TRANSCRIPT

A complete system of compatible equipment

DF6000

Key panel features

DF6000

DF6000• Large versatile touch screen display• Single two and four loop versions• Spur tolerant soft addressing

– Device addressing done by panel not by installer– Eliminates manual addressing– Faster to install– Avoids addressing errors

• Large selection of Compatible ancillaries• Full network capability• Optional integral printer• Integral battery and power supply• 150 addresses per loop

– (512 per panel as per EN54)• 96 zonal LED’s

Touch screen display

Touch any box to activate function

Indicates which menu is currently selected

Touch for further details / select

To change menus touch a tab

Touch screen display

Soft addressing

1 2 34 5 6 78 9 10 11 D

F600

0

D F6000

Panel reads first address (254)

Allocates new address 1

Panel instructs short circuit isolator to close

Panel reads next address (254)

Allocates new address 2Panel instructs

short circuit isolator to close

Allocates new address 3

Panel reads next address (254)

Spur tolerant soft addressing

Soft addressing with spurs

1 2 34 5 6 78 9 10 11 D

F600

0

D F6000

1 2

Panel identifies a spur

Addresses the spur

Then continues with the loop

3

4 5 6

7

8

910

11

1213

Spur isolator

DF6000 – Detailed features

• Cause and effect programming– Coincidence / double knock detection– Specific internal or external devices to respond to specific

devices or signals

DF6000 – Detailed features

• Input Programming– Day night mode

• Set by time or by input– Photo-thermals go to thermal only– ROR go to high temp– High temp to to ROR

– Disable pre assigned group of addresses– Non latching zone input– Evacuate

• Detailed event log

DF6000 service and commissioning features

• Change text at panel – via touch screen• Sounder level test (30 seconds on 30 seconds off)• Device test mode• Alarm counter• Programming upload and Download• Reconfigure heat detectors

Additional features

• 1 shot weekly test• Walk test mode• View analogue levels in real time• Changeable user code• Add simple devices directly at the panel• Check auto-config menu:

– Pinpoints exact point of loop breaks– Identifies type code mismatches

Integral battery and power supply

• Standard panel has 12 A/H battery• Deeper back box version with double battery capacity

Battery

Power supply

Choice of panel colours

• Light grey (standard)• Graphite (extra cost)

Optional lockable hinged clear cover

• Protects Touch screen display• Prevents unauthorised access

Optional lockable hinged clear cover

• Protects Touch screen display• Prevents unauthorised access• Includes scroll and buzzer mute buttons• Can be retro – fitted• Still allows full system visibility

Optional integral printer

Blanking plug if no printer fitted

Optional integral printer

• Simple safe access to printer via locked door• Drop in paper cradle• Printer self loads

Compatible devices

Soft addressed detectors

• Photo electric• Ionisation• Multi – mode heat

– Can be programmed as:• Rate of rise device (A1R characteristic) • Fixed temp BS (medium) characteristic• Fixed temp CS (high temperature) characteristic.

• Photo – thermal– Can be programmed as

• Combined photo thermal• Thermal only

Dedicated analogue base

• Includes shorting switch for analogue loop continuity• Includes Screen termination point

Compatible callpoints

• Soft addressed • Status LED

Compatible callpoints

• Soft addressed • Status LED• 3 types:

– Surface– Flush– Weatherproof

Callpoint accessories

Optional hinged cover

Optional resettable element Optional bezel

DF6000 sounders

• Loop powered stand alone sounder• 3 volume settings (controlled by panel)

– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap

DF6000 sounders

• Loop powered IP66 stand alone sounder• 3 volume settings (controlled by panel)

– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap

DF6000 sounders

• Loop powered base mounted sounder• 3 volume settings (controlled by panel)

– Low (84dB) +/-3dB– Medium (92dB) +/-3dB– High (95dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 910Hz– Pulsed 910 / 0Hz pulse 1Hz– Two Tone 610 / 910Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap– Optional lockable cover for use as stand alone sounder

DF6000 loop powered beacon

• Loop powered• LED technology• Fast fit mounting base• Low current

DF6000 interfaces

• 3 Channel I/O device. (MIO324)– 3 separate inputs and outputs– Inputs can be fire or non fire– Inputs monitored for open and short circuits

• Both generate faults– Only takes a single address – Fits onto a standard deep backbox

DF6000 interfaces

• 1 Channel I/O device - mains rated output switching (MIO1240)– Separate input and output– Mains rated output contact– Input can be fire or non fire– Input monitored for open and short circuits– Only takes a single address

DF6000 interfaces

• Zone monitor unit (MIU871) – Allows a zone of conventional detectors to be connected– Uses JSB base and EOLM - 1

DF6000 interfaces

• Shop unit Interface (MSU840)– Facilities to accept conventional detection zone– Output relay (activates on fire)– Facility to connect power supply (monitored)

DF6000 interfaces

• Spur Isolator (MSI850)– Allows a spur of analogue devices– Includes short circuit isolator

DF6000 interfaces

• 4 Way sounder circuit controller (MPU424)– Integral power supply and battery– 4 separately programmable sounder circuits– Sounder circuits can have cause and effect programming

Application schematic

D F6000

M a in lo o p

MIO 1240

Fire or non fire input

Mains rated output relay contact

3 independent Volt free output contacts

3 separate inputs to accept fire or non fire inputs

MIO324M PU424

4 Independently controlled conventional sounder Circu its

Spur o f ana logue devices

M SI850

MIU871

Zone o f com patib le conven tional ca llpoin ts and sounders

Zone o f com patib le conven tional callpo ints and de tectors

2 C ircuits o f conven tional sounders

Power supply

DF6000 repeaters

• DF6000 panels can be connected as active repeaters• Low cost passive repeater also available

– Can be loop connected (hold and displays text for own panel only)

– Can be Network connected (gets text for entire system via network)

– LCD display (not touch screen)– Silence evacuate and reset functionality

DF6000 connected to Network

Low cost repeater connected to network gets entire system text from network

1 2 3 4 5

FIREFAULT

Repeater connected to loop

Low cost repeater connected to ind ividual panel holds and d isp lays text for that panel only - M ANUA L TE XT U PDATE NEE DED

1 2 3 4 5

FIREFAULT

System networking

• Up to 63 panels can be networked• Panels are connected in a loop• Network is monitored• If any panel is disconnected master and faulty panel shows fault

& details

Programming overview

Create all the panels for the site

Select a panel and a loop

Add zones to the loop and populate them

Devices are colour coded for ease of recognition

Indicates an address which is used in a different zone

3 stage programming for each sounderDefinable at each stage:

Source of trigger

By panel

By address

By zone

Type of output

Continuous

Pulsing

Time delayed

Type of trigger

Double knock

Standard trigger

If non global trigger select inputs

Select up to 16 zones, addresses or panels as relevant for each stage for each sounder

Sounder settings are individually programmable

All inputs are individually configured

Select required action

top related