am comfort iss11

Upload: rob-clegg

Post on 08-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Am Comfort Iss11

    1/36

    FAN CONVECTOR HEATERS

    SERIES AM COMFORT

    Products that perform... By people who care

  • 8/7/2019 Am Comfort Iss11

    2/36

    IntroductionThis Product Catalogue provides comprehensive information about Series AM

    Comfort fan convector heaters and guidance on selection, application, use andsupply.

    Each heater consists of a casing, motor/fan platform, air filter and heating

    coil. Depending upon the model, grilles are either fitted to the casing or can be

    supplied loose for fitting by others.

    Heaters provide warm air heating, when connected to a low or medium

    temperature hot water system and a single phase electrical supply. A simple

    product description code is used to identify heaters and accessories. Each heater

    has a unique serial number.

    For low grade heating mediums and low surface temperature options refer to the

    Avant-Garde & LST fan convector brochures.

    AuthorityDunham-Bush operates a quality control system and is a registered firm of

    assessed capability BS EN ISO 900 : 000.

    Each Series AM Comfort fan convector comprises a sheet metal casing with

    lockable access panel, motor/fan platform, auto transformer, air filter and hot

    water heating coil. A single phase electric heater coil can be supplied instead of

    the hot water coil on heaters with an output up to 6kW. Depending upon the

    model selected, grilles are either fitted to the casing or can be supplied loose as anaccessory, for internal use.

    Heaters are supplied for single or dual fan speed operation. Single speed heaters

    are set to low, medium or high speed. Dual speed heaters are set to low/medium,

    low/high or medium/high speeds. Fan/heat control is by means of switches and/or

    thermostats, listed in the Accessories section of this Product Catalogue.

    RangeThe range consists of standard models, arranged in 4 groups floor, wall,

    ceiling and fixed duct or adjustable height duct, as illustrated in the Range of

    Standard Models. For vertical concealed and ceiling void models, please refer to

    our Series BM Product Catalogue.

    All models can be supplied in a range of figure numbers. The figure number

    relates to the nominal heat output and length, as shown below.

    Description

    IdentificationContents PAGEIDENTIFICATION

    Introduction

    Authority

    DESCRIPTION

    Range & 4-5

    Composition Features 3

    Accessories 6-7

    PERFORMANCE 8-9

    Heat outputs of LTHW 8

    Correction factors 8

    Heat outputs of Electric 9

    Electrical data 9Coil capacities 9

    Heater mass 9

    APPLICATION 0-

    General 0

    Selection

    Dimensions -8

    Engineering Specification 9-30

    CONSTRUCTION 3

    Handling 3

    Storage 3

    Preparation 3

    Installation details 3

    Pipework connections 3

    Electrical connections 3

    Typical wiring diagram 3

    Ceiling & wall brackets 3

    Installation detail, model 5 33

    PRICES & CONDITIONSof SALE 34

    Prices 34

    Conditions of Sale 34

    TECHNICAL SUPPORT

    SERVICES 34

    Product support 34

    SUPPLY 34

    Availability 34

    Packaging 34

    Ordering 34-35

    Delivery to site 34

    Nominal outputs are based on WA coil, LTHW flow &

    return temperatures of 80/70C, and an entering airtemperature of 18C

    Figure numberNominal output

    (kW)Casing length

    (mm)

    03 .6 695

    04 4.5 895

    06 6.0 895

    08 8.5 95

    0 9.8 95

    .0 495

    5 .5 495

  • 8/7/2019 Am Comfort Iss11

    3/363

    heater casingextruded pencil

    proof discharge grille

    access panel with locks

    inner cover

    heating coil

    coil connections

    motor/fan platform

    auto-transformer

    mains inlet connector

    washable air filter

    air vent**

    switches*

    **Air vent options type M manual, behind the access panel

    type A automatic, behind the access panel

    type P plugged tapping

    low temperature

    cut-out*

    air thermostats*

    Items marked * are accessories.

