bottom chord bracing and ul requirements – fact and fiction

12
Bottom chord bracing and UL requirements Fact and FictionA popular sales tactic of many cold formed metal truss fabricators has been to claim that their truss system is less expensive because it does not require bottom chord bracing. This claim can be dispelled by referencing CFSEI Tech Note 551d which states that all trusses must have bottom chord bracing at 10oc maximum. Another claim made by some fabricators, one that is more difficult to dispel, is the idea that the bottom chord purlins that are typically fastened to the bottom of the bottom chord for drywall attachment can also act as the bottom chord bracing of the truss itself and no additional bracing material is required. On a 50,000 ft2 school in a low wind zone, this could amount nearly 500 pieces of hat channel and cause a difference in price of $3,500 in material alone. When communicating with your prospective truss fabricators understanding the code and the related UL listings becomes critical. A 1 hour rated ceiling can be used to eliminate the requirement of a fire sprinkler or will allow the fire sprinkler to provide a significant area increase, depending on the type of construction. In other words, for construction of types I-a, I-b, II-a or III-a a 1 hour (min) rated ceiling is a must. It is usually a safe assumption that most projects requiring cold formed steel trusses due to the non- combustibility are also projects that will require at least a 1 hour rated ceiling. A simple check to confirm this is by verifying the occupancy category calculations almost always given in the architectural drawings. Once you have verified the need for the rated ceiling assembly, you are able to consult with your fabricator based on accurate information. These two generic assemblies show the main elements of flat and sloped cold- formed steel truss assemblies Truss Notes Issue 1 10/20/2014

Upload: pete-wynnik

Post on 05-Apr-2016

221 views

Category:

Documents


0 download

DESCRIPTION

Understanding Fire Rated Cold Formed Steel Truss Assemblies

TRANSCRIPT

Page 1: Bottom chord bracing and ul requirements – fact and fiction

Bottom chord bracing and UL requirements – Fact and Fiction… A popular sales tactic of many cold formed metal truss fabricators has been to claim that their truss system is less expensive because it does not require bottom chord bracing. This claim can be dispelled by referencing CFSEI Tech Note 551d which states that all trusses must have bottom chord bracing at 10’ oc maximum. Another claim made by some fabricators, one that is more difficult to dispel, is the idea that the bottom chord purlins that are typically fastened to the bottom of the bottom chord for drywall attachment can also act as the bottom chord bracing of the truss itself and no additional bracing material is required. On a 50,000 ft2 school in a low wind zone, this could amount nearly 500 pieces of hat channel and cause a difference in price of $3,500 in material alone. When communicating with your prospective truss fabricators understanding the code and the related UL listings becomes critical. A 1 hour rated ceiling can be used to eliminate the requirement of a fire sprinkler or will allow the fire sprinkler to provide a significant area increase, depending on the type of construction. In other words, for construction of types I-a, I-b, II-a or III-a a 1 hour (min) rated ceiling is a must. It is usually a safe assumption that most projects requiring cold formed steel trusses due to the non-combustibility are also projects that will require at least a 1 hour rated ceiling. A simple check to confirm this is by verifying the occupancy category calculations almost always given in the architectural drawings. Once you have verified the need for the rated ceiling assembly, you are able to consult with your fabricator based on accurate information.

These two generic assemblies show the main elements of flat and sloped

cold- formed steel truss assemblies

Truss Notes Issue 1

10/20/2014

Page 2: Bottom chord bracing and ul requirements – fact and fiction

Fire Rated Cold-Formed Steel Truss Assemblies

To properly design a building for fire safety, building designers must recognize and accurately follow building fire code regulations. Building codes may require construction assemblies to have a fire resistance rating such as 1 Hour, 1-½ Hour and 2 Hour in specific construction types and occupancies. The ratings represent the minimum length of time that a laboratory tested assembly maintained its structural integrity during standardized ASTM E119 fire conditions. At this point in time, Underwriters Laboratories Inc. (UL), is the only directory that lists cold-formed steel truss assemblies. The most current listings are available in UL Online Certification Directory at www.ul.com.

Typically in fire endurance assembly testing, a system is tested and then put to use in the field. The field applications must be identical to the tested assembly. Increases in the length, depth, and size of the actual structural members are allowed because they will perform better than the tested structural members. The single- most critical element in the fire endurance performance of an assembly is the protective membrane on the side of the assembly exposed to fire, which is typically fire rated gypsum board.

