630 a, up to 36 kv - dipee pole mounted switch disconnectors in operation everywhere in medium...

20
Pole Mounted Switch Disconnector NPS 630 A, up to 36 kV

Upload: hoangmien

Post on 02-May-2018

235 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Pole Mounted Switch Disconnector NPS

630 A, up to 36 kV

Page 2: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

NPSPole Mounted Switch Disconnectors

In operation everywhere in Medium Voltage Networks with or withoutautomation systems. With references around the world from the Artic Circleto the most tropical of jungles.

ABB is a global market leader in power technology products. We offer efficiency,quality and competitiveness.

We believe that flexible solutions and competent support are key elementsfor your continued success. We also believe that your distribution system iscost-effective when it matches the requirements of the customers operation andprocess – no more and no less. That is why ABB develops and supplies solutionsperfectly tuned to user requirements and standards.

Through ABB’s worldwide presence, we can offer local support and serviceglobally. As your partner; we believe that these are key elements that enableyou to continuously improve the performance in your networks.

Our NPS Switch Disconnector has been carefully designed and developed inco-operation with utilities providers to meet the most diverse of customerrequirements and to maintain maximum flexibility. Highly reliable, ourNPS can be the key element of your rural distribution applications.

IndexReliable air break technologyfor your distribution network

NPS as a Line Switch Disconnector

NPS for Transformer Switch Disconnector/NPF fuse holder

Components for substation switch disconnectors

Feeder Automation

Feeder Automation solutions forair insulated switch disconnectors

DTU Operating Device forpole mounted switch disconnectorstype NPS or other types

Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA

Breaking devices on NPS24A for max. Ith/Idyn 20/50 kA

Breaking devices on NPS36A for max. Ith/Idyn 21/52 kA

Unique design

Manual operating mechanisms

Technical data

3

4-5

6-7

8-9

10

11

12-13

14

15

15

16

17

19

2

Dipee.info

Page 3: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Reliable air break technologyfor your distribution network

The NPS offers a complete range from off-loaddisconnectors to switch disconnectors with differentbreaking devices, all designed according to IECstandard for limited purpose and general purposeswitch disconnectors. The design is made for allclimate conditions in different installations and buildingstandards and can be either manually or remotelyoperated. The NPS also offer a modular constructionwhich can easily be expanded or upgraded in thefuture.

The extensive range of accessories makes the NPSsuitable for every customer, pole and buildingstandard.

Easy and smart integrations� Adaptable to all customer/

country building standards� Modular concept� Suitable for live working

Flexible concept� From the simplest of manually operated units to

motorized and automated remotely controlled units� Wide range of accessories� Upgradeable in switching performances

Enhanced performance and improved reliability� Only insulators with the best materials are used

- cycloaliphatic epoxy with over 30 years of fieldexperience in more than 50 countries

- high quality silicone or porcelain insulators arealso available

� Lightweight design with a limited number ofparts guarantees a long lifetime and trouble-freeoperation

ABB / Pole Mounted Switch Disconnector NPS 3

Dipee.info

Page 4: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

NPS as a Line Switch Disconnector

ABB / Pole Mounted Switch Disconnector NPS4

Dipee.info

Page 5: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Crossarm installationOne of the most common building standards where the line switchdisconnector is integrated on the same crossarm as the lines.

Wooden poles are most often used for this type of installation.

Installation below live lineSome building styles and standards require a separate crossarmbelow the line crossarm.

Sufficient clearances to the pole and between phases can bearranged by the flexible arrangement of phase elements.

Installation above live lineA typical installation example above the live lineon a steel structure pole.

Vertical installationUsed for branching lines down to cables.The vertically installed switch disconnector is also usedas a transformer switch disconnector.

Two pole mountingAll above examples are also available for two-pole mounting.

