ADDENDUM No. 01 Date: November 5, 2019 TO CONTRACT DOCUMENTS ENTITLED: CP192061 3315 Berrywood – Medical Center Renovation at 3315 Berrywood Drive Columbia, MO 65202 Advertisement Date: October 22, 2018 Prepared for: The Curators of the University of Missouri Consultants: ARCHITECT CIVIL/STRUCTURAL ENGINEER MEP ENGINEER Simon Oswald Architecture Crockett Engineering SSC Engineering 2801 Woodard Drive, Suite 103 1000 West Nifong Blvd, Bldg 1 18207 Edison Avenue Columbia, MO 65202 Columbia, MO 65203 Chesterfield, MO 63005 573-443-1407 573-447-0292 636-530-7770 Drawings and Specifications for the above referenced project and the work covered thereby are herein modified as follows, and except as set forth herein, otherwise remain unchanged and in full force and effect: GENERAL: 1) Bids will be received until 1:30 p.m., C.T., November 21, 2019 at the General Services Building, Room L100 (Front Reception Desk) as outlined in the Advertisement For Bids. 2) Pre-Bid Meeting Attendance Record is attached for reference. 3) Bidder Question #1: Is Trane an acceptable manufacturer for Neutral Air Units? a) Response: Trane is an acceptable manufacturer for the Neutral Air Units noted in specification 230606. 4) Bidder Question #2: We have some contractors bidding this project. Can you please add Valent as an equal alternate for Neutral Air Units, Section 23 0606? Also, would you accept a Lennox mini-split system as an equal alternate for the IT room. a) Response: Valent is an acceptable manufacturer for the Neutral Air Units noted in specification 230606. Lennox is an acceptable manufacturer for the mini-split system. PROJECT MANUAL: 1) Section 1.E Special Conditions: a) REVISE Paragraph 2a Special Scheduling Requirements to add the following: “Work in adjacent tenant suite shall occur during non-business hours to avoid disruption to tenants in the occupied spaces. The fire sprinkler main work in the existing garage can occur during business hours.” DRAWINGS: 1) A201: FIRST FLOOR PLANS a) REVISE First Floor Demolition Plan to add keyed note 30 for ceiling tile removal and replacement in adjacent tenant spaces. b) REVISE keyed notes to add notes 30 and 31. c) Replace sheet in its entirety. 2) A202: SECOND FLOOR PLAN - DEMO a) REVISE Second Floor Demolition Plan to add keyed note 31 for drywall removal at exterior walls for electrical work. b) REVISE keyed notes to add notes 30 and 31. c) REVISE general note 6 to clarify batt insulation on existing ceiling tiles shall be removed. d) Replace sheet in its entirety.

Upload: others

Post on 09-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

ADDENDUMNo.01 Date:November5,2019 TO CONTRACT DOCUMENTS ENTITLED:

CP192061 3315 Berrywood – Medical Center Renovation

at 3315 Berrywood Drive Columbia, MO 65202

Advertisement Date: October 22, 2018 Prepared for: The Curators of the University of Missouri Consultants: ARCHITECT CIVIL/STRUCTURAL ENGINEER MEP ENGINEER Simon Oswald Architecture Crockett Engineering SSC Engineering 2801 Woodard Drive, Suite 103 1000 West Nifong Blvd, Bldg 1 18207 Edison Avenue Columbia, MO 65202 Columbia, MO 65203 Chesterfield, MO 63005 573-443-1407 573-447-0292 636-530-7770 Drawings and Specifications for the above referenced project and the work covered thereby are herein modified as follows, and except as set forth herein, otherwise remain unchanged and in full force and effect: GENERAL: 1) Bids will be received until 1:30 p.m., C.T., November 21, 2019 at the General Services Building, Room L100

(Front Reception Desk) as outlined in the Advertisement For Bids. 2) Pre-Bid Meeting Attendance Record is attached for reference. 3) Bidder Question #1: Is Trane an acceptable manufacturer for Neutral Air Units?

a) Response: Trane is an acceptable manufacturer for the Neutral Air Units noted in specification 230606.

4) Bidder Question #2: We have some contractors bidding this project. Can you please add Valent as an equal alternate for Neutral Air Units, Section 23 0606? Also, would you accept a Lennox mini-split system as an equal alternate for the IT room. a) Response: Valent is an acceptable manufacturer for the Neutral Air Units noted in specification

230606. Lennox is an acceptable manufacturer for the mini-split system. PROJECT MANUAL: 1) Section 1.E Special Conditions:

a) REVISE Paragraph 2a Special Scheduling Requirements to add the following: “Work in adjacent tenant suite shall occur during non-business hours to avoid disruption to tenants in the occupied spaces. The fire sprinkler main work in the existing garage can occur during business hours.”

DRAWINGS: 1) A201: FIRST FLOOR PLANS

a) REVISE First Floor Demolition Plan to add keyed note 30 for ceiling tile removal and replacement in adjacent tenant spaces.

b) REVISE keyed notes to add notes 30 and 31. c) Replace sheet in its entirety.

2) A202: SECOND FLOOR PLAN - DEMO

a) REVISE Second Floor Demolition Plan to add keyed note 31 for drywall removal at exterior walls for electrical work.

b) REVISE keyed notes to add notes 30 and 31. c) REVISE general note 6 to clarify batt insulation on existing ceiling tiles shall be removed. d) Replace sheet in its entirety.

Page 2: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

3) A203: SECOND FLOOR PLAN - RENO a) REVISE Second Floor – New Work plan to add keyed note 14 at locations where drywall patching is

required due to new power and data device installation. b) Replace sheet in its entirety.

4) A204: REFLECTED CEILING PLANS

a) REVISE sheet to add Partition Types to coordinate with partition tags on floor plans. b) Replace sheet in its entirety.

5) FP102: FIRE PROTECTION SECOND FLOOR PLAN - RENO

a) REVISE floor plan to add note to remove existing domestic sprinkler on second floor.  e) Replace sheet in its entirety.

6) PD101: PLUMBING FIRST FLOOR PLAN - DEMO

a) REVISE plan to reflect location of existing water heater and associated routing of domestic water piping and demolition work.  e) Replace sheet in its entirety.

7) P101: PLUMBING FIRST FLOOR PLAN - RENO a) REVISE plan to reflect location of existing water heater and associated routing of domestic water

piping and demolition work. b) REVISE plan to reflect routing of waste and vent piping associated with new sink. e) Replace sheet in its entirety.

8) E002: ELECTRICAL ONE-LINE DIAGRAM

a) REVISE new feeder source for new panel P3 to be from existing panel P1 and not P2 as previously indicated.  e) Replace sheet in its entirety.

9) E102: ELECTRICAL SECOND FLOOR LIGHTING PLAN - RENO a) REVISE lighting plan to add nine (9) dimmer switches to Exam Rooms and relocated one (1) dimmer switch to latch side of door.  e) Replace sheet in its entirety.

10) E202: ELECTRICAL SECOND FLOOR POWER AND DATA PLAN - RENO

a) REVISE power and data plan to revise location of twelve (12) receptacles in Exam Rooms.  e) Replace sheet in its entirety.

ATTACHMENTS:

1) Pre-Bid Meeting Attendance Record. Five (5) 8 ½ x 11 sheets. 2) A201: Replace sheet in its entirety. 3) A202: Replace sheet in its entirety. 4) A203: Replace sheet in its entirety. 5) A204: Replace sheet in its entirety. 6) FP102: Replace sheet in its entirety. 7) PD101: Replace sheet in its entirety. 8) P101: Replace sheet in its entirety. 9) E002: Replace sheet in its entirety. 10) E102: Replace sheet in its entirety. 11) E202: Replace sheet in its entirety.

End of Addendum #01

Page 3: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection
Page 4: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection
Page 5: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection
Page 6: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection
Page 7: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection
Page 8: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

REF.

11'-6 3/8"

16'-3" +/- 9'-10 1/2" 9'-10 1/2" 10'-2" 10'-1" +/-

1010

OFFICE

1009

OFFICE

1008

OFFICE

1007

OFFICE

1006

OFFICE

1005

OFFICE

1004

OFFICE

1003

OFFICE

1002

OFFICE

1017

OFFICE

1011

MECH.

11'-5 3/4"

9'-8

" +

/-9

'-8

"9

'-8

"9

'-8

"9

'-8

"

A

123456

1016

FELLOWS

1013

RR

1014

RR

1015

STOR.

1012

JAN.

C1002

CORR.

C1003

CORR.

C1004

CORR.

C1001

CORR.

