The Basics of Boiler Tune-Up and MaintenanceBoilers are major energy users in many facilities. The
combustion efficiency of a boiler will degrade over time necessitating a tune-up to restore efficiency of the unit.
• Boilers can be either steam or hot water; tune-up procedures apply to both types.
• A complete boiler Tune-Up measures the efficiency, corrects the problems, and measures efficiency regularly.
• A Tune-Up improves combustion efficiency by reducing stack losses and improving combustion.
• Regular Annual Maintenance includes inspecting, repairing as needed, cleaning, and adjusting the components of the boiler for optimum performance.
4
© 2009
Benefits of Boiler Tune-UpAnd Annual Maintenance
• Reduced energy consumption• Reduced requirement for expensive repairs• Improved efficiency will prolong boiler life• Financial savings
Photos courtesy of TSI,, ECMT Inc, and Testo Test Tools
$
© 2009
Using a Flue Gas Analyzer Determine Boiler Efficiency
• Test boiler combustion efficiency and perform required adjustments on a regular basis to ensure peak operating performance.
• Optimum efficiencies range between 75 to 80%, boiler efficiency can fall to 50% or less without proper maintenance and adjustment.
• Done by trained maintenance staff or qualified contractors as a part of regular maintenance activities annually.
• The combustion analyzer measures the: CO2, O2, CO, Exhaust temperature
© 2009
Boiler Excess AirExcess air is required to achieve complete combustion
• Is required for optimum efficiency at a minimum.• Depends on boiler configuration, burner design,
controls and fuel type.• Determined by reducing O2 until CO starts to
appear.• 2 % excess O2 with zero CO is achievable with gas-
fired boilers.• Controlling excess air is the most important tool for
managing boiler efficiency and emissions.
© 2009
Example of Benefit of Reducing Excess Air from 11% to 2%
A Boiler operating at:• O2 of 11% Excess Air• Temperature of stack is 300° F• Temperature of inlet combustion air is 85 ° F
Reducing the O2 from 11% to 2% will improve efficiency from 80% to 84%
© 20099
• Combustion efficiencies lower than 75% may be caused by:
• Dirty fire side of the heat exchanger - an indicator of poorly adjusted burners.
• Dirty water/steam/air side of the heat exchanger - often an indication of poor water treatment.
• Inadequate combustion air (air shortage problems occur most often with natural draft boilers) - excessive combustion air.
Causes of Boiler Combustion Inefficiencies
© 2009
Other Steps to Improve Boiler Efficiency
• Increase combustion air temperature• Consider air pre-heater• Draw air from a high point in the boiler
room• Clean Boiler Tubes as needed to improve
heat transfer capacity of boiler• Maintain Water Treatment to keep water side
of boiler free of scale buildup
10
© 2009
Potential Savings % by Increasing Combustion Efficiency
11
Enter left side column and find your existing efficiency.Go across the top and find you new efficiency.The percentage in the middle is your new fuel savings.
© 2009
Example of Percent of Potential Savings
12
Existing efficiency is 72%; new efficiency is 85%.By increasing your efficiency, you will save 18.06%
© 2009
Benefits of BoilerTune-Ups
On average, Un-tuned boilers may have combustion efficiencies of 60% or lower. As the exhaust temperature increases, the combustion efficiency decreases, as more heat is lost in the flue gases.
A well-tuned boiler can dramatically lower the fuel costof operating a boiler or industrial process heater.
Example-At an average of 60 cents/therm, a 10,000-lb/hr boiler with an average annual capacity factor of 50% would save about $26,000 per year in fuel costs with a 10% increase in combustion efficiency. Even a 1% increase in efficiency would save about $2,600 per year.
13
© 2009
Cost of Boiler Testing
The cost of testing and the implementation of typical remedial measures can range as follows:
Efficiency testing - $60 to $500Chemical boiler cleaning - $800 to $1,500 to ….*. Water treatment/year - $1,500 to $3,500 to ….. *Burner adjustment - $200 to $500Enlarge air intakes - $500 to $1,000* Note-Boiler plant size dictates actual cleaning,
chemicals, and water treatment costs.
