t400 ang synch app note
Post on 19-Feb-2016
222 Views
Preview:
TRANSCRIPT
MASTERDRIVE – T400 Application Guide #1
Angular Synchronization SPA440 with 6SE70, 6RA70
June 2000
Angular Synchronous Guide #1SPA440 June 2000Page 1
Title: Using the SPA440 preloaded on a T400 Technology Board, part # 6DD1-842-0AB0
1. Introduction:
The purpose of the application note is not to replace the Instruction Manual 6DD1-903-0BB0. Please refer to all sections for specific details expecially section 5 (commissioning). This application note will use the 6SE70 Demo Unit, but the 6RA70 demo unit could also be used.
2. Equipment Requirements:
2.1 6SE70 Demo Unit, part number A1-108-030-033, quantity (2)2.2 Local Bus Adapter, LBA, part number 6SE7090-0XX84-4HA0, quantity (1)2.3 T400 Board with SPA440 preloaded, part number 6DD1-842-0AB0,
quantity (1)2.4 A PC will either Drive ES Basic or Simovis 5.3.1 loaded. 2.5 Raw Shielded cable, 2 twisted pair, 10 feet.2.6 6SE70 VC Documentation CD, part number DRMS-02051 Version 3.0
3. Base Drive Setup and Programming:
3.1 Install the LBA adapter in the Slave drive, hereafter referred to as “DRIVE#2”
3.2 Install the T400 card in DRIVE#2. 3.3 For the 6SE70 Demo Unit, install standard default parameter file “Demo
Drive Suggested Tuning.DNL, as found on the 6SE70 VC Documentation CD DRMS-02051 Version 3.0. Install the same file on both Demo Units.
3.4 Make the following specific parameter adjustments to suit the T400 card on Drive#2 only.
Angular Synchronous Guide #1SPA440 June 2000Page 2
Variable Word CUVC DC-MasterBit Parameter Value Parameter Value
On / Off Command W1.0 P554 3100 P654 3100Off2 W1.1 P555 3101 P655 3101Off3 W1.2 P558 3102 P658 3102Setpoint Enable W1.6 P564 3106 P664 3106Fault Acknowledge W1.7 P565 3107 P665 3107Jogging 1 W1.8 P568 3108 P668 3108Jogging 2 W1.9 P569 3109 P669 3109External Fault 1 W1.15 P575 3115 P675 3115Speed Controller Enable W4.9 P585 3409 P685 3409Speed Setpoint (see note1) W2 P443 3002 P644 3002Suppl. Speed Setpoint from Angular Controller
W5 P224 3005 P634 3005
Pre-Control value for the Speed Controller
W8 P262 3008 P501 3008
Status Word 1 W1 P734.01 32 U734.01 32Speed Actual Value W2 P734.02 91 U734.02 40Torque W3 P734.03 182 U734.03 142Status Word 2 W4 P734.04 33 U734.04 33Drive Output Current W5 P734.05 22 U734.05 116
Drive#2 will have the following Digital Inputs / Outputs available as default.
Terminal Description BICO Parameter Enable46 Output-Sychronism Reached H631 H63747 Output – Angular Controller at limit H632 H63848 Output – Enable Status of Ang. Contr. H633 H63949 Output - Fault H634 H64051 Output - Alarm H635 N/A
53 Input – Angular Controller Enable54 Input – Synchronizing Command55 Input – Reset Position56 Input – Displacement Reset57 Input - Jog Enable
4. Wire Connections between Drive#1 and Drive#2:
Angular Synchronous Guide #1SPA440 June 2000Page 3
Terminal Connections on Drive #1 Description23 Drive #1 Encoder Feedback24 Drive #1 Encoder Feedback 25 Drive #1 Encoder Feedback 26 Drive #1 Encoder Feedback
Terminal Connections on Drive #2 Description23 Drive #2 Encoder Feedback24 Drive #2 Encoder Feedback 25 Drive #2 Encoder Feedback 26 Drive #2 Encoder Feedback
Reference Encoder Wire Connections on Drive #2 only
Description
23 T400 Terminal 6624 T400 Terminal 6225 T400 Terminal 6326 T400 Terminal 64
T400
M
Drive #1 Encoder Feedback connection to CUVC
MDrive #2 Encoder Feedback connection to CUVC
Drive #2 Reference from Drive #1
Line Speed Reference
CUVC
CUVC
Angular Synchronous Guide #1SPA440 June 2000Page 4
Note that the T400 Terminals 85, 86 and 87 need to have an external jumper installed if using Single-Ended Encoders. In the case of this Demo Unit, the jumpers did have to be installed.
5. Ready to Start:
5.1 Power to the Drive#2 Demo Unit was cycled to ensure the parameter values on the T400 card were updated.
5.2 Power to both Demo Units were restored.5.3 Since this is a simulation, P554 on Drive#2 was changed to B0018 to allow
the “slave” drive to start and be ready for when the speed change was detected on the Reference encoder.
5.4 Drive#1’s motor was manually turned and the motor shaft on Drive#2 was observed.
5.5 Drive#1 was started and the speed reference (speed pot#1) was adjusted.5.6 If specific additional tuning was required refer to main instruction manual
contained on the 6SE70 VC Documentation CD, part number DRMS-02051 Version 3.0
Additional Notes:
Note#1: If H140 is set to “0” then the speed controller is active on the CUVC board.If H140 is set to “1”, then the speed controller is active on the T400 board.
top related