Wired seeTouchR QS Wallstation: Advanced Programming Mode
Application Note #428Revision AApril 2012
Lutron Technical Support Center1.800.523.9466
Table Of Contents Wall Station Overview .................................................................................................................................3
Entering and Exiting Advanced Programming Mode (APM) ...................................................................4
Changing Wallstation Button Columns .....................................................................................................5 •Allowstheusertochangethenumberofbuttonsthatareusedonawallstation. Ex.Awallstationwasshippedfromthefactoryasa7-buttonwallstation,buta3-buttonbuttonkitwas
ordered. •Allowstheusertodivideawallstationintomorethanonecolumnthatcaneachhavedifferentcolumn
typesandbeassignedtodifferentloads,etc. Ex.A10buttonwallstationcanbemodifiedtohavetwo5buttoncolumnsthateachactasan
independentwallstation. •Awallstationcanbedividedintonomorethan4columns. •Onebutton(1B)columnsareallowed.
Enabling or Disabling a Button, Backlight LED, and/or Status LED ......................................................6 •Allowstheusertoenableordisableabutton,itsbacklightLEDoritsstatusLED.
CCI Remapping and Scene Banking .........................................................................................................7 •AllowstheusertochangethebuttononthewallstationtowhichthetwoCCIsaremapped. •ForScenecolumns,alsohastheoptionofchangingtherecalledscenesofthecolumnwhentheCCIis
closedversuswhentheCCIisopen.Thisisknownas“SceneBanking”. Ex.AScene1-3columncanbecomeaScene4-6columnwhenCCI1isclosed,andbacktoaScene
1-3columnwhenCCI1isopen.
Changing the Column Type ........................................................................................................................9 •Allowstheusertochangethecolumntypeofeachcolumninthewallstationwithoutrequiringa
GrAFIkEyeRQScontrolunitorEnergiSavrNodeTunit.
“Raise” and “Lower” Button Remapping ................................................................................................13 •Allowstheusertochangethecolumnthata“raise”and“lower”buttonpairisassociatedwith.
WiredseeTouchRQSWallstationscontainanAdvancedProgrammingMode (APM) thatallows installers tocustomizewallstationsthatarepartofQSstand-alonesystems.ThisdocumentservesasasupplementtotheseeTouchR QSWallstationsInstallationGuide.BeforeusingAPM,itisimportanttohaveagoodunderstandingoftheadvancedfeatures.
A
B
C
D
E
F
G
(continued on next page...)
Application Note #428
2 Lutron Technical Support Center1.800.523.9466®
Table Of Contents (continued) IR Association, and Remote Pass-Through/Button-Mapping Mode Toggle ......................................14 •AllowstheusertoassociatedifferenttypesofIrremotestodifferentcolumnsonthewallstation. •Ifinpass-throughmode,theIrremoteactivatesitsdefaultactions. Ex.ASceneIrremotewith5buttonswouldactivateScenes1-4andOFF. Ex.AShadeIrremotewith5buttonswouldactivateShadeOpen,Preset1,Preset2,Preset3,and
ShadeClose. •Button-mappingmodeallowsthebuttonsontheIrremotetomaptothebuttonsonthewallstation. Ex.AnytypeofIrremotewith5buttonspointedataScene7-10&OFFwallstationwouldrecall
Scenes7-10&OFFwhenthebuttonsarepushed. Ex.AnytypeofIrremotewith5buttonspointedata5buttonZoneTogglewallstationwouldperform
thesameactionsthatthewallstationbuttonsperformwhenthebuttonsontheIrremotearepressed.
Programming Lockout ..............................................................................................................................15 •Preventsaccidentalreprogrammingwhenwallstationsaremountedinpublicspacesbylockingthe
wallstationoutofallprogrammingmodes(includingProgrammingMode,ShadeAssociationMode,ShadePresetAdjustMode,ShadeLimitSetMode,APM,AdvancedConfigurationMode(ACM),etc.).AlsopreventsanyprogrammingfrombeingchangedinNormalModewhenindividualbuttonsareheld.
Information Display Sequence .................................................................................................................16 •Viewthefirmwarerevision,typeofhardware,andcolumntypesofthewallstationwithoutremovingit
fromthewallorusingotherdevicestoretrievethisinformation.
Shade Toggle Type Programming ...........................................................................................................17 •Specificinstructionsforassigningshadestoshadetoggletypewallstations.
