Avaya Communication Manager (Release 1.3.1) with an Avaya DEFINITY ® Server R Load R011r.03.1.531.0 Change Notice 1364B Attachment Package 700241888: Field technician/engineer general information...........2 Update notes............................................6 Update procedures.......................................9 “Standard (simplex) reliability” update procedures....9 “High/critical (duplicated) reliability” update procedures 11 Label formats..........................................13 Reference documents....................................14 Change description...................................14 Hardware/firmware minimum vintage table..............14 Adjunct minimum vintage table........................14 Comcode 700241888 Issue 3 November 2002

Upload: others

Post on 03-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Avaya Communication Manager (Release 1.3.1)with an Avaya DEFINITY® Server RLoad R011r.03.1.531.0Change Notice 1364BAttachment Package 700241888:

Field technician/engineer general information.................................2Update notes...................................................................................6Update procedures..........................................................................9

“Standard (simplex) reliability” update procedures......................9“High/critical (duplicated) reliability” update procedures...........11

Label formats.................................................................................13Reference documents....................................................................14

Change description.....................................................................14Hardware/firmware minimum vintage table...............................14Adjunct minimum vintage table..................................................14Related documentation..............................................................14

Comcode 700241888Issue 3

November 2002

Page 2: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Field technician/engineer general information 2

Field technician/engineer general information

Overview

The purpose of this Change Notice is to provide new features, enhancements, and modifications for customers running Avaya Communication Manager Release 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 (all Communication Manager loads prior to R011r.03.1.531.0), with an Avaya DEFINITY Server R. For more detail, see the Change Description referenced on page 15 of this document.

This Change Notice is to be reactively applied to Avaya Communication Manager Release 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 (all Communication Manager loads prior to R011r.03.1.531.0), with an Avaya DEFINITY Server R requiring this load to correct a problem, per Customer, Avaya Sales/Service, or Authorized BusinessPartner request and approved (verifying that the customer has a valid target configuration) by Tier III or the Center of Excellence (CoE).

This change is technician installable and is service interrupting.

Coordination with other Change Notices is not required.

Material Requirements

Contact 800-422-6560, prompt 4, prompt 1 for all Avaya U.S. Direct material concerns.

U.S. Authorized BusinessPartners receive material shipped from the National Distribution Center. The service center at 800-222-7278 is the contact for all Avaya U.S. Indirect material concerns.

The ITAC/GSO (International Technical Assistance Center/Global Services Organization) Change Notice Administration Group in Denver is the contact for all non-U.S. material concerns and coordinates the ordering of material per the actual customer requirements shown on the ticket created in the implementation process.

The following material is required to implement this Change Notice and should be ordered from the Denver factory via this Change Notice:

System Comcode Quantity DescriptionUnduplicated 700236847 2 Magneto Optical DiskDuplicated 700236847 4 Magneto Optical DiskSimplex 2 Duplex 4

700276413 1 DEF SFTW SERVER R COMMUNICATION MANGER 1.3.1 MO

All 700261704 1 ASA 1.3 Software CD

The following material is also required to implement this Change Notice and should be downloaded. Please DO NOT order this material via this Change Notice. To download the necessary material:

1. Go to http://www.avaya.com/support and click Product Documentation.2. In the list on the left, click Communications Systems.3. Find Communication Manager. Under that, click 1.3.1.4. Under 1.3.1, click Installation & Maintenance, and then click

Communication Manager 1.3.1 Attachment Package for Server R.

System Qty Code/Comcode DescriptionAll 1 700241888 Attachment Package (See Note Below)

Page 3: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Field technician/engineer general information 3

Note: Attachment Package 700241888 (this document) provides the following:- Technician General Information - Hardware/Firmware Minimum Vintage Table- Update Notes - Adjunct Minimum Vintage Table- Update Procedures - Change Description- Label Formats - Document Reference ListNotify the customer of how the Change Description accompanying this upgrade can be found on the Avaya support Web site:

1. Go to http://www.avaya.com/support and click Product Documentation.

2. In the list on the left, click Communication Systems.

3. Find Communication Manager. Under that, click 1.3.1.

4. Under User Information, click DEFINITY Servers: Release Notes (Release 1.3.1 of the

Avaya Communication Manager).