Pole fitting accessories for various pole types are also available- wooden poles- concrete poles- steel poles and structures

ABB / Pole Mounted Switch Disconnector NPS 5

Dipee.info

Page 6: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

NPS for Transformer Switch Disconnector/NPF fuse holder

ABB / Pole Mounted Switch Disconnector NPS6

Page 7: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

The NPS switch disconnector can be equipped with several types offuse holders. The vertically mounted NPS can be used as transformerswitch disconnector. The breaking capacity of the whip (25/50 A) isenough for disconnecting a fully loaded distribution transformer up to800/1600 kVA.

If the pole element is horizontally mounted the fuse holder for HRC fuses(6.3, 16, 25 A) or (SMIA-KR_) melting fuses can be easily integrated(up to 63 A) to the switch disconnector.

The fuses are replaced using isolated rods from ground level.

NPS can be equipped with integrated earthing contact for openand earthed position.

The separate fuse holder for HRC and SMIA-KR_ can also be equippedwith surge arresters for one-,two-, or three-phase installation.

NPS can be equipped with a separate fuse holder for DIN-type fuses(CEF outdoor HRC fuses).

7.2 kV12.0 kV17.5 kV24.0 kV36.0 kV

up toup toup toup toup to

160 A100 A100 A100 A40 A

15.5 kV25.8 kV38.0 kV

160 A100 A40 A

IEC 282 ANSI

ABB / Pole Mounted Switch Disconnector NPS 7

NPS24B1-J2and NPAC5

NPS24B1-J2,NPAC9-J2 andNPAF7-J2

NPF24B2

NPF24E5

NPS24B1-J2NPAE5

Page 8: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Components for substation switch disconnectors

ABB / Pole Mounted Switch Disconnector NPS8

Page 9: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

A wide range of accessories are available for different substation solutions.The modular construction of NPS enables the most demanding customer

requirements to be fulfilled.

Flexible droppers and additionalinsulators for lowering the cableconnections.

CT’s and Surge arresters.

Earthing on one or both sides.NPS24B1-J2NPS-ZM1

Fuse base with supportfor surge arrester.NPF24B2

ABB / Pole Mounted Switch Disconnector NPS 9

NPS24B1-J2NPAC7

NPS24B-K4J2

NPS24B1-K5J2

250 A

630 A

Automatic earthingin open position.NPS24B1-J2NPAE5

NPS24B1-J2KOHU24A2MWK

NPS24B1-J2

NPS24B1-K1J2

25 A 50 A

Basic disconnector module.NPS24B1-WWJ2

NPS24B1-J2KOHU24A2MWK

Third insulator with flexible bars.

NPS24B1-J2,NPAC9-J2 andNPAF7-J2

Page 10: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Feeder Automation

ABB / Pole Mounted Switch Disconnector NPS10

Page 11: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

○○○○○○○○○○○○○○○○

○○

○○○○○○○○○○○○○○○○○○○○○

○○○○○○○○○○○○○○○○

○○

○○○○○○○○○○○○○○○○○○○○○

Feeder Automation solutions forair insulated switch disconnectors

Our disconnector terminal units [DTU’s] are designed for remote controland local automation applications of NPS switch disconnectors and othersimilar types with up/down operating movement.

Together with REC 501 or REC 523 monitoring and control units both simpleapplications such as remote open/close operations and more sophisticatedauto sectionalizing schemes and measurements can be realized.

Standard communication protocols available for

� ANSI X3.28 HD only with REC 501

� RP570 only with REC 501

� IEC 60870-101, unbalanced

� MODBUS ASCII & RTU format

� DNP 3.0

Analog inputs available for standard CT’s and VT’s.

DTU’s can also be used without integrated motor mechanism.These can be used in applications such as master terminal for monitoringand controlling existing motor devices for indoor and outdoor switchdisconnectors and other motor operated apparatus.It is also applicable for switching devices with an integratedactuator.