1001

OPEN OFFICE

10101009100810071006

1005

1004

1003

1002

1017

21020305

01

19

08

08

022002

03

14

07070707

17

11

12

12

A50103

02

A501

017'-6 1

/2"

10

'-7

"

02

05

26

1011

1012

1013 1014

1015

1016

09

06

1001

16

28

29

14

14

14

14

2'-1

"

B

30

NEW WORK GENERAL NOTES

1. FIELD VERIFY ALL DIMENSIONS. IFDIMENSIONS VARY SIGNIFICANTLYNOTIFY THE ARCHITECT

2. ALL DIMENSIONS TO FACE OF STEELSTUD OR EXISTING FINISH UNLESSNOTED OTHERWISE

3. GRAYED WALLS & DOORS AREEXISTING TO REMAIN - PROTECTDURING CONSTRUCTION

4. DASHED GRAY COMPONENTS AREPROVIDED BY OWNER AND ARESHOWN FOR REFERENCE ONLY

5. WALL PARTITIONS ARE TYPE AUNLESS NOTED OTHERWISE

6. AFTER NEW WORK IS COMPLETEEXCEPT LAY IN CEILING, ALL HOLESIN THE DEMISING WALLS ANDDRYWALL AT BOTTOM OF FLOORJOISTS ARE TO BE SEALED TIGHTAND FIRE CAULKED INSTALLED ATPENETRATIONS.

7. REMAINING EXISTING WALLS ARE TOGO TO DECK & BE SEALED TIGHT.ADD DRYWALL TO EXISTING STUDSABOVE CEILING IF THERE IS NONE.EXISTING WALLS ARE INDICATEDLIKE THIS:

11

10

01

020302

11

15

05 05

1011

05

01

1011

05

01

10

1110

1105

10 11

10

11

07

11

10

0101

14

01

10

11

01

01

01

11

10

11

10

02

14

0611

13

12

12

09

09

04

A

123456

01

01

01 01

01

01

15

11

15

11

09

15

10

05

02

29

30

30

ADD01

ADD01

GENERAL NOTES - DEMOLITION

1. REMOVE WALLS INDICATED BY THEFOLLOWING LINETYPE (UNLESSNOTED OTHERWISE):

2. DASHED LINES INDICATE ITEMSSCHEDULED FOR REMOVAL ORMODIFICATION

3. PROTECT EXISTING SURFACES &COMPONETS SCHEDULED TO REMAIN

4. REFER TO MEP DRAWINGS FORADDITIONAL DEMOLITIONINFORMATION

5. BEFORE DEMOLITION PHASE.COORDINATE WITH OWNERREPRESENTATIVE

0"

4'-0

"8'-0

"24

'-0"

16

'-0"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11

/5/2

01

9 1

:15:1

7 P

M A201

SOA PROJECT 19033

FIRST FLOOR PLANS

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

William H. Oswald - ArchitectLicense No. A-5419

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

1/8" = 1'-0"A201

01 FIRST FLOOR - NEW WORK

KEYNOTES - NEW WORK PLAN

01 RECESSED FIRE EXTINGUISHER CABINET

02 CORNER GUARD 3"

03 CORNER GUARD TWO (2) AT 2"

04 NEW GYP BD ON EXISTING STUDS (APPROX. 5'HIGH) TO ALIGN WITH ADJACENT SURFACES

05 CONCRETE SLAB INFILL - ALIGN WITHADJACENT SURFACES

06 HIGH/LOW DRINKING FOUNTAIN - REFER TOPLUMBING & TYPICAL MOUNTING HEIGHTS

07 ROLLER SHADES

08 ALIGN WALL WITH ADJACENT SURFACES

09 KNOX BOX

10 16" HEAVY DUTY ADJUSTABLE SHELVES

11 FLOOR TRANSITION - REFER TO NEW WORKFINISH PLAN ON A702

12 ADJACENT TENANT SUITE, NO WORK THISAREA UNLESS IDENTIFIED ON MEP DRAWINGS

13 INFILL WALL WHERE SPECIMEN PASS-THRUWAS REMOVED

14 PATCH GYPSUM BOARD FROM REMOVAL OFPARTITION & DRYWALL

15 WALL PROTECTION UP TO 4'-0"

16 DOOR, FRAME AND PART OF THE HARDWARETO REMAIN. REPLACE STRIKE & DEADLOCK ASINDICATED ON DOOR HARDWARE SCHEDULEIN 08 4413

17 PROXIMITY READER

18 DIAPER CHANGING STATION (DCS)

19 MECHANICAL UNIT - REFER TO MECHANICALDRAWINGS

20 PROVIDE 20 GA SHEET MTL BACKING FOR TV

21 MOP SINK - REFER TO PLUMBING

22 EYEWASH STATION - REFER MEP

23 PUSH BUTTON FOR DOOR OPERATOR

24 CUBICLE CURTAIN TRACK

25 SPECIMEN PASS THRU

26 STEEL COLUMN - PAINT IPS-5A

27 PATCH EXISTING DRYWALL

28 FIRE DEPARTMENT CONNECTION

29 FIRE SPRINKLER RISER - REFER TO MEP ANDCIVIL

30 MOP AND BROOM HOLDER

31 CAULK AROUND NEW DUCTWORKPENETRATIONS

1/8" = 1'-0"A201

02 FIRST FLOOR - DEMOLITION

KEYNOTES - DEMOLITION PLAN 1

17 LUXURY VINYL TILE FLOORING AND RUBBERBASE - REMOVE AND DISPOSE OF

18 DRYWALL AT UNDERSIDE OF ROOF TRUSSESABOVE - REMOVE & DISPOSE OF ASREQUIRED TO RUN NEW FIRE PROTECTIONPIPING

19 STOREFRONT DOOR SYSTEM - REMOVE &DISPOSE, WALL SURROUNDING OPENING TOREMAIN UNCHANGED

20 REMOVE DRYWALL FROM EXISTING STUDS TOINSTALL NEW BLOCKING

21 SHEET VINYL FLOORING WITH COVE BASE -REMOVE AND DISPOSE OF

22 FIRE EXTINGUISHER CABINET - REMOVE

23 LAUNDRY WALL BOX - REMOVE - REFER MEP

24 DECORATIVE SCONCE - REMOVE - REFER MEP

25 WALL TRIM @ 5' AFF WITH WALL COVERINGBELOW - REMOVE THIS PORTION OF THE GYPBD (APPROX 5' HIGH) FROM EXISTING STUDS

26 PIPING IN CHASE -REFER MEP FOR REMOVAL

27 BRICK VENEER, EXTERIOR SHEATHING,INSULATION, & FRAMING TO BE REMOVED ASNEEDE FOR INSTALLATION OF DUCTWORKABOVE CEILING

28 SPECIMEN PASS-THRU BOX - REMOVE &DISPOSE OF

29 CONCRETE SIDEWALK & SLAB REMOVE ASREQUIRED FOR INSTALLATION OF WATERSERVICE FOR SPRINKLER SYSTEM - REFERTO MECHANICAL & CIVIL

