Page 1: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

Bracing Systems

Available AtVIKING SA

Tel: (+352) 58-37-37-1Fax: (+352) 58-37-36

Email: vikinglux@vikingcorp.

Page 2: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

2 www.erico.com

Bracing Systems

To help ensure the availability and operation of safety systems after an earthquake event, many building and industry codes nowinclude requirements for the design and installation of seismic sway bracing for non-structural components, such as fire sprinkler,mechanical, electrical and plumbing systems. The innovative line of CADDY® Bracing Systems was developed to help keep fire sprinklersystems intact after a seismic event and to minimize water damage resulting from leaks or ruptures.

CADDY Bracing Systems provide contractors with high-quality, engineered solutions, which include rigid bracing, cable bracing and rodstiffeners.

• Quick and easy installation• Lower total installed cost• Meets requirements of NFPA® 13• cULus® Listed• FM® Approved• OSHPD® Pre-Approved

Rigid Bracing Cable Bracing Branch LineRestraint System

Rod Stiffeners

Page 3: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 3

Rigid Bracing

The CADDY® line of innovative rigid bracing products was designed to provide superior performance and meet the highest seismicload requirements. The products have been designed with the end user in mind and provide contractors with labor-saving featuresto promote quick and easy installation. The system of products supports lateral and longitudinal bracing and offers a wide range ofstructural and pipe attachments.

• Patent-pending lateral braces eliminate need for multiple trips up and down ladders• Adjustable design can be used with different brace pipe sizes, providing flexibility on the jobsite and reducing contractor inventory• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• cULus® Listed• FM® Approved• OSHPD® Pre-Approved (OPA-2629-10) to the 2010 California Building Code

Structural Attachmentsfor Rigid Bracing

Sway Braces Replacement Nuts andBolts for Rigid Bracing

Page 4: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

4 www.erico.com

Structural Attachments for Rigid Bracing

Bar Joist Attachment Adjustable I-Beam Attachment Multi Attachment

Strut Seismic Hinge Universal Structural Attachment

Page 5: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 5

Bar Joist Attachment

• Can be installed on bar joists or I-beams• Thumb spring retainer allows for ease of positioning• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• No assembly required• No loose parts• Meets NFPA®-13 requirements for seismic sway bracing

Material: Steel

Part Number Article Number FinishFlange Thickness

FTA B C

CSBBARJEG 404354 Electro-galvanized 6,4 – 12,7 mm 50,8 mm 76,2 mm 63,5 mm

CSBBARJHD Hot-dip galvanized 6,4 – 12,7 mm 50,8 mm 76,2 mm 63,5 mm

UL Loads

Brace Direction to Structure Service Pipe Size Rating

Parallel 25 - 250 mm 13340 N

Perpendicular 25 - 300 mm 16630 N

FM Loads

Horizontal Capacity per Intallation Angle from VerticalBrace Direction Service Pipe Size

30° - 44° 45° - 59° 60° - 74° 75° - 90°

Parallel N/A 6270 N 9385 N 11300 N 12590 N

Perpendicular N/A 7740 N 7605 N 9165 N 10230 N

Page 6: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

6 www.erico.com

Adjustable I-Beam Attachment

• No loose parts• No assembly required• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part Number Article NumberFlange Thickness

FTA

HeightH

LengthL

WidthW

CSBIB075085EG 404365 6,4 – 19,1 mm 100 – 216 mm 63,5 mm 304,8 mm 69,9 mm

CSBIB075145EG 404366 6,4 – 19,1 mm 216 – 368 mm 63,5 mm 431,8 mm 69,9 mm

CSBIB125180EG 404367 19,1 – 31,8 mm 100 – 457 mm 88,9 mm 546,1 mm 79,4 mm

UL Loads

Brace Direction to Structure Service Pipe Size Rating

Parallel 25 - 300 mm 13340 N

Perpendicular 25 - 300 mm 16630 N

FM Loads

Horizontal Capacity per Installation Angle from VerticalBrace Direction Service Pipe Size

30° - 44° 45° - 59° 60° - 74° 75° - 90°

Parallel N/A 7,205 N 7,605 N 4,495 N 4,940 N

Perpendicular N/A 7,205 N 10,230 N 12,545 N 13,965 N

Page 7: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 7

Multi Attachment

• Disperses load over two anchors• Minimizes the number of installed braces needed for concrete and wood structures• Ideal for deck installations• Use for both lateral and longitudinal sway brace applications• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part NumberArticle

NumberHole Size 1

HS1Hole Size 2

HS2A B C D UL Listed Load

CSBMA050050EG 404371 14 mm 14 mm 304,8 mm 63,5 mm 63,5 mm 228,6 mm 16.636 N

CSBMA050075EG 404372 20 mm 14 mm 304,8 mm 63,5 mm 63,5 mm 228,6 mm 16.636 N

Mount to structure using holes indicated in HS1.

