cable & wiring presentation

Upload: mattcmwong

Post on 03-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Cable & Wiring Presentation

    1/71

    Schedule

    Ref. Date Topic

    A07 27 Oct 2005

    Introduction and Load Assessment

    A08 3 Nov 2005 Standards and Basic Equipment

    A09 10 Nov 2005

    Power Distribution & Final CircuitA10 17 Nov 2005 Protection & Earthing

    A11 24 Nov 2005 Cable & Wiring

    A12 1 Dec 2005 Standby Generator and PowerSupplies

  • 7/28/2019 Cable & Wiring Presentation

    2/71

    Introduction

    Load Estimation

    TerminologyBasic Equipment Codes and Standards

    Power Distribution & Final Circuit

    Protection & Cable Wiring

    Earthing

    Design of Electricity Distribution

    Standby Generatorand Power Supplies

  • 7/28/2019 Cable & Wiring Presentation

    3/71

    Earthing and Design of

    Electricity DistributionDate : 24 November 2005

    Module Code : A11Ir. KF Cheung

  • 7/28/2019 Cable & Wiring Presentation

    4/71

  • 7/28/2019 Cable & Wiring Presentation

    5/71

    Earthed Equipotential Bonding and

    Automatic DisconnectionC) Determination of Disconnection Time

    3) Compare the actual Zs with the tabulated Zs(max):

    The actual Zs value measured from the installation should besmaller than the Zs(max) value from IEE Tables in order to achieve

    safe disconnection time. Attention is drawn on that the Zs (max)form IEE Tables shall be converted to nominal supply voltagesystem in Hong Kong before comparison.

    Zs (max :220) = Zs (max : 240) in IEE Tables X 220/240

  • 7/28/2019 Cable & Wiring Presentation

    6/71

    Earthed Equipotential Bonding and

    Automatic DisconnectionC) Determination of Disconnection Time

    4) The earth fault current can be calculated using thefollowing formula:

    If= Uo /ZsUo = Phase to earth voltage

    If= earth fault current

    5) By putting the calculated fault current against thecharacteristic curves of the protective device given in IEE,the actual disconnection time can be found.

  • 7/28/2019 Cable & Wiring Presentation

    7/71

    Example

    A 220V circuit is protected by a 30A Type 2 MCB, thecable used is 2.5/1.5 twin with cpc PVC copperconductor, if the circuit length is 15m and Ze up to theMCB board is 0.5, what is the actual disconnection time?

    From table 17, R1+R2 /m = 19.51m x 1.38

    = 0.269 /m

  • 7/28/2019 Cable & Wiring Presentation

    8/71

    Time(s)

    Current (A)

  • 7/28/2019 Cable & Wiring Presentation

    9/71

    A) Cable Selection

    Factors to be considered in sizing of cable conductors Conductor material

    Insulating material

    Method of installation

    Installed environment Ambient temperature

    Thermal insulating enclosure

    Adjacent cables

    Type of protective device

    Voltage drop

    Minimum cross-sectional area

  • 7/28/2019 Cable & Wiring Presentation

    10/71

    Comparison between Copper

    Conductor and Aluminum Conductor A) Copper Conductor

    High degree of electrical conductivity

    Tough, slow to tarnish

    Can be jointed without any special provision to prevent electrolytic

    action B) Aluminum Conductor

    Lower price & light in weight

    Pliable, it can be used in solid-core cables

    Excellent resistance to corrosion

  • 7/28/2019 Cable & Wiring Presentation

    11/71

    Insulating Materials

  • 7/28/2019 Cable & Wiring Presentation

    12/71

    Bends of Non-flexible Cable

    The minimum internal radius bend in cables for fixingwiring are shown in the following table

  • 7/28/2019 Cable & Wiring Presentation

    13/71

    Correction Factor for Conductors

    Factors which affect the ability of a cable to lose heat are: Grouping (Cg or C1)

    Ambient temperature (Ca or C2)

    Thermal insulation (Ci or C3)

    Semi-enclosed fuse to BS 3036 (0.725 or C4) Type of installation (Table 4A)

  • 7/28/2019 Cable & Wiring Presentation

    14/71

    Correction Factor for Conductors

    A) Grouping factor (Cg) - 1 IEE Table 4B1 gives correction factors to be applied to te tabulated

    current-carrying capacities where cables or circuits are grouped.

