bo-cgm.3/3 mv switchgear secondary distribution networks medium voltage switchgea… · mv...

6
power www.ppi.ph pazifik Manufactured by: Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kV MV Switchgear Secondary Distribution Networks • Protection and safety for people, goods and equipment against internal arc effects, proven through test performed in accordance with IEC 62271-200 standard. • Capable of withstanding harsh environmental conditions (including flooding), long service life and absence of maintenance in live parts through full gas insulation and the use of screened connectors. • Full modularity and future extensibility in both directions through the use of connecting set. Flexibility to configure all types of diagram. • Smaller size and lower weight, making handling and installation easier. • Safe and simple operation through the use of user-friendly driving mechanisms, including interlocks as standard. BO-CGM.3/3 SMART RMU Switchgear in Metro Manila

Upload: vohanh

Post on 15-Apr-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

powerwww.ppi.ph

pazifik

Manufactured by:

Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kV

MV Switchgear Secondary Distribution Networks

•Protectionandsafetyforpeople,goodsandequipmentagainstinternalarc effects, proven through test performed in accordance with IEC62271-200standard.

•Capable of withstanding harsh environmental conditions (includingflooding), longservice lifeandabsenceofmaintenance in livepartsthroughfullgasinsulationandtheuseofscreenedconnectors.

•Fullmodularityandfutureextensibilityinbothdirectionsthroughtheuseofconnectingset.Flexibilitytoconfigurealltypesofdiagram.

•Smallersizeandlowerweight,makinghandlingandinstallationeasier.

•Safe and simple operation through the use of user-friendly drivingmechanisms,includinginterlocksasstandard.

BO-CGM.3/3

SMART RMU Switchgear in Metro Manila

Page 2: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

General Description

ConsistsofawiderangeofSF6fullyinsulatedcompact,modularcubiclesenablingtheconfigurationofanyelectricaldiagraminMediumVoltageSecondaryDistributionnetworksupto36kV.

Thisdevelopmentbringsahighlysafe,reliableanduser-friendlyassembly,capableofwithstandingallenvironmentalconditions.

The performance of routine test across the various phases ofthe assembly procedure and the use of the most innovativemanufacturingtechniquesassurethehighestlevelofquality,asreflectedinitsISO9001certification.

Features

• Protection and safety for people, goods and equipmentagainstinternalarceffects,proventhroughtestperformedinaccordancewithIEC62271-200standard.

• Capable of withstanding harsh environmental conditions(including flooding), long service life and absence ofmaintenanceinlivepartsthroughfullgasinsulationandtheuseofscreenedconnectors.

• Full modularity and future extensibility in both directionsthrough compact connecting set. Flexibility to configure alltypesofdiagramwiththeuseofaconnectingset.

• Smaller size and lower weight, making handling andinstallationeasier.

• Safe and simple operation through the use of user-friendlydrivingmechanisms,includinginterlocksasstandard.

• Extrasafety:incorporation,alightvoltagepresenceindicator;andoptionally,anacousticalarmpreventingearthing.

• Accessoriesandlivetestingasanoption.

• Horizontalfuseholderswithfrontaccess,protectedwithinagastank.

• Easy cable connection through front plug-in or screwableterminals.

Environmentally-friendly:

•Useofhighlyrecyclablematerials.•Minimalgasvolumeperfunctionalunit.•End-of-lifeproductmanagement.

Standards

IEC62271-1Common specifications for high-voltage switchgear andcontrolgearstandards.

IEC62271-200Alternatingcurrentmetal-enclosedswitchgearandcontrolgearforratedvoltagesabove1kVanduptoandincluding52kV.

IEC60265-1High-voltageswitches.Part1:Highvoltageswitchesforratedvoltagesabove1kVandlessthan52kV.

IEC62271-102Alternatingcurrentdisconnectorsandearthingswitches.

IEC62271-105Highvoltagealternatingcurrentswitch-fusecombinations.

IEC62271-100Highvoltagealternatingcurrentcircuit-breakers.

IEC60255Electricalrelays.

IEC60529Degreesofprotectionprovidedbyenclosures.

IEC61958Voltagepresenceindicatingsystems.

TheFullyGas-InsulatedModularandCompact(RMU)Systemmeetstheimmersiontestat3meterswatercolumnpressure,24 hours at rated voltage and insulating test at powerfrequency.