Page 8: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

8 www.erico.com

Strut Seismic Hinge

• Complete hinge assembly• Ideal for attaching sway bracing to MEP system supports• Attaches to strut trapezes and to structure

Material: SteelFinish: Electro-galvanized

Part Number Article NumberHole Size 1

HS1Hole Size 2

HS2Length

LWidth

WThickness

T

CSBSH00375EG 404463 14 mm 11 mm 179,8 mm 41,3 mm 6,4 mm

CSBSH00500EG 404464 14 mm 14 mm 179,8 mm 41,3 mm 6,4 mm

CSBSH00625EG 404465 14 mm 17 mm 179,8 mm 41,3 mm 6,4 mm

CSBSH00750EG 404466 14 mm 21 mm 179,8 mm 41,3 mm 6,4 mm

Page 9: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 9

Universal Structural Attachment

• Universal design allows one product to attach directly to concrete, wood, bar joist or I-beam adapters• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Use for both lateral and longitudinal sway brace applications• Works with 1" through 2" brace pipes and 1/4" angle iron braces to reduce inventory• Center bolt does not require tightening• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part Number Article NumberHole Size

HSA B C

CSBUNIV050EG 404407 14 mm 133,4 mm 101,6 mm 41,4 mm

CSBUNIV075EG 404409 21 mm 133,4 mm 101,6 mm 41,4 mm

UL Loads

Brace Type Service Pipe Size Rating

Pipe 25 mm - 250 mm 13,340 N

6mm Thick Angle 25 mm - 200 mm 8,960 N

FM Loads

Horizontal Capacity per Installation Angle from VerticalBrace Type Service Pipe Size

30° - 44° 45° - 59° 60° - 74° 75° - 90°

Pipe N/A 7,205 N 10,230 N 12,545 N 13,965 N

Page 10: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

10 www.erico.com

Shear Bolt

Material: SteelFinish: Electro-galvanized

Part Number Article Number Description

CSBBARJSB50EG 402502 Shear Bolt for Bar Joist Attachment

CSBIBSB50EG 402501 Shear Bolt for I-Beam Attachment

CSBUNIVSB62EG 402503 Shear Bolt for Universal Sway Brace and Universal Structural Attachment

Shear Nut

Material: SteelFinish: Electro-galvanized

Part Number Article Number Description

CSBIBSN37EG 402500 Shear Nut for Adjustable I-Beam Attachment

CSBQIKCLSN37EG 402505 Shear Nut for Quick Grip Jr. Lateral Sway Brace, 25 - 50 mm NB/DN

Page 11: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 11

Sway Braces

Easy Universal Sway Brace Standard UniversalSway Brace

Quick Grip Jr.Lateral Sway Brace

Quick Grip LateralSway Brace

Easy Universal Sway Brace

• Use for both lateral and longitudinal sway brace applications• Unique slotted holes provide for easy slip-on installation eliminating loose hardware• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Works with 1" through 2" brace pipes and 1/4" angle iron braces to reduce inventory• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part Number Article Number Pipe Size NB/DN A B Listings Approvals

CSBEZU0100EG 404356 1" 25 mm 174,6 mm 25,4 mm UL, FM

CSBEZU0125EG 404357 1 1/4" 32 mm 187,4 mm 25,4 mm UL, FM

CSBEZU0150EG 404358 1 1/2" 40 mm 196,9 mm 25,4 mm UL, FM

CSBEZU0200EG 404359 2" 50 mm 206,4 mm 30,2 mm UL, FM

CSBEZU0250EG 404360 2 1/2" 65 mm 225,4 mm 30,2 mm cUL, UL, FM

CSBEZU0300EG 404361 3" 80 mm 238,1 mm 30,2 mm cUL, UL, FM

CSBEZU0400EG 404362 4" 100 mm 269,9 mm 38,1 mm cUL, UL, FM

CSBEZU0500EG 404363 5" 125 mm 308 mm 38,1 mm cUL, UL, FM

CSBEZU0600EG 404364 6" 150 mm 346,1 mm 50,8 mm cUL, UL, FM

Page 12: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

12 www.erico.com

UL Loads (Listed for Restraints)

Part Number Dyna-Flow® Service Pipe Sch 10 Service Pipe Sch 40 Service Pipe

CSBEZU0100EG N/A 2910 N 2910 N

CSBEZU0125EG 2910 N 2910 N 2910 N

CSBEZU0150EG 2910 N 2910 N 2910 N

UL Loads (Listed for Sway Braces)