One terminal with REC 523 can control up to 4 slave units

ABB / Pole Mounted Switch Disconnector NPS 11

UEMC50

DTU115

DTU135

DTU131UEMC-A

DTU115 DTU135

UEMC50L1-24VDC UEMC50H1-24VDC

Page 12: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

DTU Operating Device forpole mounted switch disconnectorstype NPS or other types

ABB / Pole Mounted Switch Disconnector NPS12

Page 13: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

UEMC50L1UEMC50H1

� The product range includes master and slave units

� Can be equipped with third party electronics/IED

� Two different cabinet sizes

� Complete with batteries and chargers

� Up/down tube operation of disconnectors

� Stainless steel cabinet and mechanism

� Dust tight (IP55) to secure long lifetime of critical electrical components

� High torque, alternative 1.2 sec or 3 sec operating time

� Best possible materials used

� Over 30 years experience

� Operating voltages: 24, 48, 110, 220 VDC 110, 230 VAC

Terminals for installing different IED’s.

Cabinets available with different options for batteries, battery chargers etc.

ABB / Pole Mounted Switch Disconnector NPS 13

DTU111UEMC-A2

DTU131UEMC-A3

Page 14: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Breaking devices on NPS24B for max. Ith/Idyn 16/40 kA

Due to the flexible design of the basic phase element, the NPS can be equipped with a range of breaking devices.

NPS Basic pole element

Disconnector(IEC)

No breaking capacity For disconnectingfunctions only.Provides a safeisolating distance.

NPS with 25 A breaking whip

Limited purposeswitchdisconnector(IEC)

gnitcennocsid roFgnikaerBfunctions only.Provides a safeisolating distance.

NPS with 50 A breaking whip

Limited purposeswitchdisconnector(IEC)

With extendedbreaking capacity inrural areas andtransformer loads.

NPS with 250 A breaking chamber

Limited purposeswitchdisconnector(IEC)

For main lines andsubstations wherelarger breakingcapacity is needed.

NPS with K5 air making and breaking chamber

General purposeswitchdisconnector(IEC)

Maximum- breaking- independent

spring assistedmaking capacity

For main lines andsubstations whereboth breaking andmaking capacity isneeded. Thissolution is excellentfor remote and autosectionalizers.

25 A/24 kV40 A/12 kV

Breaking 50 A/24 kV80 A/12 kV

Breaking 250 A/24 kV

630 A/24 kV

8 kA/24 kV12.5 kA/12 kV

egasUataD

ABB / Pole Mounted Switch Disconnector NPS14

NPS24B1-WWJ2

NPS24B1-J2NPS24B1-J3

NPS24B1-K1J2

NPS24B1-K4J2

NPS24B1-K5J2, NPS24B1-K5J3 and NPAC9-J3

Page 15: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Breaking devices on NPS24A for max. Ith/Idyn 20/50 kA

For overhead networks with BIL up to 150 kV.

Silicone insulator J3

For overhead networks with BIL, up to 200 kV NPS36 can be used.

Whip (16 A) or breaking chamber K3 (400 A) can be used as breaking elements.

Two alternative silicone insulators (J2 or J3)

ABB / Pole Mounted Switch Disconnector NPS 15

NPS24A2-J3 NPS24A2-K5J3 NPS24A2-K5J3NPAC1-J3

NPS36A2-J2 NPS36A2-K3J2 NPS36A2-K3J2NPAC11-J2

Breaking devices on NPS36A for max. Ith/Idyn 21/52 kA

Page 16: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Unique design

The unique design on breaking whips and dry type breakingchambers eliminates the risk of oil leakage.

Risk of oil eliminated

� Pollution risk for soil waters

� Safety risk in case of failed interruption

� No need to check oil level or compensate for possible leakages

Risk of conventional air breaking chambers eliminated byprotected breaking contacts

� Malfunctions due to dust, sand, ice and small animals

� Risk of terrain fires due to arcing

The exceptionally high number of making operations[>50 times 8 kA] enables use to locate faulty line sections byoperating against the fault.