Restoring Factory Defaults.......................................................................................................................17
J
K
L
I
H
Application Note #428
3 Lutron Technical Support Center1.800.523.9466®
Domestic: International: North American style wallstation European style wallstation
Note:Severaladvancedfeaturesrequiretheuseofa“raise”or“lower”buttonand/orabuttonthattheusermaynotbeabletoaccessonafullyassembledwallstation.Inthiscase,theusershould:
1. Snapoffthefaceplateofthewallstation.2. removethescrewsandthefaceplateadapter(ifpresent).3. Gentlypryoffthebuttonkit
Thisshouldallowaccesstoallbuttons,statusLEDs,andbacklightLEDs.
Buttonkit
AdapterFaceplate
North American style wallbox
European style wallbox
Wallbox
MountingScrews(2)
AdapterScrews(4)
Faceplate
ControlAdapter Button
kit
2.removescrewsandfaceplateadapter (ifpresent)
1.Snapofffaceplate
3.Gentlypryoffbutton kit
Wallstation Overview A
Wallbox
Control
MountingScrews(2)
AdapterScrews(2)
Application Note #428
4 Lutron Technical Support Center1.800.523.9466®
Entering and Exiting Advanced Programming Mode (APM)To Enter APM (from Normal Mode):Simultaneouslyholdthetopandbottombuttonofthecolumnfor30seconds(ifitisasinglebutton[1B]column,holdthesinglebuttonfor60seconds).Oncetheholdtimeelapses,thestatusLEDsinthatcolumnwillallblinkrapidlytoindicatethatthecolumnisinAPMandallbacklightLEDsofthatcolumnwillbesolidon.Youmaynowreleasetheheldbuttons.
To Exit APM:Simultaneouslyholdthetopandbottombuttonofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.Note:APMwilltimeoutafter10minutesandwillreturntoNormalMode.
Group 1
Group 2
Group 3
Open
Close
Preset
North American style wallstation
Note:Forwallstationswithtwosetsofbuttons,youwillprogrameachsetasiftheywereseparatewallstations.
European style wallstation
B
Application Note #428
5 Lutron Technical Support Center1.800.523.9466®
Changing Wallstation Button ColumnsNote:SomewallstationmodelsshipfromLutronwithcertainbuttonsdisabled(i.e.Europeanstyle
wallstationswithspacesbetweenthebuttons).Ifbuttonsaredisabledonawallstation,theymustfirstbeenabledbeforetheycanbeaddedtonewcolumns.PleaseseesectionD“Enablingordisablingabutton,backlightLED,and/orstatusLED”onpage6.
Functionality:To change the number of buttons in a column:
1. Holddownthetopandbottombuttonsofthenewcolumnyouwishtocreatefor30seconds. (Ifcreatingaonebuttoncolumn,holddowntheappropriatebuttonfor60seconds)
2. Oncetheholdtimeelapses,thestatusLEDsofthenewlycreatedcolumnwillblinksimultaneously.ThisputsthenewlycreatedcolumnintoAPM.
3. ToexitAPM,holdthetopandbottombuttonsofthenewcolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).
4. Oncetheholdtimeelapses,thewallstationwillreturntoNormalMode.
To create more than one column on a wallstation: • Uptofourseparateandindependentlyfunctioningcolumnsonawallstationcanbecreatedby
usingthesamestepsabovebutwithunusedbuttons. • Wallstationcolumnscannotoverlap. • Eachcolumncreatedcanbeprogrammedwithitsowncolumntype,beassociatedtodifferent
areasordevices,etc.asifitwereitsownindividualwallstation. • Awallstationcanbedividedintonomorethanfourcolumns.Onebutton(1B)columnsareallowed.
Ex.A10button(10B)wallstationcanbemodifiedtohavetwo5button(5B)columns;OnecolumncanbeascenetypethatisassociatedtoArea1ofaGrAFIkEyeRQScontrolunitandtheothercanbeashadetypeassociatedtoagroupofLutronRSivoiaRQSshades/draperies.
Note:Customengraving,faceplates,andbuttonkitsareavailableforsinglecolumnwallstationsaswellasfordualandmulticolumnwallstations(forbothNorthAmericanandEuropeanwallstations).
Group 1
Group 2
Group 3
Open
Close
Preset
Group 1
Group 2
Group 3
Open
Close
Preset
Before
Before:1column with7buttons
Before:2columns,eachwith 5buttons
After:2columns,eachwith3buttons
After:2columns,onewiththreebuttons,one withtwobuttons
After
C
Application Note #428
6 Lutron Technical Support Center1.800.523.9466®
Enabling or Disabling a Button, Backlight LED, and/or Status LED1.EnterAPM.2.Holdanybuttonfor6seconds.Oncetheholdtimeelapses,allbacklightLEDswillturnoffand
allstatusLEDswillbeperiodicallyblipping(pulsingonforaveryshortduration)together.ThisisAdvancedConfigurationMode(ACM).