Page 3: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

Technical Characteristics Fully Gas-Insulated Modular and Compact (RMU) SystemL P V(AV) V(RAV) S S-Pt M RC RB 2LP

RatedVoltage(kV) 36RatedCurrent(A)

Busbars 400/630Outgoing 400/630 200 400/630 400/630 - - - 400/630 400/630 400/630(L)

200(P)Short-timecurrent(kA1/3s)

16/20* 16/20* 16/20* 16/20* 16/20* 16/20* - - 16/20* 16/20*

Insulationlevel:PowerFrequency(kV) 70/80 70/80 70/80 70/80 70/80 70/80 70/80 - 70/80 70/80Lightningimpulse(kV)PEAK

170/195 170/195 170/195 170/195 170/195 170/195 170/195 - 170/195 170/195

Rated-frequency(Hz) 50/60**IPrateGeneral IP2XDGastankandfuseholders IPX8PhysicalCharacteristics L P V(AV) V(RAV) S S-Pt M RC RB 2LPHeight(mm) 1745 1745 1745 1800 1745 1745 1950 1745 1745 1745Width(mm) 418 480 600 600 418 600 900/1100 368 418 1316Depth(mm) 845 1010 850 850 845 845 1160 831 850 1027Weight(kg)# 138 211 240 240 135 175 290* 42 138 421

Types of Modules

(*)Testperformedat21kA.(**)Valuesrepresentedat50Hz,forotherfrequenciespleasecontactourtechnical-CommercialDepartment.(#)Withoutrelays,motordrivingmechanismsandtransformers.

Compact cubicle with two feeder and onefused-protectionfunctionalunits(RMUtype).

Busbarrisingfunctionalunit.

Cablerisingfunctionalunit.

Incomingfeederorlinefunctionalunit.

Fused-protectionfunctionalunit

Vacuumcircuitbreakerprotectionfunctionalunit,withorwithoutrecloser(RAVorAVdrivingmechanism).

Meteringfunctionalunit(differentconfiguration)

Busbarswitchwithearthingunit.

Busbarswitchfunctionalunit

Page 4: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

Applications

Usedforawidevarietyoffacilities,bothpublicandprivateitsmainapplicationsare:

• Utilitytransformersubstations.• Privatetransformersubstations.• Switchingsubstations.• Remotecontrolledsubstations.• Infrastructures.

• Industrialfacilities• Windfarms.• Photovoltaicfacilities.• Co-generationfacilities• etc.

PublicApplication PrivateApplication

Modularity.

Theextensiblecubicleshavesidefemalebushingtoconnect themain busbars through this connectingset. This allows current to flow, while controllingtheelectric fieldbymeansof insulatingelastomerlayers,freeofpartialdischarges.

Thanks to the design of the connecting set, aninternalequipotentialareaiscreated.Hereanumberofcontactsaredistributedinacircleforconnectiontothefemalebushings.

A reliable, strong electrical continuity is thereforeachieved, even when exposed to a short-circuitcurrent. The connecting set also maintains alloperationalfeaturesofthecubicles.

Whiletheinstallationisnotbeingextended,theextensiblecubicles have removable sealing elements for the femalebushings.

The cubicle connecting procedure stands out for its ease and speed of on-siteinstallation,includinginTransformerSubstationswithunevenfloors.

The modularity and extensibility of the system ensure maximum flexibility toconfigureanykindofmediumvoltageelectricaldiagram.

Page 5: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

Safety

• Personal,goodsandequipmentprotectionagainsttheeffectsofinternalarcs.

• Capability of withstanding harsh environmental conditions(humidity,salinity,dust,pollution,etc.)andprotectionagainstindirectcontacts.

• Theleak-proofandsealedsteelgastank,housesthebreakingandswitchingcomponents.

• IP2XDIPratingofthecubicleassembly.

• Voltagepresencedetection.

• Anacousticalarmpreventingearthing(asanoption).

• Front driving mechanisms that allow safe and simpleoperations.

• Horizontalfuseholderswithfrontaccess,protectedwithinagastank.

• Standard internal interlockspreventing improperoperations,in accordance with IEC 62271-200 standard. Additionalinterlockswithpadlockorlock,asanoption.

Reliability

• Routineandtraceabilityfactory-testinginallequipments.

• Interlocksbetweentheswitchingandbreakingcomponents.

• Visualdisplayofthepositionoftheswitchgearinthesynopticdiagram,validatedbythekinematicchaintestinaccordancewithIEC62271-102.