    Where the horizontal clearance s between adjacent cables exceedtwo cable diameter (2D2), no correction factor need be applied.

  • 7/28/2019 Cable & Wiring Presentation

    15/71

    Correction Factor for Conductors

    A) Grouping factor (Cg) - 2 If a cable is expected to carry not more than 30% of its grouped

    rating, it may be ignored from the rest of the group.

  • 7/28/2019 Cable & Wiring Presentation

    16/71

    Correction Factor for Conductors

    B) Correction Factor for Ambient Temperature (Ca) Correction factor for ambient temperature is shown in IEE Table

    4C1. Where for semi-enclosed fuses are being used, see IEE Table4C2.

    It In / Ca

    Typical data are shown in the following table for quick reference.

  • 7/28/2019 Cable & Wiring Presentation

    17/71

    Correction Factor for Conductors

    C) Correction Factor for thermal Insulation (Ci) The value of current-carrying-capacity for various sizes of

    conductors shown in Tables of Appendix 4 have been taken intoaccount of cables installed in a thermally insulated wall or ceilingwhere one side of the cable is in contact with a thermally

    conductive surface.

    Where the cable is totally enclosed in thermal insulation, Ci=0.5shall be used in absence of more precise information.

    It In / Ci

    Ci shall only be applied to the open and clipped direct column ofrespective IEE Tables.

  • 7/28/2019 Cable & Wiring Presentation

    18/71

    Correction Factor for Conductors

    D) factor for Semi-enlosed fuse to BS3036 (C4) When semi-enclosed fuse is used for protecting the conductor, a

    derating factor of 0.726 shall be applied.

  • 7/28/2019 Cable & Wiring Presentation

    19/71

  • 7/28/2019 Cable & Wiring Presentation

    20/71

    Example

  • 7/28/2019 Cable & Wiring Presentation

    21/71

    Example

    Protective device : BS 3036 fuses Ambient temperature: 30oC

    Cable use :PVC twin with cpc cable

    Cabling conditions at:

    1) Bunched and clipped direct

    2) Passed through totally enclosed thermal insulation area

    3) One side in contact with thermally insulated ceiling

    4) Passed through a boiler house where ambient temperature of

    45o

    C 5) Clipped direct

    Ignore voltage drop

    What cable sizes are required?

  • 7/28/2019 Cable & Wiring Presentation

    22/71

    Voltage Drop

    The overall voltage drop shall not exceed the valueappropriate to the safe functioning of the equipment innormal service.

    The voltage drop in any circuit from the origin of

    installation to the current-using equipment should notexceed 4% of the nominal voltage.

    Volt drop pre unit value in from of mv/A/m are shown onIEE tables of Appendix 4. The values are based on the

    circuit conductor working at the maximum permittedoperating temperature and at unity power factor.

  • 7/28/2019 Cable & Wiring Presentation

    23/71

    Voltage Drop

  • 7/28/2019 Cable & Wiring Presentation

    24/71

    Voltage Drop

  • 7/28/2019 Cable & Wiring Presentation

    25/71

    Voltage Drop

  • 7/28/2019 Cable & Wiring Presentation

    26/71

    Voltage Drop

    Voltage drop (V.D.) can be calculated as follows:V.D. = design current (Ib) x circuit length (L) x volt dropper unit (mv/A/m)

  • 7/28/2019 Cable & Wiring Presentation

    27/71

    Example

    A PVC/SWA/PVC armoured cable is to be installed from anHRC 100A fuse in a distribution board to a 3-phase 380Vmotor, along with 5 other cables fixed to a perforatedmetal cable tray where the cable sheaths will be touching,

    if the cable length is 100 meters and the power factor ofthe load is 0.866, what size of cable would be required tosatisfy voltage drop if the ambient temperature is 30oCand the voltage drop in the 3 phase feeder cable up to thedistribution board is 7.7V and the total voltage drop

    allowed is 4%?