Functionality:UponenteringACM,allstatusLEDswillblipinunisontoindicatethatthewallstationisinACM.ThisinitialblipofallstatusLEDsistheACMDefaultModewhereeachbuttonisunaffecteduntilpressed.Onceabuttonispressed,itwillacquirethefunctionsshowninthetablebelowandwillnotreturntotheunaffectedDefaultModeuntilyouenterACMagain.
Eachpressofabuttonwillcyclethatbuttonthroughthefollowingpossiblestates:
Feedback in Advanced Configuration Mode
Resulting State in Normal Mode
StateBacklight LED
FeedbackStatus LED Feedback
ButtonBacklight
LEDStatus LED
1 ON ON Enabled Enabled Enabled2 ON OFF Enabled Enabled Disabled3 OFF ON Enabled Disabled Enabled4 OFF OFF Enabled Disabled Disabled5 OFF Blips Disabled Disabled Disabled
To exit :1. Holdanybuttonfor6seconds.2. Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriate
settingsinNormalMode.Note:ThesettingschosenfromthetableabovewillautomaticallysaveuponexitingACM.
North American style wallstation European style wallstation
StatusLEDs
Status LEDs
BottomLower
Top Lower
BottomRaise
Top Raise
Buttons
Buttons
Buttons
Left Lower
right Raise
Left Raise
right Lower
BacklightLED
BacklightLEDs
BacklightLEDs
D
Application Note #428
7 Lutron Technical Support Center1.800.523.9466®
Contact Closure Input (CCI) Assignment and Scene Banking1. EnterAPM.2. SimultaneouslypressandholdanybuttonofthecolumninAPMalongwithany“raise”button
for3seconds.3. Oncetheholdtimeelapses,allbacklightLEDsinthatcolumnwillgooff,thestatusLEDofthe
buttontowhichtheCCIiscurrentlyprogrammedwillremainsolidON,andtheremainingstatusLEDsofthatcolumnwillflashonceevery8seconds.
IfthebuttontowhichtheCCIiscurrentlyprogramedisaraiseorlowerbutton,itwillbeindicatedbythefollowing:
Currently Programmed Button
LED Indication North American Style Wallstations
European Style Wallstations
Button1backlightON UpperLowerButton LeftLowerButtonButton2backlightON UpperraiseButton LeftraiseButtonButton3backlightON BottomLowerButton rightLowerButtonButton4backlightON BottomraiseButton rightraiseButton
Note: Atanytime,youcanexitCCIassignmentmodebacktoAPMbyholdinganybuttonoftheAPMcolumnalongwithany“raise”buttonfor3seconds.
WhenremappingCCIs,theCCIactionsareprogrammedinthefollowingorder:1. “CCI1closed”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed
button)flashingonceevery8seconds.2. “CCI1open”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed
button)flashingtwiceevery8seconds.3. “CCI2closed”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed
button)flashingthreetimesevery8seconds.4. “CCI2open”action-indicatedbystatusLEDsofthatcolumn(exceptcurrentlyprogrammed
button)flashingfourtimesevery8seconds.5. WallstationwillautomaticallyreturntoAPMeachtimeaftercyclingthroughtheCCIactions.
(continued on next page...)
North American style wallstation European style wallstation
E
Application Note #428
8 Lutron Technical Support Center1.800.523.9466®
CCI Assignment and Scene Banking (continued)Functionality:OnceintheCCIprogrammingmode,thefollowingoptionsareavailable:
1. MakethebuttontowhichaCCIactioniscurrentlyprogrammeddo“nothing”: • Holdthecurrentlyprogrammedbuttonfor3secondstomaketheselectedCCIactionbe
“nothing”. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.2. ChangethebuttontowhichtheCCIactioniscurrentlyprogrammed: • Holdabuttonfor3secondstomakethatbuttonthecurrentlyprogrammedbuttonforthe
selectedCCIaction. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.3. NotchangingthesettingsoftheselectedCCIaction: • TapanybuttontomoveontoprogrammingthenextCCIaction.4. AssignascenebanktotheselectedCCIaction: • Simultaneouslyholdthetopandbottombuttonsofascenecolumnfor3secondstomake
thatscenecolumn“bank”whenthisCCIactionhappens. Ex.AScene1-3columncanbecomeaScene4-6columnwhenCCI1isclosed,andbacktoa
Scene1-3columnwhenCCI1isopen. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.5. UnassignascenebankfromtheselectedCCIaction • Simultaneouslyholdthetopandbottombuttonsofascenecolumn(thathasbeen
programmedto“bank”)for3seconds. • ThewallstationwillautomaticallymoveontoprogrammingthenextCCIaction.