30 ADJACENT TENANT SPACE: CEILING TILESREMOVED FOR PLUMBING WORK ARE TO BEREINSTALLED UPON COMPLETION - REFERPLUMBING

31 GYPSUM BOARD REMOVAL AS NEEDED(APPROX. 4' AFF) FOR ELECTRICAL WORK -REFER MEP

KEYNOTES - DEMOLITION PLAN 1

01 DOOR, FRAME, & HARDWARE - REMOVE &DISPOSE OF

02 BUILT-IN CASEWORK REMOVE & DISPOSE OF

03 REMOVE AND DISPOSE OF AS INDICATED ONPLUMBING PLANS

04 DRINKING FOUNTAIN REMOVE & DISPOSE OFAS INDICATED ON PLUMBING DRAWING

05 GYPSUM BOARD & METAL OR WOOD STUDFRAMING - REMOVE & DISPOSE OF

06 HOLLOW METAL FRAME AND WINDOW -REMOVE AND DISPOSE OF

07 REMOVE & SALVAGE WATER CLOSET.REINSTALL AFTER NEW FLOORING ISCOMPLETE

08 SOFFIT ABOVE - REMOVE

09 CONCRETE SLAB - SAWCUT AND REMOVE ASREQUIRED FOR UNDERGROUND PIPING -REFER PLUMBING

10 CARPET TILE & RUBBER BASE - REMOVE &DISPOSE OF

11 CEILING GRID & TILE ABOVE - REMOVE &DISPOSE OF

12 ADJACENT TENANT SUITE. NO WORK THISAREA UNLESS IDENTIFIED ON MEPDRAWINGS.

13 TILE - REMOVE AND DISPOSE OF, PREPARESUBSTRATE TO RECEIVE NEW FINISHES

14 DRYWALL CEILING & FRAMING ABOVE -REMOVE & DISPOSE OF

15 VINYL COMPOSITE TILE FLOORING ANDRUBBER BASE - REMOVE AND DISPOSE OF

16 WINDOW BLINDS REMOVE AND DISPOSE OF

FI

ISSOUR

OETA

ST

M

RE

GIS

TERED ARCH

ITE

CT

10/22/2019

WILLIAM

HOWARDOSWALDNUMBER

A-5419

REVISION DATE

ADD 01 11/05/2019

ADD01

Page 9: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

01

01

010101

01

01

01

01

0101

0101

01

01

01

01

01

01

01

01

01 01 01 01 01 01 01

10

10

05

13

16161616

16

16

161616

16

16

16

16

16

16

16 16 16 16 16 16 16 16 16

02

15

15

05

05

02

02

15 02

0305

15 02

03

05

15 02

03

05

15 02

03

05

15 02

03

05

1502

03

05

05

02

17

03

05

0205

02

10

15

15

03

02

17

17

1005

1715

03

0215

03

02

15

0505

10

1005

02

02

03

15

05

05

1010

05

10

05

05

05

10

02

05

05

02 03

02

03

01

02

03

02

02

02

02

02

03 03

03

03

05

1710

05

06

06

06

06

02 03

21

17

02

18

18

18

18

18

18

01

19

19

19

02

02

02

01

01

0101

01

07

07

01

17

01

17

17

01

01

01

07

0101

07

02

02

02

10

01

01

01

01

07

20

06

01

01

01

0301

01

13

13

13

13

1515

1010

10 10

10

08

08

15

02

0101

02

21

21

16

22

22

22

10

23 24

24

24

24

24

25

18

02

05

02

26

14

11

27

28

28

13

15 15

25

28

28

313131

31

31313131

31

31

31

31

31

31 31

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01ADD

01ADD01

GENERAL NOTES - DEMOLITION

1. REMOVE WALLS INDICATED BY THEFOLLOWING LINETYPE (UNLESSNOTED OTHERWISE):

2. DASHED LINES INDICATE ITEMSSCHEDULED FOR REMOVAL ORMODIFICATION

3. PROTECT EXISTING SURFACES &COMPONETS SCHEDULED TO REMAIN

4. REFER TO MEP DRAWINGS FORADDITIONAL DEMOLITIONINFORMATION

5. BEFORE DEMOLITION PHASE.COORDINATE WITH OWNERREPRESENTATIVE

6. AT SECOND FLOOR: REMOVE ALLEXISTING CEILING TILES AND GRID.ALSO REMOVE BATT INSULATIONABOVE CEILING.

ADD01

0"

4'-0

"8'-0

"24

'-0"

16

'-0"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11

/5/2

01

9 1

:15:1

8 P

M A202

SOA PROJECT 19033

SECOND FLOOR PLAN -DEMO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

William H. Oswald - ArchitectLicense No. A-5419

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

KEYNOTES - DEMOLITION PLAN 2

01 DOOR, FRAME, & HARDWARE - REMOVE &DISPOSE OF

02 BUILT-IN CASEWORK REMOVE & DISPOSE OF

03 REMOVE AND DISPOSE OF AS INDICATED ONPLUMBING PLANS

04 DRINKING FOUNTAIN REMOVE & DISPOSE OFAS INDICATED ON PLUMBING DRAWING

05 GYPSUM BOARD & METAL OR WOOD STUDFRAMING - REMOVE & DISPOSE OF

06 HOLLOW METAL FRAME AND WINDOW -REMOVE AND DISPOSE OF

07 REMOVE & SALVAGE WATER CLOSET.REINSTALL AFTER NEW FLOORING ISCOMPLETE

08 SOFFIT ABOVE - REMOVE

09 CONCRETE SLAB - SAWCUT AND REMOVE ASREQUIRED FOR UNDERGROUND PIPING -REFER PLUMBING

10 CARPET TILE & RUBBER BASE - REMOVE &DISPOSE OF

11 CEILING GRID & TILE ABOVE - REMOVE &DISPOSE OF

12 ADJACENT TENANT SUITE. NO WORK THISAREA UNLESS IDENTIFIED ON MEPDRAWINGS.

13 TILE - REMOVE AND DISPOSE OF, PREPARESUBSTRATE TO RECEIVE NEW FINISHES

14 DRYWALL CEILING & FRAMING ABOVE -REMOVE & DISPOSE OF

15 VINYL COMPOSITE TILE FLOORING ANDRUBBER BASE - REMOVE AND DISPOSE OF

16 WINDOW BLINDS REMOVE AND DISPOSE OF

17 LUXURY VINYL TILE FLOORING AND RUBBERBASE - REMOVE AND DISPOSE OF

18 DRYWALL AT UNDERSIDE OF ROOF TRUSSESABOVE - REMOVE & DISPOSE OF ASREQUIRED TO RUN NEW FIRE PROTECTIONPIPING

19 STOREFRONT DOOR SYSTEM - REMOVE &DISPOSE, WALL SURROUNDING OPENING TOREMAIN UNCHANGED

20 REMOVE DRYWALL FROM EXISTING STUDS TOINSTALL NEW BLOCKING

21 SHEET VINYL FLOORING WITH COVE BASE -REMOVE AND DISPOSE OF

22 FIRE EXTINGUISHER CABINET - REMOVE

23 LAUNDRY WALL BOX - REMOVE - REFER MEP

24 DECORATIVE SCONCE - REMOVE - REFER MEP

25 WALL TRIM @ 5' AFF WITH WALL COVERINGBELOW - REMOVE THIS PORTION OF THE GYPBD (APPROX 5' HIGH) FROM EXISTING STUDS

26 PIPING IN CHASE -REFER MEP FOR REMOVAL

27 BRICK VENEER, EXTERIOR SHEATHING,INSULATION, & FRAMING TO BE REMOVED ASNEEDE FOR INSTALLATION OF DUCTWORKABOVE CEILING

28 SPECIMEN PASS-THRU BOX - REMOVE &DISPOSE OF

29 CONCRETE SIDEWALK & SLAB REMOVE ASREQUIRED FOR INSTALLATION OF WATERSERVICE FOR SPRINKLER SYSTEM - REFERTO MECHANICAL & CIVIL

30 ADJACENT TENANT SPACE: CEILING TILESREMOVED FOR PLUMBING WORK ARE TO BEREINSTALLED UPON COMPLETION - REFERPLUMBING

31 GYPSUM BOARD REMOVAL AS NEEDED(APPROX. 4' AFF) FOR ELECTRICAL WORK -REFER MEP

1/8" = 1'-0"A202

01 SECOND FLOOR - DEMOLITION

FI

ISSOUR

OETA

ST

M

RE

GIS

TERED ARCH

ITE

CT

10/22/2019

WILLIAM

HOWARDOSWALDNUMBER

A-5419

REVISION DATE

ADD 01 11/05/2019

ADD01

Page 10: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

REF. ICE

ME

D-F

2021

TRTMNT - LONG

2020

EDUCATION

2019

MECH.

2018

CONFERENCE

2001

WAITING

2034

NURSE

2002A

OFFICE

V2002

VEST

2026

OFFICE

2017

EXAM - B

2016

EXAM - B

2011

EXAM - A 2010

EXAM - A

2009

EXAM - A

2008

EXAM - A

2007

EXAM - A

2006

EXAM - A

2005

EXAM - A

2003

EXAM - A

2024

MED

2029

STOR.

2022

EXAM - B

2004

EXAM - A

2023

LAB

2037

SOILED

2030

MECH.

2014

S TLT

2013

EXAM - B

2012

TRTMNT - B

2033

I.T.

2031

S TLT

2032

MECH / JAN.

2039

BREAK

2038

MECH.

2035

ADA TLT

2036

ADA TLT

2025

CLEAN

2027

EXAM - A

2001A

P TLT

2028

STOR.

V2001

VEST

2015

EXAM - B

C2003

CORR.

C2007

CORR.

C2005

CORR.

C2002

CORR.

2002

RECEPTION

07

07

07

07

07

0707

07

07

07

070707

07

07

07

07

07

07

07 07 07 07 07 07 07 07 07

12'-1" 12'-1" 12'-0" 12'-0" 12'-0" 12'-0" 12'-0"

10

'-8

"1

7'-9

" +

/-

08

19

02

02

22

C2008

CORR.

08

02

08

0201

C2004

CORR. 08

19

14

20

200320042005200620072008200920102011

2013

2014

2015

2016

2017 2020

2021 2024

2002C

C2001

CORR.01

02

02

23

C2006

CORR.

