IBR Modeling Fundamentals
Songzhe Zhu
WECC MVS WorkshopSeptember 17, 2020
ISO Public
Outline
• Modeling guideline for all IBRs connecting to transmission and subtransmission– Power Flow Representation– Dynamic Models– Active power – frequency control– Reactive power – voltage control– Fault ride-through
• Solar PV• BESS and Hybrid
Page 2
ISO Public
Basics of modeling IBR connecting to transmission and sub-transmission
Page 3
ISO Public
Power Flow Representation
• transmission and sub-transmission connected IBR
EQ
1 2 3 4 5
Interconnection Transmission
Line
Substation Transformer
Equivalent Collector System
Equivalent Pad-mounted Transformer
Plant-level Reactive
Compensation (if applicable)
Equivalent Generator
Point of Interconnection
Typical Single-Generator Equivalent Power Flow Representation
ISO Public
Collector System & IBR Equivalencing
• Equivalent impedance of the collector system shall be represented – Inverters respond to the terminal voltage– Voltage at POI and terminals are quite different
• Multi-generator representation may be needed– Multiple main GSUs, with separate collectors behind them– Significantly diverse impedances behind different feeders– Inverters by different manufacturers are installed behind the
feeders and these inverters have different control and protection settings
Page 5
ISO Public
Multi-Generator Representation
Page 6
G1
1 2 3 4 5
Interconnection Transmission
Line
Substation Transformer
Equivalent Collector System
Equivalent Pad-mounted Transformer
Equivalent Generator 1
Point of Interconnection
G2
6 7 8Equivalent
Generator 2
Equivalent Generator 3G3
9
Illustrative Multi-Generator Equivalent Power Flow Representation
* Although not illustrated by this example, all var devices should be modeled explicitly.
ISO Public
Positive Sequence Dynamic Models
• Generic models approved by WECC
• Very flexible to model different control setups
• Models are supported and benchmarked among different software platforms
• Easy access to model documents and user guides
• Generally applicable for systems with a short circuit ratio of 3 and higher at the point of interconnection
Page 7
ISO Public
Generic Dynamic Models
Page 8
Description Model Name Applicability NotesConverter REGC_A
REGC_BREGC_C
All IBR: current source modelAll IBR: voltage source modelAll IBR: REGC_B plus PLL and inner current control loops
Electrical controlREEC_AREEC_CREEC_D
Type 3 and 4 WTG, solar PV Battery energy storageEnhanced model for all types of IBR
Plant controller
REPC_AREPC_BREPC_C
For controlling single deviceFor controlling multiple devicesEnhanced model for controlling singledevice
Ride-through protection LHVRTLHFRT
Voltage ride-throughFrequency ride-through
Enhanced model approved or under development
* Models specific to WTGs are discussed in wind plant modeling session.
ISO Public
Generic Model Structure
Page 9
REPC REEC REGCQ/V reference
P reference
iq command
ip command
Network Interface
ISO Public
Scaling for the Equivalent Generator Size
• Pmax and MVA base in the power flow model and dynamic models are aggregated values
• Power flow model –– MVA base is the sum of the individual MVA rating of the inverters– Pmax is the maximum active power output from the equivalent
generator in accordance with the generation interconnection study and interconnection agreement
• often lower than the sum of the individual rated MW of the inverters due to the practice of oversizing inverters
• Dynamic models –– Model parameters are expressed in per unit of the MVA base for
the model– Typically MVA base matches the MVA base in the power flow
modelPage 10
ISO Public
Active Power – Frequency Control Options
• Power flow model: base load flag (BL)– BL = 0: Pgen can be dispatched downward and upward– BL = 1: Pgen can be dispatched downward only– BL = 2: Pgen is fixed
• Dynamic model: REPC– frqflag= 0/1: frequency response no/yes– ddn & dup: downward & upward regulation gain– fdbd1 (+) & fdbd2 (-): over- and under-frequency deadband for
frequency response (pu)
Page 11
ISO Public
Active Power – Frequency Control Options (Cont’d)
• With earlier version of the models (prior to Aug 2020)– base load flag is not used in the dynamic simulation– block frequency response through frqflag/ddn/dup
• With model enhancement– Base load flag is used to block frequency response in reec and repc
models except for repc_b.