Lateral Longitudinal

Part Number Dyna-Flow®Service Pipe

EZ FLOW™Service Pipe

Sch 10Service Pipe

Sch 40Service Pipe

Dyna-Flow®Service Pipe

Mega-FlowService Pipe

Sch 10Service Pipe

Sch 40Service Pipe

CSBEZU0200EG 13340 N N/A 13340 N 13340 N N/A N/A N/A N/A

CSBEZU0250EG 13340 N N/A 13340 N 13340 N 5620 N N/A 5620 N 5620 N

CSBEZU0300EG 13340 N N/A 13340 N 13340 N 5620 N N/A 5620 N 5620 N

CSBEZU0400EG 13340 N 13340 N 13340 N 13340 N 5620 N N/A 5620 N 5620 N

CSBEZU0500EG N/A 13340 N 13340 N 13340 N N/A 7110 N 7110 N 7110 N

CSBEZU0600EG N/A 13340 N 13340 N 13340 N N/A 7110 N 7110 N 7110 N

FM Loads (Lightwall, Sch 10 and Sch 40 Service Pipes)

Horizontal Capacity per Installation Angle from Vertical

Lateral LongitudinalPart Number

30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°

CSBEZU0100EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N

CSBEZU0125EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N

CSBEZU0150EG 3825 N 5425 N 6670 N 7430 N 1735 N 2445 N 2980 N 3335 N

CSBEZU0200EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N

CSBEZU0250EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N

CSBEZU0300EG 6805 N 9610 N 11790 N 13165 N 2315 N 3070 N 3690 N 4136 N

CSBEZU0400EG 6985 N 9875 N 12100 N 13480 N 2800 N 4005 N 4895 N 5470 N

CSBEZU0500EG 6985 N 9875 N 12100 N 13480 N 2800 N 4005 N 4895 N 5470 N

CSBEZU0600EG 8805 N 12500 N 15300 N 17080 N 3245 N 4450 N 5470 N 6095 N

Page 13: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 13

Standard Universal Sway Brace

• Use for both lateral and longitudinal sway brace applications• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Works with 1" through 2" brace pipes and 1/4" angle iron braces to reduce inventory• Slotted design grabs service pipe for added gripping strength• Meets NFPA®-13 requirements for seismic sway bracing

Material: Steel

Part Number Article Number Pipe Size NB/DN A B Listings Approvals

Finish: Electro-galvanized

CSBSTU0100EG 404385 1" 25 mm 174,6 mm 25 mm UL, FM

CSBSTU0125EG 404386 1 1/4" 32 mm 187,4 mm 25,4 mm UL, FM

CSBSTU0150EG 404387 1 1/2" 40 mm 196,9 mm 25,4 mm UL, FM

CSBSTU0200EG 404388 2" 50 mm 206,4 mm 30,2 mm UL, FM

CSBSTU0250EG 404389 2 1/2" 65 mm 225,4 mm 30,2 mm cUL, UL, FM

CSBSTU0300EG 404390 3" 80 mm 238,1 mm 30,2 mm cUL, UL, FM

CSBSTU0400EG 404391 4" 100 mm 269,9 mm 38,1 mm cUL, UL, FM

CSBSTU0500EG 404392 5" 125 mm 308 mm 38,1 mm cUL, UL, FM

CSBSTU0600EG 404393 6" 150 mm 346,1 mm 50,8 mm cUL, UL, FM

CSBSTU0800EG 404394 8" 200 mm 400,1 mm 50,8 mm cUL, UL, FM

CSBSTU1000EG 404395 10" 250 mm 457,2 mm 50,8 mm cUL, UL, FM

Finish: Hot-dip galvanized

CSBSTU0100HD 1" 25 mm 174,6 mm 25 mm UL, FM

CSBSTU0125HD 1 1/4" 32 mm 187,4 mm 25,4 mm UL, FM

CSBSTU0150HD 1 1/2" 40 mm 196,9 mm 25,4 mm UL, FM

CSBSTU0200HD 2" 50 mm 206,4 mm 30,2 mm UL, FM

CSBSTU0300HD 3" 80 mm 238,1 mm 30,2 mm cUL, UL, FM

CSBSTU0400HD 4" 100 mm 269,9 mm 38,1 mm cUL, UL, FM

CSBSTU0500HD 5" 125 mm 308 mm 38,1 mm cUL, UL, FM

CSBSTU0600HD 6" 150 mm 346,1 mm 50,8 mm cUL, UL, FM

CSBSTU0800HD 8" 200 mm 400,1 mm 50,8 mm cUL, UL, FM

CSBSTU1000HD 10" 250 mm 457,2 mm 50,8 mm cUL, UL, FM

UL Loads (Listed for Restraints)