19

15

A502

05

06

A50214

08

08

08

2022

A502

23

A50219

A50217

A502

SIM14

A502

04

A50213

02

03

02

11

25

A502

06

A502

07

A50208

A502

01

A203

04

2001A

C2004

C2001

A50220

2018

V2002

V2001A

02

SIM 14

V2001B

25

24

2012

2036

2035

2039

2029

2033

17

17

17

17

1717

17

03

2025 2026 2028

2002A

2002B2031

2032 2030

20372038

2019

11'-7"

18

A502

SIM14

SIM 14

17

17

17

2027

07

07

A203

07

A203

08

02 02

0723

07

07

09

07 23

23

23 02

19

02 02

02

01

24

21

A203

08SIM

7'-6

"

7'-4"

10

'-0

"

1'-0

"

08

08

08

A502

09

10

11

04

A502SIM

13

13

27

27

27

27

14 14 14

14

14 14 14 14

14

14

14

10

10

14

14

14

14

14

14

14

14

2034A

2034B

12

A502

16

1'-6"

A502

22

2023

S2

S1S1

A50221

A203

05Sim

10'-6" 09

A501

10

A501

23

23

30

08

08

9'-0"

10'-3" 12'-4"

10

'-8

"1

0'-8

"5

'-8

"1

0'-2

"1

4'-10

"

27

16'-2" 10'-8" 8'-8" 8'-8" 10'-4" 10'-5" 12'-2"

A203

08SIM

A203

07SIM

A203

08SIM

A203

06

31

14 14

ADD01

ADD01

14

14

14

ADD01

ADD01

ADD01

14

14

ADD01

ADD01

NEW WORK GENERAL NOTES

1. FIELD VERIFY ALL DIMENSIONS. IFDIMENSIONS VARY SIGNIFICANTLYNOTIFY THE ARCHITECT

2. ALL DIMENSIONS TO FACE OF STEELSTUD OR EXISTING FINISH UNLESSNOTED OTHERWISE

3. GRAYED WALLS & DOORS AREEXISTING TO REMAIN - PROTECTDURING CONSTRUCTION

4. DASHED GRAY COMPONENTS AREPROVIDED BY OWNER AND ARESHOWN FOR REFERENCE ONLY

5. WALL PARTITIONS ARE TYPE AUNLESS NOTED OTHERWISE

6. AFTER NEW WORK IS COMPLETEEXCEPT LAY IN CEILING, ALL HOLESIN THE DEMISING WALLS ANDDRYWALL AT BOTTOM OF FLOORJOISTS ARE TO BE SEALED TIGHTAND FIRE CAULKED INSTALLED ATPENETRATIONS.

7. REMAINING EXISTING WALLS ARE TOGO TO DECK & BE SEALED TIGHT.ADD DRYWALL TO EXISTING STUDSABOVE CEILING IF THERE IS NONE.EXISTING WALLS ARE INDICATEDLIKE THIS:

10'-6"

A502

SIM14

SIM 142002C

2002A

OFFICE

2029

STOR.

2033

I.T.

2031

S TLT

2032

MECH / JAN.

2029

2033 20312032

2002A

2002

RECEPTION

A502

15

A50221

3 5

/8"

6'-7

"3

5/8

"1

0'-0

"

3 5/8" 5'-5"

30

9'-0"

15

'-8

"

13'-6"

DOASUINT

CONCRETE PAD

02

A203

03

A203

13'-10 13/16" ±

15

'-8

"

3'-0

"5

'-0

"

3'-0"

EXISTING STOREFRONT

EMSEAL QUIETJOINT ACOUSTICAL JOINT FILLER

PRE-MANUFACTURED ALUMINUM WALL CAP, PAINT TO MATCH WALL

EXISTING STOREFRONT

EMSEAL QUIETJOINT ACOUSTICAL JOINT FILLER

PRE-MANUFACTURED ALUMINUM WALL CAP, PAINT TO MATCH WALL

2'-6

"2

'-0

"1

'-0

"

8"

4'-6

"

1'-0" 8" 1'-4 1/16"

3/4" CHAMFER

6" CONCRETE SLAB -REFER TO SHEET CE5

FINISH GRADE

1/2" COMPRESSIBLE FILLER

SEALANT

7"

3'-5

"1

'-0

"

2'-0"

FINISH GRADE

8"8"8"

4'-0

"

STEEL REINFORCEMENT -REFER TO SHEET CE5

6" CONCRETE SLAB - REFER TO CIVIL

STEEL REINFORCEMENT -REFER TO SHEET CE5

CONCRETE STEMWALL -REFER TO CE5

STEEL REINFORCEMENT -REFER TO SHEET CE5

3/4" CHAMFER

CLEAN FILL GRAVEL

EXISTING WINDOWS

DUCTWORK PENETRATIONS -REFER MEP

CEILING

DOUBLE FULL HEIGHT STUDS

SINGLE FULL HEIGHT STUDS

0"

4'-0

"8'-0

"24

'-0"

16

'-0"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11

/5/2

01

9 1

:15:2

0 P

M A203

SOA PROJECT 19033

SECOND FLOOR PLAN -RENO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

William H. Oswald - ArchitectLicense No. A-5419

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

1/8" = 1'-0"A203

01 SECOND FLOOR - NEW WORK

KEYNOTES - NEW WORK PLAN

01 RECESSED FIRE EXTINGUISHER CABINET

02 CORNER GUARD 3"

03 CORNER GUARD TWO (2) AT 2"

04 NEW GYP BD ON EXISTING STUDS (APPROX. 5'HIGH) TO ALIGN WITH ADJACENT SURFACES

05 CONCRETE SLAB INFILL - ALIGN WITHADJACENT SURFACES

06 HIGH/LOW DRINKING FOUNTAIN - REFER TOPLUMBING & TYPICAL MOUNTING HEIGHTS

07 ROLLER SHADES

08 ALIGN WALL WITH ADJACENT SURFACES

09 KNOX BOX

10 16" HEAVY DUTY ADJUSTABLE SHELVES

11 FLOOR TRANSITION - REFER TO NEW WORKFINISH PLAN ON A702

12 ADJACENT TENANT SUITE, NO WORK THISAREA UNLESS IDENTIFIED ON MEP DRAWINGS

13 INFILL WALL WHERE SPECIMEN PASS-THRUWAS REMOVED

14 PATCH GYPSUM BOARD FROM REMOVAL OFPARTITION & DRYWALL

15 WALL PROTECTION UP TO 4'-0"

16 DOOR, FRAME AND PART OF THE HARDWARETO REMAIN. REPLACE STRIKE & DEADLOCK ASINDICATED ON DOOR HARDWARE SCHEDULEIN 08 4413

17 PROXIMITY READER

18 DIAPER CHANGING STATION (DCS)

19 MECHANICAL UNIT - REFER TO MECHANICALDRAWINGS

20 PROVIDE 20 GA SHEET MTL BACKING FOR TV

21 MOP SINK - REFER TO PLUMBING

22 EYEWASH STATION - REFER MEP

23 PUSH BUTTON FOR DOOR OPERATOR

24 CUBICLE CURTAIN TRACK

25 SPECIMEN PASS THRU

26 STEEL COLUMN - PAINT IPS-5A

27 PATCH EXISTING DRYWALL

28 FIRE DEPARTMENT CONNECTION

29 FIRE SPRINKLER RISER - REFER TO MEP ANDCIVIL

30 MOP AND BROOM HOLDER

31 CAULK AROUND NEW DUCTWORKPENETRATIONS

1/4" = 1'-0"A203

04 OFFICE & RECP. ENLARGED PLAN

3/16" = 1'-0"A203

05 MECHANICAL PAD - ENLARGED PLAN

1 1/2" = 1'-0"A203

DTL - TYP WALL AT MULLION071 1/2" = 1'-0"A203

DTL - TYP WALL TO GLASS08

1 1/2" = 1'-0"A203

SECTION 1 @ MECHANICAL PAD02

1 1/2" = 1'-0"A203

SECTION 2 @ MECHANICAL PAD03

1/4" = 1'-0"A203

ELEVATION - EAST FRAMING06

FI

ISSOUR

OETA

ST

M

RE

GIS

TERED ARCH

ITE

CT

10/22/2019

WILLIAM

HOWARDOSWALDNUMBER

A-5419

REVISION DATE

ADD 01 11/05/2019

Page 11: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

8'-0"

8'-0"

8'-0"

8'-0"

8'-0" 8'-0" 8'-0" 8'-0"

8'-5"

8'-0"

8'-0"

8'-0"8'-0"8'-0"8'-0"

8'-0"8'-0"8'-0"

7'-9"

04

A204

8'-0"8'-0"8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-5"

8'-5"

8'-5"

8'-5"

8'-0"8'-0"

8'-5"

8'-0"8'-0"

8'-0"

7'-8"

7'-8"

7'-8"

7'-8"

7'-8"

7'-6"

8'-0"8'-0"

04

A204

SIM

04

A204

SIM

04

A204

SIM

04

A204

SIM

7'-8"

01 TYPICAL

8'-0"

03

A204

GENERAL NOTES - REFLECTED CEILING

1. FIELD VERIFY ALL DIMENSIONS. IFDIMENSIONS VARY SIGNIFICANTLYNOTIFY THE ARCHITECT

2. ALL DIMENSIONS TO FACE OF STEELSTUD OR EXISTING FINISH UNLESSNOTED OTHERWISE

SUPPLY AIR DIFFUSER

RETURN AIR GRILLE

CAN LIGHT FIXTURE

2 X 4 LIGHT FIXTURE

2' X 2' LAY-IN ACOUSTICAL CEILING PANEL & GRID SYSTEM

LEGEND - REFLECTED CEILING

PENDANT LIGHT FIXTURE, REFER TO ELEC. DWGS FOR LIGHT FIXTURE SCHEDULE

SLOT TYPE AIR DIFFUSER

STRIP LIGHT, REFER TO ELEC. DWGS FOR LIGHT FIXTURE SCHEDULE

GYP. BD. CEILING

2 X 2 LIGHT FIXTURE

8'-0" 8'-0" 8'-0" 8'-0" 8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

7'-9"

01 TYPICAL

8'-0"

5/8" TYPE "X" GYP. BD.