Page 12
Functionality BL frqflag ddn dup
No response 2 0 - -
Down regulation only 1 1 >0 0
Up and down regulation 0 1 >0 >0
Functionality BL frqflag ddn dup
No response 2 - - -
Down regulation only 1 1 >0 -
Up and down regulation 0 1 >0 >0
ISO Public
Active Power – Frequency Control Key Parameters
• Other control parameters in REPC for frequency response– Kpg: proportional gain– Kpi: integral gain– Tlag: lag time constant
Page 13
Non-step deadband
ISO Public
Reactive Capacity Requirement
• Interconnection requirement for IBR reactive capacity has evolved, e.g.– No requirement– 0.95 power factor at POI– FERC Order No. 827: 0.95 power factor (dynamic var)
at high side of the substation transformer• The modeling recommendation in this presentation
focuses on IBR complying with FERC Order No. 827
Page 14
ISO Public
Model IBR Reactive Capability
• Inverter P-Q capability– Manufacturer provides P-Q capability curves under different ambient
temperatures and DC voltages– Use the P-Q capability curves to verify if there is sufficient capability to
meet the interconnection requirement
• Generator reactive capability in the power flow model– Model the required reactive capability– Qmax and Qmin of the equivalent generator are reactive capability at
Pmax, limited by the minimum amount to meet the interconnection requirement
• Generator reactive capability in the dynamic models– The physical capability is modeled, not limited by the PF requirement
Page 15
ISO Public
Reactive Power – Voltage Control in Power Flow
Assuming the only dynamic var sources are inverters –• If inverters regulating voltage at point of measuring (POM)
– Voltage regulation bus is the high-side bus of the GSU– The Generator is set to cont_mode = 2 with pf = 0.95, i.e. the power
flow solution will try to hold voltage at the regulated bus constant within Q limits specified by pf
• If inverters regulating terminal voltage– The Generator is set to cont_mode = -2 with pf ≤ 0.95, i.e. the
power flow solution will try to hold terminal voltage constant within Q limits specified by pf
• Voltage regulation of LTC transformers• Controlled shunts – SVD
Page 16
ISO Public
Power Flow Modeling Limitation on Reactive Power / Voltage Control Coordination
• Reactive power – voltage control is coordinated by the power plant controller (PPC)
• Inverter reactive output is controlled along a voltage droop curve
• Most power flow softwares do not currently model PPC and can’t do voltage droop control– PPC power flow model is under development. WECC MVS has
published the model specification.
• Discuss more on PPC control in the hybrid plant modeling session.
Page 17
ISO Public
Reactive Power – Voltage Control in Dynamic Models
• Different voltage control options are modeled by the combination of pfflag, vflag and qflag in reec model and refflag in repc model
Page 18
Functionality PfFlag Vflag Qflag RefFlag
Constant local PF control 1 N/A 0 N/A
Constant local Q control 0 N/A 0 N/A
Local V control 0 0 1 N/A
Local coordinated V/Q control 0/1 1 1 N/A
Plant level Q control 0 N/A 0 0
Plant level V control 0 N/A 0 1Plant level Q control + local coordinated V/Q control 0 1 1 0
Plant level V control + local coordinated V/Q control 0 1 1 1
Plant level PF control* 0 N/A 0 2Plant level PF control + local coordinated V/Q control* 0 1 1 2
* repc_b only
ISO Public
Plant Level Reactive Power – Voltage Control Options
• Voltage Control: RefFlg=1– Select the regulating bus (Vreg)– Set the monitored branch– Set VcmpFlg=1 if using line
drop compensation (Rc and Xc) – Set VcmpFlg=0 if using reactive
droop (Kc)
Page 19
• Constant Q Control: RefFlg=0– Select the monitored branch
ISO Public
Multiple Device Plant Control: REPC_B
Page 20
Plant PF Control Multiple Device Control
ISO Public
Plant Level Reactive Power – Voltage Control Key Parameters
• Key parameters– Control deadband (dbd)– Input (emax/emin) and output (qmax/qmin) limits– Control gains (kp/ki)– Intentional phase lead (Tft)– Communication lag (Tfv)– Voltage threshold to freeze plant voltage integral control (vfrz)
Page 21
ISO Public
Inverter Level Reactive Power – Voltage Control Options
Page 22
PF Control
Constant Q Control
If no plant controller –
Local V Control
Local Coordinated Q/V Control
ISO Public
Inverter Level Reactive Power – Voltage Control Options (Cont.)