    extruded pencil proof

    recirculation grille

    isolating valves*line connector

    pipework cover plate

    Model 3 figure number 4(left hand connections)

    Composition - features

  • 8/7/2019 Am Comfort Iss11

    4/364

    Range of standard models

  • 8/7/2019 Am Comfort Iss11

    5/365

    Note: refer models , , 3, 60 & 9, the pipework connections can be manufactured in a top orbottom orientation, please indicate on works order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    6/366

    Fitted on/off and speed change capillary

    thermostats

    Fitted type LTC

    Fitted high/low and manual/off/auto

    switches

    Air thermostatsAir thermostats can be provided to automatically switch the heater on/off and/or

    to change the fan speed/heat output, in response to a fall or rise in ambient airtemperature.

    Fitted air thermostats, Models 3, 5, 7, 0, , 3 and 5 only.Capillary thermostats or room thermostats with accelerator heater, can be fitted for

    on/off and speed change control.

    Remote thermostatsStandard or tamper resistant room thermostats with accelerator heater, can be

    provided for on/off and speed change control.

    Low temperature cut-out thermostat (LTC)A low temperature cut-out thermostat can be provided to prevent the heateroperating until the heating water temperature is hot enough for it to work

    efficiently. This thermostat will automatically stop the heater at the end of the

    normal operating period, when the boiler plant closes down.

    Type 1, fixed setting LTC, break circuit 38C3K, make circuit 50C3KIf fitted, type is wired into the control circuit and clamped to the coil tube

    nearest to the LTHW flow connection. Note, maximum operating temperature of

    95C

    Type 2, adjustable setting LTC, range 30C to 90C.If supplied, type is wired into the control circuit and stored inside of the heater

    casing, for clamping to the LTHW flow pipe by the installer. Note, maximum

    operating temperature of 95C

    SwitchesFitted external, internal or remote room switches can be provided to switch the

    heater on/off, change fan speed, allow thermostats to work automatically or

    to override any thermostats. The override manual switch allows the fans to

    circulate room air when the boiler plant is shut down during the summer. A switch

    can also be provided to open or close motorised dampers (models 9, , 53 and

    88 with motorised damper).

    Fitted switches . on/off, . high/off/low, 3. manual/off/auto, 4. manual/off/auto and high/low, 5. FAI/recirc., 6. FAI/recirc. and high/off/low, 7. FAI/recirc.,

    and manual/off/auto, 8. FAI/recirc., manual/off/auto and high/low.Please note: a) fitted switches are not recommended for ceiling and wall mounting

    models, due to inaccessibility. b) FAI refers to fresh air inlet.

    Remote switches-surface or flush mounting . on/off, . high/off/low, 3. manual/off/auto, 4. manual/off/auto and high/low, 5. FAI/recirc., 6.

    FAI/recirc. and high/off/low, 7. FAI/recirc. and manual/off/auto, 8. FAI/recirc. ,

    manual/off/auto and high/low.

    Motorised damperDamper models 9, , 53 and 88 can be provided with a 30V AC damper motor

    as a standard option. 4V AC damper motors are available if specially requested.

    Range of standard models

  • 8/7/2019 Am Comfort Iss11

    7/367

    Electric heatingAll models, figure numbers 3, 4 and 6 only, can be fitted with a single phase, one

    or two stage electric heating module, instead of the standard hot water heating

    coil. The module includes electric element(s), power relay(s), high temperature cut-

    out and miniature circuit breakers. Please refer to the Performance section of this

    catalogue for outputs of models with electric heater modules.

    Electronic speed control ESCAll models can be supplied with electronic speed control, instead of the standard

    auto transformer. The ESC automatically varies the fan motor speed, air volume

    flow rate and heat output (in the heating mode), in response to a change in

    recirculation or room air temperature. On a rise in air temperature, the fan

    gradually slows down and stops when the air temperature is 1K above the set-point.

    A set-point adjustment knob and heating/cooling mode switch are provided. In the

    cooling mode the operation is reversed to allow room air to be recirculated.