5. On the bottom of the page under Files, click the link View HTML.

6. In the left hand pane, click the link titled Resolutions and Patches. This will present a list of .pdf documents

describing the changes from Release 1.3.

See the tables below for the billing breakdown of services based on contract terms.

U.S. Billing Information

Warranty/Maintenance Contract/Self Maintenance CustomersMaterial No charge - for all customersHelpline Assistance No charge - for all customersTechnician Labor 8AM-5PM

M-F No Charge S-S Applicable Overtime Rate

5PM-8AMM-F Applicable Overtime RateS-S Applicable Overtime Rate

Time and Material (T&M) CustomersMaterial No charge - for all customersHelpline Assistance Standard Charges ApplyTechnician Labor 8AM-5PM

M-F Standard Rate S-S Applicable Overtime Rate

5PM-8AMM-F Applicable Overtime RateS-S Applicable Overtime Rate

Non-U.S. Billing Information

Warranty/Maintenance Contract/Self Maintenance Offer Customers -

Helpline assistance is available at the CoEs at no charge. No customer charges for material. Customer charges for labor apply for work performed outside of normal business hours.

T&M Customers –

Helpline assistance is available at the CoEs at the predetermined in-country labor rate.

No customer charges for material. Labor charges for technician time apply at the predetermined in-country labor rate.

Page 4: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Field technician/engineer general information 4

Upgrade Instructions

In addition to travel time, it should take a technician an estimated 1.5 hours, maximum, for a simplex system software update or 2 hours, maximum, for a duplicated system software update per the instructions provided in the Update procedures section starting on page 9. Service is interrupted for approximately 10-15 minutes for an upgrade to a simplex system. Service is interrupted for less than one minute for a duplicated system software update on a DEFINITY Server R, except as indicated in the Update Procedures that begin on page 9.

The update instructions in this document are applicable only when updating the load on a configuration already running Avaya Communication Manager Release 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3, with a valid license file installed. Adding features or changing processor hardware requires the creation and installation of a license file using the Remote Feature Activation (RFA) process. See the RFA web site at https://rfa.avaya.com for further information. See the RFA Users Guide, chapter 5, on the aforementioned web site.

Avaya Site Administration version 1.11.05 is the minimum network administration solution required for Avaya Communication Manager Release 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3, with an Avaya DEFINITY Server R (hereafter Communication Manager R 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3).

Material Disposition

U.S. Direct, U.S. Indirect, Non-U.S. Direct, and Non-U.S. Indirect: There are no returns required per this Change Notice.

U.S. Indirect: The optical disks with software earlier than R011r.03.1.531.0 should be destroyed and disposed of locally in accordance with environmental guidelines. These optical disks are not reusable with any other software load and should not be left in a useable condition. Compliance with this measure prevents old software from being mistakenly re-installed, causing system problems.

The optical disks with R011r.03.1.531.0 software are to remain with the system. One optical disk should remain in each optical disk drive (TN2211). Additional optical disks should be given to the customer.

U.S. Indirect: The National Distribution Service Center will close the ticket immediately, since there are no returns required per this Change Notice.

Technical Escalation

The formal Technical Escalation Process to be used for technical questions pertaining to the application of this Change Notice is:

U.S. Direct: Contact the Technician “Help-Me” line at 1-800-248-1234 for assistance.

U.S. Indirect: Contact the Technician “Help-Me” line at 1-877-295-0099 for assistance.

NON-U.S.: Customers and dealers contact their Regional CoE.

Normal escalation procedures apply to this Change Notice.

Technician Time Reporting

Field Technicians implementing this change for U.S. customers are to report all activity for this Change Notice using the Activity Code “S”.