Page 23
Plant level Q or V Control
If coordinated with plant controller –
Plant level Q or V Control and Local Coordinated Q/V Control
ISO Public
Inverter Level Reactive Power – Voltage Control during Voltage Dip
• Voltage dip: Vt < Vdip or Vt > Vup• During voltage dip, local Q control and local V control
freeze• K-factor control: proportional gain Kqv
Page 24
ISO Public
Coordinate Plant Level and Inverter Level Controls
• Key factors to achieve desired control performance –– Choose control option: plant level control or plant level control
and local coordinated control– At what voltage levels, freeze plant level Q/V control (vfrz) and
local Q/V control (vdip), taking into account plant controller regulates POM bus voltage while the inverter controller regulates terminal bus voltage
– At what voltage levels, k-factor control shall be activated– Control gains and time constant associated with each control
mode– P/Q priority
Page 25
ISO Public
Inverter Current Limit
Page 26
iq control
ip control
Ip and Iq control come together
ISO Public
Invert Current Limit (Cont.)
• Define the maximum inverter current imax
• REEC_A: voltage-dependent current limits for ip and iq separately (VDL1 and VDL2)
• Total current 𝑖𝑖𝑝𝑝2 + 𝑖𝑖𝑞𝑞2 is
limited by imax
• During low voltage, ipcmd or iqcmd may be reduced until the voltage recovers depending on P/Q priority
Page 27
ISO Public
P-Q Priority
Page 28
ISO Public
Example of Different Control Strategies
Vdip=0.9, Kqv = 2.0
Vt at fault is below 0.25.Iqcmd rises quickly to 1.07.
After fault, initial Vt is 1.196.
Plant control freezes for voltage outside [0.9,1.1]. Iqcmd reduces immediately post fault.
Kvi = 40 & plant control
Vt at fault is below 0.25.Iqcmd rises quickly to 1.3.
After fault, initial Vt is 1.2.
Slower plant control keeps voltage at 1.2 for about 0.13 sec.
Control Setup 2: enable voltage dip and kqv controlControl Setup 1: slow plant control and no voltage dip and kqv control
ISO Public
Frequency Ride-through
• Lhfrt model parameters should reflect the actual frequency protective relay settings
• The settings should be PRC-024 compliant• Frequency calculation in positive sequence stability programs are
not accurate during and immediately following the fault• Work-around of false frequency tripping for a close-by simulated
fault –– Use lhfrt in “alarm only” mode and analyze each individual alarms– Disable frequency tripping under low voltage condition (dypar[0].v_f_inh
in javaini.p)– Do not set instantaneous tripping and always include some delay for
frequency tripping
Page 30
ISO Public
Voltage Ride-through
• Lhvrt model parameters should reflect the actual voltage protective relay settings
• The settings should be PRC-024 compliant– PRC-024 requirement is set with voltage at the high side of the
substation transformer (POM)– The actual protection is set with terminal voltage– The voltage setpoints should take into account the difference between
inverter terminals and POM
Page 31
ISO Public
Modeling solar PV plants connecting to transmission and sub-transmission
Page 32
ISO Public
Model Solar PV Momentary Cessation
• Model structure: REGC, REEC_D, REPC• Modeling elements
– Current reduction during cessation [REEC_D].VDLq and VDLp• set current limits to 0 for both ip and iq when the voltage is below Vmc-lv or
above Vmc-hv
– Disable low voltage power logic [REGC].lvplsw = 0– Ramp control [REGC].rrpwr, iqrmax and iqrmin– P/Q priority during recovery [REEC_D].pqflag– Voltage dip logic [REEC_D].vblkl = Vmc-lv, vblkh = Vmc-hv
– Current recovery delay [REEC_D].Tblk_delay
Page 33
ISO Public
Comparison of REEC_D with REEC_A for Modeling Momentary Cessation
• REED_D has the full capability of modeling momentary cessation, while REEC_A does not.