Restrained vs. Unrestrained Fire Rated Steel Truss Assemblies

Steel assemblies may be rated as restrained or unrestrained. These are two different test procedures to mimic two types of installations. ANSI/UL 263 defines these conditions: “Floor-ceiling and roof-ceiling assemblies and individual beams in buildings shall be considered restrained when the surrounding or supporting structure is capable of resisting substantial thermal expansion throughout the range of anticipated elevated temperatures. Constructions not complying with this definition are assumed to be free to rotate and expand and shall be therefore considered as unrestrained.” ASTM E119 Table 3.1 lists restrained and unrestrained construction systems. Note that restraint in fire testing is not the same as restraint in structural design.

Because of the more restrictive criteria, unrestrained assembly ratings may be used for floors and roofs designed for either restrained or unrestrained conditions. The decision on whether to use a restrained or unrestrained steel truss assembly will depend on what the building designer and building code requires. Only the UL “Lxxx” assemblies do not list both a restrained and unrestrained rating.

Summaries The following tables are summaries to aid in steel truss assembly selection. Always consult the full current listings for complete assembly information.

Page 3: Bottom chord bracing and ul requirements – fact and fiction

Rating Illustration Construction UL Report Number

FLOOR

1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional 1x4 T&G, 15/32” panel, or 3/4” topping on 23/32”

subfloor; or mineral or fiber board on subfloor

L549, L551, L552, L553, L559, L560 L565

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional Metal lath, welded wire fabric, and normal or

lightweight concrete

G540, G542, G543, G544, G545, G546

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type C gypsum Resilient channel 16” oc Ceiling insulation not allowed Metal lath, welded wire fabric, and normal or

lightweight concrete

G540

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc Ceiling insulation not allowed Metal lath, welded wire fabric, and normal or

lightweight concrete

G545

ROOF

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing Min. depth 11-7/8” or 5” with a min. 3/12 slope 2 layers 5/8” Type X gypsum (Type C, if insul.

within 1” of gyp.) Resilient channel 24” oc, not req. for trusses

spaced max. 24” oc Ceiling insulation optional. Roof insulation

required Roof covering, roof membrane or metal roof deck

panel; steel roof deck; gypsum board

P515, P541

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing Min. depth 11-7/8” or 8” with a min. 3/12 slope 2 layers 5/8” Type X gypsum Resilient channel 24” oc, not req. for trusses

spaced max. 24” oc Ceiling insulation required. Roof insulation not

allowed Roof covering, roof membrane or metal roof deck

panel; steel roof deck; gypsum board

P524

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc, 12” oc with insulation Ceiling insulation optional. Roof insulatin may be

required UL Class A, B, C roofing system or prepared roof

covering on 23/32” panel; steel roof deck, or for P523, P534, P537 only, steel floor and form units. P526, P528 and P530 allow 15/32” panel with trusses 24” oc and min. 9-½” ceiling insulation

P523, P526, P528, P530, P534, P537

Page 4: Bottom chord bracing and ul requirements – fact and fiction

Rating Illustration Construction UL Report Number

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type X gypsum Resilient channel 12” oc Minimum 9-½” ceiling insulation. Roof insulation

may be required UL Class A, B, C roofing system or prepared roof

covering on 23/32” panel; steel roof deck, or for P523, P534, P537 only, steel floor and form units. P526 allows 15/32” panel with trusses 24” oc

P523, P526, P534, P537

1 Hr Unrestrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation. Roof insulation required, no

minimum thickness Steel roof deck; cementitious backer or gypsum

board; roof covering, membrane or metal deck panel

P527, P529

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, Minimum 2” roof insulation Steel roof deck; cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P527, P529

1 Hr Restrained 1 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, Roof insulation minimum

thickness may be required Steel floor and form units, min. gauge varies;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P532, P536, P540

1-1/2 Hr Restrained 1-1/2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P532, P536

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 1 layer 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P532

2 Hr Restrained 2 Hr Unrestrained

Max. 48” oc truss spacing 2 layers 5/8” Type C gypsum Resilient channel 16” oc No ceiling insulation, min. thickness roof

insulation required Steel floor and form units, min. 22 gauge;

cementitious backer or gypsum board; roof covering, membrane or metal roof deck panel

P521, P525, P536

The following is a commonly used UL rated assembly.