All arrangements for reimbursement/credit to BusinessPartner Accounts for implementation of this Change Notice follow standard processes. Contact local CoE Change Notice Coordinators for details on this process.

Page 5: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Field technician/engineer general information 5

Technicians report their time to the appropriate Regional Workgroup Service Manager in order to log their expenses to the appropriate International Change Notice Monthly Activity Report.

Reimbursement is limited as per the following:

Class S3 (Software) Time and Expense AuthorizationU.S. Avaya Warranty and Maintenance Time and MaterialTravel Time to Site 0.75 hour 0.75 hourImplementation Time (per site) Simplex System

Duplicated System1.5 hours2 hours

1.5 hours2 hours

Travel Expense N/A No reimbursementShipping Expense N/A No reimbursementNON-U.S. Avaya Warranty and Maintenance Time and MaterialTravel Time to Site 0.75 hours 0.75 hourImplementation Time (per site) Simplex System

Duplicated System1.5 hours2 hours

1.5 hours2 hours

Travel Expense N/A No reimbursementShipping Expense N/A No reimbursement

Page 6: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update notes6

Update notes

WARNING

READ THE FOLLOWING NOTES BEFORE PROCEEDING WITH THE UPDATE!

This information is intended to aid in the software update process.

WARNING!! WARNING!! WARNING!! WARNING!! WARNING!! WARNING!!

The update instructions in this document are applicable only when updating the load on configurations already running Communication Manager 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 with a valid license file installed. Upgrading from a previous release, adding features, or changing processor/MSS-NET (Mass Storage System Network Control) hardware requires the creation and installation of a license file using the RFA process. You must take training and pass a certification test before registering to use the RFA process. See the DEFINITY RFA URL:

https://rfa.avaya.com/

The most recent Communication Manager 1.1 init password change was made in load 01.0.059.0. Please contact the TSC (Technical Service Center) Data Base Administration group at 1-800-422-6560 for the new init password.

The default secret keys for Access Security Gateway (ASG) were also changed in load 01.0.059.0 for the craft, inads, and init logins. The new default secret keys are invoked for new software installs only. For updates and upgrades, the secret keys saved in translations remain in effect. For security reasons, most hand-held ASG challenge/response devices are no longer supported.

The default Product Identifier (PID) was changed in load 01.0.059.0 to indicate default ASG secret key selection to services and provisioning tools. Like the default ASG secret keys, the default PID is invoked only for new software installs. The existing PID is preserved during software updates or upgrades.

Before beginning the update, review the following for customer impact:

1. Multimedia Call Handling:

Multimedia-to-voice station calls are not preserved during an update. In order to properly release multimedia conversion resources and restore them to service after the update, the following steps must be executed prior to updating a Communication Manager 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 switch that has the Multimedia Call Handling (MMCH) customer option turned on. These steps apply only to High/Critical (duplicated) reliability configurations.

● Locate all MULTIMEDIA INTERFACE circuit cards (TN787) in the system using the “list configuration all” command.

● Locate all VOICE CONDITIONER circuit cards (TN788) in the system using the “list configuration all” command.

● Busy-out all MULTIMEDIA INTERFACE and VOICE CONDITIONER circuit cards using the “busyout board” command. This prevents any further multimedia-to-voice connections and drops any active connections.

Failure to busy-out the circuit cards before doing the update may result in unusable Multimedia Interface (TN787) and Voice Conditioner (TN788) ports.

2. Daylight Savings Rule:

Check to make sure that the system defaults to a rule value of “0”. Or, if the customer wants the switch to change time automatically for daylight savings, make sure that whatever number is selected for the Daylight Savings Rule on the SAT (System Access Terminal) screen “set time” is also entered as the “daylight savings rule” on the SAT screen “change locations”.

Page 7: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update notes7

3. Basic System Features:

● The “upgrade software” command preserves only calls in which two or more parties are connected and talking. Held calls, dialing calls, calls in queue, and calls connected to announcements, speech synthesis, or tones are not preserved. The only supported operation on a preserved call is to drop it. Other feature activation attempts are ignored.