3 5/8" MTL. STD.

AC-1

5/8" TYPE "X" GYP. BD.

ACOUSTIC CEILING TILE WALL ANGLE

6"

IPS-2A IPS-2A

2'-2 3/4"

6"

EXISTING FRAMING ABOVE

BRACING AS REQUIRED

3 5/8" METAL FRAMING @ 16" O.C.

CAN LIGHT BEYOND -REFER TO ELECTRICAL

5/8" TYPE "X" GYPSUM BOARD

6"

WC-2

IPS-2A

IPS-2A

FLOOR LINE

STRUCTURAL DECK

B1B2

CEILING LINE

5/8" TYPE "X" GYPSUM BOARD

3 5/8" 22 GAUGE METAL STUDS @ 16" O.C.

A

5/8" TYPE "X" GYPSUM BOARD

3 5/8" 22 GAUGE METAL STUDS @ 16" O.C.

B

1 5/8" 22 GAUGE METAL STUDS @ 16" O.C.

B1

7/8" METAL HAT CHANNEL @ 16" O.C.

B2

3 5/8" 22 GAUGE METAL STUDS @ 16" O.C., W/ SOUND ATTENUATION, 1 HR RATED

A1

3 5/8" 22 GAUGE METAL STUDS @ 16" O.C., W/ SOUND ATTENUATION, NON-RATED

A2

A2

0"

4'-0

"8'-0

"24

'-0"

16

'-0"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11

/5/2

01

9 1

:15:2

2 P

M A204

SOA PROJECT 19033

REFLECTED CEILINGPLANS

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

William H. Oswald - ArchitectLicense No. A-5419

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

1/8" = 1'-0"A204

02 SECOND FLOOR - REFLECTED CEILING PLAN

1/8" = 1'-0"A204

01 FIRST FLOOR - REFLECTED CEILING PLAN

KEYNOTES - NEW WORK REFLECTED CEILING

01 BEFORE LAY IN CEILINGS ARE INSTALLED ALL VOIDS ANDDAMAGED DRYWALL IS TO BE REPAIRED ON REPLACEDAND SEALED TIGHT. ALL PENETRATIONS THROUGH THISASSEMBLY IS TO BE FIRE CAULKED.

1 1/2" = 1'-0"A204

DTL - TYP. BULKHEAD04

1 1/2" = 1'-0"A204

SOFFIT DETAIL03

FI

ISSOUR

OETA

ST

M

RE

GIS

TERED ARCH

ITE

CT

10/22/2019

WILLIAM

HOWARDOSWALDNUMBER

A-5419

REVISION DATE

ADD 01 11/05/2019

1 1/2" = 1'-0"

PARTITION TYPES

ADD01

Page 12: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

REF. ICEM

ED

-F

A

123456

1TRTMNT -LONG2021

EDUCATION2020

MECH.2019

CONFERENCE2018

WAITING2001

NURSE2034

OFFICE2002A

VESTV2002

OFFICE2026

EXAM - B2017

EXAM - B2016

EXAM - AEXAM - A EXAM - A EXAM - A EXAM - A EXAM - A EXAM - A

EXAM - A

MED2024

EXAM - B2022

EXAM - A2004

LAB2023

EXAM - B2015

S TLT2014

EXAM - B2013

TRTMNT -B

2012

S TLT2031MECH /

JAN.2032

BREAK2039

SOILED2037

MECH.2038

ADA TLT2035

ADA TLT2036

CLEAN2025

EXAM - A2027

P TLT2001A

STORAGE2028

VESTV2001

MECH.2030

CORR.C2007

CORR.C2005

CORR.C2002

RECEPTION2002

8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0"

8'-5"

8'-0"

8'-5"

8'-0"8'-0"8'-0"8'-0"8'-0"8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-5"

I.T.2033

CORR.C2003

STOR.2029

2

8'-0"

8'-5"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-0"

8'-5"

3

33

3

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

0"4'

-0"

8'-0

"24

'-0"

16'-0

"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

FP102SOA PROJECT 19033

FIRE PROTECTIONSECOND FLOOR PLAN -

RENO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NORTH

SCALE: 1/8" = 1'-0"

FIRE PROTECTION LEVEL 02 PLAN - RENO

GENERAL NOTES:

1. REFER TO SHEET FP001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

FIRE PROTECTION KEYED NOTES FP102# DESCRIPTION

1 PROVIDE THE DESIGN AND INSTALLATION OF A COMPLETE AND FUNCTIONALWET-PIPE FIRE PROTECTION SYSTEM FOR AREA INDICATED.

2 PROVIDE DRY RISER ASSEMBLY WITH FLOOR-MOUNTED, TANK, WITH TANK-MOUNTEDAIR COMPRESSOR. AIR COMPRESSOR SHALL BE GENERAL AIR QUIET-SERIES.CONTRACTOR TO COORDINATE RISER LOCATION SHOWN WITH OWNER.

3 REMOVE EXISTING DOMESTIC WATER SPRINKLER SYSTEM DURING DEMOLITIONPHASE OF WORK. CONTRACTOR TO COORDIANTE WITH TENANT.

ADD01

ADD01

ADD01

ADD01

ADD01

REVISION DATE

ADD 01 11/05/2019

Page 13: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

EWH

EX

2" EX-W

2" EX-W

2" EX-W

2" EX-W

2" EX-W2" EX-W

1/2" EX-HW

4" EX-W

2" EX-W

2" EX-W

2" EX-W

2" EX-W

2" EX-W

2" EX-W

4" EX-W

1

1

1

1

1

2

2

EX 4" W UP

EX 4" W UP

CO

EX 4" W UP

EX 4" W UPEX 3" W UP

3" W

FD

EX

EX 3" W UP

4" W DN

4

4

EX 2" W UP

EX 2" W UP

EX 2" W UP

EX 2" W UP EX 2" W UPEX 2" W UP

EX 2" W UP

EX 2" W UP

EX 2" W UP

5

5

GCO

EXISTING SANITARY SEWER BELOW GRADE

1/2" EX-HW

1/2" EX-CW

6

6

6

6

7 7

1/2" EX-CW

EWH

EX

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

0"4'

-0"

8'-0

"24

'-0"

16'-0

"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

PD101SOA PROJECT 19033

PLUMBING FIRSTFLOOR PLAN - DEMO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING LEVEL 01 PLAN - DEMO

1

2

GENERAL NOTES:

1. REFER TO SHEET P001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

KEYED NOTES:

EXISTING PLUMBING FIXTURES TO REMAIN.

DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE AND RELATED PIPE.

SAW CUT AND REMOVE EXISTING FLOOR SLAB FOR NEW PLUMBING FIXTURE SEWER PIPE INSTALLATION. PATCH FLOOR TO MATCH EXISTING.

NOT IN SCOPE.

COORDINATE WITH BUILDING OWNER AND TENANT FOR WORK TO BE DONE AFTER NORMAL WORKING HOURS.

FIXTURE VENT PIPING TO BE REMOVED AND RE-ROUTED THROUGH NEW WALLS ON FLOOR ABOVE, SEE P102.

REMOVE AND REPLACE FAUCET AND TRIM, EXISTING FIXTURE TO REMAIN.

3

4

5

6

7

ADD01

ADD01

REVISION DATE

ADD 01 11/05/2019

Page 14: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

1

1

1

1

11/2" CW& HW

1" CW

1/2" HW4" EX-W

2" EX-W

4" EX-W2" EX-W

2" EX-W

4" EX-W

2" EX-W

S

1

EX 4" W UP

2" W UP

2" W UP2" W UP2" W UP2" W UP2" W UP2" W UP

2" W UP

OFFICE1010

OFFICE1009

OFFICE1008OFFICE

1007

OFFICE1006

OFFICE1005

OFFICE1004

OFFICE1003

OFFICE1002

OFFICE1017

MECH.1011

FELLOWS1016

RR1013

RR1014

STOR.1015

JAN.1012

CORR.C1002

CORR.C1003

CORR.C1004

CORR.C1001

OPENOFFICE

1001

3" EX-W

EX 4" W UP

1

2" W

2" W

2" W

2" W

2" W

4" W DN

2" W

2" W

EWC

1

2" W UP

2" W

2" W UP

1/2" CW2" W

2" W UP

2" EX-W

2" EX-W

6

2

3

UP TO FLOOR DRAIN ABOVE

LAV

2

LAV

2

5

4

5

2" V

2" V

2" V

8

7

7

8

1 1/2" V UP

GCO

EXISTING SANITARY SEWER BELOW GRADE

WH

1

3/4" CW UP

1 1/2" V

EWH

EX

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

0"4'

-0"

8'-0

"24

'-0"

16'-0

"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

P101SOA PROJECT 19033

PLUMBING FIRSTFLOOR PLAN - RENO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NORTH

SCALE: 1/8" = 1'-0"

PLUMBING LEVEL 01 PLAN - RENO

1

GENERAL NOTES:

1. REFER TO SHEET P001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

KEYED NOTES:

EXISTING PLUMBING FIXTURE TO REMAIN.

