premset : a new generation of mv switchgear
DESCRIPTION
Premset : A New generation of MV Switchgear. Amith Ganasram August 15, 2014. Wiki : “Innovation is finding a better way of doing something. The term innovation can be defined as something original and, as a consequence, new, that "breaks into" the market or society.” . - PowerPoint PPT PresentationTRANSCRIPT
Premset : A New generation of MV Switchgear
Amith GanasramAugust 15, 2014
Schneider Electric 2- Energy – Premset – Weili Ding - Sep 2013
Wiki : “Innovation is finding a better way of doing something.
The term innovation can be defined as something original and, as a consequence, new, that "breaks into" the market or society.”
Schneider Electric 3- Premset Openline
A1
A3
A5
A4
A6
A2
A4
A4
What’s Premset and where is it sold ?● Premset core technical application
● Compact, modular, smart ready switchgear● Circuit breaker up to 17.5KV, 1250A, 25 KA 3s, IAC 25 KA 0,5s
● Market main application: ● Low-end Primary● High End Secondary
●Targeted segments● CIB : Commercial and Industrial Buildings● Utility : MV/MV Substations● Data Centres● Hospital● Industry● MMM● Infrastructure
Schneider Electric 5- Energy – Premset – Weili Ding - Sep 2013
Voice from Customers in MV Distribution network
- “ you have to take in account the smart grid trend ”
- “ expected life duration of switchgear is increasing ”
- “ maintenance-free is far more important than SF6-free”
- “ we want a switchgear with Easy Operation for our maintenance and operation teams”
- “ cost effective and compact Circuit Breakers are needed for small primary substations or loop management ”
- “ no problems with GIS switchgear, because reliable in harsh environment (humidity, temperature, dust, poor installation, partial discharges) ”
- “ I’ll never compromise about end-users safety ”
Schneider Electric 6- Energy – Premset – Weili Ding - Sep 2013
New generation of switchgear - Premset
Premset
Schneider Electric 7- Premset Openline
Key BenefitsS
impl
e -
Saf
e -
Sm
art
Safety
Reliability
Flexibility
Efficiency
Schneider Electric 8- Energy – Premset – Weili Ding - Sep 2013
Premset Totally Shielded Solid Insulation System design for optimized safety and extended equipment life
3
1
2
1- Low Voltage cabinet
2- Cable test
3- Top connections
4 - Core unit
5 - Bottom connections
6 - Bottom compartment
7 - Sensors (CTs and VTs)
8 - Gas exhaust duct
4
5
6
7
8
Schneider Electric 9- Energy – Premset – Weili Ding - Sep 2013
All surfaces at earth potential● No dielectric ageing● Long product life expectancy● Reduced internal arc risk● Accidentally touchable● Insensitive to harsh environment
Safety & Reliability - SSISTotally Shielded Solid Insulation System design for optimized safety and extended equipment life
Schneider Electric 10- Energy – Premset – Weili Ding - Sep 2013
Safety & Reliability - SSIS
Well-known
Technologies
(epoxy, EPDM*)
All surfaces at earth potential
*EPDM: Ethylene Propylene Diene Monomer rubber
Single bus bar (630A) Cable connection
Busbars with shielded solid insulationPatented flat connectics
Solid insulation
covered by a
conductive layer
Schneider Electric 11- Energy – Premset – Weili Ding - Sep 2013
Safety & Reliability - SSISEarth shield continuity ensured by Patented Flat Interface
Main advantages compared with traditional conical interface ● Simplicity of installation● Compactness● Flexibility
Flat interface cross-sectionElectrical field calculation .
Schneider Electric 12- Energy – Premset – Weili Ding - Sep 2013
Safety & Reliability – 3 Position SchemeDisconnection in vacuum & earthing switch in controlled air
● redundancy of isolation
- vacuum bottles for breaking
and disconnection
- controlled air for downstream
earthing switch in sealed-for-life screened tank.