● For a call-preserving update, the length of time during which calls cannot be originated is very short (estimated at less than 5 seconds for most cases). In the worst case, it is estimated that there can be up to 1 minute of service outage. The length of the service outage is dependent on the number of calls active when the SPE (Switch Processing Element) interchange occurs.

● Status information is lost on a “reset system 3” and therefore on an update. This impacts user-controlled restrictions and group-controlled restrictions which are kept as status information in the switch.

● ISDN trunk facilities may go out-of-service during an update. Verify that the facilities are in-service after completion of the update process. If the trunks are not in-service, busy/release the trunk group. If the trunks are still out-of-service, contact the network service provider in order to restart the trunk group.

● Wireless facilities may go out-of-service during an update. Verify that the facilities are in-service after completion of the update process. If the wireless stations are not in-service, busy/release the station. A “reset system 3” also brings the wireless facilities back into service; however, this may result in other service outages.

● Calls over wireless facilities are not preserved during an update.

● IP telephony calls are not preserved during an update.

● Attendant features are lost. Some features have to be reactivated following the update, including night service; trunk/hunt group control; and manual/clock-manual override status on time-of-day routing.

● Administered connections are dropped. They are automatically re-established after the interchange.

● SPE-based “Leave Word Calling” messages are not preserved. All SPE-based “Leave Word Calling” messages are lost.

● After the update, lamps may be inconsistent for up to an hour (until background maintenance completes one cycle).

● Use the “change system-parameters features” command to disable TTI (Terminal Translation Initialization) changes during the update.

● Find all Maintenance Objects (MOs) that are demand-busied-out. Enter the “display errors print” command and select “Error Type 18”. All demand-busied-out MOs are lost during all forms of update and must be re-entered afterward.

● Disable scheduled maintenance to prevent any conflicts during the update. Note that it must be rescheduled after the update has been successfully completed.

● Reports that are currently printing or queued to print are lost (“list report-scheduler” command). The technician may delay the update until they have finished printing. The “status sp-link” command indicates if reports are printing; the link state is “up” if the system printer is available.

● If a user dials a TAC (Trunk Access Code) for a trunk and then dials less than the minimum number of digits needed to make it a valid number dialed, the trunk is not disconnected from the TDM bus. This results in noise on some talkpaths.

4. ACD (Automatic Call Distribution) Update Information:

● ACD queues are lost after an update. There is no mechanism in mips-processor switches to drain the queues. CMS (Call Management System) or BCMS (Basic CMS) can be used to monitor queue lengths. If it is important to empty all queues before the update, the technician must coordinate with the customer to redirect traffic away from ACD splits before the update, for example, by changing vectors to temporarily route calls to a disconnect announcement.

Page 8: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update notes8

● All ACD agents are logged out after an update and must re-login to receive calls.

● Status lamps associated with ACD are incorrect after the update. The lamp inconsistencies are corrected by background maintenance within 1 hour.

● The CMS link is dropped and restarted. This causes CMS data to be lost after the update. The amount of CMS data lost can be minimized if the update is done just after the last CMS measurement interval.

● All measurement data is lost after a software update (including BCMS). If needed, the reports may be printed prior to the update.

5. Property Management System (PMS) Features:

● Client Room Names are temporarily lost on an update and need to be restored by the PMS. This happens automatically since the PMS link drops and is re-established, triggering a database swap.

● “list wakeup print” shows scheduled wakeup calls. The technician should consider rescheduling to avoid conflicting with large numbers of scheduled wakeup calls, or printing the report and rescheduling them after the update.

● “list do-not-disturb print” shows stations with do-not-disturb activated. This status is lost during an update and must be re-entered after an update is completed.

6. Validating System Health Before Upgrading:

Use the following commands to verify the overall health of the switch before starting the upgrade:

● status spe – Shows the overall state of the system. Any alarms shown could preclude the update and should be investigated before proceeding. The “Health” of both the active and standby SPEs should be “Functional”.