SIZE AND ROUTING OF WASTE PIPE FOR EXISTING FLOOR DRAIN IN MECHANICAL ROOM IS UNKNOWN.

WASTE PIPE DOWN IN WALL TO BELOW FLOOR. SIZE AND ROUTING OF WASTE PIPE IS UNKNOWN.

THIS SPACE WAS NOT SURVEYED BECAUSE IT WAS LOCKED AND NO ACCESS COULD BE OBTAINED.

SAW-CUT FLOOR FOR NEW WASTE PIPE FROM EWC-1 AND S-1 AND CONNECT TO EXISTING WASTE AT EXISTING TOILET ROOMS.

COORDINATE WITH BUILDING OWNER AND TENANT FOR WORK TO BE DONE AFTER NORMAL WORKING HOURS.

REMOVE AND REPLACE FAUCET AND TRIM, EXISTING FIXTURE TO REMAIN.

PROVIDE NEW 3" VENT UP THROUGH FLOOR TO EXISTING TOILET ROOMS, SEE P102.

2

3

4

5

6

7

8

ADD01

ADD01

REVISION DATE

ADD 01 11/05/2019

Page 15: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

CU

CO

ND

UC

TO

RS

ELECTRICAL GENERAL NOTES:

FEEDER SCHEDULE

PLAN

MARK AMPERAGE FEEDER SIZE

1 20A. 3 #12 & 1 #12G., 3/4"C.

4 #12 & 1 #12G., 3/4"C.20A.2

3 #10 & 1 #10G., 3/4"C.30A.3

4 #10 & 1 #10G., 3/4"C.30A.4

3 #8 & 1 #10G., 3/4"C.40A.5

4 #8 & 1 #10G., 3/4"C.40A.6

3 #6 & 1 #10G., 3/4"C.55A.7

4 #6 & 1 #10G., 1"C.55A.8

3 #4 & 1 #8G., 1"C.85A.9

4 #4 & 1 #8G., 1-1/4"C.85A.10

3 #3 & 1 #8G., 1-1/4"C.100A.11

4 #3 & 1 #8G., 1-1/4"C.100A.12

OVERCURRENT

PROTECTION

20A.

20A.

25A.,30A.

25A.,30A.

35A.,40A.

35A.,40A.

45A.,50A.,60A.

45A.,50A.,60A.

70A.,80A.

70A.,80A.

90A.,100A.

90A.,100A.

1. ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND HVAC WORK SHALL BE COORDINATED BY THECONTRACTOR DOING THE WORK. ANY CORRECTIONS TO ANY OF THE ABOVE SHALL BE AT THE CONTRACTOR'S

EXPENSE.

2. ALL DISCONNECTS REQUIRED SHALL BE PROVIDED BY THE EC, U.N.O. SEE MECHANICAL SCHEDULE PLAN FOR

DISCONNECTS FURNISHED BY OTHERS. REFER TO MANUFACTURER'S DETAILS FOR MECHANICAL EQUIPMENTCONNECTIONS.

3. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDERS, SIZED IN ACCORDANCE WITH NEC ARTICLE 250.122,SEE SPECIFICATIONS.

4. REFER TO SHEET E000 FOR ADDITIONAL NOTES. ALL CONDUCTORS COPPER UNLESS NOTED OTHERWISE.

5. ALL EXTERIOR ELECTRICAL EQUIPMENT AND DISCONNECT SWITCHES SHALL BE IN RATED NEMA 3R OR 4XENCLOSURES. FINAL CONDUIT CONNECTIONS TO MECHANICAL EQUIPMENT SHALL BE MADE WITH LFMC.

6. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE AVAILABLE FAULT CURRENT WITH THE UTILITY COMPANY ANDPROVIDE EQUIPMENT RATED ACCORDINGLY. SUBMIT FAULT CURRENT CALCULATIONS WITH SHOP DRAWING

SUBMITTAL.7. PROPER CLEARANCE MUST BE MAINTAINED ABOUT ELECTRICAL EQUIPMENT PER N.E.C. FIELD VERIFY EXACT

MOUNTING SPACE AVAILABLE IN ELECTRICAL ROOM/AREA PRIOR TO INSTALLATION OF ELECTRICAL EQUIPMENT.

8. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH NEC ARTICLE 110.16 FOR LABELING OF PANELS FOR ARC FLASH

HAZARD WARNING.

EXISTING PADMOUNTEDXFMR

1200A MCB120/208V3PH, 4W

METER BANK(EXISTING)

102

103 202

101

HOUSE

206

1200A

101

225AMLO

120/208V

3PH, 4W

(EXISTING)

HOUSE

125AMLO

120/208V

3PH, 4W

(EXISTING)

102

225AMLO

120/208V

3PH, 4W

(EXISTING)

P1

225AMLO

120/208V

3PH, 4W

(EXISTING)

P2

225AMLO

120/208V

3PH, 4W

(EXISTING)

125A

200A

200A

200A

200A

200A

ELECTRICAL KEYED NOTES:

1 PROVIDE ELECTRICAL ARC FLASH HAZARD ANALYSIS AND SHORT CIRCUIT STUDY PER

SPECIFICATION 260574. PROVIDE AND INSTALL ARC FLASH LABELS ON PANEL BOARDS.

NEW PANEL SHALL BE COMMERCIAL LIGHTING AND APPLIANCE PANELBOARD SQUARE D

TYPE NQOD OR EQUIVALENT BY GE OR EATON WITH COPPER BUS BARS, ISOLATEDNEUTRAL BUS, AND GROUND BUS. LOAD CENTER IS NOT ACCEPTABLE. PROVIDE PLASTICNAME PLATE WITH 1/4" WHITE LETTERS ON OUTSIDE OF PANEL INDICATING PANEL NAME,

VOLTAGE, PHASE, AND FEEDER ORIGIN.

11111

P3

100AMLO

120/208V3PH, 4W10KAIC

(NEW)

1

#

2

2

8

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

E002SOA PROJECT 19033

ELECTRICAL ONE-LINEDIAGRAM

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NOT TO SCALE

PARTIAL ELECTRICAL ONE LINE DIAGRAM

ADD01

REVISION DATE

ADD 01 11/05/2019

Page 16: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

REF. ICEM

ED

-F

OS

OSDOSDDDD

e fOS

OS

D

OS

DD

D

eOS

cOSOS

DO

S

D

OSOSOS

OS

ba

OS

OS

OS

OS

OS

OS OS

OS

OS

OS

OSOS

d

OS

OS OS

SS

S

SSSSSS

S

S

S

S S S S S S

S SS

S S

OS

OS

OS

g

D

OS

OS

h

DDDDDDD

DD

D

3P2 -

A

3hP2 -

A

3P2 -

A

3P2 -

A

3hP2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3hP2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3hP2 -

A

3P2 -

B

3P2 -

A

3P2 -

A

3hP2 -

A

3eP2 -

A

3eP2 -

A3P2 -

A

5fP2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

5P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

3P2 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A

10P1 -

A

10P1 -

A

10P1 -

A

10P1 -

A

10P1 -

A

10P1 -

A

10gP1 -

A

10gP1 -

A

10gP1 -

A

10gP1 -

A

5fP2 -

A

5fP2 -

A

5fP2 -

A

5fP2 -

A

5fP2 -

A

5fP2 -

A

32P1 -

B

32P1 -

B

5fP2 -

A

32P1 -

A

32P1 -

A

32P1 -

A

5P2 -

A

5P2 -

A

5P2 -

A

5fP2 -

A

32P1 -

A

32P1 -

A

5fP2 -

A

5fP2 -

A

5fP2 -

A

5P2 -

A

5P2 -

A

5P2 -

A

5P2 -

A

A

5P2 -

A

10P1 -

A

10P1 -

A

10P1 -

A

32P1 -

A

32P1 -

A

32P1 -

A2

32P1 -

A

32P1 -

A2

32P1 -

A2

32P1 -

A2

32P1 -

A

5fP2 -

A

32P1 -

A

16P1 -

B

16P1 -

A2

A

16P1 -

A

10gP1 -

A

16P1 -

A2

16eP1 -

A2

16eP1 -

A2

16eP1 -

A2

16eP1 -

A2

16eP1 -

A

10gP1 -

A

10gP1 -

A

10gP1 -

A

10P1 -

B

10P1 -

A

16aP1 -

A

16dP1 -

A2

16dP1 -

A2

16dP1 -

A2

16dP1 -

A2

16dP1 -

A2

16P1 -

B 16cP1 -

C

16cP1 -

C

16cP1 -

C16cP1 -

C

16cP1 -

C

16cP1 -

C

16aP1 -

A

10gP1 -

A

16bP1 -

A

16bP1 -

A

16bP1 -

A

16bP1 -

A

16bP1 -

A

10gP1 -

A

16bP1 -

A

16bP1 -

A

10P1 -

C

16aP1 -

CTRTMNT -

LONG2021

EDUCATION2020

MECH.2019

CONFERENCE2018

WAITING2001

NURSE2034

OFFICE2002A

VESTV2002

OFFICE2026

EXAM - B2017

EXAM - B2016

EXAM - A2011

EXAM - A2010

EXAM - A2009

EXAM - A2008

EXAM - A2007

EXAM - A2006

EXAM - A2005

EXAM - A2003

MED2024

STOR.2029

EXAM - B2022

EXAM - A2004

LAB2023

EXAM - B2015

S TLT2014

EXAM - B2013

TRTMNT -B

2012

??