  • 7/28/2019 Cable & Wiring Presentation

    28/71

    Sizing Circuit Protective Conductors

    If the conductor 35mm2 : Zs = Ze + R1 + R2>35mm2 : Zs = Ze + Z1 + Z2

    Use the formula : S {(I2t)} / K Value of K : from IEE Tables 54B to 54F

    If= Uo / Zs Value of t from IEE Fig. 1 to 8 of Appendix 3

    Use Table 54G to size the minimum size of protectiveconductors.

  • 7/28/2019 Cable & Wiring Presentation

    29/71

    Thermal Constraint

    To protect conductor insulation against thermal damageduring short circuit conditions.

    I2 t = K2 S2

    t = K2 S2/ I2

    t = duration in second

    S = cross-sectional area in mm2

    I = effective short-circuit current in A

    K = 115 for copper conductor insulated with PVC

  • 7/28/2019 Cable & Wiring Presentation

    30/71

    Thermal Constraint

    Procedure To check the prospective short-circuit current at the

    farthest point of the circuit from the point where thedevice is installed

    To check the operation time of the device according to theshort-circuit current from the time/ current characteristicof the device

    To check the adiabatic line of the conductor by

    superimposing onto the characteristics of protectivedevices.

  • 7/28/2019 Cable & Wiring Presentation

    31/71

    Cable Selection Procedure

    Select wiring system to be installed and type of cable Calculate the equipment current demand using Table 4A

    (15 Edition)

    Calculate the circuit design current (Ib) and using diversity

    allowance. Determine the overcueent protective device (In) : type;

    rating

    Check Ib In

    Determine correction factors for installation Grouping (Cg)

    Ambient temperature (Ca)

    Thermal insulation (Ci)

    Semi-enclosed fuse (C4)

  • 7/28/2019 Cable & Wiring Presentation

    32/71

    Cable Selection Procedure

    Calculate the tabulated current carrying capacity ofconductor:

    It (min) In x (1/ Cg) x (1/ Ca) x (1/ Ci) x (1/ C4)

    Select cable size from Appendix 4

    Check Ib In Iz

    Calculate volt drop at the farthest point of circuit

  • 7/28/2019 Cable & Wiring Presentation

    33/71

    Cable Selection Procedure

    Dose device offer shock protection in accordance withtable 41B1, 41B2 & 41D for Zs (max)?

    Check Zs Zs (max) from the tables

    If No :

    Re-select device or re-select phase conductor size

    Re-select cpc size

    Use alternative method as stated in Reg. 413-02-12

    Checked by calculation

    Obtain Ze form supply authority Calculate R1 + R2 using Table 17A & B

    Determine actual Zs = Ze + (R1 + R2)

  • 7/28/2019 Cable & Wiring Presentation

    34/71

    Cable Selection Procedure

    Dose the type and size of cpc offer protection?Check : S {(I2t)} / K

    If No : re-select type and/ or size of cpc

    Check the adiabatic line of conductor against the

    characteristic of overcurrent protective device.

  • 7/28/2019 Cable & Wiring Presentation

    35/71

    B1) Type of Conduit

    B2) Sizing of Conduit

    B3) Type of TrunkingB4) Sizing of Trunking

    B5) Ducting

    B6) Segregation of Circuit

    B) Conduit & Trunking

  • 7/28/2019 Cable & Wiring Presentation

    36/71

    Steel Conduit to BS 4568 : Part 1

    A) Light duty type: plain and conduits Limited to use in dry situation;

    Unsuitable for bending Low degree of mechanical protection

    B) Heavy duty type: screwed-end conduits Back enamel for internal use in dry situation;

    Hot-dip galvanized for external use in situationsubject to dampness or water condensation;

    Good mechanical strength and electrical continuity.