    Air sensors can only be fitted within models 3, 5, 7, 0, , 3 and 5. Remote

    sensors can be provided with all models.Electronic speed control is not suitable for use with:

    a) models selected to introduce a constant quantity of outside or primary air.

    b) ceiling mounting models, due to the risk of stratification, as the air volume flow

    rate decreases and the leaving air temperature increases.

    c) models with electric heater coil.

    Special controlsVarious special control arrangements can be supplied to suit particular applications.

    A 4V AC relay can be fitted, to allow a heater to be switched on/off remotely by a

    controlled 4V AC supply.

    4V AC relays can also be fitted, to allow master/slave operation of several fan

    convectors from one pair of room thermostats. Please contact our local Agent/Sales Engineer for details.

    Fitted plinthA 00mm or 50mm plinth, finished in black powder coating, can be fitted to all

    floor and duct models, to raise the heater above the finished floor level.

    Fitted isolating valvesDN0(3/4 BSP.) isolating ball valves or gate valves, can be provided fitted within

    the casing.

    Pencil proof loose grille and fixing framePencil proof loose grilles with fixing frames can be provided for use with heaters

    which do not have fitted grilles. The fixing frame is intended for installation in

    a wall opening, allowing the loose grille to be fixed to the frame with screws,

    which are recessed between the grille blades. A loose grille has a natural anodised

    surround and black powder coated grille core.

    Loose grilles are unsuitable for external use. Proprietary weatherproof louvres are

    recommended where outside air is to be introduced.

    Special colours and finishesThe standard casing finish is powder coated flake grey, 0 A 03, BS4800.

    As an option, heater casings can be supplied powder coated to a colour and finish

    from our preferred range. A colour chart is available on request. Other BS 4800

    and RAL colours are also available, subject to quantity. Please contact our local

    Agent/Sales Engineer.

    Note: when a special colour finish is applied to the casing, any fitted grilles and the back of

    the heater will be finished standard black, unless otherwise specified.

    Electric heating

    Fitted plinth

    Loose grille and fixing frame

    Fitted isolating ball valves

  • 8/7/2019 Am Comfort Iss11

    8/368

    Figurenumber

    coiltype

    low speed medium speed high speed

    kW l/s C kPa kW l/s C kPa kW l/s C kPa03 WA .69 50 46 0.8 .56 75 47 0.6 3.58 0 45 .6

    04 WA 3.09 75 5 .00 4.5 0 5 .03 5.9 50 5 3.37

    06 WA 4.3 05 5 .86 5.9 50 5 3.37 6.6 75 49 4.3

    08 WA 5.6 30 5 .3 8.49 0 50 .5 9.95 75 48 .68

    10 WA 8.08 05 5 .4 9.8 70 48 .64 0.34 90 48 .8

    12 WA 8.60 0 5 .45 .4 80 5 .35 3.06 350 49 3.7

    15 WA .4 80 5 .35 .5 330 50 .93 3.06 350 49 3.7

    Figurenumber

    coiltype

    low speed medium speed high speed

    kW l/s C kPa kW l/s C kPa l/s kW C kPa

    03 WA .4 50 4 0. . 75 4 0.4 .9 0 40 0.8

    04 WA . 75 4 0.5 3.3 0 43 . 4. 50 4 .8

    06 WA 3. 05 43 .0 4. 50 4 .8 4.7 75 40 .

    08 WA 3.6 30 4 0.7 6. 0 4 .8 7.0 75 39 .3

    10 WA 5.8 05 4 .6 6.9 70 39 .3 7. 90 39 .5

    12 WA 6. 0 43 .0 8.0 80 4 .3 9. 350 40 .6

    15 WA 8.0 80 4 .3 8.4 330 40 .5 9. 350 40 .6

    Table Heat outputsHeat outputs (kW), air volume flow rates (l/s), leaving air temperatures (C) and hydraulic resistances (kPa).Conditions: LTHW 75C mean, 10K drop across the coil at medium speed, same water flow rate at low and high speeds.

    Entering air temperature 18C.