?? S TLT

2031

MECH /JAN.2032

BREAK2039

SOILED2037

MECH.2038

ADA TLT2035

ADA TLT2036

CLEAN2025

EXAM - A2027

P TLT2001A

STORAGE2028

VESTV2001

MECH.2030

CORR.C2003

CORR.C2007

CORR.C2005

CORR.C2002

RECEPTION2002

CORR.C2008

CORR.C2004

CORR.C2001

CORR.C2006

C

CC

1

1 1

2

5

A

5

A

5

A

10

10gP1 -

A

16bP1 -

A

16bP1 -

A

16bP1 -

A

I.T.2033

32P1 -

B

32P1 -

B

32P1 -

B

3 TYP.

5fP2 -

A

XA

XA

XA

XA

XA

XA

XA

P1

P2

10P1 -

A

10P1 -

A

XA

XA

16aP1 -

A

16aP1 -

A

16aP1 -

A

D

5P2 -

XA

NL

NL

5fP2 -

A

P1-10g

P2-3h

P2-5e

4

P3

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

0"4'

-0"

8'-0

"24

'-0"

16'-0

"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

E102SOA PROJECT 19033

ELECTRICAL SECONDFLOOR LIGHTING PLAN

- RENO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL LIGHTING LEVEL 02 PLAN - RENO

1

ELECTRICAL GENERAL NOTES:

1. REFER TO SHEET E001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

2. REFER TO THE ELECTRICAL DETAILS SHEET(S) FOR LIGHTING CONTROL SCHEMATIC.

3. SUSPENDED CEILING SYSTEMS ARE DESIGNED TO SUPPORT THE WEIGHT OF ALL LIGHTING FIXTURES. THE STRUCTURAL FRAMING SHALL SUPPORT ALL CONDUITS, JUNCTION BOXES, ETC ABOVE CEILINGS.

4. EMERGENCY LIGHTING SHALL BE SWITCHED AND NOT BE USED AS A NIGHT LIGHT UNLESS SPECIFICALLY NOTED AS SUCH. EXIT SIGNS SHALL NOT BE SWITCHED.

5. INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT AND FIXTURES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

6. CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND FIXTURES PRIOR TO STARTING WORK. NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.

KEYED NOTES:

INSTALL LED LIGHT IN EXISTING OPENING AT CANOPY.

PROVIDE (3) EMERGENCY LIGHTING MINI-INVERTER RATED 250W. CIRCUIT LIGHT FIXTURES INDICATED WITH HATCHING TO INVERTER. MOUNT INVERTER IN ACCESSIBLE LOCATION. CONNECT TO LIGHTS INDICATED WITH HATCHING AND EXIT SIGNS.

NURSE CALL DOME LIGHT. REF TO DETAIL ON SHEET E003 FOR WIRING REQUIREMENTS AND SHEET E302 ADDITIONAL NURSE CALL SYSTEM INFORMATION.

1-HOUR RATED FIRE WALL. SEAL CONDUIT PENETRATIONS TO MAINTAIN FIRE RATING. REFERENCE SHEET G002.

2

3

4

ADD01

ADD01

ADD01

REVISION DATE

ADD 01 11/05/2019

Page 17: ADDENDUM No. 01 Date: 5, 2019operations-webapps.missouri.edu/pdc/adsite/projects/cp192061/add… · 13 infill wall where specimen pass-thru ... partition & drywall 15 wall protection

REF. ICEM

ED

-F

GF

I

GFI

GFI GFI GFI GFI

GFI

GFI

GFI

GFI+66"

GFIGFI

GF

IG

FI

GF

I

GFI

GFIGFIGFIGFI

GFI

GFI

GF

IG

FI

GF

I

GF

I

GFI

GF

IG

FI

GFI

GF

IJ

6DGFI

GF

I

GF

I

GF

I/W

P

GFI/WPPC

J

J

J

J

J

J

P2

P1

TRTMNT -LONG2021

EDUCATION2020

MECH.2019

CONFERENCE2018

WAITING2001

NURSE2034

OFFICE2002A

VESTV2002

OFFICE2026

EXAM - B2017

EXAM - B2016

EXAM - A2011

EXAM - A2010

EXAM - A2009

EXAM - A2008

EXAM - A2007

EXAM - A2006

EXAM - A2005

EXAM - A2003

MED2024

STOR.2029

EXAM - B2022

EXAM - A2004

LAB2023

EXAM - B2015

S TLT2014

EXAM - B2013

TRTMNT -B

2012

I.T.2033

S TLT2031

MECH /JAN.2032

BREAK2039

SOILED2037

MECH.2038

ADA TLT2035

ADA TLT2036

CLEAN2025

EXAM - A2027 P TLT

2001A

STORAGE2028

VESTV2001

MECH.2030

CORR.C2003

CORR.C2007

CORR.C2005

CORR.C2002

RECEPTION2002

CORR.C2008

CORR.C2004

CORR.C2001

CORR.C2006

4

3 TYP

5

2

22

2

2

2

2

2

1

7

8

7

7 23 23

23

27

23

12

14

42

29

29

29

31 31

31

33

33

33 18

18 35 20

35 20

31 11 29

7 7

5

7

5

5

55

3

33

3

1

1

18

181616

16 1610

10

10

14

12

6 6

39

48

6

6

6

6

6

28

28

28

28

28

6 9

15

17

17

1717

15

17

17

19

19

19

21

99

1

31

14

9

29

11

11

13

13

31

3120

2035

35

18

183329

11

1331

13

1

1

18

10

12

1212

29

42

27

25

12

29

42

42

27

27

25

25

25

7 7

12

1

17

29

6

17

CIRCUIT TO PANEL P2 U.N.O. CIRCUIT TO PANEL P1 U.N.O.

6

6

9

9

9

P3 - 6,8P3 - 2,4

P3 - 1

P3 - 1

P3 - 1

P3 - 1

22

34

37

28

30

30

27

9

9

10

DOAS

1

11

11

6 11

6 11

12

13 13

25

+ 64"

+ 6

4"

+ 6

4"

+ 6

4"

+ 64"

+ 64"

+ 64"+ 64" + 64" + 64"

+ 64" + 64"

+ 64"+ 64"

+ 64"

+ 64"+ 64"

+ 6

4"

+ 6

4"

+ 6

4"

+ 64"

+ 64"

+ 64"+ 64" + 64" + 64"

+ 64"

+ 64"

+ 64"

+ 64"+ 64"

+ 64"

+ 64"+ 64"

2911 9

1331

2035183331

29

42

25

1

16

41

16

1012

12

33

14

FF

1215

15

15

15

15

15 15 15 15 15 15 15 15 15

151515

1

19

19

19

27

4

9

9

9

9

12

12

20

20

P1 - 35

TTB

P3 - 3,54

2

16

17

18

16

CU

1

P3 18

19

19

P1 - 8

P1 - 8

P1 - 22

P1 - 22

P1 - 22

P1 - 22

P1 - 2220

20 P1 - 22

20

20

20

P2-36,38,40

ADD01

JEREMY M SCHUETTEMO LIC#:PE-2014000082

EXP: 12/31/20

20

19

227

Th

e S

eal a

nd

Sig

na

ture

app

ly o

nly

to th

e D

ocu

me

nt to

whic

h th

ey a

re A

ffix

ed

, a

nd

Exp

ressly

Dis

cla

im a

ny

Re

sp

on

sib

ility

for

all

oth

er

Pla

ns, S

pe

cific

ation

s,

Estim

ate

s, R

ep

ort

s, o

r oth

er

Docum

ents

or

Instr

um

en

ts

rela

ting

to

or

inte

nd

ed

to

be u

sed

for

an

y p

art

or

pa

rts o

f th

e A

rchitectu

ral o

r E

ng

inee

rin

g P

roje

ct.

Cop

yrig

ht ©

20

19

by S

SC

Engin

ee

ring

, In

c.