    B1) Type of Conduit

  • 7/28/2019 Cable & Wiring Presentation

    37/71

    B1) Type of Conduit

    Steel Conduit to BS 4568 : Part 1

    C) Classification for protection:

    Class Protection Applied Example

    1 Light protection both inside & outside Priming paint

    2 Medium protection both inside &outside

    Stoved enamel;

    Air-drying paint

    3 Medium heavy protection : inside asClass 2;

    Outside as Class 4

    Stoved enamel inside;Sherardized outside

    4 Heavy protection both inside &outside

    Hot-dip zinc coating,sherardizing

  • 7/28/2019 Cable & Wiring Presentation

    38/71

    Steel Conduit to BS 4568 : Part 1

    D) Heavy duty hot-dip galvanized steelconduit system is the most common usesystem for surface conduit wiring andconcealed conduit wiring. Conduit issupplied in standard lengths of 4 meters

    and is manufactured in accordance withBS4568.

    B1) Type of Conduit

  • 7/28/2019 Cable & Wiring Presentation

    39/71

    Plastic conduits

    To BS4607 Part 1 and 2;

    Characteristics : light, easily bend, lessinstallation time, no water condensation,lower cost;

    Heavy duty PVC conduits can beconcealed but CPC are required.

    B1) Type of Conduit

  • 7/28/2019 Cable & Wiring Presentation

    40/71

    Copper Conduits

    High resistance to corrosion;

    Last for long time; Higher cost;

    Act as excellent circuit protective

    conductor (CPC)

    B1) Type of Conduit

  • 7/28/2019 Cable & Wiring Presentation

    41/71

    Aluminum Conduits

    Light weight and lower cost;

    Not so good in mechanical protection

    Flexible Conduits

    To BS731 : Part 1

    Used for final connection to machinery;

    CPC are required.

    B1) Type of Conduit

  • 7/28/2019 Cable & Wiring Presentation

    42/71

    B2) Sizing of Conduit

    IEE Regulation (15th Edition) provide thefollowing tables for ease of conduit sizing:

    Table A, B for 1/C PVC cables in a straight run 3m;

    Table C, D for 1/C PVC cable in conduit run > 3m. The conduit size is considered satisfactory if the

    conduit factor is equal to or exceeds the sum ofthe cable factors

  • 7/28/2019 Cable & Wiring Presentation

    43/71

    B2) Sizing of Conduit

    Type of Conductor C.S.A. of Conductor (mm2) Factor

    Solid 1

    1.5

    2.5

    22

    27

    39

    Stranded 1.5

    2.5

    4

    6

    10

    31

    43

    58

    68

    146

    Table A Cable factors for short straight runs

  • 7/28/2019 Cable & Wiring Presentation

    44/71

    B2) Sizing of Conduit

    Conduit Diameter (mm) Factor

    16 290

    20 460

    25 800

    32 1400

    Table B Conduit factors for short straight runs

    ) S f C

  • 7/28/2019 Cable & Wiring Presentation

    45/71

    B2) Sizing of Conduit

    Type of Conductor C.S.A. of Conductor(mm2)

    Factor

    Solid or Stranded 1 16

    1.5 22

    2.5 304 41

    6 58

    10 105

    Table C Cable factors for long straight runs, or runs incorporating bends

    B2) Si i f C d i

  • 7/28/2019 Cable & Wiring Presentation

    46/71

    B2) Sizing of Conduit

    Table D Conduit factors for runs incorporating bends

    Refer to

    Table A and B

    B2)Si i f C d it

  • 7/28/2019 Cable & Wiring Presentation

    47/71

    B2) Sizing of Conduit

    Example

    In a conduit installation the length of run is 10m,assuming 2 right-angle bend. What is the

    conduit size to enclose four 2.5 mm2 PVC cables? From Table C, factor for one 2.5mm2 cable = 30

    Therefore, four 2.5mm2 cables = 4 x 30 = 120

    From Table D, suitable conduit size with a factor of

    141(>120) is 20mm.[10m Vs 2 bends, cable factor : 141]

  • 7/28/2019 Cable & Wiring Presentation

    48/71

    B3) Type of Trunking

    Use in conditions where a considerable no. ofcables are required in an installation or wherecables are too large for drawing into conduits.

