coefficient of utilization (cu)
DESCRIPTION
coefficient of uti;ization calculation is explained in the presentationTRANSCRIPT
![Page 1: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/1.jpg)
AWP x EWP
No. of = luminaires (lumens/lamp) x (lamps/luminaires)
x CU x LLFTOTAL
The coefficient of utilization is a factor used to determine the efficiency of a lighting fixture in delivering light for a specific application
The coefficient of utilization is determined as a ratio of light output from the luminaire that reaches the workplane to the light output of the lamps alone
Coefficient of Utilization (CU)
![Page 2: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/2.jpg)
Coefficient of Utilization (CU)
Factors influencing coefficient of utilization:
The efficiency of the luminaire
The luminaire distribution
The geometry of the space
The reflectance's of the room surface
Each luminaire has its own CU table specific to that luminaire’s light distribution and efficiency. CU values are listed in tables for different room geometries and room surface reflectance.
![Page 3: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/3.jpg)
![Page 4: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/4.jpg)
![Page 5: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/5.jpg)
![Page 6: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/6.jpg)
For a given room, the cavity ratios are in direct proportion to their respective cavity heights. For the case where the luminaires are mounted on the surface of the ceiling or are recessed into the ceiling, the ceiling cavity ratio is zero.
It is necessary to convert the actual ceiling reflectance into an effective ceiling cavity reflectance (pCC) and the actual floor reflectance must be converted to an effective floor cavity reflectance (pFC).
![Page 7: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/7.jpg)
CU DeterminationStep 1. Determine the room cavity ratio using the equation below
Room cavity height (hRC) = Luminaire height – Workplane height
RCR = 5 x Room cavity height (Length + Width)
Length x Width
![Page 8: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/8.jpg)
Step 2. Since the Lumen Method considers what occurs only within the room cavity, the ceiling and floor reflection factor are replaced with their effective reflectances.
Ceiling reflection factor:
70% For very light colours and white
50% For light colours
30% for medium shades
Wall reflection factor:
50% For light colours and white
30% For medium shades
10% For dark shades
![Page 9: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/9.jpg)
To find the effective reflectance of a floor or ceiling cavity, find the floor cavity ratio and ceiling cavity ratio using the equations below
![Page 10: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/10.jpg)
• Step 3. Find the effective cavity reflectances using cavity surface reflectances.
![Page 11: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/11.jpg)
Step 4. Once all room cavity reflectances and the room cavity ratio are known, the CU value can be determined by selecting the appropriate value from the luminaire’s CU table.
![Page 12: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/12.jpg)
Example 1Classroom 20’ x 27’ x 12’ E=50 fcWP= 2’-6” AFFρc= 80% hcc= 0.0’
ρw= 50% hrc= 9.5’
ρf= 20% hfc= 2.5’
fixture: fluorescent (#38)maintenance: yearlyreplacement: on burnout voltages & ballast: normalenvironment: medium clean
![Page 13: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/13.jpg)
Example 1
Confirm fixture data
S: T.15.1 p. 641
![Page 14: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/14.jpg)
Example 1
Complete #1-6
![Page 15: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/15.jpg)
Example 1
7. Determine lumens per luminaire
Obtain lamp lumens from manufacturer’s data (or see Stein: Chapter 12)
S: T. 12.5 p. 546
![Page 16: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/16.jpg)
Lumen Flux Method
8. Record dimensional data
20’
27’
0’
9.5’
2.5’
ρc= 80%ρw= 50%ρf= 20%
![Page 17: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/17.jpg)
Coefficient of Utilization Factor(CU) Calculation9. Calculate Cavity Ratios
![Page 18: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/18.jpg)
Example 1: Cavity Ratios
CR = 5 H x (L+W)/(L x W)
RCR = 5 Hrc x (L+W)/(LxW) = 4.1
CCR = 5 Hcc x (L+W)/(LxW) = 0
FCR = 5 Hfc x (L+W)/(LxW) = 1.1
![Page 19: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/19.jpg)
Coefficient of Utilization Factor(CU) Calculation10. Calculate EffectiveCeiling Reflectance
![Page 20: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/20.jpg)
3. Obtain effective ceiling reflectance:
Example 1: Coefficient of Utilization (CU)
S: T.15.2 p. 667
![Page 21: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/21.jpg)
Example 1
11. Calculate EffectiveFloor Reflectance
Stein: T.15.2 P. 666
![Page 22: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/22.jpg)
3. Obtain effective ceiling reflectance:
Example 1: Coefficient of Utilization (CU)
S: T.15.2 p. 667
CU= 0.19 0.20
![Page 23: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/23.jpg)
Example 1
12. Select CU from mfr’s data or see
![Page 24: Coefficient of utilization (cu)](https://reader033.vdocuments.us/reader033/viewer/2022052119/554a3bb6b4c905293a8b4b9c/html5/thumbnails/24.jpg)
CU=0.32
Example 1: Coefficient of Utilization (CU)
RCR CU 4.0 0.394.1 X5.0 0.35
CU= 0.386
S: T.15.1 p. 641