● status logins – Shows active logins to the system. Only the technician should be logged into the system during an update.

● display alarms – Shows active alarms, which may preclude the update.

● display errors – Shows active system errors, which may preclude the update.

● status health – Shows the current system load. It is recommended to postpone the update if call-processing occupancy is greater than 50%. Nothing prevents the technician from updating under heavy call load, but customer impact is more noticeable.

7. Translation Sanity Check

Validate the sanity of the existing translations before upgrading to the new load, using the following steps:

● Execute “list station type 7303s” (or some other infrequently administered station type) and “list trunk-group” commands. Note that on larger systems (greater than 500 stations), this check may take several minutes.

● If the response “Error encountered, can’t complete request” appears, discontinue the update and proceed with the Technical Escalation process.

Page 9: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update procedures 9

Update procedures

“Standard (simplex) reliability” update procedures

WARNING

These procedures are applicable only when updating a switch already running Communication Manager 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 software. To upgrade an R from a previous release to Communication Manager 1.1, see the instructions in the “Upgrades and Additions” manual (555-233-115), available online under Product Documentation at http://www.avaya.com/support.

No administration changes should be entered during the following software update procedure. There can be substantial time gaps between steps and, since the system cannot prevent administration changes, it is up to the system technician to see that none are attempted before the update completes. Use the “status login” command to see that no one, including the customer, is logged into the switch during the update.

Step Action Minutes (Optical Disk)

Purpose Service Affecting?

1 Login as craft and verify that Communication Manager 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 software is installed and there are no “License Error” or “No License” warning messages.

2 Determine that a valid license is installed. Changing processor hardware, increasing capacities, or adding features requires creating a new license file through the RFA process.

No

2 Validate system sanity, as described in “Validating System Health Before Upgrading” on page 8 of this document.

5 Verify that the system is operating properly. No

3 Disable TTI using the change system-parameters features command.

2 Prevent background activity from interfering with the update. TTI must be re-activated after the update.

No

4 Disable scheduled maintenance using the change system-parameters maintenance command. Set the “start time” field to a value after the update will complete. If scheduled maintenance is active, set the “stop time” field to 1 minute from now.

2 Prevent background activity from interfering with the update. Scheduled maintenance must be re-activated after the update.

No

5 If a TN750/B announcement circuit card is present, and the customer has not backed up the annaouncements on it, execute save announcements

40 Save volatile announcements. No

6 If MMCH is active, use list config all to find all TN787 and TN788 boards, and then use the busyout board command to remove them from service.

variable Remove TN787 and TN788 boards from service.

Yes

7 Execute save translation 2 Preserve existing translations. No8 Execute backup disk 9 Back up the current software load to the

removable media. Do not press the return key once execution begins. Doing so clears the screen immediately after the backup completes, thus losing any messages.

No

9 Remove the backup removable media. 1 Keep the backup in a safe place. No10 Insert the new removable media. 1 Check that the optical disk, if any, is NOT

write-protected.No

11 Execute list config soft 3 Verify that the removable media contains the expected new load.

No

12 Execute restore disk install 3 Copy the new software version on the removable media to disk.

No

13 Execute upgrade software R011r.03.1.531.0Follow the instructions on the screen.Install the license file, if necessary.

15 Reboot the new load, causing a service outage.

Yes

14 Login as craft and check that no “translation corruption” messages are displayed

1 Verify that the upgraded translations are sane.

No

15 Enable scheduled maintenance using change system-parameters maintenance and set the “Start” and “Stop” time fields to their original values.

2 Re-enable scheduled maintenance. No

16 If TTI was originally enabled, re-enable TTI using change system-parameters features

2 Re-enable TTI. No

17 Use the release busyout command to release any TN787 and 2 Re-enable TN787 and 788 boards as needed. No

Page 10: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update procedures 10

TN788 boards busied in step 12.18 Validate system sanity, as described in “Validating System

Health Before Upgrading” on page 8 of this document.5 Verify that the system is operating properly. No

19 When the system is confirmed to be running normally, execute save translation

10 Save the upgraded translations. Investigate any errors, and do not override any warnings. Doing so could cause total loss of translations. Follow the Technical Escalation Procedure if any problems are encountered.