    Table Heat outputs

    Heat outputs (kW), air volume flow rates (l/s), leaving air temperatures (C) and hydraulic resistances (kPa). Conditions: LTHW 75C mean, 10K drop across the coil at medium speed, same water flow rate at low and high speeds.Entering air temperature 18C

    Table 3 Correction factorsApproximate factors for heat output and hydraulic resistance, at various mean water temperatures, entering air temperatures

    and water temperature drops across the coil.

    Meanwater C

    Enteringair

    Temperature drop across coil

    5K 10K 15K 20K

    output hyd.res output hyd.res output hyd.res output hyd.res

    500 0.9 3.0 0.86 0.75 - - - -8 0.55 .9 0.50 0.8 - - - -

    0 0.5 .04 0.46 0.4 - - - -

    55

    0 .0 3.75 0.96 0.9 - - - -

    8 0.65 .8 0.60 0.38 - - - -

    0 0.6 .45 0.56 0.34 - - - -

    65

    0 . 5.9 .6 .33 . 0.57 - -

    8 0.85 .67 0.80 0.65 0.75 0.7 - -

    0 0.8 .44 0.76 0.59 0.7 0.5 - -

    75

    0 .43 7. .37 .8 .33 0.80 .8 0.43

    8 .05 3.98 .00 .00 0.95 0.43 0.9 0.3

    0 .00 3.69 0.95 0.9 0.9 0.39 0.87 0.

    850 - - .56 .37 .53 .05 .49 0.588 - - .0 .4 .6 0.6 . 0.33

    0 - - .6 .3 . 0.58 .07 0.3

    90

    0 - - .67 .80 .60 .67 .59 0.63

    8 - - .30 .69 .6 .59 . 0.37

    0 - - .5 .58 .0 .48 .7 0.34

  • 8/7/2019 Am Comfort Iss11

    9/369

    Table 4 Heat outputs Electric heatingHeat outputs (kW), air volume flow rates (l/s), leaving air temperatures (C)Conditions: 230/240 Volts, single phase, 50 Hertz, entering air temperature 18C.

    Figurenumber

    coil type kW stageslow speed medium speed high speed

    l/s C l/s C l/s C

    03 E .5 x.5 50 43 75 35 0 9

    03 E3 3.0 x3.0 50 68 75 5 0 4

    03 E3 3.0 x.5 50 43/68 75 5 0 4

    04 E .0 x.0 75 40 0 33 50 9

    04 E3 3.0 x3.0 75 5 0 4 50 35

    04 E4 4.0 x4.0 75 6 0 48 50 40

    04 E4 4.0 x.0 75 40/6 0 48 50 40

    06 E5 5.0 x5.0 05 58 50 46 75 4

    06 E5 5.0 x.5 05 38/58 50 46 75 4

    06 E6 6.0 x6.0 05 66 50 5 75 47

    06 E6 6.0 x3.0 05 4/66 50 5 75 47

    Table 6 Coil capacitiesApproximate coil capacities, litre.

    Table 5 Electrical DataElectrical Data running and starting currents in Amperes,

    at low, medium and high speeds and motor outputs in Watts.

    Table 7 Heater massesApproximate shipping masses, kg.

    Sound dataSeries AM fan convectors are

    commercially quiet.

    Sound power levels are available onrequest and may be used to calculate

    NR or NC levels in accordance with

    CIBSE guide or other procedures.

    Note: leaving air temperatures are shown for the total heat output, except for low speed, where the leaving air temperature forone and two stage heat outputs is shown.

