wired seetouch qs wallstation: advanced programming mode app

Post on 14-Feb-2017

235 Views

Category:

Documents

2 Downloads

Preview:

Click to see full reader

TRANSCRIPT

®

Wired seeTouchR QS Wallstation: Advanced Programming Mode

Application Note #428Revision AApril 2012

Lutron Technical Support Center1.800.523.9466

Table Of Contents Wall Station Overview .................................................................................................................................3

Entering and Exiting Advanced Programming Mode (APM) ...................................................................4

Changing Wallstation Button Columns .....................................................................................................5 •Allowstheusertochangethenumberofbuttonsthatareusedonawallstation. Ex.Awallstationwasshippedfromthefactoryasa7-buttonwallstation,buta3-buttonbuttonkitwas

ordered. •Allowstheusertodivideawallstationintomorethanonecolumnthatcaneachhavedifferentcolumn

typesandbeassignedtodifferentloads,etc. Ex.A10buttonwallstationcanbemodifiedtohavetwo5buttoncolumnsthateachactasan

independentwallstation. •Awallstationcanbedividedintonomorethan4columns. •Onebutton(1B)columnsareallowed.

Enabling or Disabling a Button, Backlight LED, and/or Status LED ......................................................6 •Allowstheusertoenableordisableabutton,itsbacklightLEDoritsstatusLED.

CCI Remapping and Scene Banking .........................................................................................................7 •AllowstheusertochangethebuttononthewallstationtowhichthetwoCCIsaremapped. •ForScenecolumns,alsohastheoptionofchangingtherecalledscenesofthecolumnwhentheCCIis

closedversuswhentheCCIisopen.Thisisknownas“SceneBanking”. Ex.AScene1-3columncanbecomeaScene4-6columnwhenCCI1isclosed,andbacktoaScene

1-3columnwhenCCI1isopen.

Changing the Column Type ........................................................................................................................9 •Allowstheusertochangethecolumntypeofeachcolumninthewallstationwithoutrequiringa

GrAFIkEyeRQScontrolunitorEnergiSavrNodeTunit.

“Raise” and “Lower” Button Remapping ................................................................................................13 •Allowstheusertochangethecolumnthata“raise”and“lower”buttonpairisassociatedwith.

WiredseeTouchRQSWallstationscontainanAdvancedProgrammingMode (APM) thatallows installers tocustomizewallstationsthatarepartofQSstand-alonesystems.ThisdocumentservesasasupplementtotheseeTouchR QSWallstationsInstallationGuide.BeforeusingAPM,itisimportanttohaveagoodunderstandingoftheadvancedfeatures.

A

B

C

D

E

F

G

(continued on next page...)

Application Note #428

2 Lutron Technical Support Center1.800.523.9466®

Table Of Contents (continued) IR Association, and Remote Pass-Through/Button-Mapping Mode Toggle ......................................14 •AllowstheusertoassociatedifferenttypesofIrremotestodifferentcolumnsonthewallstation. •Ifinpass-throughmode,theIrremoteactivatesitsdefaultactions. Ex.ASceneIrremotewith5buttonswouldactivateScenes1-4andOFF. Ex.AShadeIrremotewith5buttonswouldactivateShadeOpen,Preset1,Preset2,Preset3,and

ShadeClose. •Button-mappingmodeallowsthebuttonsontheIrremotetomaptothebuttonsonthewallstation. Ex.AnytypeofIrremotewith5buttonspointedataScene7-10&OFFwallstationwouldrecall

Scenes7-10&OFFwhenthebuttonsarepushed. Ex.AnytypeofIrremotewith5buttonspointedata5buttonZoneTogglewallstationwouldperform

thesameactionsthatthewallstationbuttonsperformwhenthebuttonsontheIrremotearepressed.

Programming Lockout ..............................................................................................................................15 •Preventsaccidentalreprogrammingwhenwallstationsaremountedinpublicspacesbylockingthe

wallstationoutofallprogrammingmodes(includingProgrammingMode,ShadeAssociationMode,ShadePresetAdjustMode,ShadeLimitSetMode,APM,AdvancedConfigurationMode(ACM),etc.).AlsopreventsanyprogrammingfrombeingchangedinNormalModewhenindividualbuttonsareheld.

Information Display Sequence .................................................................................................................16 •Viewthefirmwarerevision,typeofhardware,andcolumntypesofthewallstationwithoutremovingit

fromthewallorusingotherdevicestoretrievethisinformation.