Note:ThewallstationwillnotalwayscyclethroughallfourCCIoptions.Theexceptionoccurswhenthecurrentlyprogrammedbuttonisaraiseorlowerbutton,orafinetunebutton.
Ex.Ifthecurrentlyprogrammedbuttonisalowerbutton,“CCIclosed”willbelikepressingthatlowerbutton(dimmingtheload)and“CCIopen”willbelikereleasingit(stopdimming).Inthiscase,thewallstationwouldskipprogrammingthe“CCI1open”(sinceitisautomaticallyset)andjumptoprogramming“CCI2closed.”
Afterthefinal(“CCI2Open”)actionhasbeenprogrammed,thewallstationwillautomaticallyreturntoAPM.ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Oncetheholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
E
Application Note #428
9 Lutron Technical Support Center1.800.523.9466®
Changing the Column Type ColumnsA“column”inaseeTouchRQSmulti-columnwallstationisdefinedasagroupof(typicallyadjacent)buttonsthatallperformasimilarlogicfeature.
Column TypeThe“type”ofacolumndeterminesthelogicofhowthatcolumnoperates.
Tochangeyourwallstation’scolumntypesusingColumnTypeChangeMode:1. EnterAPM.2. SimultaneouslypressandholdanybuttonofthecolumninAPMalongwithany“Lower”button
for3seconds.
3. Oncetheholdtimeelapses,allbacklightsofthatcolumnwillremainsolidonandthestatusLEDswillblipinthefollowingpattern(eachcolumntypeislistedbelowandexplainedinsubsequentpages):
•1blipevery8seconds =“ScenewithOFF”columntype(notanoptionfor1Bcolumn)•2blipsevery8seconds =“Scene”columntype•3blipsevery8seconds =“ZoneToggle”columntype•4blipsevery8seconds =“Partition”columntype•5blipsevery8seconds =“Shade”columntype(notanoptionfor1Bcolumn)•6blipsevery8seconds =“ShadeToggle”columntype•7blipsevery8seconds =“ShadeGroup”columntype(notanoptionfor1Bcolumn)•8blipsevery8seconds =“Panic”,“Sequence”,or“Timeclock”columntype(2Bcolumnsonly)•9blipsevery8seconds =“FineTune”columntype(2Bcolumnsonly)•10blipsevery8seconds=(Althoughthedeviceallowstheusertoselectthiscolumntype,it
currentlyhasnofunctionality.Donotuse.)
Note:Wallstationwillskipcertainblippatternsdependingonthecapabilitiesofthewallstationbeingcurrentlyprogrammed(Ex.Acolumnmusthaveonly2buttonsinordertobeprogrammedwiththe“Sequence”or“FineTune”columntypes).
Note:Whilea1Bcolumnwillaccept“Scene”columntypeandwillnotaccept“SceneWithOff”columntype,a1BscenecolumnalwaystogglesbetweentheprogrammedSceneandSceneOff.
(continued on next page...)
North American style wallstation European style wallstation
F
Application Note #428
10 Lutron Technical Support Center1.800.523.9466®
Changing the Column Type (continued)
Column TypeThefollowingisalistingofallthepossiblecolumntypesforaseeTouchRQSwallstation:
Scene Type (with OFF): Controlsscenesonascenecontroller(suchasaGrafikEyeRQScontrolunit,oranareaonanEnergiSavrNodeTunit)ormultiplescenecontrollers.Allbuttonsinthecolumnwillalwayscontrolthesamescenecontrollers(youcannothavedifferentbuttonswithinthecolumncontrollingdifferentscenecontrollers).Thescenerecalledbythefirstbuttonisprogrammable,thesubsequentbuttonsrecallthenextnumericalscene,andthelastbuttonalwaysrecallsSceneOFF.
Ex.A5-button(5B)columnwiththiscolumntypesettostartatScene3wouldrecallScenes3,4,5,6,andOFFrespectively.
Scene Type (without OFF):SameasSceneTypeWithOFF,exceptthelastbutton-ratherthanrecallingSceneOFF-recallsthenextconsecutivescene.