    Figurenumber

    Running current Startingcurrent

    MotoroutputWattslow med high

    03 0.7 0. 0.4 0.45 5

    04 0.7 0.3 0.36 0.75 40

    06 0.30 0.36 0.4 0.75 40

    08 0.43 0.48 0.48 .5 75

    0 0.46 0.47 0.46 .5 75

    0.53 0.57 0.53 .5 75

    5 0.56 0.54 0.53 .5 75

    Figurenumber

    litre

    03 0.63

    04 0.77

    06 0.7708 .03

    0 .03

    .5

    5 .5

    Modelfgure

    number03

    fgurenumber04/06

    fgurenumber08/10

    fgurenumber12/15

    3, 5, 6, 7,3, 37, 4, 5

    36 45 55 65

    9 39 49 60 7

    5 35 44 54 64

    8, 30, 38 37 46 56 66

    34 38 47 57 67

    53 40 50 6 788 38 48 59 70

    0, , 3, 60,9

    67 83 06

    70 87 8

  • 8/7/2019 Am Comfort Iss11

    10/360

    The versatile range of standard

    models (see page 4-5), each produced

    in four casing lengths and with two

    hot water coil types, allows Series AM

    fan convectors to be used for many

    applications, such as: Schools, Colleges,

    Homes for Elderly People, Libraries,

    Offices and Churches.

    From the range of standard models,

    it can be seen that there are models

    suitable for floor, wall and ceiling

    mounting within the room being

    heated. Models 5, 3, 4 and 9 are

    intended for installation in an adjacent

    room. Where it is necessary to concealheaters within the building fabric or

    ceiling void, we recommend our basic

    uncased Series BM fan convectors.

    Models 9, , 53 and 88 can be

    used for heating, ventilating and free

    cooling as they allow the introduction

    of tempered primary or outside air

    through the fan convector. These

    models have a manually operated

    damper but a motorised damper

    can be fitted as an accessory, during

    manufacture. If outside air is to be

    introduced during the heating season,

    the hot water coil must have frost

    protection. Weatherproof louvres must

    be supplied by others.

    Care should be taken to ensure

    heaters are sited so that there are noobstructions directly in front of them,

    which could affect air circulation.

    This is particularly important when

    using reversed air flow models 37

    and 4, and any model with electric

    heating.

    Ceiling mounted models 8, 30, 3 and

    34 are generally less effective than floor

    mounted models, since the entering air

    temperature is higher at ceiling level

    and the warm buoyant discharge air

    may cause stratification and take longer

    to produce comfortable conditions at

    occupancy level. For these reasons,

    we recommend floor or wall mounted

    models, where the application allows.

    Model 5 with optional plinth.

    Application

    General

  • 8/7/2019 Am Comfort Iss11

    11/36

    a) From table , heat output 8.49kW , air volume flow rate 0 l/s, hydraulic

    resistance .5 kPa

    b) From table 3, heat output factor 0.50, hydraulic resistance factor 0.8.

    c) Heat output 8.49kW x 0.50 = 4.5kW Hydraulic resistance .5kPa x 0.8

    =0.35kPa

    d) To estimate the leaving air temperature with the new output, find the

    temperature rise t, and add it to the entering air temperature

    t = = 16C + 18C = 34C

    Refer to the range of standard

    models (see page 4-5) to select the

    model most suitable for the particular

    application. From the calculated heat

    loss and the operating conditions, the

    quantity of heaters, heat output, figure

    number and coil type can be selected,

    using the Performance tables. If the

    operating conditions are different to

    those stated, use the appropriate factor

    from table 3.For large rooms, it is usually better to

    select two small heaters, rather than

    one large one, to give better heat

    distribution and lower spot noise levels.

    Whenever possible, heaters should be

    located near windows or in areas of

    disproportionately high heat loss.

    It is recommended that heaters are

    selected to operate at medium speed

    for general use or at low speed

    for rooms where noise levels are

    particularly important. Heaters should

    only be selected at high speed for non

    critical applications, such as entrancefoyers, corridors etc. or for initial rapid

    warm up. Sound power levels are

    available on request.

    By design, Dunham-Bush fan

    convectors have moderate leaving air

    temperatures, low outlet velocities and

    low air throws. Comfortable conditions

    throughout the heated space are

    achieved by good air circulation. It is

    recommended that wherever possible,

    the total volume of the room should

    be circulated through the sum of the

    heaters in the room, four to five times

    per hour.