Shade Toggle Type Programming ...........................................................................................................17 •Specificinstructionsforassigningshadestoshadetoggletypewallstations.

Restoring Factory Defaults.......................................................................................................................17

J

K

L

I

H

Application Note #428

3 Lutron Technical Support Center1.800.523.9466®

Domestic: International: North American style wallstation European style wallstation

Note:Severaladvancedfeaturesrequiretheuseofa“raise”or“lower”buttonand/orabuttonthattheusermaynotbeabletoaccessonafullyassembledwallstation.Inthiscase,theusershould:

1. Snapoffthefaceplateofthewallstation.2. removethescrewsandthefaceplateadapter(ifpresent).3. Gentlypryoffthebuttonkit

Thisshouldallowaccesstoallbuttons,statusLEDs,andbacklightLEDs.

Buttonkit

AdapterFaceplate

North American style wallbox

European style wallbox

Wallbox

MountingScrews(2)

AdapterScrews(4)

Faceplate

ControlAdapter Button

kit

2.removescrewsandfaceplateadapter (ifpresent)

1.Snapofffaceplate

3.Gentlypryoffbutton kit

Wallstation Overview A

Wallbox

Control

MountingScrews(2)

AdapterScrews(2)

Application Note #428

4 Lutron Technical Support Center1.800.523.9466®

Entering and Exiting Advanced Programming Mode (APM)To Enter APM (from Normal Mode):Simultaneouslyholdthetopandbottombuttonofthecolumnfor30seconds(ifitisasinglebutton[1B]column,holdthesinglebuttonfor60seconds).Oncetheholdtimeelapses,thestatusLEDsinthatcolumnwillallblinkrapidlytoindicatethatthecolumnisinAPMandallbacklightLEDsofthatcolumnwillbesolidon.Youmaynowreleasetheheldbuttons.

To Exit APM:Simultaneouslyholdthetopandbottombuttonofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.Note:APMwilltimeoutafter10minutesandwillreturntoNormalMode.

Group 1

Group 2

Group 3

Open

Close

Preset

North American style wallstation

Note:Forwallstationswithtwosetsofbuttons,youwillprogrameachsetasiftheywereseparatewallstations.

European style wallstation

B

Application Note #428

5 Lutron Technical Support Center1.800.523.9466®

Changing Wallstation Button ColumnsNote:SomewallstationmodelsshipfromLutronwithcertainbuttonsdisabled(i.e.Europeanstyle

wallstationswithspacesbetweenthebuttons).Ifbuttonsaredisabledonawallstation,theymustfirstbeenabledbeforetheycanbeaddedtonewcolumns.PleaseseesectionD“Enablingordisablingabutton,backlightLED,and/orstatusLED”onpage6.

Functionality:To change the number of buttons in a column:

1. Holddownthetopandbottombuttonsofthenewcolumnyouwishtocreatefor30seconds. (Ifcreatingaonebuttoncolumn,holddowntheappropriatebuttonfor60seconds)

2. Oncetheholdtimeelapses,thestatusLEDsofthenewlycreatedcolumnwillblinksimultaneously.ThisputsthenewlycreatedcolumnintoAPM.

3. ToexitAPM,holdthetopandbottombuttonsofthenewcolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).

4. Oncetheholdtimeelapses,thewallstationwillreturntoNormalMode.

To create more than one column on a wallstation: • Uptofourseparateandindependentlyfunctioningcolumnsonawallstationcanbecreatedby

usingthesamestepsabovebutwithunusedbuttons. • Wallstationcolumnscannotoverlap. • Eachcolumncreatedcanbeprogrammedwithitsowncolumntype,beassociatedtodifferent

areasordevices,etc.asifitwereitsownindividualwallstation. • Awallstationcanbedividedintonomorethanfourcolumns.Onebutton(1B)columnsareallowed.

Ex.A10button(10B)wallstationcanbemodifiedtohavetwo5button(5B)columns;OnecolumncanbeascenetypethatisassociatedtoArea1ofaGrAFIkEyeRQScontrolunitandtheothercanbeashadetypeassociatedtoagroupofLutronRSivoiaRQSshades/draperies.

Note:Customengraving,faceplates,andbuttonkitsareavailableforsinglecolumnwallstationsaswellasfordualandmulticolumnwallstations(forbothNorthAmericanandEuropeanwallstations).