Part Number Dyna-Flow® Service Pipe Sch 10 Service Pipe Sch 40 Service Pipe

CSBSTU0100xx N/A 2910 N 2910 N

CSBSTU0125xx 2910 N 2910 N 2910 N

CSBSTU0150xx 2910 N 2910 N 2910 N

Page 14: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

14 www.erico.com

UL Loads (Listed for Sway Braces)

Lateral Longitudinal

Part Number Dyna-Flow®Service Pipe

EZ FLOW™Service Pipe

Sch 10Service Pipe

Sch 40Service Pipe

Dyna-Flow®Service Pipe

EZ FLOW™Service Pipe

Sch 10Service Pipe

Sch 40Service Pipe

CSBSTU0200xx 13340 N N/A 13340 N 13340 N N/A N/A N/A N/A

CSBSTU0250xx 13340 N N/A 13340 N 13340 N 8960 N N/A 8960 N 8960 N

CSBSTU0300xx 13340 N N/A 13340 N 13340 N 8960 N N/A 8960 N 8960 N

CSBSTU0400xx 13340 N 13340 N 13340 N 13340 N 8960 N N/A 8960 N 8960 N

CSBSTU0500xx N/A 13340 N 13340 N 13340 N N/A N/A 8960 N 8960 N

CSBSTU0600xx N/A 13340 N 13340 N 13340 N N/A 8960 N 8960 N 8960 N

CSBSTU0800xx N/A N/A 13340 N 13340 N N/A N/A 13340 N 13340 N

CSBSTU1000xx N/A N/A 13340 N 13340 N N/A N/A 13340 N 13340 N

FM Loads (Lightwall, Sch 10 and Sch 40 Service Pipes)

Horizontal Capacity per Installation Angle from Vertical

Lateral LongitudinalPart Number

30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°

CSBSTU0100xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N

CSBSTU0125xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N

CSBSTU0150xx 3825 N 5425 N 6670 N 7430 N 4315 N 3200 N 3825 N 4270 N

CSBSTU0200xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N

CSBSTU0250xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N

CSBSTU0300xx 6805 N 9610 N 11790 N 13165 N 3870 N 3070 N 3690 N 4136 N

CSBSTU0400xx 6985 N 9875 N 12100 N 13480 N 6895 N 6185 N 7475 N 8320 N

CSBSTU0500xx 6985 N 9875 N 12100 N 13480 N 6895 N 6185 N 7475 N 8320 N

CSBSTU0600xx 8805 N 12500 N 15300 N 17080 N 6540 N 5205 N 6270 N 6985 N

FM Loads (4.8 mm wall and Sch 40 Service Pipes)

Horizontal Capacity per Installation Angle from Vertical

Lateral LongitudinalPart Number

30° - 44° 45° - 59° 60° - 74° 75° - 90° 30° - 44° 45° - 59° 60° - 74° 75° - 90°

CSBSTU0800xx 9075 N 12855 N 15745 N 17570 N 5340 N 7560 N 9295 N 10365 N

CSBSTU1000xx 9075 N 12855 N 15745 N 17570 N 5340 N 7560 N 9295 N 10365 N

Page 15: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 15

Quick Grip Jr. Lateral Sway Brace

• Easy two-step installation elminates extra trips between structure and service pipe• Works with 1" and 1 1/4" (25 mm and 32 mm) brace pipes to reduce inventory• Snap-off bolt head helps enable easy installation and inspection of seismic sway braces• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part Number Article Number Pipe Size NB/DNHeight

HWidth

W

CSBQIKCL0100EG 404373 1" 25 mm 130,2 mm 65,3 mm

CSBQIKCL0125EG 404374 1 1/4" 32 mm 136,5 mm 74,4 mm

CSBQIKCL0150EG 404375 1 1/2" 40 mm 142,9 mm 80,2 mm

CSBQIKCL0200EG 404376 2" 50 mm 161,9 mm 92,3 mm

UL Loads (Listed for Restraints)