    Erection time is reduced (wiring is easier andquicker)

    Multi-compartment trunking provides circuitsegregation.

  • 7/28/2019 Cable & Wiring Presentation

    49/71

  • 7/28/2019 Cable & Wiring Presentation

    50/71

    B3) Type of Trunking

    Classification for protection against corrosion:

    Class 1 Electroplated zinc having a minimum thicknessof zinc coating of 0.0012mm, inside and outside.

    Class 2 As Class 1 but additional coating of stoved or airdrying paint, applied at least to the externalsurface.

    Class 3 Hot dip zinc coated steel.

  • 7/28/2019 Cable & Wiring Presentation

    51/71

    B4) Sizing of Trunking

    Type of Conductor C.S.A of Conductor (mm2) Factor

    Solid 1.5

    2.5

    7.1

    10.2

    Stranded 1.5

    2.5

    4

    6

    10

    8.1

    11.4

    15.2

    22.9

    36.3

    Table E Cable factors for trunking

  • 7/28/2019 Cable & Wiring Presentation

    52/71

    B4) Sizing of Trunking

    Dimension of Trunking (mm x mm) Factor

    50 x 37.5 767

    50 x 50 1037

    75 x 25 738

    75 x 37.5 1145

    75 x 50 1555

    75 x 75 2371

    100 x 25 993

    100 x 37.5 1542100 x 50 2091

    100 x 75 3189

    100 x 100 4252

    Table F Factors for trunking

  • 7/28/2019 Cable & Wiring Presentation

    53/71

    B4) Sizing of Trunking

    Example

    What is the maximum no. of 10mm2 PVC cablespermitted in 50mm x 50mm trunking?

    From Table E, factor of 10mm2 conductor = 36.3 From Table F, factor of 50 x 50mm trunking = 1037

    Maximum no. of cable= 1037 36.3

    = 28.56 (say 28)

  • 7/28/2019 Cable & Wiring Presentation

    54/71

    B5) Ducting

    It provided mechanical protection for cable runin the ground or under concreted floor.

    Types of ducting:

    Concrete ducts Steel underfloor ducts

    Fibre underfloor ducts

    Maximum spacing factor is 35%.

    It should be securely fixed and protected againstcorrosion and mechanical damage.

  • 7/28/2019 Cable & Wiring Presentation

    55/71

    B5) Ducting

    Entries to duct must be protected against theinflow of water.

    Cables installed in underground ducts shall havea metal sheath.

    Underfloor trunking should be fabricated withsheet steel of not less than 12mm thickness forcompartment width up to 100mm, but at least1.6mm thickness for compartment width over100mm. The minimum thickness of 1mm shallbe used for the partitions and connectormaterial.

  • 7/28/2019 Cable & Wiring Presentation

    56/71

    B6) Segregation of Circuits

    1) Suitable segregation between enclosed circuits with differentcategories shall be provided in wiring. For example, a low voltagecircuit shall be separated from an extra-low voltage circuit.

    2) Types of Circuit:

    Category 1 Circuit A circuit (other than a fire alarm or emergencylighting circuit) operation at low voltage andsupplied directly from a main supply system

    Category 2 Circuit With the exception of firm alarm and emergencylighting circuits, ant circuit for telecommunication

    (e.g. radio, telephone) which is supplied form asafety source.

    Category 3 Circuit A fire alarm circuit or an emergency lightingcircuit.

    Category 4 Circuit A high voltage circuit.