No

20 Execute backup disk 9 Back up the current software load to the removable media. Do not press the return key once execution begins. Doing so clears the screen immediately after the backup completes, thus losing any messages.

No

21 Execute list config soft 3 Conduct final verification of installed files. No22 Inform the appropriate organization that the update is

complete.5 Inform INADS (Initialization and

Administration System) administration by calling 1-800-248-1234 (US/Canada only).For non-US sites, notify the appropriate CoE in the International CoE Contact Table on page 12.

No

Back Out Procedure

If, after escalating problems through the Technical Escalation procedure, it is necessary to revert to the original software load, insert the backup removable media and execute the restore disk full command followed by the reset system 4 command. Use the list configuration software-version command to verify software release information in memory, disk, and removable media.

Page 11: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update procedures 11

“High/critical (duplicated) reliability” update procedures

WARNING

These procedures are applicable only when updating a switch already running Communication Manager 1.1 or 1.1.1 software. To upgrade an R from a previous release to Communication Manager 1.1, see the instructions in the “Upgrades and Additions” manual (555-233-115), available online under Product Documentation at http://www.avaya.com/support.

No administration changes should be entered during the following software update procedure. There can be substantial time gaps between steps and, since the system cannot prevent administration changes, it is up to the system technician to see that none are attempted before the update completes. Use the “status login” command to see that no one, including the customer, is logged into the switch during the update.

Step Action Minutes (Optical Disk)

Purpose Service Affecting?

1 Login as craft and verify that Communication Manager 1.1 or 1.1.1 or 1.1.2 or 1.1.3 or 1.2 or 1.3 software is installed and there are no “License Error” or “No License” warning messages.

2 Determine that a valid license is installed. Changing processor hardware, increasing capacities, or adding features requires creating a new license file through the RFA process.

No

2 Validate system sanity, as described in “Validating System Health Before Upgrading” on page 8 of this document.

5 Verify that the system is operating properly. No

3 Disable TTI using the change system-parameters features command.

2 Prevent background activity from interfering with the update. TTI must be re-activated after the update.

No

4 Disable scheduled maintenance using the change system-parameters maintenance command. Set the “start time” field to a value after the update will complete. If scheduled maintenance is active, set the “stop time” field to 1 minute from now.

2 Prevent background activity from interfering with the update. Scheduled maintenance must be re-activated after the update.

No

5 If a TN750/B announcement circuit card is present, and the customer has not backed up the annaouncements on it, execute save announcements

40 Save volatile announcements. No

6 Execute save translation 2 Preserve existing translations. No7 Execute backup disk 9 Back up the current software load to the

removable media. Do not press the return key once execution begins. Doing so clears the screen immediately after the backup completes, thus losing any messages.

No

8 Remove the backup removable media. 1 Keep the backup in a safe place. No9 Insert the new removable media. 1 Check that the optical disk, if any, is NOT

write-protected.No

10 Execute list config soft long 3 Verify that the removable media contains the expected new load.

No

11 Execute restore disk install both 3 Copy the new software version on the removable media to disk.

No

12 If MMCH is active, use list config all to find all TN787 and TN788 boards, and then use the busyout board command to remove them from service.

variable Remove TN787 and TN788 boards from service.

Yes

13 Execute upgrade software R011r.03.1.531.0 15 Reboot the new load, causing a service outage.

Yes

14 Login as craft and check that no “translation corruption” messages are displayed

1 Verify that the upgraded translations are sane.

No

15 Execute status spe 5 Repeat this command until standby handshake = yes

No

16 Execute reset spe-standby 4 1 Install new software load on the standby SPE. No17 Execute status spe 5 Repeat this command until both SPEs’ “state

of health” is “functional”.No

18 Enable scheduled maintenance using change system-parameters maintenance and set the “Start” and “Stop” time fields to their original values.