Page 5: Bottom chord bracing and ul requirements – fact and fiction

Fire Resistance Ratings - ANSI/UL 263 Design No. P521

September 27, 2002

Restrained Assembly Rating — 1, 1-1/2 and 2 Hr. (See Items 3A, 5, 5A, 5B and 8)

Unrestrained Assembly Rating — 1, 1-1/2 and 2 Hr. (See Items 3A, 5, 5A, 5B and 8)

Page 6: Bottom chord bracing and ul requirements – fact and fiction

1. Structural Steel Members* — Pre-fabricated light gauge steel truss system consisting of cold-formed, galvanized steel chord and web sections. Trusses fabricated in various sizes, depths, and from various steel thickness. Trusses spaced a max of 48 in. OC.

AEGIS METAL FRAMING LLC — Ultra-Span, Pre-fabricated Light Gauge Steel Truss System

2. Bridging — (Not Shown) — Location of lateral bracing for truss chord and web sections to be specified on truss engineering.

3. Steel Floor and Form Units — (Classified or Unclassified) — Corrugated or fluted steel form units, min 22 MSG painted or galv steel, welded or mechanically fastened max 12 in. OC to truss-top chords.

3A. Steel Floor and Form Units* — As an alternate to Item 3 - min 25 MSG, 15/16 in. deep, painted or galv units welded or mechanically fastened max 12 in. OC to the top chord of trusses. When used, max hourly rating is reduced to 1 hr.

LOADMASTER SYSTEMS INC — Types HD, ED or PS.

4. Cementitious Backer Units* — Nom 1/2 or 5/8 in. thick sheets. End-joists to occur over crests of steel roof deck with end-joints staggered in adjacent rows. Units loosely laid, adhered or mechanically attached to steel roof deck.

UNITED STATES GYPSUM CO — Durock Exterior Cement Board or Durock Cement Board.

4A. Gypsum Board — (Classified or Unclassified) — (Not Shown) — As an alternate to Item 4, Gypsum sheathing, min 1/2 in. thick, applied perpendicular to steel roof deck. End joints to occur over crests of steel roof deck. Sheathing loosely laid, adhered or mechanically attached to steel roof deck. See Gypsum Board (CKNX) category for names of classified companies.

5. Roof Insulation — Foamed Plastic* — Any polyisocyanurate foamed plastic insulation boards bearing the UL Classification Marking. Min thickness is 1 in. for the 1 hr assembly ratings, 2 in. for the 1-1/2 hr assembly ratings and 4 in. for the 2 hr ratings, with no limit on max overall thickness. Boards installed over the cementitious backer units (Item 4) or gypsum sheathing (Item 4A), with the end-joints staggered in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below in order to lap all joints. Boards loosely laid, adhered or mechanically fastened to cementitious backer units or gypsum sheathing, and to steel roof deck (Item 3). See Foamed Plastic (CCVW) Category in the Fire Resistance Directory.

5A. Roof Insulation — Foamed Plastic* — (Not Shown) — As an alternate to Item 5 — For 1 and 1-1/2 hr ratings only — Any polystyrene foamed plastic insulation boards bearing the UL Classification Marking. Min thickness is 1 in. for

Page 7: Bottom chord bracing and ul requirements – fact and fiction

the 1 hr assembly ratings, and 2 in. for the 1-1/2 hr assembly ratings, with no limit on max overall thickness. Boards installed over the cementitious backer units (Item 4) or gypsum sheathing (Item 4A), with the end-joints staggered in adjacent rows. When applied in more than one layer, each layer or board to be offset in both directions from layer below in order to lap all joints. Boards loosely laid, adhered or mechanically fastened to cementitious backer units or gypsum sheathing, and to steel roof deck (Item 3). See Foamed Plastic (BRYX) category in the Building Materials Directory or Foamed Plastic (CCVW) category in the Fire Resistance Directory.