LateralPart Number Service Pipe Schedule

25 mm Brace Pipe 32 mm Brace Pipe

Dyna-Flow® N/A N/A

10 2910 N 2910 NCSBQIKCL0100EG

40 2910 N 2910 N

Dyna-Flow® 2910 N 2400 N

10 2910 N 2400 NCSBQIKCL0125EG

40 2910 N 2400 N

Dyna-Flow® 3330 N 2910 N

10 3330 N 2910 NCSBQIKCL0150EG

40 3330 N 2910 N

Dyna-Flow® 3330 N 2400 N

10 3330 N 2400 NCSBQIKCL0200EG

40 3330 N 2400 N

Page 16: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

16 www.erico.com

FM Loads

Lateral

Horizontal per Installation Angle from VerticalPart Number Service Pipe Schedule

30° - 44° 45° - 59° 60° - 74° 75° - 90°

Lightwall 1290 N 1830 N 2200 N 2445 N

10 665 N 935 N 1245 N 1400 NCSBQIKCL0100EG

40 2115 N 2960 N 3670 N 4115 N

Lightwall 1290 N 1830 N 2200 N 2445 N

10 665 N 935 N 1245 N 1400 NCSBQIKCL0125EG

40 2115 N 2960 N 3670 N 4115 N

Lightwall 1290 N 1830 N 2200 N 2445 N

10 665 N 935 N 1245 N 1400 NCSBQIKCL0150EG

40 2115 N 2960 N 3670 N 4115 N

Lightwall 1735 N 2445 N 2980 N 3335 N

10 1555 N 2225 N 2760 N 3070 NCSBQIKCL0200EG

40 2180 N 3070 N 3780 N 4225 N

Quick Grip Lateral Sway Brace

The Quick Grip Lateral Brace, part of the CADDY® line of fire sprinkler bracing systems from ERICO, is designed to help simplifyinstallations when bracing service pipe for seismic or other catastrophic events. It features an innovative design for quick attachment ofbrace pipe to service pipe saving time and money.

• Easy two-step installation elminates extra trips between structure and service pipe• Works with 1" and 1 1/4" (25 mm and 32 mm) brace pipes to reduce inventory• Yellow tips provide a visual indicator that the bolts have been properly torqued• Easy installation with an impact wrench from the bottom side of the clamp• Meets NFPA®-13 requirements for seismic sway bracing

Material: SteelFinish: Electro-galvanized

Part Number Article Number Pipe Size NB/DNHeight

HWidth

W

CSBQG0250EG 404468 2 1/2" 65 mm 138,1 – 148,6 mm 172 mm

CSBQG0300EG 404469 3" 80 mm 155 – 165,5 mm 190 mm

CSBQG0400EG 404470 4" 100 mm 180,4 – 190,9 mm 222 mm

CSBQG0500EG 404471 5" 125 mm 205,8 – 217,9 mm 260 mm

CSBQG0600EG 404472 6" 150 mm 235,5 – 244,9 mm 298 mm

CSBQG0800EG 404473 8" 200 mm 289,2 – 300 mm 351,8 mm

Page 17: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 17

UL Loads

LateralPart Number Service Pipe Schedule

25 mm Brace Pipe 32 mm Brace Pipe

Dyna-Flow® 8960 N 8960 N

10 8960 N 8960 NCSBQG0250EG

40 8960 N 8960 N

Dyna-Flow® 8960 N 8960 N

10 8960 N 8960 NCSBQG0300EG

40 8960 N 8960 N

Dyna-Flow® 8960 N 8960 N

10 8960 N 8960 NCSBQG0400EG

40 8960 N 8960 N

10 8960 N 8960 NCSBQG0500EG

40 8960 N 8960 N

Mega-Flow 8960 N 8960 N

10 8960 N 8960 NCSBQG0600EG

40 8960 N 8960 N

10 8960 N 8960 NCSBQG0800EG

40 8960 N 8960 N

FM Loads

Lateral

Horizontal Capacity per Installation Angle from VerticalPart Number Service Pipe Schedule

30° - 44° 45° - 59° 60° - 74° 75° - 90°

Lightwall 6270 N 8895 N 10900 N 12190 N

10 6270 N 8895 N 10900 N 12190 NCSBQG0250EG

40 6270 N 8895 N 10900 N 12190 N

Lightwall 5295 N 7475 N 9163 N 10230 N

10 5295 N 7475 N 9163 N 10230 NCSBQG0300EG

40 5295 N 7475 N 9163 N 10230 N

Lightwall 5295 N 7475 N 9163 N 10230 N

10 5295 N 7475 N 9163 N 10230 NCSBQG0400EG

40 5295 N 7475 N 9163 N 10230 N

Lightwall 3870 N 5470 N 6715 N 7515 N

10 3870 N 5470 N 6715 N 7515 NCSBQG0500EG

40 4315 N 6095 N 7475 N 8320 N

Lightwall 3870 N 5470 N 6715 N 7515 N

10 3870 N 5470 N 6715 N 7515 NCSBQG0600EG

40 4315 N 6095 N 7475 N 8320 N

4.8 mm (Wall Thickness) 3515 N 4940 N 6050 N 6760 NCSBQG0800EG

40 3515 N 4940 N 6050 N 6760 N

Page 18: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

18 www.erico.com

Cable Bracing

CADDY® cable bracing is an ideal alternative to rigid bracing for fire sprinkler systems when brace lengths greater than 19’ - 8” (6 m)are required or when confined/crowded spaces make rigid systems difficult to install. The system includes pre-stretched steel cable,attachment fittings, crimping sleeves and related tools. The system can also be used to brace electrical, mechanical and plumbingsystems.