Ex. A5-button(5B)columnwiththiscolumntypesettostartatScene3wouldrecallScenes3,4,5,6,and7respectively.
Zone Toggle Type: Zonetogglebuttonstoggleazoneorgroupofzonesbetweenprogrammablepresetvalues(eachzonecanbeprogrammedtoadifferentvalue),andOFF(allzonesareOFF).EachbuttoninaZoneTogglecolumncanbeindividuallyprogrammedtodifferentloads.
Partition Type:Allowstheusertoassignindividualbuttonsofacolumntodifferentscenecontrollers(GrAFIkEyeRQScontrolunitand/orEnergiSavrNodeT unitareas).Whenabuttonispressedonthewallstation,theLEDislitonthewallstationforthatbutton,andthepartitionisopen.Whenitispressedagain,theLEDisOFFforthatbutton,andthepartitionisclosed.Anopenpartitionmakesthedevicesprogrammedtothatbuttontalktoeachotherinbothdirections.Aclosedpartitionmakesthedevicesnottalktoeachotherineitherdirection.
FNorth American style wallstation European style wallstation
StatusLEDs
Status LEDs
BottomLower
Top Lower
BottomRaise
Top Raise
Buttons
Buttons
Buttons
Left Lower
right Raise
Left Raise
right Lower
BacklightLED
BacklightLEDs
BacklightLEDs
(continued on next page...)
Application Note #428
11 Lutron Technical Support Center1.800.523.9466®
Changing the Column Type (continued)Two-Button (2B) Special Functions2B Partition Type: SameasnormalPartitiontypeexceptthatatopbuttonpressopensthepartitionandabottombuttonpressclosesthepartition.
2B Fine Tune Type: Thebuttonsofthewallstationinthismodefunctionasraiseandlowerbuttonsfortheassignedzones.Tappingthebuttonswillraise/lowerthelevelofallassignedzonesbyonepercent.Holdingthebuttonswillsmoothlyraisetohighendorsmoothlylowertolowend.2B Sequence Type: Thesequencecolumntypecausesalltheassignedscenecontrollerstocontinuouslycyclethroughtheirscenes(eitherScenes1-4orScenes5-16)usingtheprogrammedfadetimesforeachscene.Thisisusefulforspacesthatdesiredynamiclightingsuchasdecorativelightingordisplaysinretailstores.
2B Panic Type:PanictypecausesalltheassignedscenecontrollerstogotoScene16,andtemporarilydisablesallbuttonspressesandignoressceneorzonelevelchanges.
2B Timeclock:TimeclocktypeallowstheusertoenableordisabletheTimeclockonaGrafikEyeRQScontrolunit.Pressingthetopbuttonofthe2BcolumnenablestheTimeclockandpressingthebottombuttondisablestheTimeclock.
Shade Type:Inshadetype,thetopbuttonofacolumnbecomestheOpenbuttonandthebottombuttonbecomestheClosebuttonfortheassociatedLutronRSivoiaRQSshades/draperiesorthirdpartyACshades.Ifthewallstationhasmorethantwobuttons,themiddlebuttonsbetweenOpenandCloseserveasprogrammablepresetbuttonsforLutronRSivoiaRQSshades/draperies,or“stop”buttonsforthirdpartyACshades.
Shade Group Type: Ashadegroupcolumncanonlyexistonamulti-columnwallstation,whereoneoftheothercolumnsisashadecolumn.Theshadegroupcolumnwillmaketheshadecolumnappeartooperateasmultipleindependentwallstations(oneindependentwallstationpergroup).Thepurposeoftheshadegroupcolumnistoselectwhichoftheindependentwallstationsiscurrentlyactive(onegroupisalwaysactive;namelythegroupbuttonwhoseLEDison).Ex.Ifashadegroupcolumnhas3buttons,theshadecolumnwilloperateas3independentshade
wallstations.IfthetopgroupbuttonispusheditsLEDwillturnonandthefirstindependentwallstationisselected,ifthesecondgroupbuttonispusheditsLEDwillturnonandthesecondindependentwallstationisselected,andifthe3rdgroupbuttonispusheditsLEDwillturnonandthe3rdindependentwallstationisselected.