    Model 38

    Using factors exampleTo calculate the approximate heat

    output, hydraulic resistance and leaving

    air temperature of a Series AM figure 08

    heater fitted with a WA coil, operating

    at medium speed with LTHW 50Cmean, a 10K drop and an entering air

    temperature of 18C.

    (Where 0.00 is an approximation, derived from the specific

    volume and specific heat capacity of the entering air.)

    4.5kW

    220 l/s x 0.00122kJ/lC

    Selection

  • 8/7/2019 Am Comfort Iss11

    12/36

    Dimensions

  • 8/7/2019 Am Comfort Iss11

    13/363

  • 8/7/2019 Am Comfort Iss11

    14/364

    Model 9

  • 8/7/2019 Am Comfort Iss11

    15/365

    Note: pipework connections can be manufactured in a top or bottom orientation, please indicate onworks order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    16/366

    Model 0 Model 3

  • 8/7/2019 Am Comfort Iss11

    17/367

    Note: pipework connections can be manufactured in a top or bottom orientation, please indicate onworks order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    18/368

    Note: pipework connections can be manufactured in a top or bottom orientation, please indicate onworks order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    19/369

    Note: pipework connections can be manufactured in a top or bottom orientation, please indicate onworks order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    20/360

  • 8/7/2019 Am Comfort Iss11

    21/36

  • 8/7/2019 Am Comfort Iss11

    22/36

    Model 3

  • 8/7/2019 Am Comfort Iss11

    23/363

    Note on model 37: pipework connections can be manufactured in a top or bottom orientation, pleaseindicate on works order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    24/364

    Note on model 4: pipework connections can be manufactured in a top or bottom orientation, pleaseindicate on works order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    25/365

  • 8/7/2019 Am Comfort Iss11

    26/36

  • 8/7/2019 Am Comfort Iss11

    27/367

    Note: pipework connections can be manufactured in a top or bottom orientation, please indicate onworks order (option 4b) for required coil connections.

  • 8/7/2019 Am Comfort Iss11

    28/368

  • 8/7/2019 Am Comfort Iss11

    29/36

  • 8/7/2019 Am Comfort Iss11

    30/3630

    Fan motor

    Motors shall be quiet running, resiliently

    mounted, capacitor start and run,

    totally enclosed, having class B

    insulation and rated in accordance with

    BS5000 part .

    Figure 03 motor shall be 5W, single

    shaft, all other figure numbers shall be

    double shaft, figure numbers 04 and 06

    shall be 40W, figure numbers 08, 0,

    and 5 shall be 75W.

    Motors shall be wound 30/40 VAC,

    single phase, 50 Hz and shall have

    sealed for life ball bearings.

    Centrifugal fansEach fan shall be double inlet, forwardcurved, statically and dynamically

    balanced, secured to the fan motor

    shaft by a grub screw.

    Figure number 03 shall be provided

    with one fan, all other figure numbers

    shall be provided with two fans.

    Electrical connections andwiringEach heater shall be provided with an

    IEC mains inlet connector, fused A,

    with a spare fuse and an IEC mains

    inlet plug, located behind the access

    panel, at the opposite end of the casingto the hot water coil connections.

    Internal wiring shall be tri-rated, high

    temperature PVC insulated 6/0.00.

    Fan motor-speed controlAn auto-transformer shall be fitted

    within the heater casing to provide

    energy efficient fan motor speed

    control. Transformers shall be wired

    to provide one or two speeds from the

    range low, medium and high.

    An isolated 4V AC (30VA) supply shall

    be available.

    PerformanceSeries AM fan convectors performance

    shall be tested and rated in accordance

    with BS4856, part .

    PackagingEach heater shall be properly packed

    in a carton, marked with the model

    and figure number, and any other

    reference specified on the order for site

    identification.

    AccessoriesIf specified, accessories listed in the

    manufacturers Product Catalogue shall

    be provided.

    Model 5

  • 8/7/2019 Am Comfort Iss11

    31/363

    HandlingThe purchaser is responsible for off

    loading. Heaters are individually

    cartoned and three men can usually

    handle the heaviest heater.