• Color-coated cable conforms to NFPA® 13 requirements and makes it highly visible and easier to identify cable sizes• UL® Listed• OSHPD® Pre-Approved (OPA-0619)

Cable Spool Crimping Sleeve Loop Attachment Kit

No Pry Clip Stake Eye Kit Cable Cutter

Page 19: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 19

Swaging Tools Universal Restraint Clip Universal Restraint Clip, Retrofit

Cable Spool

• Cut to length as needed• Pre-stretched restraint cable

Material: SteelFinish: Pre-galvanized, Painted

Part Number Article Number Brace Size Diameter Cable Length UL Listed Load Color

CSB12CBL 402190 #12 2,4 mm 76,2 m 2.668 N Red

CSB18CBL 402191 #18 3,2 mm 76,2 m 4.893 N White

CSB36CBL 402192 #36 4,8 mm 76,2 m 12.455 N Blue

CSB48CBL 402193 #48 6 mm 76,2 m 20.461 N Yellow

Cable is powder coated.

Page 20: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

20 www.erico.com

Crimping Sleeve

• Creates secure loop ends• Crimp with swaging tools

Material: CopperFinish: Electro-galvanized

Part Number Article Number Brace Size

CSB12SLVB 402194 #12

CSB18SLVB 402195 #18

CSB36SLVB 402196 #36

CSB48SLVB 402197 #48

Two side-by-side crimps required on #12 and #18 cable. Three side-by-side crimps required on #36 and #48 cable.

Check crimp with gauge (not included).

Loop Attachment Kit

• Two-way bracing kit with crimp sleeves• Wraps around structural steel members

Material: Steel

Part Number Article Number Brace Size Brace Length Cable Length UL Listed Load Color

CSB12B00L7 402230 #12 2,1 m 3,3 m 2.668 N Red

CSB12B00L10 402232 #12 3,0 m 4,2 m 2.668 N Red

CSB18B00L7 402231 #18 2,1 m 3,3 m 4.893 N White

CSB18B00L10 402233 #18 3,0 m 4,2 m 4.893 N White

Stake eyes not included.

Page 21: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 21

No Pry Clip

• Eliminates prying effect on fasteners and anchors

Material: SteelFinish: Electro-galvanized

Part Number Article Number Brace Size Hole Size UL Listed Load

CSBNPC12 402208 #12, #18, #36 14 mm 12.460 N

Stake Eye Kit

• Attaches to steel, wood or concrete structures• Two-way bracing kit with crimp sleeves and stake eyes• Swaged-on stake eye, pre-bent to 45 degrees

Material: Steel

Part NumberArticle

NumberBrace Size Hole Size Brace Length Cable Length UL Listed Load Color

CSB12BD38L7 402218 #12 11 mm 2,1 m 3,3 m 2.668 N Red

CSB12BD38L10 402221 #12 11 mm 3,0 m 4,2 m 2.668 N Red

CSB12BD50L7 402224 #12 14 mm 2,1 m 3,3 m 2.668 N Red

CSB12BD50L10 402227 #12 14 mm 3,0 m 4,2 m 2.668 N Red

CSB18BD38L7 402219 #18 11 mm 2,1 m 3,3 m 4.893 N White

CSB18BD38L10 402222 #18 11 mm 3,0 m 4,2 m 4.893 N White

CSB18BD50L7 402225 #18 14 mm 2,1 m 3,3 m 4.893 N White

CSB18BD50L10 402228 #18 14 mm 3,0 m 4,2 m 4.893 N White

CSB36BD38L7 402220 #36 11 mm 2,1 m 3,3 m 12.455 N Blue

Page 22: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

22 www.erico.com

Part NumberArticle

NumberBrace Size Hole Size Brace Length Cable Length UL Listed Load Color

CSB36BD38L10 402223 #36 11 mm 3,0 m 4,2 m 12.455 N Blue

CSB36BD50L7 402226 #36 14 mm 2,1 m 3,3 m 12.455 N Blue

CSB36BD50L10 402229 #36 14 mm 3,0 m 4,2 m 12.455 N Blue

Kits contain copper sleeves.

