Boiler Interlock And Protection
Manish DhruwAsst Manager
14843Cpp-540
Boiler Interlock - A Boiler Interlock is an arrangement of heating controls. It ensures the boiler does not fire when there is no demand for heat.
Protection of boiler – Boiler protection are provide to detect the abnormal condition by constantly measuring the various parameter under normal and faulty condition. If any abnormality happened trip the boiler to prevent from major damage.
Need of Interlocks & Protection◦ To avoid operational faults◦ To avoid equipments damage.◦ To avoid accidents to individuals.◦ To avoid system disturbances
Boiler interlock and protection
1. Both ID fan trip. 2. Both FD fans trip. 3. Emergency manual
trip. 4. Turbine tripped and
HPLP bypass not opened (RH protection act).
5. Drum level low low low (<-325mm with 5 sec delay).
6. Total air flow<30%. 7. Furnace pressure
low low low (<-254 mm of H2O).
8. Furnace pressure high high high (>+330 mm of H2O).
In case of MFT Trip
• 9. Unit flame failure.• 10. Loss of fuel.• 11. Loss of scanner
cooling air (Scanner air pressure<2 KPa with 5 min time delay).
• 12. Both APH tripped.• 13. Oil burner light off
failed. • Other than MFT-• 1. MS
temperature≥5850C (5 sec time delay).
• 2. RH temperature≥5850C (5 sec time delay).
Master Fuel Trip - it produces trip signal for fuel systems from operation , then trip the boiler out of service away from danger. this relay needs many conditions to operate , these conditions will be found at the following points.
Interlocks cum protections
1. If one ID fan trips, one FD fan will trip in the same sequence. 2. If one FD fan trips, one ID fan will trip in the same sequence. 3. If one APH trips, one ID fan, one FD fan and one PA fan will
trip in the same sequence. 4. In case of GCB opening, top elevation mill or non adjacent
mill will trip. 5. If drum level≥200 mm, EBD will open. 6. If drum level≤150 mm, EBD will close. 7. Feed water flow<50 TPH, Economiser recirculation MOV will
open. 8. Feed water flow>80 TPH, Economiser recirculation MOV will
close. 9. If superheated steam pressure is higher than 14.86 MPa ERV
will open and if pressure is lower than the value ERV will close (if kept in service).
Boiler
1. Boiler drum pressure- a) Higher than 17.24 MPa LHS safety valve will lift
and it will reset @ 16.35 MPa. b) Higher than 16.74 MPa RHS safety valve will lift
and it will reset @ 16.21 MPa.
2. Superheated steam pressure- a) Higher than 15.29 MPa, LHS safety valve will lift
and it will reset @ 14.765 MPa. b) Higher than 15.2 MPa, RHS safety valve will lift
and it will reset @ 14.747 MPa.
3. CRH steam pressure- a) Higher than 3.058 MPa, LHS safety valve will lift
and it will reset @ 2.947 MPa. b) Higher than 2.963 MPa, RHS safety valve will lift
and it will reset @ 2.867 MPa.
4. HRH steam pressure- a) Higher than 2.817 MPa, LHS safety valve will lift
and it will reset @ 2.726 MPa. b) Higher than 2.75 MPa, RHS safety valve will lift
and it will reset @ 2. 62 MPa.
Other Protections
Drum level 1. Level>125 mm: high
priority alarm. 2. Level>-125 mm: high
priority alarm. 3. Level>250 mm:
emergency priority alarm. 4. Level>-250 mm:
emergency priority alarm. Furnace pressure 1. Pressure>30 mm of
H2O: high priority alarm. 2. Pressure>-30 mm of
H2O: high priority alarm. 3. Pressure>50 mm of
H2O: emergency priority alarm.
4. Pressure>-50 mm of H2O: emergency priority alarm.
MS flow 1. MS flow>200 TPH: high
priority alarm. 2. MS flow>450 TPH:
emergency priority alarm.
Alarm
• MS & RH Temperature• 1. MS temperature>5450C:
high priority alarm.• 2. MS temperature>5500C:
emergency priority alarm.• 3. RH temperature>5450C:
high priority alarm.• 4. RH temperature>5500C:
emergency priority alarm.• Others• 1. APH flue gas inlet
temperature<3000C: high priority alarm.
• 2. O2<1: high priority alarm.