0"4'

-0"

8'-0

"24

'-0"

16'-0

"

If you must print this drawing, please recycle

www.soa-inc.com

Missouri Certificate of

Authority Number: 000826

1/8

"=1'-0"

Architecture

Interior Design

Planning

Sustainability

2801 Woodard Drive, Suite 103

Columbia, MO 65202

573.443.1407

MEP ENGINEER:

SSC ENGINEERING, INC.18207 EDISON AVECHESTERFIELD, MO 63005636-530-7770www.sscengineering.com

CIVIL/STRUCTUAL ENGINEER:

1000 W NIFONG BLVD., BLDG. 1 COLUMBIA, MO 65203573-447-0292www.crockettengineering.com

11/05/2019

E202SOA PROJECT 19033

ELECTRICAL SECONDFLOOR POWER ANDDATA PLAN - RENO

ISSUE FOR BID

CLIENT PROJECTCP192061

OCTOBER 22, 2019

Simon Oswald Associates, Inc.

CP

192

061

331

5 B

err

yw

oo

d -

Med

ica

l C

en

ter

3315 B

ER

RY

WO

OD

DR

IVE

CO

LU

MB

IA,

MO

65202

NORTH

SCALE: 1/8" = 1'-0"

ELECTRICAL POWER, DATA, VOICE,AV LEVEL 02 PLAN - RENO

1

ELECTRICAL GENERAL NOTES:

1. REFER TO SHEET E001 FOR SYMBOLS, ABBREVIATIONS AND GENERAL CONSTRUCTION NOTES.

2. ALL MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, AND HVAC WORK SHALL BE COORDINATED BY THE CONTRACTOR DOING THE WORK. ANY CORRECTIONS SHALL BE AT THE CONTRACTOR'S EXPENSE.

3. ALL DISCONNECTS REQUIRED SHALL BE PROVIDED BY THE EC, U.N.O. SEE MECHANICAL & PLUMBING EQUIPMENT SCHEDULE(S) FOR EQUIPMENT DETAILS AND FOR DISCONNECTS FURNISHED BY OTHERS. REFER TO MANUFACTURER'S SPECIFICATIONS FOR MECHANICAL & PLUMBING EQUIPMENT CONNECTION DETAILS. COORDINATE WITH APPLICABLE TRADES.

4. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDERS, SIZED IN ACCORDANCE WITH NEC ARTICLE 250.122, SEE SPECIFICATIONS.

5. ALL EXTERIOR ELECTRICAL EQUIPMENT AND DISCONNECT SWITCHES SHALL BE IN RATED NEMA 3R OR 4X ENCLOSURES. FINAL CONDUIT CONNECTIONS TO EXTERIOR MECHANICAL EQUIPMENT SHALL BE MADE WITH LFMC.

6. REFER TO ELECTRICAL DETAILS SHEET(S) FOR ADDITIONAL PHONE AND DATA REQUIREMENTS.

7. CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF ALL CORE DRILLS ARCHITECT PRIOR TO INSTALLATION. LOCATION SHALL BE COORDINATED TO AVOID STRUCTURAL ELEMENTS AND MATCH FURNITURE LOCATIONS.

8. INFORMATION ON THIS SHEET IS COMPILED FROM EXISTING DRAWINGS AND CASUAL FIELD OBSERVATIONS AND SHALL BE CONSIDERED APPROXIMATE ONLY. VERIFICATION OF ALL EQUIPMENT AND DEVICES, EITHER SHOWN OR NOT SHOWN ON THESE PLANS, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

9. CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT AND DEVICES PRIOR TO STARTING WORK. NOTIFY ENGINEER IMMEDIATELY IF DISCREPANCIES EXIST.

10. CONTRACTOR SHALL INSTALL OWNER SUPPLIED CAT 6a CABLING. OWNER TO SUPPLY AND TERMINATE END CONNECTORS. CONTRACTOR SHALL INSTALL CAT 6a CABLE DIRECTIONALLY FROM THE TELECOM ROOM TO DATA OUTLETS, CCTV CAMERAS, WAPS, AND PAGING SPEAKERS INDICATED. CONTRACTOR SHALL LABEL BOTH ENDS OF CABLE.

KEYED NOTES:

PROVIDE 48"X96" FIRE RATED TTB ON ALL WALLS OF IT CLOSET TO 8'-0" AFF.

INSTALL OWNER PROVIDED (1) CAT 6a CABLE FOR WAP. WAP PROVIDED AND INSTALLED BY OWNER.

INSTALL OWNER PROVIDED (2) CAT 6a CABLES FOR EACH DATA OUTLET SHOWN, U.N.O. FACEPLATE SHALL ACCOMMODATE (4) DATA PORTS. PROVIDE AND INSTALL BLANK INSERTS.

PROVIDE (1) DATA DROP AND (1) DEDICATED ANALOG PHONE LINE FOR COPIER/FAX MACHINE. REFER TO SHEET E302 FOR ADDITIONAL ANALOG PHONE LINE REQUIREMENTS (FOR FIRE ALARM SYSTEM).

PROVIDE (4) DUPLEX RECEPTACLES IN IT ROOM AND (2) L5-30R RECEPTACLES FOR DATA RACKS.

PROVIDE NEW BOXES, HOSPITAL GRADE NEMA 5-20R RECEPTACLES, AND HEALTHCARE RATED MC CABLE WITH INSULATED GROUNDING CONDUCTOR FOR EXAM AND TREATMENT ROOMS.

PROVIDE (2) DATA AND (1) DUPLEX POWER RECEPTACLE FOR COMMUNICATION STATION MONITORS. REFER TO DETAIL PROVIDED BY MU I.T.

PROVIDE (3) 4" SLEEVES IN IT ROOM TO FLOOR BELOW FOR LV WIRING. INSTALL FIRESTOP PILLOWS PROVIDED BY OWNER.

MOTORIZED DOOR PUSHBUTTONS. CONNECT TO MOTOR AND INTERFACE WITH CARD READER AND ELECTRONIC LOCKING HARDWARE. REFERENCE SHEET E302 AND ARCH DOOR SCHEDULE SHEET A701.

PROVIDE 20A, 208V CIRCUIT FOR SPLIT A/C SYSTEM FOR NEW IT ROOM. INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE HEAVY DUTY DISCONNECT ADJACENT TO OUTDOOR UNIT AND WIRING PER MANUFACTURER'S RECOMMENDATIONS TO INDOOR UNIT.

REFER TO ARCHITECTS TYPICAL ELEVATIONS ON SHEET A503 OF EXAM ROOMS FOR EQUIPMENT LOCATIONS. CONTRACTOR SHALL COORDINATE MOUNTING HEIGHTS OF (1) DUPLEX AND (1) DATA OUTLET WITH OWNER PROVIDED V6 MONITOR.

PROVIDE POWER AND DATA FOR MONITOR HIGH ON WALL. PROVIDE CHIEF PAC 526 FLUSH TV BOX WITH DUPLEX RECEPTACLE. COORDINATE EXACT LOCATION WITH OWNER PRIOR TO ROUGH-IN.

PROVIDE RECESSED CHIEF PAC 526 BOX FOR MONITOR WITH DUPLEX POWER RECEPTACLE, RG6 COAX CABLE, AND DATA AT +60" AFF. ROUTE RG6 AND OWNER PROVIDED CAT6a CABLE TO IT ROOM.

RE-INSTALL EXISTING PHOTOCELLS. COORDINATE WITH GC DURING CONSTRUCTION OF NEW RETAINING WALL ON THIS SIDE OF BUILDING AND LOCATE TO AVOID SHADOWING FROM NEW WALL.

MOUNT BELOW WINDOW SILL. INSTALL OWNER PROVIDED (1) CAT 6a CABLE TERMINATION. FACEPLATE SHALL ACCOMMODATE (4) DATA PORTS.

PROVIDE (3) STI FIRE STOP EX-PATH FIRE RATED SLEEVES 4X4 ABOVE DROP CEILING FROM CORRIDOR TO IT ROOM.

1-HOUR RATED FIRE WALL. SEAL CONDUIT PENETRATIONS TO MAINTAIN FIRE RATING. REFERENCE SHEET G002.

NEW PANELBOARD P3 SHALL BE LOCATED TO COORDINATE WITH I.T. RACKS AND MAINTAIN NEC REQUIRED WORKING SPACE AND CLEARANCE AROUND PANEL.

PROVIDE NEW EXTRA DUTY WHILE IN USE WP COVER ON EXISTING RECEPTACLE.

PROVIDE 120V, 20A CIRCUIT AND 120V:12V XFMR FOR NEW FAUCET SENSOR. LOCATE XFMR IN ACCESSIBLE LOCATION.

GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL EQUIPMENT IN PATIENT CARE AREAS SHALL COMPLYWITH THE REQUIREMENTS OF NEC 517.13.

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

ADD01

ADD01

ADD01

ADD01

ADD01

ADD01