5B. Roof Insulation — Mineral and Fiber Boards* — (Not Shown) — As an alternate to Item 5 — Mineral wool, glass fiber or perlite insulation boards, 24 by 48 in. min size, applied in one or more layers. Min thickness is 1 in. for the 1 hr assembly ratings, 2 in. for the 1-1/2 hr assembly rating and 4 in. for the 2 hr ratings, with no limit on max overall thickness. Boards installed over the cementitious backer units (Item 4) or gypsum sheathing (Item 4A), with the end-joints staggered in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below in order to lap all joints. Boards loosely laid, adhered or mechanically fastened to cementitious backer units or gypsum sheathing, and to steel roof deck (Item 3).

See Mineral and Fiber Boards (BQXR) Category in the Building Materials Directory or Mineral and Fiber Boards (CERZ) Category in the Fire Resistance Directory.

5C. Roof Insulation —Building Units* (Not Shown) — As an alternate to Item 5—Any polyisocyanurate foamed plastic insulation faced on the top surface with oriented strand board or faced on the underside or both sides with wood fiber board, bearing the UL Classification Marking for Fire Resistance. No min thickness of the polyisocyanurate foamed plastic core required for the 1 hr assembly ratings, min 2 in. polyisocyanurate foamed plastic core for the 1-1/2 hr assembly ratings and min 4 in. polyisocyanurate foamed plastic core for the 2 hr rating with no limit on max overall thickness. Boards installed over the cementitious backer units (Item 4) or gypsum sheathing (Item 4A), with the end-joints staggered in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below in order to lap all joints. Boards loosely laid, adhered or mechanically fastened to cementitious backer units or gypsum sheathing and to steel roof deck (Item 3). See Building Units (BZXX) category in the Fire Resistance Directory.

6. Roof Covering* — Consisting of hot-mopped or cold-application materials compatible with insulation(s) described herein which provide Class A, B or C coverings. See Roofing Materials and Systems Directory-Roof Covering Materials (TEVT).

6A. Roofing Membrane* — (Not Shown) — In lieu of Item 6, single-ply membrane that is either ballasted, adhered or mechanically attached to the insulation(s) described herein as permitted under the respective company's Classification. See Fire Resistance Directory-Roofing Membranes (CHCI) Category.

6B. Metal Roof Deck Panels* — In Lieu of or in addition to Items 6 and 6A, the roof covering may consist of mechanically fastened galv or painted steel roof deck panels. Panels may be installed above a steel purlin assembly per metal

Page 8: Bottom chord bracing and ul requirements – fact and fiction

roof deck manufacturer's specifications. Steel purlin assembly to be installed transverse to steel roof trusses (Item 1). A line of sealant or tape may be used at panel side and end laps. See Metal Roof Deck Panels Category in the Roofing Materials and Systems Directory (TJPV) or Fire Resistance Directory (CETW) for names of manufacturers.

6C. Roof Covering* — In Lieu of Item 6 —Any UL Class A, B or C Prepared Roof Covering (TFWZ) acceptable for use over plywood sheathing or nonveneer APA Rated Series Sheathing. Sheathing mechanically fastened through roof insulation to top chord of steel trusses with fasteners spaced a max of 12 in. OC. As an alternate to the plywood sheathing or nonveneer APA Rated Series Sheathing, the Prepared Roof Covering (TFWZ) may be applied directly to the Building Units* (Item 5C) if the building units also carry the UL Classification Marking for Prepared Roofing Accessories (TGDY).

7. Furring Channels — Resilient channels formed of 25 MSG galv steel, installed perpendicular to the trusses (Item 1), spaced a max of 16 in. OC. Channels oriented opposite at wallboard butt-joints. Channel spices overlapped 4 in. beneath steel trusses. Channels secured to each truss with Type S-12 by 1/2 in. long screws.

7A. Furring Channels — (Not Shown) — As an alternate to Item 7 — Hat channels min 20 MSG galv steel, min 2-5/8 in. wide by min 7/8 in. deep, installed perpendicular to the trusses (Item 1) spaced a max of 16 in. OC. Two courses of channel positioned 6 in. OC, 3 in. from each end of wallboard. Channel splices overlapped 6 in. beneath steel trusses. Channels secured to each truss with No. 18 SWG steel wire double strand saddle ties. Channels tied together with double strand of No.18 SWG steel wire at each end overlap.