Group 1

Group 2

Group 3

Open

Close

Preset

Group 1

Group 2

Group 3

Open

Close

Preset

Before

Before:1column with7buttons

Before:2columns,eachwith 5buttons

After:2columns,eachwith3buttons

After:2columns,onewiththreebuttons,one withtwobuttons

After

C

Application Note #428

6 Lutron Technical Support Center1.800.523.9466®

Enabling or Disabling a Button, Backlight LED, and/or Status LED1.EnterAPM.2.Holdanybuttonfor6seconds.Oncetheholdtimeelapses,allbacklightLEDswillturnoffand

allstatusLEDswillbeperiodicallyblipping(pulsingonforaveryshortduration)together.ThisisAdvancedConfigurationMode(ACM).

Functionality:UponenteringACM,allstatusLEDswillblipinunisontoindicatethatthewallstationisinACM.ThisinitialblipofallstatusLEDsistheACMDefaultModewhereeachbuttonisunaffecteduntilpressed.Onceabuttonispressed,itwillacquirethefunctionsshowninthetablebelowandwillnotreturntotheunaffectedDefaultModeuntilyouenterACMagain.

Eachpressofabuttonwillcyclethatbuttonthroughthefollowingpossiblestates:

Feedback in Advanced Configuration Mode

Resulting State in Normal Mode

StateBacklight LED

FeedbackStatus LED Feedback

ButtonBacklight

LEDStatus LED

1 ON ON Enabled Enabled Enabled2 ON OFF Enabled Enabled Disabled3 OFF ON Enabled Disabled Enabled4 OFF OFF Enabled Disabled Disabled5 OFF Blips Disabled Disabled Disabled

To exit :1. Holdanybuttonfor6seconds.2. Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriate

settingsinNormalMode.Note:ThesettingschosenfromthetableabovewillautomaticallysaveuponexitingACM.

North American style wallstation European style wallstation

StatusLEDs

Status LEDs

BottomLower

Top Lower

BottomRaise

Top Raise

Buttons

Buttons

Buttons

Left Lower

right Raise

Left Raise

right Lower

BacklightLED

BacklightLEDs

BacklightLEDs

D

Application Note #428

7 Lutron Technical Support Center1.800.523.9466®

Contact Closure Input (CCI) Assignment and Scene Banking1. EnterAPM.2. SimultaneouslypressandholdanybuttonofthecolumninAPMalongwithany“raise”button

for3seconds.3. Oncetheholdtimeelapses,allbacklightLEDsinthatcolumnwillgooff,thestatusLEDofthe

buttontowhichtheCCIiscurrentlyprogrammedwillremainsolidON,andtheremainingstatusLEDsofthatcolumnwillflashonceevery8seconds.

IfthebuttontowhichtheCCIiscurrentlyprogramedisaraiseorlowerbutton,itwillbeindicatedbythefollowing:

Currently Programmed Button

LED Indication North American Style Wallstations

European Style Wallstations

Button1backlightON UpperLowerButton LeftLowerButtonButton2backlightON UpperraiseButton LeftraiseButtonButton3backlightON BottomLowerButton rightLowerButtonButton4backlightON BottomraiseButton rightraiseButton

Note: Atanytime,youcanexitCCIassignmentmodebacktoAPMbyholdinganybuttonoftheAPMcolumnalongwithany“raise”buttonfor3seconds.

WhenremappingCCIs,theCCIactionsareprogrammedinthefollowingorder:1. “CCI1closed”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed

button)flashingonceevery8seconds.2. “CCI1open”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed

button)flashingtwiceevery8seconds.3. “CCI2closed”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed

button)flashingthreetimesevery8seconds.4. “CCI2open”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed

button)flashingfourtimesevery8seconds.5. WallstationwillautomaticallyreturntoAPMeachtimeaftercyclingthroughtheCCIactions.

(continued on next page...)

North American style wallstation European style wallstation

E

Application Note #428

8 Lutron Technical Support Center1.800.523.9466®

CCI Assignment and Scene Banking (continued)Functionality:OnceintheCCIprogrammingmode,thefollowingoptionsareavailable:

1. MakethebuttontowhichaCCIactioniscurrentlyprogrammeddo“nothing”: • Holdthecurrentlyprogrammedbuttonfor3secondstomaketheselectedCCIactionbe

“nothing”. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.2. ChangethebuttontowhichtheCCIactioniscurrentlyprogrammed: • Holdabuttonfor3secondstomakethatbuttonthecurrentlyprogrammedbuttonforthe

selectedCCIaction. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.3. NotchangingthesettingsoftheselectedCCIaction: • TapanybuttontomoveontoprogrammingthenextCCIaction.4. AssignascenebanktotheselectedCCIaction: • Simultaneouslyholdthetopandbottombuttonsofascenecolumnfor3secondstomake

thatscenecolumn“bank”whenthisCCIactionhappens. Ex.AScene1-3columncanbecomeaScene4-6columnwhenCCI1isclosed,andbacktoa

Scene1-3columnwhenCCI1isopen. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.5. UnassignascenebankfromtheselectedCCIaction • Simultaneouslyholdthetopandbottombuttonsofascenecolumn(thathasbeen

programmedto“bank”)for3seconds. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.