    When a significant quantity of heaters

    is delivered, they may be palletised

    and shrink wrapped, so a fork lift truck

    or some form of lifting equipment is

    desirable.

    Care should be taken to ensure the

    heaters are not dropped or knocked

    under any circumstances.

    StorageHeaters should be stored under clean,

    dry conditions. The cartons should not

    be removed until heaters are required

    for installation, unless damage in transit

    is suspected.

    Note the purchaser must examine

    the heaters promptly upon receipt and

    any claims for damage will only be

    accepted if, at the time of delivery, the

    consignment note is endorsed with a

    note detailing the damage and counter

    signed by the transport driver.

    Each heater is marked to show the

    model, figure number, serial number

    and any reference given on the order

    for site identification. This information

    also appears on the consignment note.

    PreparationMake proper provision for fixings.

    The structure to which heaters are to

    be fixed must be fit for purpose and

    capable of accepting plugs and screws

    or drop rods. Floor models require

    a level base. Floor and wall models

    require a sound flat perpendicular

    surface. Heater casings are supplied

    with knockouts for pipework and

    conduit entry.

    Installation detailsThe access panel can only be removed

    with the key provided.

    The inner cover, motor/fan platform,

    pipework cover plate, filter and fitted

    grilles (where applicable) can all be

    removed to provide better access when

    making pipework connections.

    Please refer to the Sitework

    Instructions/Recommendations supplied

    with the heater. Additional copies are

    available on request.

    Pipework connectionsCoil connections are DN0 (3/4 BSP.)

    female parallel. Local isolating and

    regulating valves are recommended.

    Observe the correct flow and return

    positions, to ensure the rated heat

    output.

    Electrical connectionsA 30/40 VAC, single phase 50 Hz

    supply must be connected to the IEC

    mains inlet plug.

    Any remote accessories must be

    connected as shown on the wiring

    diagram supplied with the heater.

    Wiring DiagramA project specific wiring diagram is

    supplied separately along with the

    installation instructions for reference

    when connecting the remote

    components where specified.

    Construction

  • 8/7/2019 Am Comfort Iss11

    32/363

  • 8/7/2019 Am Comfort Iss11

    33/3633

  • 8/7/2019 Am Comfort Iss11

    34/3634

    Prices

    Dunham-Bush Ltd do not issue price lists but will be

    pleased to supply a written quotation upon request.

    Standard conditions of saleThe standard conditions of sale appear on all quotation

    and order acknowledgement forms. Additional copies are

    available upon request

    Product supportIn the United Kingdom and Ireland, Dunham-Bush has anetwork of Sales Agents, situated at strategic locations, to

    provide local support.

    AvailabilitySeries AM fan convector heaters are supplied direct from

    our manufacturing plant. The availability varies with

    demand and should therefore be checked at the time of

    ordering.

    PackagingHeaters are packed in individual cartons.

    Each heater is marked to show the model, figure number,

    serial number and any reference given on the order for

    site identification. This information also appears on the

    consignment note.

    Supply

    Technical Support services

    Prices & conditions of saleOrderingTo allow us to process your order promptly, please refer

    to any quotation we have supplied and any relevant

    correspondence. Please send your order to our Agent or

    Sales Engineer who provided the quotation.

    There are two ways of providing information necessary for

    us to supply the required heaters

    ) please photocopy the Fan Convector Description Code

    form and fill in your requirements or,

    ) please advise the following details:

    a) quantity of each model and figure number

    b) left or right hand coil connections, as viewed looking at

    the access panel

    c) coil type

    d) air vent type

    e) overall height-fixed duct models

    f) fan speed(s)

    g) details of any accessories required, including finish, if

    other than standard.

    h) reference or stencil, for site identification

    Deliver to siteSeries AM fan convectors are delivered to site in accordance

    with our Conditions of Sale. The purchaser is responsible

    for the off loading and proper safe storage.

