetting to the IO-Link device to factory defaults

• Changing IO-Link device parameters using the ISDU Interface

Loading IODD Files

IODD file packages must be unzipped and the appropriate files located and rezipped or loaded individually.

1. Click Attached Devices | IODD Files.

2. Click the UPLOAD FILE button.

3. Click the CHOOSE FILE button.

Page 8: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 8

4. Select the file set to upload and click Open.

5. Click the UPLOAD button.

6. If there are files in the IODD file set that are not required by the associated xml file, the IO-Link Master does not load the files, and displays an Ignored Files message. Click Ok to close the message.

Page 9: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 9

7. The IODD Files page now displays the IODD files loaded on the IO-Link Master. If you want to view the xml file, click the corresponding IODD FILENAME in the table

8. Optionally, click the hyperlink to view the xml file in your browser.

Page 10: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 10

Verifying that the Correct IODD Files Are Loaded

Use the IO-Link Device Configuration Summary page to verify that the correct IODD files for the attached IO-Link devices have been loaded on the IO-Link Master. The correct file is loaded if an xml file name displays in the IODD Name field.

Page 11: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 11

Changing Parameters on the O5D100 with the GUI

1. The O5D100 displays as expected in the PORT page.

Page 12: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 12

2. Click the EDIT button to make parameter changes using the GUI.

Page 13: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 13

3. Click the SAVE button. If there are parameters that change dynamically based on the other parameter changes, you may want to click REFRESH to verify that the changes occurred as expected.

Page 14: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 14

Changing Parameters Using the ISDU Interface

This shows using the IO-Link ISDU Interface to change configuration parameters. Open the IO-Link Device ISDU Interface by clicking the + next the name.

Please note:

• You must enter the decimal value for the ISDU Block Index and ISDU Sub-index.

• The following images do not display the complete web page.

• The following screenshots do not illustrate the system responses. The IO-Link Master responds with a command executed notification.

1. If necessary, retrieve the current value of the ISDU Index that you are planning on changing.

Page 15: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 15

2. Change Index 74 from 200 to 300.

3. Change Index 76 from 100 to 200.

4. Click REFRESH to observe that the parameter changes executed.

Page 16: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 16

Restore Factory Defaults

Returning the O5D100 to factory defaults is easy using the IO-Link Device - Port page.

1. Click the COMMAND button and scroll down to the Restore Factory Settings option.

Page 17: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 17

2. Click the Ok button to refresh the table.

Page 18: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 18

3. Verify that the parameters have reverted to their original values.

Page 19: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 19

Using the Data Storage Feature

The Data Storage feature can be implemented automatically or manually using Application Base v1.2.4 or higher.

The PN7007 has been configured accordingly before enabling the Automatic Upload Data Storage feature.

• ISDU Index 24 = Distance#105 (Default = ***)

• ISDU Index 74 = 300 (Default = 100)

• ISDU Index 76 = 200 (Default = 0)

• ISDU Index 78 = 100 (Default = 0)

Page 20: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 20

Automatic Data Storage - Upload

The following illustrates how the Automatic Data Storage feature works. This example shows how to upload data storage from the IO-Link device to the IO-Link Master.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click Automatic Upload Enable to On.

4. Click the SAVE button. The data storage (IO-Link device configuration) uploads to the IO-Link Master as soon as the SAVE button is clicked.

5. Refresh the web page and observe that it now shows Storage Contents.

Page 21: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 21

6. Notice that the IO-Link Diagnostics page displays that Automatic Data Storage Configuration for uploading and downloading is enabled.

7. Return to the IO-Link Settings page and disable Automatic Upload Enable.

8. Reset the O5D100 to factory defaults using the Attached Devices | Port page for this device.

Page 22: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 22

9. Verify that the settings have been reset.

10. Remove the O5D100 from the IO-Link Master.

Page 23: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 23

Automatic Data Storage - Download

The following illustrates how the Automatic Data Storage feature works. This example shows how to upload data storage from the IO-Link device to the IO-Link Master.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click Automatic Download Enable to On.

4. Click the SAVE button.

5. Reattach the O5D100 to the IO-Link Master.

Page 24: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 24

6. Verify that the data storage downloads to the O5D100.

Page 25: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 25

Clearing Data Storage

Clearing Data Storage from a port is easy. Simply click the EDIT button and then the CLEAR button.

Notice that the Storage Contents field now displays as empty.

Page 26: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 26

Manual Data Storage

The O5D100 has been configured with the parameters in the Using the Data Storage Feature section on Page 19.

Data Storage was cleared in the previous discussion. In addition, Automatic upload and download are disabled.

The following illustrates how Manual Data Storage works.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click the UPLOAD button under Data Storage Manual Ops.

4. Click CONTINUE.

5. Click Ok to the DONE message and then click SAVE.

Page 27: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 27

6. Notice that the Storage Contents now displays the Vendor and Device IDs.

7. Reset the O5D100 to factory defaults, as displayed in this illustration.

Page 28: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 28

8. Click Configuration | IO-Link Settings and then the EDIT button.

9. Click the DOWNLOAD button and the CONTINUE button.

10. Click Ok to the DONE message.

11. Observe that the parameters have been downloaded from the IO-Link Master to the O5D100.

Page 29: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 29

Using the Device Validation Feature

The O5D100 supports Compatible Device Validation. A device serial number is required for Identical Device Validation.

This report does not illustrate Compatible Device Validation with another O5D100 because a single O5D100 was available for testing and the O5D100 did not have a serial number.

Incompatible Device Attached to Port

1. In the IO-Link Configuration page, click EDIT, set Device Validation mode to Compatible.

2. Click the GET ATTACHED button.

3. Click SAVE.

4. Remove the O5D100 and connect another IO-Link device (not an O5D100).

Page 30: Comtrol IO-Link Master and ifm  · PDF fileCompatibility Report Comtrol IO-Link Master. ifm O5D100 Optical Distance Sensor

2/9/2016 Comtrol IO-Link Master | ifm O5D100 Optical Distance Sensor P a g e | 30

5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.