Note:ThewallstationwillnotalwayscyclethroughallfourCCIoptions.Theexceptionoccurswhenthecurrentlyprogrammedbuttonisaraiseorlowerbutton,orafinetunebutton.

Ex.Ifthecurrentlyprogrammedbuttonisalowerbutton,“CCIclosed”willbelikepressingthatlowerbutton(dimmingtheload)and“CCIopen”willbelikereleasingit(stopdimming).Inthiscase,thewallstationwouldskipprogrammingthe“CCI1open”(sinceitisautomaticallyset)andjumptoprogramming“CCI2closed.”

Afterthefinal(“CCI2Open”)actionhasbeenprogrammed,thewallstationwillautomaticallyreturntoAPM.ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

E

Application Note #428

9 Lutron Technical Support Center1.800.523.9466®

Changing the Column Type ColumnsA“column”inaseeTouchRQSmulti-columnwallstationisdefinedasagroupof(typicallyadjacent)buttonsthatallperformasimilarlogicfeature.

Column TypeThe“type”ofacolumndeterminesthelogicofhowthatcolumnoperates.

Tochangeyourwallstation’scolumntypesusingColumnTypeChangeMode:1. EnterAPM.2. SimultaneouslypressandholdanybuttonofthecolumninAPMalongwithany“Lower”button

for3seconds.

3. Oncetheholdtimeelapses,allbacklightsofthatcolumnwillremainsolidonandthestatusLEDswillblipinthefollowingpattern(eachcolumntypeislistedbelowandexplainedinsubsequentpages):

•1blipevery8seconds =“ScenewithOFF”columntype(notanoptionfor1Bcolumn)•2blipsevery8seconds =“Scene”columntype•3blipsevery8seconds =“ZoneToggle”columntype•4blipsevery8seconds =“Partition”columntype•5blipsevery8seconds =“Shade”columntype(notanoptionfor1Bcolumn)•6blipsevery8seconds =“ShadeToggle”columntype•7blipsevery8seconds =“ShadeGroup”columntype(notanoptionfor1Bcolumn)•8blipsevery8seconds =“Panic”,“Sequence”,or“Timeclock”columntype(2Bcolumnsonly)•9blipsevery8seconds =“FineTune”columntype(2Bcolumnsonly)•10blipsevery8seconds=(Althoughthedeviceallowstheusertoselectthiscolumntype,it

currentlyhasnofunctionality.Donotuse.)

Note:Wallstationwillskipcertainblippatternsdependingonthecapabilitiesofthewallstationbeingcurrentlyprogrammed(Ex.Acolumnmusthaveonly2buttonsinordertobeprogrammedwiththe“Sequence”or“FineTune”columntypes).

Note:Whilea1Bcolumnwillaccept“Scene”columntypeandwillnotaccept“SceneWithOff”columntype,a1BscenecolumnalwaystogglesbetweentheprogrammedSceneandSceneOff.

(continued on next page...)

North American style wallstation European style wallstation

F

Application Note #428

10 Lutron Technical Support Center1.800.523.9466®

Changing the Column Type (continued)

Column TypeThefollowingisalistingofallthepossiblecolumntypesforaseeTouchRQSwallstation:

Scene Type (with OFF): Controlsscenesonascenecontroller(suchasaGrafikEyeRQScontrolunit,oranareaonanEnergiSavrNodeTunit)ormultiplescenecontrollers.Allbuttonsinthecolumnwillalwayscontrolthesamescenecontrollers(youcannothavedifferentbuttonswithinthecolumncontrollingdifferentscenecontrollers).Thescenerecalledbythefirstbuttonisprogrammable,thesubsequentbuttonsrecallthenextnumericalscene,andthelastbuttonalwaysrecallsSceneOFF.

Ex.A5-button(5B)columnwiththiscolumntypesettostartatScene3wouldrecallScenes3,4,5,6,andOFFrespectively.