Page 34
REEC_A REEC_DMC low voltage threshold vdip vblklMC high voltage threshold vup vblkhVoltage-dependent reactive current limit*
VDL14 pairs of (vq, iq)
VDLq10 pairs of (vq, iq)
Voltage-dependent reactive current limit*
VDL24 pairs of (vp,ip)
VDLp10 pairs of (vp, ip)
Active current recovery delay Thld2 Tblk_delayReactive current recovery delay Not modeled Tblk_delay
ISO Public
REEC_D Model Enhancement
Page 35
ISO Public
Converting REEC_B to REEC_D
• REEC_D is an expansion of REEC_B. If the solar PV inverters do not use momentary cessation, the previous REEC_B models can be easily converted to REEC_D by adding parameters in this table.
Page 36
Parameter Name Value
rc 0Xc 0Tr1 0Kc 0Vcmpflag 0Ke 0Iqfrz 0Thld 0VDLq (-1.0, imax), (2, imax), (0,0) …VDLp (-1.0, imax), (2, imax), (0,0) …vblkl 0vblkh 2Tblk_delay 0iqfrz 0thld 0thld2 0vref1 0pflag 0
ISO Public
Modeling BESS and hybrid power plants connecting to transmission and sub-
transmission
Page 37
ISO Public
Definition of Hybrid Power Plant
• A generating resource that is comprised of multiple generation technologies that are controlled by a single entity and operated as a single resource behind a single point of interconnection (POI).
• Single point control of multiple generators is the key that requires additional modeling capability.
Page 38
ISO Public
Two Types of Configuration
DC-Coupled AC-Coupled
Page 39
ISO Public
BESS Plant and DC-Coupled Hybrid Plant – Power Flow Model
• DC-coupled hybrid plant is modeled the same way as a BESS only plant
• Batteries and solar PV arrays on the DC side are modeled in a single generator
• Pmin in the power flow model represents the maximum charging power – For stand-alone BESS, pmin < 0;– For hybrid, pmin <0 if charging from the grid; pmin = 0
if DC-side charging only.
Page 40
ISO Public
BESS Plant and DC-Coupled Hybrid Plant – Dynamic Model
• Use the second generation RES models: regc, reec_c or reec_d, repc
• Reec_c includes simulation of the state of charge
• Reec_d does not have the state of charge logic any more.