14
© 2009
Major Energy SavingOpportunities
• As a ‘Rule of Thumb,’ boiler efficiency can be increased by 1% for each 15% reduction in excess air or 40 degree reduction in stack temperature.
• The clean operation of a boiler makes all the difference.
• Just 1/16th layer of soot on the fire side of the boiler tube can cost 10% to 20% of the fuel efficiency, increasing fuel costs by 10% to 20%.
• The same percent loss can also happen if scale on the water side of boiler tube is 2 human hairs thick.
15
© 2009
Portable Analyzers vs. Automatic Stationary Trim Systems
Portable Flue Gas AnalyzersThe flue gas can be measured by inexpensive
gas-absorbing test kits. More expensive (ranging in cost from $500 to $10,000) hand-held, computer-based analyzers display percent oxygen, stack gas temperature, and boiler efficiency. They are a recommended investment for any boiler system with annual fuel costs exceeding $50,000.
16
Photos courtesy of TSI,, ECMT Inc, and Testo Test Tools
© 2009
Portable Analyzers vs. Automatic Stationary Trim SystemsAutomatic Oxygen Control or O2 Trim SystemsWhen fuel composition is highly variable or where steam flows are
highly variable, an online oxygen analyzer should be considered. The oxygen “trim” system provides feedback to the burner controls to automatically minimize excess combustion air and optimize the air-to-fuel ratio.
17Photos courtesy of Cleaver-Brooks
© 2009
Boiler Maintenance Recommendations
Check water level at try cock valves.
Check pop off relief valves as recommended by manufacturer.
Annually clean and check the low water float safety controls.
Check pressure controls.
Photos courtesy of Greg Jourdan
© 2009
Boiler Tube Inspections
• If the fire side of the heat exchanger is dirty, but the fuel/air mixture is correct, check for excessive boiler room dust.
• Remedy; clean the floor more often and paint the boiler room floor to reduce dust levels.
• If the water side of a boiler has scale buildup, water treatment may be inadequate.
• If the water side of a boiler appears to have corrosion
• Remedy, maintain proper water treatment levels as per water chemical expert recommendations.
© 2009
Annual Maintenance
Clean fireside surfaces
• Brush & vacuum tubes
• Clean tube sheets & refractory
• Amount of soot indicates how well burner is performing
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Repair refractory
• Cracks 1/8” and under will close up when heated
• Look for loose sections
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Check hydraulic valves
• Bubble test for valve seat tightness check
• Actuators open & close properly
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Remove and Recondition safety valves
• Inspect piping for loose hangers putting weight on valves
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Recondition Boiler feed pumps
• Wear rings• Seals• Packing• Bearings• Recondition shaft
and/or impellers
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Check condensate receivers
• Flush out• Check any lining for
failure• Clean pump
strainers
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Check chemical feed system
• Clean out tank• Recondition pump• Inspect & clean out
piping to injection points
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Tighten electrical terminals
• Power off!!• All panels, all
controls & components
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Check de-aerator or boiler feed system
• Water spray head• Collector cone
assembly & steam atomizing valve of spray types
• Check any possible lining
• Clean out pump strainers
Courtesy Cleaver-Brooks Boilers
© 2009
Annual Maintenance
Check linkages
• Lubricate• Tighten• Replace worn parts
Courtesy Cleaver-Brooks Boilers
© 2009
Working with Outside Contractors Offering Boiler Tune-up Services
• Look for experienced contractors• Verify combustion analyzers are calibrated
annually• Ask for combustion analyzer print-out report• Don’t just look for the cheapest
contractor….look for quality!• Ask your GAS Utility if Boiler Tune-Ups are
subsidized.
30
© 200931
Boiler manufacturer resourcesand Tune-Up Info
• Cleaver-Brooks
• Burnham Commercial Boilers
• Lochinvar Boilers
• Hays Cleveland Oxygen Trim Controllers
• Testo Combustion Analyzers
• Bacharach Combustion Analyzers
• TSI Test Tools
© 200932
Thank –YouQuestions?
BOC Webinar
Boiler Tune-Up and MaintenanceSeptember 9th, 2009
Instructor-Greg JourdanWenatchee Valley College
For more informationBOC Information
Phone: 206-292-4793 x2Web: www.theBOC.info
Email: [email protected]