2 Re-enable scheduled maintenance. No

19 If TTI was originally enabled, re-enable TTI using change system-parameters features

2 Re-enable TTI. No

Page 12: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Update procedures 12

20 Use the release busyout command to release any TN787 and TN788 boards busied in step 12.

2 Re-enable TN787 and 788 boards as needed. No

21 Validate system sanity, as described in “Validating System Health Before Upgrading” on page 8 of this document.

5 Verify that the system is operating properly. No

22 When the system is confirmed to be running normally, execute save translation

10 Save the upgraded translations. Investigate any errors, and do not override any warnings. Doing so could cause total loss of translations. Follow the Technical Escalation Procedure if any problems are encountered.

No

23 Execute backup disk 9 Back up the current software load to the removable media. Do not press the return key once execution begins. Doing so clears the screen immediately after the backup completes, thus losing any messages.

No

24 Execute test stored-data long 9 Verify all MSS files are consistent. No25 Execute list config soft long 3 Conduct final verification of installed files. No26 Inform the appropriate organization that the update is

complete.5 Inform INADS (Initialization and

Administration System) administration by calling 1-800-248-1234 (US/Canada only).For non-US sites, notify the appropriate CoE in the International CoE Contact Table below.

No

International CoE Contact TableLocation NumberAVAYA USA/Canada TSO (Technical Services Organization) 800-422-6560, prompt 4AVAYA RSC Hungary 361-345-4334AVAYA Caribbean and Latin America Headquarters 786-331-0860AVAYA Western Europe CoE (Guildford) 44-8702-410-518AVAYA Asia/Pacific Regional Support Center 65-872-8686

Back Out Procedure

If, after escalating problems through the Technical Escalation procedure, it is necessary to revert to the original software load, insert the backup removable media and execute the restore disk full command followed by the reset system 4 command. Follow that with the reset spe-standby 4 command. Use the list configuration software-version command to verify software release information for memory, disk, and removable-media.

Page 13: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Label formats 13

Label formatsThe following information shall be imprinted on the MV 1.3.1 G3r MO label:

Avaya DEFINITY Server RAvaya MultiVantageTM Software 1.2

11r.01.2.110.4.Comcode # 700236847

Avaya Proprietary – RestrictedLimited Use SoftwareRegistration Enclosed

Copyright 2002 Avaya Inc.All Rights Reserved

Page 14: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Label formats 14

Page 15: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved

Document reference list 15

Reference documentsIf the screen asks you to log in as you retrieve these documents, log in as anonymous, without a password.

Change description

For the change description for Communication Manager 1.3.1:

1. Go to http://www.avaya.com/support and click Product Documentation.

2. In the list on the left, click Communication Systems.

3. Find Communication Manager. Under that, click 1.3.1.

4. Under User Information, click DEFINITY Servers: Release Notes (Release 1.3.1 of the

Avaya Communication Manager).

5. On the bottom of the page under Files, click the link View HTML.

6. In the left hand pane, click the link titled Resolutions and Patches. This will present a list of .pdf documents

describing the changes from Release 1.3.

http://support.avaya.com/elmodocs2/definity/chngdesc/chngdesc.jhtml.

Hardware/firmware minimum vintage table

The hardware and firmware minimum vintage table can be found at ftp://ftp.avaya.com/incoming/Up1cku9/tsoweb/media/minhardwarevintages.pdf.

Adjunct minimum vintage table

The adjunct minimum vintage table can be found at ftp://ftp.avaya.com/incoming/Up1cku9/tsoweb/media/minsoftwarevintages.xls.

Related documentation

For documentation on Communication Manager with a Server R:

1. Go to http://support.avaya.com and click Product Documentation.

2. In the list that appears at the left, click Communications Systems.

3. Click Avaya Communication Manager.

Page 16: Base template; changes from time to time (see Original.DOT).support.avaya.com/elmodocs2/release_notes/CM131/... · Web viewSPE-based “Leave Word Calling” messages are not preserved