Page 23: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 23

Swaging Tools

Manual Swaging Tool Multi-Size Manual Swaging Tool

Manual Swaging Tool

Material: Steel

Part Number Article Number Brace Size Listings

CSB12SBHS 404461 #12 -

CSB48 402212 #48 UL

Page 24: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

24 www.erico.com

Multi-Size Manual Swaging Tool

Material: Steel

Part Number Article Number Brace Size

CSB3346SB 402209 #12, #18, #36

Universal Restraint Clip

• Attaches cable brace to structure

Material: SteelFinish: Electro-galvanized

Part Number Article Number Brace SizeHole Size

HSUL Listed Load

CSBURC38 402198 #12, #18, #36 11 mm 7.117 N

CSBURC12 402199 #12, #18, #36 14 mm 7.117 N

CSBURC58 402200 #12, #18, #36 17 mm 7.117 N

CSBURC4812 402204 #48 14 mm 20.460 N

CSBURC4858 402205 #48 17 mm 20.460 N

CSBURC4834 402206 #48 21 mm 20.460 N

Mount to the structure using the center hole. Loop cable through the holes in the bent tabs and crimp in place.

For #48 cable, use two clips stacked together.

Page 25: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 25

Universal Restraint Clip, Retrofit

• Slotted design ideal for attaching to existing threaded rod on trapezes

Material: SteelFinish: Electro-galvanized

Part Number Article Number Brace SizeRod Size

RS

CSBURCR38 402201 #12, #18 M10

CSBURCR12 402202 #12, #18 M12

CSBURCR58 402203 #12, #18 M16

One fastener required for #12 cable. Two stacked fasteners required for #18 cable.

Page 26: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

26 www.erico.com

Branch Line Restraint System

Traditional methods for installing branch line restraints in fire sprinkler systems are cumbersome and time-consuming. Contractors oftencut (and re-cut) threaded rod to precise measurements to restrain the sprinkler pipe with a loop hanger and surge restraint. Traditionalmethods also commonly require five or more parts per restraint.

To avoid these labor-intensive methods, ERICO has streamlined the process and developed the Branch Line Restraint System, part ofthe CADDY® line of hanging and bracing solutions for the fire protection market. Ideal for restraining 1” (25 mm) through 2” (50 mm)branch lines, this innovative system is significantly faster and easier to install than current methods. It attaches directly to steel bar joists,I-beams or purlins, as well as concrete and wood structures. The hardware is installed with only one tool, a 5/16” (8 mm) socket drilldriver, which provides significant labor savings and convenience. It features a simple, two-step installation process, allowing a timesavings of up to 80% compared to other methods.

Unlike most solutions that only accept 3/8” (M10) threaded rod, the versatile Branch Line Restraint System features a swivel attachmentthat can be rotated to accept 3/8” or 1/2” (M10 or M12) threaded rod. This allows greater restraint distances from the pipe to structurewith 1/2” (M12) threaded rod.

The system meets the requirements of NFPA® 13, making it ideal for new construction applications. The total system is cULus® Listedand FM® Approved, and has been pre-approved by the state of California (OSHPD OPA-2629-10).

• Complete restraint system is quick and easy to install• Offers up to 80% time savings per branch line restraint• Eliminates need to cut threaded rod to exact dimensions• Works with 3/8” and 1/2” (M10 and M12) rod• Capable of restraint distances up to 40” (960 mm) from pipe to structure with 1/2” (M12) threaded rod• Meets requirements of NFPA® 13 section 9.3.6

Branch Line RestraintPipe Attachment

Branch LineRestraint Structure

Attachment to Steel

Branch Line RestraintStructure Attachment

to Wood/Concrete

Branch Line RestraintStructure Attachment

to Threaded Hole

Page 27: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 27

Branch Line Restraint Pipe Attachment

• Accepts 3/8” or 1/2” (M10 or M12) threaded rod• Quick grip clamp simplifies measuring and cutting of threaded rod• Works with rough-cut threaded rod and eliminates pipe-side deburring• Can be installed with threaded rod above or below the service pipe• Shear-off head helps ensure correct torque and simplifies inspection

Material: SteelFinish: Electro-galvanized

Part NumberArticle

NumberPipe Size NB/DN

Outer DiameterOD

Rod SizeRS

HeightH

LengthL

WidthW

CSBBRP0100EG 404477 1" 25 mm 33,4 mm M10, M12 169,4 mm 41,4 mm 22,2 mm

CSBBRP0125EG 404478 1 1/4" 32 mm 42,2 mm M10, M12 192 mm 50 mm 22,2 mm

CSBBRP0150EG 404479 1 1/2" 40 mm 48,3 mm M10, M12 208,4 mm 56,1 mm 22,2 mm

CSBBRP0200EG 404480 2" 50 mm 60,3 mm M10, M12 240 mm 68,3 mm 22,2 mm

Page 28: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

28 www.erico.com

Branch Line Restraint Structure Attachment to Steel

• Swivel connector accepts 3/8” or 1/2” (M10 or M12) threaded rod• Attaches to steel members with self-drilling/tapping screw

Material: SteelFinish: Electro-galvanized

Part NumberArticle

NumberRod Size

RS

FlangeThickness

FT

HeightH

LengthL

WidthW

Screw DiameterSc

Screw LengthL

CSBBRS1MEG 402239 M10, M12 2,7 – 12,7 mm 28,2 mm 40,4 mm 26,9 mm #12 32 mm

Branch line structural attachments are for restraint only and not for the hanging of fire sprinkler piping.