• 3. O2 zero: emergency priority alarm.
• 4. Furnace DP≥90 mm of H2O: high priority alarm.
• 5. Furnace DP≤10 mm of H2O: high priority alarm.
1. No ID fan A/B converter/ device fault. 2. No ID fan protection acted. 3. ID fan A/B inlet & outlet damper
closed. 4. ID fan IGV in minimum position. 5. APH A/B flue gas inlet & outlet damper
open. 6. APH A/B running
1. ID fan A/B breaker protection acted. Or
2. BMS trip ID fan A/B. Or 3. FD fan A/B tripped. Or 4. APH A/B tripped. Or 5. ID fan A/B temperature protection
acted. 6. ID fan A/B vibration protection acted. 7. ID fan A/B running and fan outlet
damper closed.
Start enabl
e Interlock:
TRIP enabl
e Interlock:
ID Fan interlock & protection
AND
OR
ALARM
1. Fan/ motor bearing temperature≥750C: high priority alarm.
2. Fan/ motor bearing temperature≥800C: emergency priority alarm.
3. Fan bearing vibration≥6.3 mm/sec: high priority alarm.
4. Fan bearing vibration≥11mm/sec: emergency priority alarm.
5. Motor winding temperature≥1100C: high priority alarm.
6. Motor winding temperature≥1200C: emergency priority alarm
TRIP 1. Motor winding temperature≥1300C (2 out of
6 temperatures with 60sec time delay). 2. Fan/ motor bearing temperature≥900C (with
60 sec time delay). 3. Fan bearing vibration≥11mm/sec ( with 60
sec time delay). 4. ID fan motor protection (over current, earth
fault, negative sequence, phase fault etc) acted.
5. BMS trip ID fan. 6. FD fan trip to ID fan trip. 7. ID fan running and fan discharge damper
closed. 8. APH trip to ID fan trip.
1. No FD fan A/B converter/ device fault. 2. No FD fan protection acted. 3. FD fan A/B outlet damper closed. 4. FD fan IGV in minimum position. 5. APH A/B flue gas inlet & outlet damper
open. 6. APH A/B running. 7. ID fan A/B running.
1. FD fan A/B breaker protection acted. Or
2. BMS trip FD fan A/B. Or 3. ID fan A/B tripped. Or 4. APH A/B tripped. Or 5. FD fan A/B temperature protection
acted. 6. FD fan A/B vibration protection acted. 7. FD fan A/B running and fan outlet
damper closed.
AND
OR
FD Fan interlock & protection
Start enable Interlock:
TRIP enable Interlock:
ALARM 1. Fan/ motor bearing temperature≥750C: high
priority alarm. 2. Fan/ motor bearing temperature≥800C: emergency
priority alarm. 3. Fan bearing vibration≥6.3 mm/sec: high priority
alarm. 4. Fan bearing vibration≥11mm/sec: emergency
priority alarm. 5. Motor winding temperature≥1100C: high priority
alarm. 6. Motor winding temperature≥1200C: emergency
priority alarm.TRIP
1. Motor winding temperature≥1300C (2 out of 6 temperatures with 60sec time delay).2. Fan/ motor bearing temperature≥900C with 60 sec time delay.3. Fan bearing vibration≥11mm/sec with 60 sec time delay.4. FD fan motor protection (over current, earth fault, negative sequence, phase fault etc) acted.5. BMS trip FD fan.6. ID fan trip to FD fan trip.7. FD fan running and fan discharge damper closed
1. No PA fan A/B converter/ device fault. 2. No PA fan protection acted. 3. PA fan A/B outlet damper closed. 4. PA fan IGV in minimum position. 5. APH A/B flue gas inlet & outlet
damper open. 6. APH A/B running. 7. ID fan A/B running. 8. FD fan A/B running. 9. No boiler trip command.
1. PA fan A/B breaker protection acted. Or
2. MFT trip PA fan A/B. Or 3. ID fan A/B tripped. Or 4. FD A/B tripped. Or 5. PA fan A/B temperature protection
acted. 6. PA fan A/B vibration protection acted. 7. PA fan A/B running and fan outlet
damper closed
Start enable Interlock
Trip enable Interlock:
PA Fan interlock & protection
AND
• OR
ALARM 1. Fan/ motor bearing temperature≥750C: high priority alarm. 2. Fan/ motor bearing temperature≥800C: emergency priority
alarm. 3. Fan bearing vibration≥6.3 mm/sec: high priority alarm. 4. Fan bearing vibration≥11mm/sec: emergency priority alarm. 5. Motor winding temperature≥1100C: high priority alarm. 6. Motor winding temperature≥1200C: emergency priority alarm.
