A complete system of compatible equipment

DF6000

Page 3: Cooper 03008324979 Sajid Mehmood Butt

Key panel features

DF6000

Page 4: Cooper 03008324979 Sajid Mehmood Butt

DF6000• Large versatile touch screen display• Single two and four loop versions• Spur tolerant soft addressing

– Device addressing done by panel not by installer– Eliminates manual addressing– Faster to install– Avoids addressing errors

• Large selection of Compatible ancillaries• Full network capability• Optional integral printer• Integral battery and power supply• 150 addresses per loop

– (512 per panel as per EN54)• 96 zonal LED’s

Page 5: Cooper 03008324979 Sajid Mehmood Butt

Touch screen display

Touch any box to activate function

Indicates which menu is currently selected

Touch for further details / select

To change menus touch a tab

Page 6: Cooper 03008324979 Sajid Mehmood Butt

Touch screen display

Page 7: Cooper 03008324979 Sajid Mehmood Butt

Soft addressing

1 2 34 5 6 78 9 10 11 D

F600

0

D F6000

Panel reads first address (254)

Allocates new address 1

Panel instructs short circuit isolator to close

Panel reads next address (254)

Allocates new address 2Panel instructs

short circuit isolator to close

Allocates new address 3

Panel reads next address (254)

Page 8: Cooper 03008324979 Sajid Mehmood Butt

Spur tolerant soft addressing

Page 9: Cooper 03008324979 Sajid Mehmood Butt

Soft addressing with spurs

1 2 34 5 6 78 9 10 11 D

F600

0

D F6000

1 2

Panel identifies a spur

Addresses the spur

Then continues with the loop

3

4 5 6

7

8

910

11

1213

Spur isolator

Page 10: Cooper 03008324979 Sajid Mehmood Butt

DF6000 – Detailed features

• Cause and effect programming– Coincidence / double knock detection– Specific internal or external devices to respond to specific

devices or signals

Page 11: Cooper 03008324979 Sajid Mehmood Butt

DF6000 – Detailed features

• Input Programming– Day night mode

• Set by time or by input– Photo-thermals go to thermal only– ROR go to high temp– High temp to to ROR

– Disable pre assigned group of addresses– Non latching zone input– Evacuate

• Detailed event log

Page 12: Cooper 03008324979 Sajid Mehmood Butt

DF6000 service and commissioning features

• Change text at panel – via touch screen• Sounder level test (30 seconds on 30 seconds off)• Device test mode• Alarm counter• Programming upload and Download• Reconfigure heat detectors

Page 13: Cooper 03008324979 Sajid Mehmood Butt

Additional features

• 1 shot weekly test• Walk test mode• View analogue levels in real time• Changeable user code• Add simple devices directly at the panel• Check auto-config menu:

– Pinpoints exact point of loop breaks– Identifies type code mismatches

Page 14: Cooper 03008324979 Sajid Mehmood Butt

Integral battery and power supply

• Standard panel has 12 A/H battery• Deeper back box version with double battery capacity

Battery

Power supply

Page 15: Cooper 03008324979 Sajid Mehmood Butt

Choice of panel colours

• Light grey (standard)• Graphite (extra cost)

Page 16: Cooper 03008324979 Sajid Mehmood Butt

Optional lockable hinged clear cover

• Protects Touch screen display• Prevents unauthorised access

Page 17: Cooper 03008324979 Sajid Mehmood Butt

Optional lockable hinged clear cover

• Protects Touch screen display• Prevents unauthorised access• Includes scroll and buzzer mute buttons• Can be retro – fitted• Still allows full system visibility

Page 18: Cooper 03008324979 Sajid Mehmood Butt

Optional integral printer

Blanking plug if no printer fitted

Page 19: Cooper 03008324979 Sajid Mehmood Butt

Optional integral printer

• Simple safe access to printer via locked door• Drop in paper cradle• Printer self loads

Page 20: Cooper 03008324979 Sajid Mehmood Butt

Compatible devices

Page 21: Cooper 03008324979 Sajid Mehmood Butt

Soft addressed detectors

• Photo electric• Ionisation• Multi – mode heat

– Can be programmed as:• Rate of rise device (A1R characteristic) • Fixed temp BS (medium) characteristic• Fixed temp CS (high temperature) characteristic.

• Photo – thermal– Can be programmed as

• Combined photo thermal• Thermal only

Page 22: Cooper 03008324979 Sajid Mehmood Butt

Dedicated analogue base

• Includes shorting switch for analogue loop continuity• Includes Screen termination point

Page 23: Cooper 03008324979 Sajid Mehmood Butt

Compatible callpoints

• Soft addressed • Status LED

Page 24: Cooper 03008324979 Sajid Mehmood Butt

Compatible callpoints

• Soft addressed • Status LED• 3 types:

– Surface– Flush– Weatherproof

Page 25: Cooper 03008324979 Sajid Mehmood Butt

Callpoint accessories

Optional hinged cover

Optional resettable element Optional bezel

Page 26: Cooper 03008324979 Sajid Mehmood Butt

DF6000 sounders

• Loop powered stand alone sounder• 3 volume settings (controlled by panel)

– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap

Page 27: Cooper 03008324979 Sajid Mehmood Butt

DF6000 sounders

• Loop powered IP66 stand alone sounder• 3 volume settings (controlled by panel)

– Low (87dB) +/-3dB– Medium (93dB) +/-3dB– High (100dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 984Hz– Pulsed 984 / 0Hz pulse 1Hz– Two Tone 644 / 984Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap

Page 28: Cooper 03008324979 Sajid Mehmood Butt

DF6000 sounders

• Loop powered base mounted sounder• 3 volume settings (controlled by panel)

– Low (84dB) +/-3dB– Medium (92dB) +/-3dB– High (95dB) +/-3dB

• 3 tones (controlled by panel)– Continuous 910Hz– Pulsed 910 / 0Hz pulse 1Hz– Two Tone 610 / 910Hz @ 1Hz cycle– Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap– Optional lockable cover for use as stand alone sounder

Page 29: Cooper 03008324979 Sajid Mehmood Butt

DF6000 loop powered beacon

• Loop powered• LED technology• Fast fit mounting base• Low current

Page 30: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• 3 Channel I/O device. (MIO324)– 3 separate inputs and outputs– Inputs can be fire or non fire– Inputs monitored for open and short circuits

• Both generate faults– Only takes a single address – Fits onto a standard deep backbox

Page 31: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• 1 Channel I/O device - mains rated output switching (MIO1240)– Separate input and output– Mains rated output contact– Input can be fire or non fire– Input monitored for open and short circuits– Only takes a single address

Page 32: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• Zone monitor unit (MIU871) – Allows a zone of conventional detectors to be connected– Uses JSB base and EOLM - 1

Page 33: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• Shop unit Interface (MSU840)– Facilities to accept conventional detection zone– Output relay (activates on fire)– Facility to connect power supply (monitored)

Page 34: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• Spur Isolator (MSI850)– Allows a spur of analogue devices– Includes short circuit isolator

Page 35: Cooper 03008324979 Sajid Mehmood Butt

DF6000 interfaces

• 4 Way sounder circuit controller (MPU424)– Integral power supply and battery– 4 separately programmable sounder circuits– Sounder circuits can have cause and effect programming

Page 36: Cooper 03008324979 Sajid Mehmood Butt

Application schematic

D F6000

M a in lo o p

MIO 1240

Fire or non fire input

Mains rated output relay contact

3 independent Volt free output contacts

3 separate inputs to accept fire or non fire inputs

MIO324M PU424

4 Independently controlled conventional sounder Circu its

Spur o f ana logue devices

M SI850

MIU871

Zone o f com patib le conven tional ca llpoin ts and sounders

Zone o f com patib le conven tional callpo ints and de tectors

2 C ircuits o f conven tional sounders

Power supply

Page 37: Cooper 03008324979 Sajid Mehmood Butt

DF6000 repeaters

• DF6000 panels can be connected as active repeaters• Low cost passive repeater also available

– Can be loop connected (hold and displays text for own panel only)

– Can be Network connected (gets text for entire system via network)

– LCD display (not touch screen)– Silence evacuate and reset functionality

Page 38: Cooper 03008324979 Sajid Mehmood Butt

DF6000 connected to Network

Low cost repeater connected to network gets entire system text from network

1 2 3 4 5

FIREFAULT

Page 39: Cooper 03008324979 Sajid Mehmood Butt

Repeater connected to loop

Low cost repeater connected to ind ividual panel holds and d isp lays text for that panel only - M ANUA L TE XT U PDATE NEE DED

1 2 3 4 5

FIREFAULT

Page 40: Cooper 03008324979 Sajid Mehmood Butt

System networking

• Up to 63 panels can be networked• Panels are connected in a loop• Network is monitored• If any panel is disconnected master and faulty panel shows fault

& details

Page 41: Cooper 03008324979 Sajid Mehmood Butt

Programming overview

Page 42: Cooper 03008324979 Sajid Mehmood Butt

Create all the panels for the site

Page 43: Cooper 03008324979 Sajid Mehmood Butt

Select a panel and a loop

Page 44: Cooper 03008324979 Sajid Mehmood Butt

Add zones to the loop and populate them

Devices are colour coded for ease of recognition

Indicates an address which is used in a different zone

Page 45: Cooper 03008324979 Sajid Mehmood Butt

3 stage programming for each sounderDefinable at each stage:

Source of trigger

By panel

By address

By zone

Type of output

Continuous

Pulsing

Time delayed

Type of trigger

Double knock

Standard trigger

Page 46: Cooper 03008324979 Sajid Mehmood Butt

If non global trigger select inputs

Select up to 16 zones, addresses or panels as relevant for each stage for each sounder

Page 47: Cooper 03008324979 Sajid Mehmood Butt

Sounder settings are individually programmable

Page 48: Cooper 03008324979 Sajid Mehmood Butt

All inputs are individually configured

Page 49: Cooper 03008324979 Sajid Mehmood Butt

Select required action

Page 50: Cooper 03008324979 Sajid Mehmood Butt