Scene Type (without OFF):SameasSceneTypeWithOFF,exceptthelastbutton-ratherthanrecallingSceneOFF-recallsthenextconsecutivescene.

Ex. A5-button(5B)columnwiththiscolumntypesettostartatScene3wouldrecallScenes3,4,5,6,and7respectively.

Zone Toggle Type: Zonetogglebuttonstoggleazoneorgroupofzonesbetweenprogrammablepresetvalues(eachzonecanbeprogrammedtoadifferentvalue),andOFF(allzonesareOFF).EachbuttoninaZoneTogglecolumncanbeindividuallyprogrammedtodifferentloads.

Partition Type:Allowstheusertoassignindividualbuttonsofacolumntodifferentscenecontrollers(GrAFIkEyeRQScontrolunitand/orEnergiSavrNodeT unitareas).Whenabuttonispressedonthewallstation,theLEDislitonthewallstationforthatbutton,andthepartitionisopen.Whenitispressedagain,theLEDisOFFforthatbutton,andthepartitionisclosed.Anopenpartitionmakesthedevicesprogrammedtothatbuttontalktoeachotherinbothdirections.Aclosedpartitionmakesthedevicesnottalktoeachotherineitherdirection.

FNorth American style wallstation European style wallstation

StatusLEDs

Status LEDs

BottomLower

Top Lower

BottomRaise

Top Raise

Buttons

Buttons

Buttons

Left Lower

right Raise

Left Raise

right Lower

BacklightLED

BacklightLEDs

BacklightLEDs

(continued on next page...)

Application Note #428

11 Lutron Technical Support Center1.800.523.9466®

Changing the Column Type (continued)Two-Button (2B) Special Functions2B Partition Type: SameasnormalPartitiontypeexceptthatatopbuttonpressopensthepartitionandabottombuttonpressclosesthepartition.

2B Fine Tune Type: Thebuttonsofthewallstationinthismodefunctionasraiseandlowerbuttonsfortheassignedzones.Tappingthebuttonswillraise/lowerthelevelofallassignedzonesbyonepercent.Holdingthebuttonswillsmoothlyraisetohighendorsmoothlylowertolowend.2B Sequence Type: Thesequencecolumntypecausesalltheassignedscenecontrollerstocontinuouslycyclethroughtheirscenes(eitherScenes1-4orScenes5-16)usingtheprogrammedfadetimesforeachscene.Thisisusefulforspacesthatdesiredynamiclightingsuchasdecorativelightingordisplaysinretailstores.

2B Panic Type:PanictypecausesalltheassignedscenecontrollerstogotoScene16,andtemporarilydisablesallbuttonspressesandignoressceneorzonelevelchanges.

2B Timeclock:TimeclocktypeallowstheusertoenableordisabletheTimeclockonaGrafikEyeRQScontrolunit.Pressingthetopbuttonofthe2BcolumnenablestheTimeclockandpressingthebottombuttondisablestheTimeclock.

Shade Type:Inshadetype,thetopbuttonofacolumnbecomestheOpenbuttonandthebottombuttonbecomestheClosebuttonfortheassociatedLutronRSivoiaRQSshades/draperiesorthirdpartyACshades.Ifthewallstationhasmorethantwobuttons,themiddlebuttonsbetweenOpenandCloseserveasprogrammablepresetbuttonsforLutronRSivoiaRQSshades/draperies,or“stop”buttonsforthirdpartyACshades.

Shade Group Type: Ashadegroupcolumncanonlyexistonamulti-columnwallstation,whereoneoftheothercolumnsisashadecolumn.Theshadegroupcolumnwillmaketheshadecolumnappeartooperateasmultipleindependentwallstations(oneindependentwallstationpergroup).Thepurposeoftheshadegroupcolumnistoselectwhichoftheindependentwallstationsiscurrentlyactive(onegroupisalwaysactive;namelythegroupbuttonwhoseLEDison).Ex.Ifashadegroupcolumnhas3buttons,theshadecolumnwilloperateas3independentshade

wallstations.IfthetopgroupbuttonispusheditsLEDwillturnonandthefirstindependentwallstationisselected,ifthesecondgroupbuttonispusheditsLEDwillturnonandthesecondindependentwallstationisselected,andifthe3rdgroupbuttonispusheditsLEDwillturnonandthe3rdindependentwallstationisselected.