Branch Line Restraint Structure Attachment to Wood/Concrete

• Swivel connector accepts 3/8” or 1/2” (M10 or M12) threaded rod• Attaches to wood or concrete structures

Material: SteelFinish: Electro-galvanized

Part NumberArticle

NumberRod Size

RSHeight

HLength

LWidth

WScrew Diameter

ScScrew Length

LDrill Bit Size

CSBBRS2MEG 402240 M10, M12 28,2 mm 40,4 mm 26,9 mm 6,4 mm 45 mm 4,8 mm

Branch line structural attachments are for restraint only and not for the hanging of fire sprinkler piping.

Page 29: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 29

Branch Line Restraint Structure Attachment to Threaded Hole

• Swivel connector accepts 3/8” or 1/2” (M10 or M12) threaded rod• Attaches to concrete anchors or structural attachments with female threads

Material: SteelFinish: Electro-galvanized

Part NumberArticle

NumberRod Size

RSHeight

HLength

LWidth

WScrew Diameter

ScScrew Length

L

CSBBRS3MEG 402241 M10, M12 28,2 mm 40,4 mm 26,9 mm M10 19 mm

Branch line structural attachments are for restraint only and not for the hanging of fire sprinkler piping.

Page 30: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

30 www.erico.com

Rod Stiffeners

Pipe Rod Stiffener

Pipe Rod Stiffener

• For use with Schedule 40 or Schedule 10 pipe• Secures pipe to threaded rod for stiffening

Material: SteelFinish: Electro-galvanized

Part Number Article Number Brace Pipe Size Brace NB/DN Rod Size

CSBRS1 402207 1" 25 mm M10, M12, M16

Page 31: Bracing Systems - Viking Group Inc support/Bracing... · CADDY Bracing Systems ... • Meets NFPA®-13 requirements for seismic sway bracing Material: Steel ... • Attaches to strut

www.erico.com 31

cULus is a registered certification mark of UL LLC. Dyna-Flow is a registered trademark of Allied Tube & Conduit Corporation. EZ FLOW is a trademark of Northwest Pipe Company. FM is aregistered certification mark of FM Approvals LLC, LTD. NFPA is a registered trademark of National Fire Protection Association, Inc. UL is a registered certification mark of UL LLC.

WARNINGERICO products shall be installed and used only as indicated in ERICO’s product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from yourERICO customer service representative. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction,property damage, serious bodily injury and death.

WARRANTYERICO products are warranted to be free from defects in material and workmanship at the time of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR IMPLIED (INCLUDING ANYWARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), SHALL EXIST IN CONNECTION WITH THE SALE OR USE OF ANY ERICO PRODUCTS. Claims for errors,shortages, defects or nonconformities ascertainable upon inspection must be made in writing within 5 days after Buyer's receipt of products. All other claims must be made in writingto ERICO within 6 months from the date of shipment or transport. Products claimed to be nonconforming or defective must, upon ERICO's prior written approval in accordance with itsstandard terms and procedures governing returns, promptly be returned to ERICO for inspection. Claims not made as provided above and within the applicable time period will be barred.ERICO shall in no event be responsible if the products have not been stored or used in accordance with its specifications and recommended procedures. ERICO will, at its option, eitherrepair or replace nonconforming or defective products for which it is responsible or return the purchase price to the Buyer. THE FOREGOING STATES BUYER’S EXCLUSIVE REMEDY FORANY BREACH OF ERICO WARRANTY AND FOR ANY CLAIM, WHETHER SOUNDING IN CONTRACT, TORT OR NEGLIGENCE, FOR LOSS OR INJURY CAUSED BY THE SALE OR USE OF ANYPRODUCT.

LIMITATION OF LIABILITYERICO excludes all liability except such liability that is directly attributable to the willful or gross negligence of ERICO's employees. Should ERICO be held liable its liability shall in no eventexceed the total purchase price under the contract. ERICO SHALL IN NO EVENT BE RESPONSIBLE FOR ANY LOSS OF BUSINESS OR PROFITS, DOWNTIME OR DELAY, LABOR, REPAIR ORMATERIAL COSTS OR ANY SIMILAR OR DISSIMILAR CONSEQUENTIAL LOSS OR DAMAGE INCURRED BY BUYER.

Copyright © 2013 ERICO International Corporation. All rights reserved.CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.