TRIP 1. Motor winding temperature≥1300C (2 out of 6 temperatures
with 60 sec time delay). 2. Fan/ motor bearing temperature≥900C with 60 sec time delay. 3. Fan bearing vibration≥11mm/sec with 60 sec time delay. 4. PA fan motor protection (over current, earth fault, negative
sequence, phase fault etc) acted. 5. MFT trip PA fan. 6. ID fan/ FD fan A/B trip to PA fan A/B trip. 7. PA fan running and fan discharge damper closed.
1. No fan converter/ device/ breaker fault.
2. Any one PA fan running. 3. Fan IGV in minimum position. 4. In case of one fan running & other
fan standby- a) If running fan getting tripped
due to any protection acting then stand by fan will start in interlock if selected.
b) If seal air pressure becomes low (<6 KPa), then standby fan will start by interlock.
4. During unit start up fan start enable will come with the start of any PA fan if selected in fan auto start interlock.
**Command will go to Seal air fan IGV for 60% opening in auto with the start of the fan.
1. Fan breaker protection acted. Or 2. Both PA fans are stopped (after
2S fan will stop).or 3. In case of both seal air fan
running and seal air header pressure>22 KPa then one seal air fan will stop in auto if selected in interlock (discharge pressure
Start enable interlock
Trip enable interlock:
Seal air fan interlock & protection
• AND
• OR
1. Seal air fan current>200 Amp: high priority alarm.
2. Seal air fan current>260 Amp: emergency priority alarm.
3. Seal air discharge pressure<800: high priority alarm.
4. Seal air discharge pressure<600: emergency priority alarm.
1. Seal air fan current≥ 284Amp.
2. Both PA fans stopped/ tripped (fan trip after 2Sec).
3. Seal air fan breaker protection acted.
4. Seal air header pressure>22 KPa (in case of both fans are running), trip one fan.
ALAR
M
TRIP
1. No motor or breaker protection acted.
2. Fan is in remote. 3. In case of one fan is running
and the other is in stopped condition-
a) By interlock input if one fan is stopped/ tripped, standby fan will start in auto.
b) If scanner air header pressure<2 KPa for 5 sec, then standby fan will start in auto by interlock input.
1. Scanner air header pressure< low switch acting: emergency priority alarm.
2. Scanner air fan trip: emergency priority alarm.
1. Scanner air fan breaker protection acted.
2. Scanner air fan motor protection acted.
Start Enable Interlo
ck
Alarm
Trip
Scanner Air Fan Interlock Protection
AND
1. No breaker/ motor protection acted.
2. Lube oil pressure normal for > 5 minutes.
3. No MFT acted. 4. Boiler drum pressure>3.4
kg/cm2. 5. Secondary air
temperature>1770C. 6. Total air flow<40%
(230TPH). 7. MDVs are open. 8. Mill outlet
temperature<1150C. 9. Cold air gate is open. 10. Coal feeder is in remote. 11. PA permit satisfied. 12. Mill ignition permit
satisfied.
AND
Mill Interlock & Protection
Start Enable
Interlock
1. Feeder trip and no mill ignition permit.
2. MFT. 3. MDVs closed. 4. Lube oil pressure low (2 out of
3 lube oil pressure<low switch act).
5. Seal air differential pressure low low.
6. Loss of primary air (differential pressure between APH outlet primary air and furnace pressure less than 460mm of H2O.
Other Interlocks: 1. On tripping of mill Close
command will go to HAG. 2. In case of GCB opening and
unit coming to house load, top/ non adjacent mill will trip.