Shade Toggle Type: Eachbuttoninthecolumncanbeprogrammedtoanindependentshadeorgroupofshades.Pressingthebuttonwillcausetheassignedshades/draperiestotoggle(oneachsubsequentbuttonpress)betweenthefollowingstates:• MovetowardsOpenlimit• Stop(ifanyassignedshade/draperyisstillmoving)• MovetowardsCloselimit• Stop(ifanyassignedshade/draperyisstillmoving)Ifthecolumnhasraise/Lowerbuttons,theywillaffecttheshades/draperiesassociatedtothelastbuttonthatwaspressed.Ex.AtwobuttonShadeTogglecolumnthathasbuttonB1thataffectsshade/draperyS1,andbutton

B2thataffectsshade/draperyS2.IfyoupressB1andthenraise/Lower,S1willraise/Lower.IfyoupressB2andthenraise/Lower,S2willraise/Lower.

F

(continued on next page...)

Application Note #428

12 Lutron Technical Support Center1.800.523.9466®

Changing the Column Type (continued)Functionality:OnceintheColumnTypeChangeModedescribedonpreviouspage,theuserhasthefollowingoptions:

1. Tappinganybuttonwillcontinuescrollingtothenextvalidcolumntypeoption.2. IfthewallstationtypeisScenewithOFF,Scene,or2BSpecialFunctions,theusermaychoosea

subtypeasfollows:• Pressandholdanybuttonofthatcolumnfor3seconds.• Onceholdtimeelapses,allstatusLEDswillgotoOFFindicatingthattheuserenteredthesub

mode.Then,thestatusLEDswillblipinthefollowingpattern:

Column Type Programming Mode

SelectionStatus LED Indication Sub Mode Options

Scene with OFF

1blipevery8seconds StartswithScene12blipsevery8seconds StartswithScene23blipsevery8seconds StartswithScene3

…Continuessequentially… …Continuessequentially…16blipsevery8seconds StartswithScene16

Scene

1blipevery8seconds StartswithScene12blipsevery8seconds StartswithScene23blipsevery8seconds StartswithScene3

…Continuessequentially… …Continuessequentially…16blipsevery8seconds StartswithScene16

2B Special Functions

1blipevery8seconds Panic2blipsevery8seconds SequenceScenes5-163blipsevery8seconds SequenceScenes1-4

4blipsevery8seconds TimeclockDisable

• Eachtapofany“raise”buttonwillprogressforwardthroughthedifferentoptionsandeachtapofany“Lower”buttonwillprogressbackwardsthroughthedifferentoptions.

• Toautomaticallysavethechosensubtype:

° Exitthesubmodebyholdinganybuttonofthatcolumnfor3seconds.

° Onceholdtimehaselapsed,thecolumnwillreturntoColumnTypeChangeModewithallbacklightLEDsofthecolumnsolidONandallstatusLEDsofthatcolumnblippingtoindicatetheselectedcolumntype.

• Forscenecolumns,certainoptionsinthesubmodemaynotbeavailable,dependingonthenumberofbuttonsinthecolumn.

Ex.a10Bcolumnwith“Scene”columntypecanonlygouptoScene7asthestartingscene(the10buttonswillrecallScene7throughScene16respectively).A10Bcolumnwith“ScenewithOFF”columntypecangouptoScene8asthestartingscene(thefirst9buttonswillrecallScene8throughScene16,andthefinalbuttonwillrecallSceneOFF).

3. SavetheselectedcolumntypeautomaticallybyexitingColumnTypeChangeMode.• Simultaneouslypressandholdanybuttonofthecolumnalongwithanylowerbuttonfor

3 seconds.• Onceholdtimeelapses,thecolumnwillreturntoAPMwithallbacklightLEDsofthecolumn

solidonandallstatusLEDsofthecolumnflashingrapidly.

F

(continued on next page...)

Application Note #428

13 Lutron Technical Support Center1.800.523.9466®

Changing the Column Type (continued)Note:IfonecolumnonadualcolumnwallstationentersColumnTypeChangeMode,allothercolumns

onthatwallstationwillalsoenterColumnTypeChangeModetoallowtheusertomoreeasilychangethecolumntypeofmorethanonecolumnwithouthavingtoexitandre-enterAPM.

ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,all statusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

“Raise” and “Lower” Button Remapping

1. EnterAPM.2. Simultaneouslypressandholdthe“raise”and“lower”buttonsthatyouwishtoassigntothe

columninAPMfor3seconds.3. Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,

indicatingthatthe“raise”and“lower”buttonshavebeenassignedtothatcolumn,thenreturntoAPM.

4. ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

European style wallstationNorth American style wallstation

F

G

Application Note #428

14 Lutron Technical Support Center1.800.523.9466®

Assigning an IR Remote1. EnterAPM2. PointanIrremotetowardthewallstationinAPM2. Holdtheraisebuttonfor3seconds4. StatusLEDsonthewallstationwillthenflashslowlyfor3secondstoindicatethattheIrremotehas

beensuccessfullyassigned5. WallstationwillautomaticallyreturntoAPM6. ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor

3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

IR Remote Pass-through and Button-mapping Modes1.EnterAPM.

Functionality:Note: ThedefaultmodeforanyIrremoteispass-throughmode.OnceinAPM,theuserhasthefollowingoptions:

A. Enablebutton-mappingmode: • PressandholdthefavoritebuttonoftheIrremotefor3seconds • Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,

indicatingthatthecolumnhasswitchedtobutton-mappingmode,thenreturntoAPM.

B. Enablepass-throughmode: • Pressandholdthefirstbutton(topbutton)oftheIrremotefor3seconds. • Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,

indicatingthatthecolumnhasswitchedtopass-throughmode,thenreturntoAPM.

Note: Ifacolumnissettoa“ZoneToggle”type,anIrremoteineithermodewillactasremotebuttonpresses.

2.ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

RR

Open

Close

First Button First Button

Favorite Button

Favorite Button

H

Application Note #428

15 Lutron Technical Support Center1.800.523.9466®

Programming lockout

Functionality:To enable programming lockout mode:

1. Simultaneouslypressandhold“raise”,“Lower”,andanyactivebuttonfor30seconds.

2. Oncetheholdtimeelapses,allstatusLEDswilllightinasequentialflashofstatusLEDsfromthebottomtotopofthewallstation,indicatingthattheuserhaslockedoutofprogrammingmode.(Thissequenceofflashesisknownasareversewaterfall).

3. Then,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.Note: Eachtimetheuserattemptstoenteraprogrammingmodeafterlockingoutofprogramming

mode,allstatusLEDswilllightinasequentialflashofstatusLEDsfromthebottomtotopofthewallstationindicatingthatallprogrammingislockedout.

To disable programming lockout mode:1. Simultaneouslypressandhold“raise”,“lower”,andanybuttonofthecolumninAPMforthe

30 seconds.2. Oncetheholdtimeelapses,allstatusLEDswilllightinasequentialflashofstatusLEDsfrom

thebottomtotopofthewallstation(reversewaterfall),indicatingthattheuserhasremovedtheprogramminglockout.

3. Then,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

European style wallstationNorth American style wallstation

I

Application Note #428

16 Lutron Technical Support Center1.800.523.9466®

Information Display SequenceFunctionality:

1. Tapthesamebuttoninacolumn20timesconsecutively.ThiswillcausestatusLEDstobeginflashing.

2. Thefirst3timesthestatusLEDsflashconsecutively,theyareshowingthecoderevisionofthewallstation(withtheformatx.yz).

Note: Anumber“0”isdisplayednotbyzeroflashes,butinsteadbyaquicksequentialflashofstatusLEDsfromthebottomtotopofthecolumn(for1second).

• Oncetheuserhastappedthesamebuttonofacolumn20consecutivetimes,thecolumnwillenterinformationdisplaymodeandthestatusLEDswillimmediatelybeginflashingconsecutively“x”amountoftimes.

• Countthe“x”numberofflashes.• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthesecondtime

(6secondsafterenteringinformationdisplaymode),“y”amountoftimes.• Countthe“y”numberofflashes.• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthethirdtime

(12secondsafterenteringinformationdisplaymode)“z”amountoftimes.• Countthe“z”numberofflashes.• Oncetheuserhasreachedthisstep,thewallstationhasshownthefullnumber

(x,y,z)representingthecoderevisionofthewallstation.3. ThenexttimethestatusLEDsflashconsecutively,theyareshowingthetypehardwareinsidethe

wallstation• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthefourthtime

(18secondsafterenteringinformationdisplaymode),for“n”amountoftimes.• Countthe“n”numberofflashes.• The“n”numberofflashesrepresentsthefollowing:

“n” Hardware Type1 V1Hardware,NOTHomeWorksRQSenabled2 V2Hardware,NOTHomeWorksRQSenabled3 V1Hardware,HomeWorksRQSenabled4 V2Hardware,HomeWorksRQSenabled

• Oncetheuserhasreachedthisstep,thewallstationhasshownthenumberrepresentingthe

typeofhardwareinsidethewallstation.