Page 41
Common simulation set-up mistake: PGEN < 0 and SOCini = 1.0; PGEN > 0 and SOCini = 0
ISO Public
AC-Coupled Hybrid Plant
• Different technologies are modeled by separate generators
• Single point control needs to be implemented in both the power flow model and the dynamic model – Power Plant Controller (PPC) power flow model is
being developed– Repc_b has been enhanced for better hybrid
frequency response control
ISO Public
Modeling Requirement for AC-Coupled Plant
• Frequency / active power control– The total MW injection at the point of interconnection is limited
by the contractual maximum– Different components have different frequency response
• Voltage / reactive power control– Plant reactive output limit is typically 0.95 power factor at the
high side of substation transformer– Power plant controller coordinates operation of the inverters,
transformer tap changers, SVDs, and other var devices to maintain the regulated bus voltage within a deadband from the voltage schedule
ISO Public
Proposed PPC Power Flow Model
• A PPC model is defined by:– Individual devices such as generators, SVDs, and
other controllable reactive devices*– A regulated bus– QV characteristics at the regulated bus– Plant real power limits
*Transformers that control tap will not be part of the PPC
Page 44
ISO Public
PPC QV Characteristics
• The power flow solution represents an operating point such that the Mvar being injected at the Regulated Bus from the devices in the PPC will follow a QV characteristic with a deadband.– For example, Qdb is 0 or equal to the var losses on the gen-tie;
qmax and qmin represents 0.95 lag/lead power factor at the regulated bus
Page 45
ISO Public
Real Power Monitoring
• The PPC model monitors the real power injection at the monitored bus and generate warning messages if the injection is outside the plant real power limits.
Page 46
ISO Public
An Example of PPC Model
Page 47
PV
1 2 3 4 5
Interconnection Transmission
Line
Substation Transformer
Equivalent Collector System
Equivalent Pad-mounted Transformer
Equivalent Generator for
Solar PV
Point of Interconnection
BT
6 7 8 Equivalent Generator for
Battery
230kV 34.5kV 690V
SVD“SD”
T1
T2
PPC: Solar-BESSDevices Device Type
Bus 5 "PV" GeneratorBus 8 "BT" GeneratorBus 3 "SD" SVDReactive Power ControlRegulated Bus Bus 2Qmax (Mvar) 34Qmin (Mvar) -34Real Power MonitorMonitored MW At Bus 1 from Bus 2 Pmax 100Pmin -100
100 MW
100 MW
QV Curve at Bus 2
ISO Public
Dynamic Model for AC-Coupled Hybrid
• Use regc, reec and repc_b modules.
Page 48
Module PSLF modules PSSE modules
BESS Component
Grid interface regc_* REGC*Electricalcontrols
reec_c or reec_d
REECC1 or REECD1
Non-BESS Component Use appropriate modules for the gen type
Plant controller repc_b PLNTBU1Aux control REAX4BU1 or
REAX3BU1Voltage/frequency protection lhvrt/lhfrt VRGTPA/FRQTPA
ISO Public
More on REPC_B
• Invocation notes– In PSLF implementation, REPC_B is invoked from one of generators in the plant.
It is important to have REPC_B invoked from an online generator. – The regulated bus and the monitored branch must be specified for REPC_B.
• Reactive control– Qmax and qmin are plant level reactive limits; on the system MVA base in PSLF
implementation
• Frequency control– Set frqflag to enable plant level frequency response– Use base load flag to enable or block individual component response
Page 49
Component BaseLoad flag ModuleSolar PV - Frequency response, down only regulation
1 reec_d
BESS - Frequency response, up and down
0 reec_c or reec_d
Plant controller Repc_b withFrqflag=1, dup > 0, ddn > 0
ISO Public
Reference
• WECC MVS, Solar PV Plant Modeling and Validation Guidelinehttps://www.wecc.org/Reliability/Solar%20PV%20Plant%20Modeling%20and%20Validation%20Guidline.pdf• Pouyan Pourbeik, Memo RES Modeling Updates 083120_Rev17https://www.wecc.org/Administrative/Memo_RES_Modeling_Updates_083120_Rev17_Clean.pdf• WECC MVS, Converting REEC_B to REEC_A/Dhttps://www.wecc.org/Reliability/WECC%20White%20Paper%20on%20Converting%20REEC%20rev202008.pdf• WEC MVS, Hybrid Plant Modeling Enhancementhttps://www.wecc.org/_layouts/15/WopiFrame.aspx?sourcedoc=/Administrative/WECC%20White%20Paper%20on%20modeling%20hybrid%20solar-battery.pdf