Breaking and disconnection
Earthingswitch
Operation of earthingswitchOperation of mainswitch
Schneider Electric 13- Energy – Premset – Weili Ding - Sep 2013
“The most intuitive operations for breaking, disconnection and earthing”
3-in-1 integrated architecture: easiest and safest operation, with built-in interlocking
Safety & Reliability - Interlocking
Schneider Electric 14- Energy – Premset – Weili Ding - Sep 2013
Safety & Reliability – 3 Position SchemeDisconnection in vacuum & earthing switch in controlled air
Schneider Electric 15- Energy – Premset – Weili Ding - Sep 2013
Safety – Cable Testing Device Cable testing and diagnosis: dedicated device, for easy access and total safety
● Cable testing without accessing cable box or dismantling cable connections
● Test device connection from the front of the switchboard, while cables remain earthed
● Failsafe interlocks with earthed star point
Easy cabling All cables connections are aligned in front at a height of 700 mm
Schneider Electric 16- Energy – Premset – Weili Ding - Sep 2013
Safety – Cable Testing DeviceCable testing and diagnosis: dedicated device, for easy access and total safety
Schneider Electric 17- Energy – Premset – Weili Ding - Sep 2013
Safety & Reliablity – Live Cable Interlocking Live cable interlock - Electrical lock-out of earthing switch when live cables
● Earthing switch lock-out function
- Prevent the earthing switch to be closed on earth when cables are still alive
- Positively blocked in case of auxiliary power loss
- Override unlocking by key
- Remote indication of locked position
Schneider Electric 18- Energy – Premset – Weili Ding - Sep 2013
Efficiency Flexible approach & Embedded intelligence in switchgear
Today: set of products to connect - Protections: Sepam, Micom
- Measurement metering: Power Logic
- Local fault monitoring & Remote control: Easergy
Sepam & Micom
Easergy
Power Logic
Modules fully integrated in functional unit - Including sensors, switchgear interface, power supply, communication, HMI
- Pre- engineered, factory-tested, cost effective
- Easy integration based on :. Field bus communication between modules. Pre-cabling inside cubicle
- Gradual solution : from local control up to complex feeder automation
Schneider Electric 19- Energy – Premset – Weili Ding - Sep 2013
Efficiency“Integrated intelligence” in MV switchgear
SC100
Energy Quality Monitoring
Self powered Protection
Flair
Modbus
Faultdetection
VIPPM200
Switch Controller
R200 PS100
Power SupplyRTU/ATS
SMART
- IEC61850 access to Substation automation through gateway (G3200…)
Schneider Electric 20- Energy – Premset – Weili Ding - Sep 2013
Efficiency Low cost Supervision & Control system
Example of web access
● Switchboard information is stored in a Web page● Need just a PC, Tablet, Smart Phone with a standard Web browser
Schneider Electric 21- Energy – Premset – Weili Ding - Sep 2013
FlexibilityA new level for MV switchgear Modularity ► assembly of functional bricks
CBCBLBSLBS CB
LV cabinet
Cable test
Top connection
Bottom connections
Bottom compartment
Core unit
Metering
Schneider Electric 22- Premset Openline
Technical Description & Applications
Schneider Electric 23- Energy – Premset – Weili Ding - Sep 2013
Main Characteristics
Rated voltage 15 kV
Short time withstand 25 kA x 3s*, 21 kA x 3s, 20 kA x4s
Rated busbar current 630 A, 1250 A (under development)
Rated BIL withstand voltage 95 / 110 kV
Rated PF withstand voltage 42 / 48 kV 1mn
Cable earthing switch 25 kA, M0, E2
Degree of protection IP3X (indoor), IP54 (outdoor)
Dimensions W x H x D (mm) 375 x 1600 x 900 (indoor)
Ran
ge
* : 25kA x 3son request
Internal arc Standard design is virtually arc free Optional : type tested 21KA 1s A-FLR / 25KA 0.5s A-FLR
: top or bottom exhaust Comply with new IEC standard 62271-200 ALFR
INDOOR
OUTDOOR
Schneider Electric 24- Energy – Premset – Weili Ding - Sep 2013
Four basic functional units
630A disconnecting load break switch1000 operations
► I06 TNetwork management
100 or 200A disconnecting circuit breaker O-15 sec- CO2000 operations
► D01-02 NTransformer protection
630A disconnecting circuit breaker O-15 sec-CO.2000 operations
► D06 N Feeder protection
630A disconnecting circuit breaker O-0,3s-CO-15s-CO 10,000 operations
► D06 H Feeder protectionAuto-reclose
Schneider Electric 25- Energy – Premset – Weili Ding - Sep 2013
Typical applications
Building
Industry
Energy
2.25m
3.75 m
3.75 m
2.25 m
IEC standard 62271-200 ALFR
Schneider Electric 26- Energy – Premset – Weili Ding - Sep 2013
MV Innovation in 20 years – Premset !
Amith GanasramCell : 076 411 2263Tel: 011 254 6638Email: [email protected]
Thank you for your attention…