• Highanti-corrosivelevelsachievedwiththeuseofinnovativematerials.

• Maintenance-freeliveparts.

• Possibility of assembling accessories and performing testundervoltage.

• Easycableconnection,withplug-inorscrewedconnectors.

Protection, Control and Automation

FocusingonMediumVoltage,Ormazabalhasabroadrangeofprotectionandautomationapplicationsandservicescapableofmeetingtheneedsofanydistributionnetwork.

Medium voltage cubicle-integrated units provide the ideasolutionforimplementationinthemostdemandingoffacilities,offeringahighlevelofserviceincomparisonwithconventionalsystem.

Applications

Protection• MVCustomerSupplies• ProtectionforSwitchingandPrivateIndustrialSubstations• RuralTS(CTR)protection• GeneratorSetProtection• SubstationProtection

AutomationandRemoteControl• RemoteControl• AutomaticTransfers• FaultDetection• Acousticvoltagepresencealarm• SecondarySwitchingPoints

Internal Arc

Thecubiclesaredesignedtoprotectpeopleandgoodsagainstthe effect of internal arcs, complying with the criteria of IEC62271-200standard,AppendixA:

Gastankinternalarc:16kA0,5s/20*kA0,5sGastankinternalarc:16kA1s/20*kA1s#IACAFLClass:16kA1s/20*kA1s#

(*)Testsperformedat21kA(#)ExceptforCGM.3-VwithRAVmechanism.

Page 6: BO-CGM.3/3 MV Switchgear Secondary Distribution Networks Medium Voltage Switchgea… · MV Switchgear Secondary Distribution Networks ... Technical Characteristics Fully Gas-Insulated

TRIDELTA

Single HighPrecision Superstatic and Tamper Proof Meter

(Landis+Gyr, Switzerland)

A solution package for system integration, substation automation and energy management system.(SCADAFLEX, PPI Pazifik Power

Inc., Phils.)

Turnkey Substation up to 100MVA (PPI Pazifik Power, Inc., Philippines)

Modular UPS solutions in multiple capacity options

(Gamatronics, Israel)

State of the art Meter Testing and Calibration Equipment and

Instrument Test Set(MTE, Switzerland)

Protection of transformers, switch-gears and plants against

atmospheric and switchingovervoltages

(Tridelta, Germany)

Glass Fibre reinforced vacuum technology (GVT) for various

applications(WTW, Germany)

Fully Automatic Measurement of the dielectric strength of liquid

insulators up to 100 kV.(BAUR, Austria)

Dry-Type Resin Insulated Out-door/Indoor Current Transformer

and Potential Transformer(WTW, Germany)

Batteries that are robust energy storage solutions, with a proven

technology that has been used for decades.

(Sunlight, Greece)

pazifikpowerwww.ppi.ph

manage energy better

Instrument Transformers

®

Our Power Your Confidence Instrument Transformers

HORSTMANNGmbH

HORSTMANNGmbH

Fully Electronic and Self-Adjusting Fault Circuit Indicator

(Horstmann, Germany)

scadaflexSubstation Automation System

Disconnecting Switches15kV up to 800kV

(Hapam, Netherlands)

Efficient Electricity SolutionsPPIisacompanywithmorethantwenty(20)yearsofsuccessfuloperationinthePhilippines.

Overtheyears,ithasdevelopedandactivelysuppliedanextensiveandfullpowerlineofproductsandservicesfromthebestmanufacturersinEurope.Amongitsmostsoughttopofthelineproductsare:Turnkeyprojectsinthesupplyofsubstationswithratedvoltageofupto230kV,electricitymeters,meter test equipment, instrument transformers, power transformers, disconnectors, fault indicators, surgearresters, switchgears, oiltesters,cablediagnostics,batteries,harmonicfilters,andautomationsystems,amongothers.

Ourcommitmenttoestablishclosercustomerrelationshipsmakeusunderstandyourbusinessneedsandpowersolutionrequirements.

MAKATI HEAD OFFICE4/Fand6/F,SouthParkPlaza,SantiagoStreetPaseodeMagallanesCommercialCenter1232MakatiCity,MetroManila,Philippines

CEBU BRANCHUnit3ASYBldg.A.C.CortesAve.MandaueCity,Cebu,Philippines

Tel.:+6325118888|Fax:+6328364323E-mail:[email protected]|Website:www.ppi.phFacebook:www.facebook.com/PazifikPowerInc