7B. Furring Channels — As an alternate to Items 7 and 7A, resilient channels, double legged formed of 25 MSG galv steel, 2-7/8 in. wide by 1/2 in. deep, spaced max 16 in. OC, perpendicular to steel trusses. Two courses of resilient channel positioned 6 in. OC at wallboard butt-joints (3 in. from each end of wallboard). Channel splices overlapped 4 in. beneath steel trusses. Channels secured to each truss with Type S12 by 1/2 in. long screws or with No. 18 SWG galv steel wire double strand saddle ties. Channels tied together with double strand of No. 18 SWG galv steel wire at each end of overlap.

8. Gypsum Board* — For all ratings except the 2 Hr Assembly Ratings — One layer of nom 5/8 in. thick by 48 in. wide boards, installed with long dimension parallel to trusses. Attached to the resilient channels using 1 in. long Type S bugle-head screws spaced 12 in. OC along butted end-joints and 12 in. OC in the field. For the 2 Hr Ratings — Two layers of nom 5/8 in. thick by 48 in. wide boards, installed with long dimension parallel to trusses. Base layer attached as described above. Face layer attached to the resilient channels using 1-5/8 in. long Type S bugle-head screws spaced 12 in. OC along butted end-joints and 12 in. OC in the field. Screws staggered from base layer screws. Face layer side and end joints offset a minimum 16 in. from base layer side and end joints.

CANADIAN GYPSUM COMPANY — Types C, IP-X2, IPC-AR. UNITED STATES GYPSUM CO — Types C, IP-X2, IPC-AR. USG MEXICO S A DE C V — Types C, IP-X2, IPC-AR.

Page 9: Bottom chord bracing and ul requirements – fact and fiction

9. Finishing System — (Not Shown) — Vinyl, dry of premixed joint compound, applied in two coats to joints and screw heads, paper tape, 2 in. wide, embedded in first layer of compound over all joints.

Alternate Ceiling Membrane — Not shown.

10. Steel Framing Members —

a. Main runners — Installed perpendicular to Structural Steel Members, - Nom 12 ft long, 15/16 in. or 1-1/2 in. wide face, spaced 4 ft OC. Main runners hung a min of 2 in. from bottom chord of Structural Steel Members with 12 SWG galv steel wire. Wires located a max of 48 in. OC.

b. Cross tees or channels — Nom 4 ft long, 15/16 in. or 1-1/2 in. wide face or cross channels, nom 4 ft long, 1-1/2 in. wide face, installed perpendicular to the main runners, spaced 16 in. OC. Additional cross tees or channels used at 8 in. from each side of butted wallboard end joints. The cross tees or channels may be riveted or screw-attached to the wall angle or channel to facilitate the ceiling installation.

c. Wall angles or channels — Used to support steel framing member ends and for screw-attachment of the gypsum wallboard - Painted or galvanized steel angles with 1 in. legs or channels with 1 in. legs and 1-9/16 in. deep, attached to walls at perimeter of ceiling with fasteners 16 in. OC.

11. Gypsum Board* — For use with Steel Framing Members (Item 10) - For the 1 and 1-1/2 hr ratings - One layer of nom 5/8 in. thick by 48 in. wide boards, installed with long dimension parallel to the main runners. Wallboard fastened to each cross tee or channel with five wallboard screws, with one screw located at the midspan of the cross tee or channel, one screw located 12 in. from and on each side of the cross tee or channel mid span and one screw located 1-1/2 in. from each wallboard side joint. Except at wallboard end joints, wallboard screws shall be located on alternating sides of cross tee flange. At wallboard end joints, wallboard screws shall be located 1/2 in. from the joint. Wallboard fastened to main runners with wallboard screws 1/2 in. from side joints, midway between intersections with cross tees or channels (16 in. OC). End joints of adjacent wallboard sheets shall be staggered not less than 32 in. Wallboard sheets screw attached to leg of wall angle with wallboard screws spaced 12 in. OC. Joints treated as described in Item 8. For the 2 hr rating - Two layers of nominal 5/8 in. thick by 48 in. wide boards. Inner layer installed with long dimension perpendicular to cross tees with side joints centered along main runners and end joints centered along cross tees. Inner layer fastened to cross tees with 1-1/4 in. long Type S bugle-head steel screws spaced 8 in. OC along butted end joints and 12 in. OC in the field of the board. End joints of adjacent wallboard sheets shall be staggered not less than 4 ft OC. Outer layer attached to the cross tees through inner layer using 1-7/8 in. long Type S bugle-head steel screws spaced 8 in. OC at butted end joints and 12 in. OC in the field. Butted end joints to be centered along cross tees and be offset a min of 32 in. from end joints of inner layer. Rows of screws on both sides of butted end joints of each layer shall be