Shade Toggle Type: Eachbuttoninthecolumncanbeprogrammedtoanindependentshadeorgroupofshades.Pressingthebuttonwillcausetheassignedshades/draperiestotoggle(oneachsubsequentbuttonpress)betweenthefollowingstates:• MovetowardsOpenlimit• Stop(ifanyassignedshade/draperyisstillmoving)• MovetowardsCloselimit• Stop(ifanyassignedshade/draperyisstillmoving)Ifthecolumnhasraise/Lowerbuttons,theywillaffecttheshades/draperiesassociatedtothelastbuttonthatwaspressed.Ex.AtwobuttonShadeTogglecolumnthathasbuttonB1thataffectsshade/draperyS1,andbutton
B2thataffectsshade/draperyS2.IfyoupressB1andthenraise/Lower,S1willraise/Lower.IfyoupressB2andthenraise/Lower,S2willraise/Lower.
F
(continued on next page...)
Application Note #428
12 Lutron Technical Support Center1.800.523.9466®
Changing the Column Type (continued)Functionality:OnceintheColumnTypeChangeModedescribedonpreviouspage,theuserhasthefollowingoptions:
1. Tappinganybuttonwillcontinuescrollingtothenextvalidcolumntypeoption.2. IfthewallstationtypeisScenewithOFF,Scene,or2BSpecialFunctions,theusermaychoosea
subtypeasfollows:• Pressandholdanybuttonofthatcolumnfor3seconds.• Onceholdtimeelapses,allstatusLEDswillgotoOFFindicatingthattheuserenteredthesub
mode.Then,thestatusLEDswillblipinthefollowingpattern:
Column Type Programming Mode
SelectionStatus LED Indication Sub Mode Options
Scene with OFF
1blipevery8seconds StartswithScene12blipsevery8seconds StartswithScene23blipsevery8seconds StartswithScene3
…Continuessequentially… …Continuessequentially…16blipsevery8seconds StartswithScene16
Scene
1blipevery8seconds StartswithScene12blipsevery8seconds StartswithScene23blipsevery8seconds StartswithScene3
…Continuessequentially… …Continuessequentially…16blipsevery8seconds StartswithScene16
2B Special Functions
1blipevery8seconds Panic2blipsevery8seconds SequenceScenes5-163blipsevery8seconds SequenceScenes1-4
4blipsevery8seconds TimeclockDisable
• Eachtapofany“raise”buttonwillprogressforwardthroughthedifferentoptionsandeachtapofany“Lower”buttonwillprogressbackwardsthroughthedifferentoptions.
• Toautomaticallysavethechosensubtype:
° Exitthesubmodebyholdinganybuttonofthatcolumnfor3seconds.
° Onceholdtimehaselapsed,thecolumnwillreturntoColumnTypeChangeModewithallbacklightLEDsofthecolumnsolidONandallstatusLEDsofthatcolumnblippingtoindicatetheselectedcolumntype.
• Forscenecolumns,certainoptionsinthesubmodemaynotbeavailable,dependingonthenumberofbuttonsinthecolumn.
Ex.a10Bcolumnwith“Scene”columntypecanonlygouptoScene7asthestartingscene(the10buttonswillrecallScene7throughScene16respectively).A10Bcolumnwith“ScenewithOFF”columntypecangouptoScene8asthestartingscene(thefirst9buttonswillrecallScene8throughScene16,andthefinalbuttonwillrecallSceneOFF).
3. SavetheselectedcolumntypeautomaticallybyexitingColumnTypeChangeMode.• Simultaneouslypressandholdanybuttonofthecolumnalongwithanylowerbuttonfor
3 seconds.• Onceholdtimeelapses,thecolumnwillreturntoAPMwithallbacklightLEDsofthecolumn
solidonandallstatusLEDsofthecolumnflashingrapidly.
F
(continued on next page...)
Application Note #428
13 Lutron Technical Support Center1.800.523.9466®
Changing the Column Type (continued)Note:IfonecolumnonadualcolumnwallstationentersColumnTypeChangeMode,allothercolumns
onthatwallstationwillalsoenterColumnTypeChangeModetoallowtheusertomoreeasilychangethecolumntypeofmorethanonecolumnwithouthavingtoexitandre-enterAPM.
ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,all statusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
“Raise” and “Lower” Button Remapping
1. EnterAPM.2. Simultaneouslypressandholdthe“raise”and“lower”buttonsthatyouwishtoassigntothe
columninAPMfor3seconds.3. Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,
indicatingthatthe“raise”and“lower”buttonshavebeenassignedtothatcolumn,thenreturntoAPM.
4. ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
European style wallstationNorth American style wallstation
F
G
Application Note #428
14 Lutron Technical Support Center1.800.523.9466®
Assigning an IR Remote1. EnterAPM2. PointanIrremotetowardthewallstationinAPM2. Holdtheraisebuttonfor3seconds4. StatusLEDsonthewallstationwillthenflashslowlyfor3secondstoindicatethattheIrremotehas
beensuccessfullyassigned5. WallstationwillautomaticallyreturntoAPM6. ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor
3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
IR Remote Pass-through and Button-mapping Modes1.EnterAPM.