3. In case of one ID fan tripping, one top elevation mill will trip.
TRIP Enabl
e Interlock
AND
1. Mill lube/ hydraulic oil tank temperature>750C: high priority alarm.
2. Mill lube oil thrust pad oil temperature>600C: high priority alarm.
3. Mill lube oil thrust pad oil temperature>700C: emergency priority alarm.
4. Mill motor front/ rear bearing temperature>750C: high priority alarm.
4. Mill motor winding temperature>1000C: high priority alarm.
5. Mill outlet, roller bearing temperature>900C: high priority alarm.
6. Mill current>60 amp: high priority alarm.
7. Mill inlet PA flow< 50 TPH: high priority alarm.
8. Mill hydraulic pressure>150 kg/cm2: high priority alarm.
9. Mill hydraulic pressure<70 kg/cm2: high priority alarm.
10. Seal air header pressure<800 mm of H2O: high priority alarm.
11. Seal air header pressure<600 mm of H2O: emergency priority alarm.
Alarm
1. Mill motor protection (over current, earth fault, negative sequence, phase fault etc) acted.
2. MFT trip mills. 3. MDVs closed trip mill (2 out of 4
MDVs). 4. Mill lube oil pressure low (2 out of
lube oil pressure<low switch acting) trip mill.
5. Loss of primary air (differential pressure between APH outlet primary air and furnace pressure less than 460mm of H2O).
6. Feeder trip and no mill ignition permit.
7. Seal air differential pressure low low.
8. Mill lube oil pump in local. OTHERS 1. In case of GCB opening and unit
coming to house load, top/ non adjacent mill will trip.
2. In case of one ID fan tripping, one top elevation mill will trip.
Trip
Start enable Interlock: 1. No breaker or motor
protection acted. 2. Respective mill ignition
permit. 3. Feeder speed (VFD
command) minimum. 4. No mill trip command. 5. Feeder is in remote.
1. Mill trip/ emergency stop. 2. MFT. 3. Feeder running and no coal. 4. Mill outlet
temperature<540C and HAG closed and feeder VFD command<2%.
AND
OR
Coal Feeder Interlock & Protection
Start Enable
Interlo
ck
Stop/Trip Enable Interlo
ck:
1. Belt deviation of feeder switch act: high priority alarm.
2. No coal switch act: high priority alarm.
3. Coal jam switch act: low priority alarm.
4. Feeder cleaner motor fault: low priority alarm.
5. Coal flow zero: low priority alarm.
1. Mill trip to feeder trip. 2. MFT to feeder trip. 3. Feeder motor/ breaker protection
acted. 4. Feeder running and no coal. 5. Mill outlet temperature<540C and
HAG closed and feeder VFD command<2%.
Alarm
Trip
1. No breaker or motor protection acted.
2. LOP is in remote. 3. Oil pool temperature of lube
oil>600C.
1. Oil pool temperature of lube oil<450C.
2. After LOP starting if oil pool temperature of lube oil<450C and mill not running (30 mins time delay).
3. After mill stopping after 4 hrs time delay stop command will go for LOP.
AND
OR
Start enable Interlock
Stop/trip enable Interlock
Mill Lub Oil Pump Interlock & Protection
1. Lube oil pump stopped: emergency priority alarm.
2. Lube oil pressure<low switch act: emergency priority alarm.
3. Oil pool temperature>: 750C high priority alarm.
4. Lube oil thrust liner sump temperature>: 600C high priority alarm.
5. Lube oil thrust liner sump temperature>: 700C emergency priority alarm.
1. LOP motor/ breaker protection acted.
2. Oil pool temperature of lube oil<450C.
3. After LOP starting if oil pool temperature of lube oil<450C and mill not running (30 mins time delay).
4. After mill stopping after 4 hrs time delay stop command will go to LOP.
Alarm
Trip
1. No breaker or motor protection acted. 2. APH is in remote. 3. Guide and support bearing oil pump
running for minimum of 300 sec (for U#2 APH).
1. APH flue gas inlet temperature<800C
and fans (ID, FD & PA) are running. 2. For APH auxiliary motor, with the start
of APH main motor trip command will go.
Start enabl
e Interlock
Stop/trip
enable
Interlock:
APH Interlock & Protection
AND
OR
• Other Interlocks:• 1. Start command will go for APH auxiliary motor (DC) with
the tripping of APH main motor.• 2. In case of APH main motor VFD getting bypassed due to
any fault, APH main motor DOL supply will pick up.• 3. For U#2 APH-• a) If APH support/guide bearing temperature> 540C, lube oil
pump will start.• b) If APH support/guide bearing temperature< 500C, lube oil
pump will stop