J

(continued on next page...)

Application Note #428

17 Lutron Technical Support Center1.800.523.9466®

Information Display Sequence (continued)4. ThenexttimethestatusLEDsflashconsecutively,theyareshowingthecolumntypeofcolumn.

• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthefifthtime (24secondsafterenteringinformationdisplaymode),for“m”amountoftimes.

• Countthe“m”numberofflashes.• The“m”amountofconsecutiveflashesrepresentsthefollowing:

“m” Column Type1 ScenewithOFF2 Scene3 ZoneToggle4 Partition

5 Shade

6 ShadeToggle

7 ShadeGroup

8 2BSpecialFunctions

9 FineTune

• Oncetheuserhasreachedthisstep,thewallstationhasgiventheuserthenumberrepresentingthetypeoftheselectedcolumn.

5. Oncethecolumnhassequencedthroughthecoderevision,hardwaretype,andcolumntype,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.

Shade Toggle Type ProgrammingProgramming a Shade Toggle Type Column:

1. Enterthecolumnintoprogrammingmodebyholdingthe“top”and“bottom”buttonsofthe shadetoggletypecolumntogetherfor5seconds(ifit’sa1Bcolumn,holdthesinglebuttonfor10seconds).

2. Tapthebuttonthatyouwishtoprogram.ItsLEDwillblinkrapidly.3. Eachtimeyoutapthissamebutton,thenextshade/draperywillbeselected.Eachtimeyou

doubletapit,thepreviousshade/draperywillbeselected.4. Toassignthecurrentlyselectedshade/drapery,tapthe“Lower”button.Tounassignthecurrently

selectedshade/drapery,tapthe“raise”button.5. Onceallshades/draperiesareassignedtothatbutton,tapthenextbuttonandrepeatthe

process.repeatforallbuttonsinthecolumn.6. Onceprogrammingiscomplete,holdthe“top”and“bottom”buttonsfor5secondstoreturnto

NormalMode(ifit’sa1Bcolumn,holdthesinglebuttonfor10seconds).

J

K

Application Note #428

®Lutron Electronics Co., Inc.7200 Suter RoadCoopersburg, PA 18036-1299 U.S.A.04/2012 P/N 048-428 Rev. A

Lutron Contact Numbers

WORLD HEADQUARTERS USA

Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 TEL:+1.610.282.3800 FAX:+1.610.282.1243 Toll-Free:1.888.LUTrON1 TechnicalSupport:1.800.523.9466

intsales@lutron.com

North & South America Technical Hotlines

USA, Canada, Caribbean: 1.800.523.9466 Mexico: +1.888.235.2910 Central/South America: +1.610.282.6701

EUROPEAN HEADQUARTERS United Kingdom

Lutron EA Ltd. 6 Sovereign Close London, E1W 3JF United Kingdom TEL:+44.(0)20.7702.0657 FAX:+44.(0)20.7480.6899 FrEEPHONE(Uk):0800.282.107 TechnicalSupport:+44.(0)20.7680.4481

lutronlondon@lutron.com

ASIAN HEADQUARTERS Singapore

Lutron GL Ltd. 15 Hoe Chiang Road #07-03, Tower 15 Singapore 089316 TEL:+65.6220.4666 FAX:+65.6220.4333 TechnicalSupport:800.120.4491

lutronsea@lutron.com

Asia Technical HotlinesNorthernChina:10.800.712.1536 SouthernChina:10.800.120.1536 Hongkong:800.901.849 Indonesia:001.803.011.3994 Japan:+81.3.5575.8411 Macau:0800.401 Taiwan:00.801.137.737 Thailand:001.800.120.665853 OtherCountries:+65.6220.4666

L. Restoring Factory DefaultsTorestorefactorydefaultstoawallstation,useanyenabledbuttononthewallstationtoperformthefollowing:

1. Tapbutton,tapbutton,tapbuttonandhold(untilallLEDsonthewallstationstarttoblinkslowly).2. releasethebuttonandimmediatelytapbutton,tapbutton,tapbutton(allLEDsonthewallstation

willblinkrapidly).

OnlyoncetheLEDsareblinkingrapidlyhasthewallstationstartedrestoringitsfactorydefaults(ifthisproceduredoesnotfunctionproperly,leavethewallstationidleforafewseconds,andthentryagain).

AftertheLEDsstopblinking,theywillgooffforashortinterval,andthenthewallstationwillturnoninitsfactorydefaultstate.

L

top related