Functionality:Note: ThedefaultmodeforanyIrremoteispass-throughmode.OnceinAPM,theuserhasthefollowingoptions:
A. Enablebutton-mappingmode: • PressandholdthefavoritebuttonoftheIrremotefor3seconds • Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,
indicatingthatthecolumnhasswitchedtobutton-mappingmode,thenreturntoAPM.
B. Enablepass-throughmode: • Pressandholdthefirstbutton(topbutton)oftheIrremotefor3seconds. • Onceholdtimeelapses,statusLEDsofthatcolumnwillflashslowlyfor3additionalseconds,
indicatingthatthecolumnhasswitchedtopass-throughmode,thenreturntoAPM.
Note: Ifacolumnissettoa“ZoneToggle”type,anIrremoteineithermodewillactasremotebuttonpresses.
2.ExitAPMbysimultaneouslypressingandholdingthetopandbottombuttonsofthecolumnfor3 seconds(ifitisa1Bcolumn,holdthesinglebuttonfor10seconds).Onceholdtimeelapses,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
RR
Open
Close
First Button First Button
Favorite Button
Favorite Button
H
Application Note #428
15 Lutron Technical Support Center1.800.523.9466®
Programming lockout
Functionality:To enable programming lockout mode:
1. Simultaneouslypressandhold“raise”,“Lower”,andanyactivebuttonfor30seconds.
2. Oncetheholdtimeelapses,allstatusLEDswilllightinasequentialflashofstatusLEDsfromthebottomtotopofthewallstation,indicatingthattheuserhaslockedoutofprogrammingmode.(Thissequenceofflashesisknownasareversewaterfall).
3. Then,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.Note: Eachtimetheuserattemptstoenteraprogrammingmodeafterlockingoutofprogramming
mode,allstatusLEDswilllightinasequentialflashofstatusLEDsfromthebottomtotopofthewallstationindicatingthatallprogrammingislockedout.
To disable programming lockout mode:1. Simultaneouslypressandhold“raise”,“lower”,andanybuttonofthecolumninAPMforthe
30 seconds.2. Oncetheholdtimeelapses,allstatusLEDswilllightinasequentialflashofstatusLEDsfrom
thebottomtotopofthewallstation(reversewaterfall),indicatingthattheuserhasremovedtheprogramminglockout.
3. Then,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
European style wallstationNorth American style wallstation
I
Application Note #428
16 Lutron Technical Support Center1.800.523.9466®
Information Display SequenceFunctionality:
1. Tapthesamebuttoninacolumn20timesconsecutively.ThiswillcausestatusLEDstobeginflashing.
2. Thefirst3timesthestatusLEDsflashconsecutively,theyareshowingthecoderevisionofthewallstation(withtheformatx.yz).
Note: Anumber“0”isdisplayednotbyzeroflashes,butinsteadbyaquicksequentialflashofstatusLEDsfromthebottomtotopofthecolumn(for1second).
• Oncetheuserhastappedthesamebuttonofacolumn20consecutivetimes,thecolumnwillenterinformationdisplaymodeandthestatusLEDswillimmediatelybeginflashingconsecutively“x”amountoftimes.
• Countthe“x”numberofflashes.• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthesecondtime
(6secondsafterenteringinformationdisplaymode),“y”amountoftimes.• Countthe“y”numberofflashes.• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthethirdtime
(12secondsafterenteringinformationdisplaymode)“z”amountoftimes.• Countthe“z”numberofflashes.• Oncetheuserhasreachedthisstep,thewallstationhasshownthefullnumber
(x,y,z)representingthecoderevisionofthewallstation.3. ThenexttimethestatusLEDsflashconsecutively,theyareshowingthetypehardwareinsidethe
wallstation• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthefourthtime
(18secondsafterenteringinformationdisplaymode),for“n”amountoftimes.• Countthe“n”numberofflashes.• The“n”numberofflashesrepresentsthefollowing:
“n” Hardware Type1 V1Hardware,NOTHomeWorksRQSenabled2 V2Hardware,NOTHomeWorksRQSenabled3 V1Hardware,HomeWorksRQSenabled4 V2Hardware,HomeWorksRQSenabled
• Oncetheuserhasreachedthisstep,thewallstationhasshownthenumberrepresentingthe
typeofhardwareinsidethewallstation.