16

Page 17: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Manual operating mechanisms

UEKE 5A1Hook stick leverHook stick operation mechanism for NPS24B_ models.Also available for mounting on lower level.

UEKO 1A1One hand grip operating mechanismfor low end disconnectors

UEKE 3A1Standard two hand grip operatingmechanism for all NPS_ models.

UEKE 3B1Standard two hand grip operating mechanismfor all NPS_ models with additional quickadjustment rod.

UEKE 2/1With auxiliary contacts and heatingelement IP55.

UEKE 6A1Wire operation

ABB / Pole Mounted Switch Disconnector NPS 17

Page 18: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

ABB / Pole Mounted Switch Disconnector NPS18

NPS Easy is factory assembledfor 80 x 80 or 100 x 100 mmRHS-beam.

Page 19: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

Technical data

1) Type NPS36A204 with earthing contact have lower ratings

- lightning impulse withstand voltage 170 kV

- power frequency wet withstand voltage 80 kV

- short-time withstand current 16 kA 1 s

- peak withstand current 40 kA

2) With breaking chambers

3) 7 closing operations, manual or motor

4) fast manual operation

5) When standard breaking whips are used special whips 24 kV 50 A available

6) With breaking chambers

ABB / Pole Mounted Switch Disconnector NPS 19

Type

Insulator

- creepage

- arcing distance (insulator)

- arcing distance (min to earth)

- cantilever strength

- salt fog test, IEC 507, (1 h) salt solution

Rated voltage, max.

Rated current

Rated frequency

Rated lighting impulse withstand voltage

- across the isolating distance

- to earth and between phases

Rated power frequency withstand

voltage in wet conditions

- across the isolating distance

- to earth and between phases

Min. distance between phases 2)

Min. isolating distance

Rated short-time withstand current

Rated peak withstand current

Rated short-circuit making current

Rated breaking current 5)

- mainly active load with 100 closing

and opening operations

- cable- and line-charging with 20

closing and opening operations

Mechanical endurance 6)

Permissible ice thickness

Ambient temperature limits

mm

mm

mm

kN

g/l

kV

A

Hz

kV

kV

kV

kV

mm

mm

1 s kA

3 s kA

kA

kA

12 kVA

15 kVA

24 kVA

36 kVA

A

Operat.

mm

°C

NPS24B1-J2

Epoxy

740

272

200

2

160

24

630

50/60

145

125

75

55

260

200

16

12.5

40

5 3)

40

32

25

-

15

2000

-

-50…+40

NPS24B1-J3

Silicone

715

300

255

9

-

24

630

50/60

145

125

75

55

260

200

16

12.5

40

5 3)

40

32

25

-

15

2000

-40…+40

NPS24A2-J3

Silicone

760

305

260

9

-

24

630

50/60

165

150

75

55

350

230

20

16

50

5 3)

40

32

25

-

15

2000

-

NPS36A2-J2

Silicone

1205

450

380

6.2

-

36

630

50/60

220 1)

200 1)

88 1)

80 1)

430

350

21 1)

16 1)

52 1)

7.5 4)

-

-

16

16

10

2000

-40…+40

NPS36A2-J3

Silicone

1365

465

385

6.2

-

36

630

50/60

220 1)

200 1)

88 1)

80 1)

430

350

21 1)

16 1)

52 1)

7.5 4)

-

-

16

16

10

2000

-40…+40

Page 20: 630 A, up to 36 kV - dipee Pole Mounted Switch Disconnectors In operation everywhere in Medium Voltage Networks with or without automation systems. With references around the world

ABB OyMV Apparatus & SwitchgearP.O.Box 613, FI-65101 Vaasa, FinlandTel: +358 10 22 11Fax: +358 10 22 44661www.abb.com

4/07

-03

0-60 B

G5S

PN