Page 10: Bottom chord bracing and ul requirements – fact and fiction

located 3/8 to 1/2 in. from end joints. Butted side joints of outer layer to be offset a min of 18 in. from butted side joints of inner layer. Joints treated as described in Item 8.

CANADIAN GYPSUM COMPANY — Type C or IP-X2 UNITED STATES GYPSUM CO — Type C or IP-X2 USG MEXICO S A DE C V — Type C or IP-X2

*Bearing the UL Classification Mark

Page 11: Bottom chord bracing and ul requirements – fact and fiction

Cold-formed Steel Truss Assemblies by CF Steel, LLC Floor-Ceiling: G540, L549, L565 Roof-Ceiling: P521, P523, P540

Product Substitutions Where branded products are specified in assemblies, product substitutions are not allowed. Where generic product categories are listed, substitutions of products within the category with equal or greater specifications may be allowed.

Gypsum Board Specifications “Regular” gypsum board has a naturally occurring fire resistance from the gypsum used as its core. “Type X” gypsum board has additives to the core that increase the fire resistance of regular gypsum board. “Improved Type X” (often referred to as “Type C”) has been improved with additives which further enhance the fire resistive characteristics. “Improved Type X” can be substituted for “Type X”, but not the reverse. Gypsum may be listed as generic or as proprietary.

Type X: FSW= NGC Fire-Shield SCX= USG FIRECODE Core IP-X1= USG Plaster Base (Type X)

Improved Type X (Type C or G): FSW-C= NGC FireShield C FSW-G = NGC FireShield G C= USG FIRECODE C Core IP-X2= USG Plaster Base (Type C) IPC-AR = USG Plaster Base C (Abuse Resistant)

Category (CKNX), per UL/ANSI 263, section 9. Gypsum Board: “For designs containing the statement ‘See Gypsum Board (CKNX) Category for names of Classified Companies,’ any product in the Category (CKNX) that meets the specifications (i.e. thickness, size, etc.) described in the design may be used.”

References Fire Resistance Directory, Underwriters Laboratories Inc., Northbrook, IL. www.ul.com. ASTM E119-98. “Standard Test Methods for Fire Tests of Building Construction and Materials”, American Society for

Testing and Materials (ASTM), West Conshohocken, PA. 1998. www.astm.org. SA100 Construction Selector (rev.3-02). United States Gypsum Company, Chicago, IL. www.usg.com. Gypsum Construction Guide, 7th Edition (rev. 8/2001). National Gypsum Company, Charlotte, NC. www.nationalgypsum.com

Tim Liescheidt, P.E. Mobile: (704) 516-1750

[email protected]

Pete Wynnik / Technical Services Mobile: (501) 413-6154

[email protected]

Page 12: Bottom chord bracing and ul requirements – fact and fiction

At CF-Steel, we offer personalized service. While we welcome phone calls and faxes regarding bids, we are making continual efforts to streamline our bid process and provide convenience to our customers. Please feel free to submit bid submissions by email to [email protected] or contact one of our representatives below: Tim Liescheidt / Managing Partner Chrissy Liescheidt / Director of Sales [email protected] [email protected] Mobile: (704) 516-1750 Direct: (704) 737-8023 Scott Dickson / Sales Representative Adrian Kennedy / Sales Representative Mobile: (704) 340-7724 Mobile: (704) 322-9270 [email protected] [email protected]

Headquarters &

Primary Manufacturing Facility 152 American Drive Oakboro, NC 28129 Ph: (704) 485-2234 Fax: (704) 485-5750 www.cf-steel.com

Arkansas Sales Office & Manufacturing Facility 23389 Hwy 64

Knoxville, AR 72485

NY Design & Technical Sales Office 28 Champlain St.

Rouses Point, NY 12979 Ph: (518) 206-4075