    Model 3

  • 8/7/2019 Am Comfort Iss11

    35/3635

    Remote switches ush part number surface part number

    on/off -60-00 -60-00

    high/off/low -60-0 -60-00

    man/off/auto -60-0 -60-003

    man/off/auto & high/low -60-05 -60-006

    FAI/recirc -60-03 -60-004

    FAI/recirc & high/off/low -60-06 -60-007

    FAI/recirc & man/off/auto -60-07 -60-008

    FAI/recirc, man/off/auto & high/low -60-08 -60-009

    Room thermostats standard part number tamper resistant

    Honeywell T6360B08 903-00-056 -

    Honeywell T6360B069 - 903-00-057

    3 4a 4b 5 6 7 8 9 0 a b 3 4 5 6

    Codeposition

    Component Component description

    series AM - fan convector

    model 3, 5, 0 ETC. - model number

    3 gure number 03, 04, 06, 08, 0, & 5 - heater size

    4a coil connections L - left hand, R - right hand

    4b connection orientation T - top facing pipework connections, B - bottom facing pipework connections

    5 coil type WA, WA - LTHW, E, E3, E3 etc. Electric heating elements

    6 air vent M - manual, A - automatic, P - plugged

    7 xed duct height - 700mm, - 900mm, 3 - 00mm, N - none

    8 tted plinth 0 - 00mm, 5 - 50mm, N - none

    9 tted isolating valves B - ball, G - gate, N - none

    0 fan speedsLN - low, MN - medium, HN - high, LM - low/medium, MH - medium/high,LH - low/high

    a air thermostat on/off C - capillary tted, F - room tted, R - remote, N - none

    b air thermostat high/low C - capillary tted, F - room tted, R - remote, N - none

    low temp. cut-out LTC 1 - xed setting, 2 - adjustable setting, N - none

    3 switch location E- external, I - internal, R - remote, N - none

    4 switch typeN - none, - on/off, - high/off/low, 3 - man/off/auto, 4 - man/off/auto & high/low,5 - FAI/recirc, 6 - FAI/recirc & high/off/low, 7 - FAI/recirc & man/off/auto,8 - FAI/recirc, man/off/auto & high.low

    5 ESC F - tted, R - remote, N - none

    6 inlet damper M - manual, E - electric actuator, N - none

    Series AM Fan convector description codes

    Notes ) please refer to accessories section, for items applicable to the various models.2) advise casing nish, if other than standard.3) select any remote switches and/or thermostats required from the following lists.4) if connection orientation is not dened on works order, pipework direction will be as illustrated in this catalogue.

  • 8/7/2019 Am Comfort Iss11

    36/36

    QQualityDunham-Bush operates a quality controlsystem and is a company of assessed

    capability to BS EN ISO 900 : 000

    Whatever the product, wherever its

    eventual destination, Dunham-Bush design

    and manufacturing policy has always been

    rmly based on technical quality.

    Product supportIn the United Kingdom and Ireland,Dunham-Bush has a network of sales

    agents and representatives, situated atstrategic locations, to provide local support

    in pricing and selection. Further technical

    and application support is available at the

    Dunham-Bush ofce and factory in Havant.

    Other Dunham-Bush productsSeries BM fan convectors

    Series CM fan convectors

    Series 600 Ceiling Tile heaters

    Avant-Garde fan convectors

    LST fan convectors

    Evolution radiant panels

    Evo-Lite radiant panels

    Dunham Strip radiant panels

    Series F fan coil units

    Panther fan coil units

    Cougar fan coil units

    Leopard fan coil units

    Puma fan coil units

    Lynx fan coil units

    Jaguar fan coil units

    DBB Slimline Hydronic air handling units

    DBM Hydronic air handling unitsFinvector perimeter heating

    Hydrocourse trench heating

    Series UH unit heaters

    Warmsafe LST radiators

    Sentry door curtains

    Thermocold packaged water chillers and

    heat pumps

    Dunham-Bush Ltd

    Downley Road

    Havant

    Hants PO9 JD

    Tel 03 947 7700