J
(continued on next page...)
Application Note #428
17 Lutron Technical Support Center1.800.523.9466®
Information Display Sequence (continued)4. ThenexttimethestatusLEDsflashconsecutively,theyareshowingthecolumntypeofcolumn.
• Ashortpausewilloccur,thenthestatusLEDswillflashconsecutivelyforthefifthtime (24secondsafterenteringinformationdisplaymode),for“m”amountoftimes.
• Countthe“m”numberofflashes.• The“m”amountofconsecutiveflashesrepresentsthefollowing:
“m” Column Type1 ScenewithOFF2 Scene3 ZoneToggle4 Partition
5 Shade
6 ShadeToggle
7 ShadeGroup
8 2BSpecialFunctions
9 FineTune
• Oncetheuserhasreachedthisstep,thewallstationhasgiventheuserthenumberrepresentingthetypeoftheselectedcolumn.
5. Oncethecolumnhassequencedthroughthecoderevision,hardwaretype,andcolumntype,allstatusLEDsandbacklightLEDswillreturntotheirappropriatesettingsinNormalMode.
Shade Toggle Type ProgrammingProgramming a Shade Toggle Type Column:
1. Enterthecolumnintoprogrammingmodebyholdingthe“top”and“bottom”buttonsofthe shadetoggletypecolumntogetherfor5seconds(ifit’sa1Bcolumn,holdthesinglebuttonfor10seconds).
2. Tapthebuttonthatyouwishtoprogram.ItsLEDwillblinkrapidly.3. Eachtimeyoutapthissamebutton,thenextshade/draperywillbeselected.Eachtimeyou
doubletapit,thepreviousshade/draperywillbeselected.4. Toassignthecurrentlyselectedshade/drapery,tapthe“Lower”button.Tounassignthecurrently
selectedshade/drapery,tapthe“raise”button.5. Onceallshades/draperiesareassignedtothatbutton,tapthenextbuttonandrepeatthe
process.repeatforallbuttonsinthecolumn.6. Onceprogrammingiscomplete,holdthe“top”and“bottom”buttonsfor5secondstoreturnto
NormalMode(ifit’sa1Bcolumn,holdthesinglebuttonfor10seconds).
J
K
Application Note #428
®Lutron Electronics Co., Inc.7200 Suter RoadCoopersburg, PA 18036-1299 U.S.A.04/2012 P/N 048-428 Rev. A
Lutron Contact Numbers
WORLD HEADQUARTERS USA
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 TEL:+1.610.282.3800 FAX:+1.610.282.1243 Toll-Free:1.888.LUTrON1 TechnicalSupport:1.800.523.9466
North & South America Technical Hotlines
USA, Canada, Caribbean: 1.800.523.9466 Mexico: +1.888.235.2910 Central/South America: +1.610.282.6701
EUROPEAN HEADQUARTERS United Kingdom
Lutron EA Ltd. 6 Sovereign Close London, E1W 3JF United Kingdom TEL:+44.(0)20.7702.0657 FAX:+44.(0)20.7480.6899 FrEEPHONE(Uk):0800.282.107 TechnicalSupport:+44.(0)20.7680.4481
ASIAN HEADQUARTERS Singapore
Lutron GL Ltd. 15 Hoe Chiang Road #07-03, Tower 15 Singapore 089316 TEL:+65.6220.4666 FAX:+65.6220.4333 TechnicalSupport:800.120.4491
Asia Technical HotlinesNorthernChina:10.800.712.1536 SouthernChina:10.800.120.1536 Hongkong:800.901.849 Indonesia:001.803.011.3994 Japan:+81.3.5575.8411 Macau:0800.401 Taiwan:00.801.137.737 Thailand:001.800.120.665853 OtherCountries:+65.6220.4666
L. Restoring Factory DefaultsTorestorefactorydefaultstoawallstation,useanyenabledbuttononthewallstationtoperformthefollowing:
1. Tapbutton,tapbutton,tapbuttonandhold(untilallLEDsonthewallstationstarttoblinkslowly).2. releasethebuttonandimmediatelytapbutton,tapbutton,tapbutton(allLEDsonthewallstation
willblinkrapidly).
OnlyoncetheLEDsareblinkingrapidlyhasthewallstationstartedrestoringitsfactorydefaults(ifthisproceduredoesnotfunctionproperly,leavethewallstationidleforafewseconds,andthentryagain).
AftertheLEDsstopblinking,theywillgooffforashortinterval,andthenthewallstationwillturnoninitsfactorydefaultstate.
L