  • 7/28/2019 Cable & Wiring Presentation

    57/71

    B6) Segregation of Circuits

    3) Low Voltage circuit shall be segregated form extra-low voltagecircuit. Extra-low voltage cables shall not be drawn into the sameconduit or duct, or terminated in the same box or block as lowvoltage cables unless the former are insulated for the highestvoltage present in the low voltage circuit.

    4) Cables of fire alarm and emergency lighting circuits shall not inany circumstances be drawn into the same conduit duct or ductingof other cables.

  • 7/28/2019 Cable & Wiring Presentation

    58/71

    B6) Segregation of Circuits

    5) Electrical services shall not be installed with pipes or tubes ofnon-electrical services (e.g. air, gas, oil, or water) in the sameconduit, ducting or trunking. This requirement does not apply wherethe various services are under common supervision and it isconfirmed that no mutual detrimental influence can occur.

    6) For cables of category 1,2,3 circuits that are installed withoutenclosure or underground, a minimum separation of 50mm shouldbe provided between different category circuits or alternatively atleast 25mm separation with slabs of concrete inserted between the

    circuits and the shortest path round the concrete should exceed75mm.

  • 7/28/2019 Cable & Wiring Presentation

    59/71

    B6) Segregation of Circuits

    7) Insulated bridge of at least 6mm thick should be used forseparation of surface wiring of Category 1,2,3 circuit running acrosseach other. The bridge should overlap the cables by at least 25mmon either side of point of crossing.

    8) For cables of Category 4 circuit that are installed withoutenclosure or underground, a minimum separation of 300mm shouldbe provided between Categories or alternatively a reducedseparation with 50mm thick slabs of concrete inserted between thecircuits and the shortest path round the concrete should exceed

    180mm.

  • 7/28/2019 Cable & Wiring Presentation

    60/71

    Example

    Descriptions:

    A flat of about 90m2 (useable area), with three bedrooms, (the masterbedroom with en-suite bathroom), a guest bathroom, a kitchen, adining room, lounge (living room) and a store room.

    An air-conditioner (2 h.p., i.e. >=15A input current) is

    expected to be in the dining room, and it also for the lounge.

    An electric cooker of about 14A rating is expected to be installed in thekitchen.

    Hot water is provided by gas heaters in bathrooms and the kitchen Battery operated door bell and clocks are expected.

  • 7/28/2019 Cable & Wiring Presentation

    61/71

    Example

  • 7/28/2019 Cable & Wiring Presentation

    62/71

    Example

  • 7/28/2019 Cable & Wiring Presentation

    63/71

    Example

    To provision here is more than that of theminimum recommended requirements in the CPfor WR.

    No socket outlet is provided in the bathrooms,and the switches for lighting and the ventilationfan should be installed outside the bathrooms.

  • 7/28/2019 Cable & Wiring Presentation

    64/71

    Example

  • 7/28/2019 Cable & Wiring Presentation

    65/71

    Example

  • 7/28/2019 Cable & Wiring Presentation

    66/71

    Typical Earthing Systems - 1

    TT system A system having one point of the source of energy

    directly earthed, the exposed-conductive parts of theinstallation being connected to earth electrodes

    electrically independent of the earth electrodes of thesource.

  • 7/28/2019 Cable & Wiring Presentation

    67/71

    Typical Earthing Systems - 2

    TN-S system

    A system having one point of the source of energy directlyearthed and having separate neutral and protective conductorsthroughout the system.

  • 7/28/2019 Cable & Wiring Presentation

    68/71

    Typical Earthing Systems - 3

    TNC-S system

    A system having one point of the source of energy directlyearthed, the neutral and protective functions are combined in asingle conductor in part of the system.

  • 7/28/2019 Cable & Wiring Presentation

    69/71

    Type of Earth Electrode

    The following Earth Electrode

    Deep driven earth rods and/ or parallel driven earthrods

    Buried tapes/ plated Welded metal reinforcement of concrete

  • 7/28/2019 Cable & Wiring Presentation

    70/71

    Q & A

  • 7/28/2019 Cable & Wiring Presentation

    71/71

    The End