740 6 George Road Edgbaston Birmingham B15 1NP 12 th July 2016 ENERGY PERFORMANCE CERTIFICATE UK-wide services Energy Performance Certificates Air-conditioning Inspections Asbestos Surveys Fire Risk Assessments Land Registry Plans Energy Efficiency Upgrades Vacant Building Alarms Facilities Management We keep buildings safe, secure & sustainable

Upload: ngokiet

Post on 18-May-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

740

6 George Road Edgbaston

Birmingham B15 1NP

12th July 2016

ENERGY PERFORMANCE CERTIFICATE

UK-wide services

Energy Performance Certificates Air-conditioning Inspections Asbestos Surveys Fire Risk Assessments

Land Registry Plans Energy Efficiency Upgrades Vacant Building Alarms Facilities Management

We keep buildings safe, secure & sustainable

Page 2: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

Green Deal Information

The Green Deal will be available from later this year. To find out more about how the Green Deal can make yourproperty cheaper to run, please call 0300 123 1234.

Energy Performance CertificateNon-Domestic Building

Certificate Reference Number:9747-3053-0869-0600-9791

6, George RoadEdgbastonBIRMINGHAMB15 1NP

This certificate shows the energy rating of this building. It indicates the energy efficiency ofthe building fabric and the heating, ventilation, cooling and lighting systems. The rating iscompared to two benchmarks for this type of building: one appropriate for new buildings andone appropriate for existing buildings. There is more advice on how to interpret this informationon the Government's website www.communities.gov.uk/epbd.

Energy Performance Asset Rating

Technical Information Benchmarks

Main heating fuel: Natural Gas

Building environment: Heating and Natural Ventilation

Total useful floor area (m2): 216

Building complexity (NOS level): 3

Building emission rate (kgCO2/m2): 51.75

Buildings similar to thisone could have ratings asfollows:

If newly built

If typical of theexisting stock

Page 3: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

Administrative Information

This is an Energy Performance Certificate as defined in SI 2007:991 as amended.

Assessment Software: iSBEM v5.2.g   using calculation engine   SBEM v5.2.g.3

Property Reference: 779876540000

Assessor Name: Marrianne Salter

Assessor Number: STRO003685

Accreditation Scheme: Stroma Certification

Employer/Trading Name: MJS Property Assessment Services

Employer/Trading Address: 15 Weston Close, Hawkes Green, Cannock, STAFFORDSHIRE, WS11 7YX

Issue Date: 12 Jul 2016

Valid Until: 11 Jul 2026 (unless superseded by a later certificate)

Related Party Disclosure: Not related to the owner.

Recommendations for improving the property are contained in Report Reference Number:   0970-0646-4899-7593-7002

If you have a complaint or wish to confirm that the certificate is genuine

Details of the assessor and the relevant accreditation scheme are on the certificate. You can get contact details ofthe accreditation scheme from the Department's website at www.communities.gov.uk/epbd, together with details ofthe procedures for confirming authenticity of a certificate and for making a complaint.

Opportunity to benefit from a Green Deal on this property

The Green Deal can help you cut your energy bills by making energy efficiency improvements at no upfront costs.Use the Green Deal to find trusted advisors who will come to your property, recommend measures that are right foryou and help you access a range of accredited installers. Responsibility for repayments stays with the property –whoever pays the energy bills benefits so they are responsible for the payments.

To find out how you could use Green Deal finance to improve your property please call 0300 123 1234.

Page 4: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

(*) Unless superseded by a later recommendation report Page 1 of 10

Recommendation ReportReport Reference Number: 0970-0646-4899-7593-7002

6, George RoadEdgbastonBIRMINGHAMB15 1NP

Building Type(s): D1 Non-residential Institutions - Primary HealthCare Building

ADMINISTRATIVE INFORMATIONIssue Date: 12 Jul 2016

Valid Until: 11 Jul 2026 (*)

Total Useful Floor Area (m²): 216

Calculation Tool Used: CLG, iSBEM, v5.2.g, SBEM,v5.2.g.3

Property Reference: 779876540000Energy Performance Certificate for the property is contained in ReportReference Number: 9747-3053-0869-0600-9791

ENERGY ASSESSOR DETAILSAssessor Name: Marrianne Salter

Employer/Trading Name: MJS Property AssessmentServices

Employer/Trading Address: 15 Weston Close,Hawkes Green, Cannock,STAFFORDSHIRE, WS117YX

Assessor Number: STRO003685

Accreditation Scheme: Stroma Certification

Page 5: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 2 of 10

Related party disclosure:

Page 6: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 3 of 10

Table of Contents

1. Background................................................................ 4

2. Introduction................................................................ 4

3. Recommendations..................................................... 5

4. Next Steps................................................................. 7

5. Glossary..................................................................... 9

6. Green Deal Information............................................ 10

Page 7: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 4 of 10

1. BackgroundStatutory Instrument 2007 No. 991, The Energy Performance of Buildings(Certificates and Inspections) (England and Wales) Regulations 2007, asamended, transposes the requirements of Articles 7.2 and 7.3 of theEnergy Performance of Buildings Directive 2002/91/EC. This report is aRecommendation Report as required under regulations 16(2)(a) and 19 of theStatutory Instrument SI 2007:991.

This section provides general information regarding the building:

Total Useful Floor Area (m²): 216

Building Environment: Heating and Natural Ventilation

2. IntroductionThis Recommendation Report was produced in line with the Government'sapproved methodology and is based on calculation tool CLG, iSBEM, v5.2.g,SBEM, v5.2.g.3.

In accordance with Government's current guidance, the Energy Assessordid undertake a walk around survey of the building prior to producing thisRecommendation Report.

Page 8: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 5 of 10

3. RecommendationsThe following sections list recommendations selected by the energy assessorfor the improvement of the energy performance of the building. Therecommendations are listed under four headings: short payback, mediumpayback, long payback, and other measures.

a) Recommendations with a short paybackThis section lists recommendations with a payback of less than 3 years:

Recommendation Potentialimpact

Replace tungsten GLS lamps with CFLs: Payback perioddependent on hours of use.

LOW

Consider replacing T8 lamps with retrofit T5 conversion kit. LOW

In some spaces, the solar gain limit defined in the NCMis exceeded, which might cause overheating. Considersolar control measures such as the application of reflectivecoating or shading devices to windows.

MEDIUM

b) Recommendations with a medium paybackThis section lists recommendations with a payback of between 3 and 7 years:

Recommendation Potentialimpact

Introduce HF (high frequency) ballasts for fluorescenttubes: Reduced number of fittings required.

LOW

Some windows have high U-values - consider installingsecondary glazing.

MEDIUM

Page 9: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 6 of 10

c) Recommendations with a long paybackThis section lists recommendations with a payback of more than 7 years:

Recommendation Potentialimpact

Some loft spaces are poorly insulated - install/improveinsulation.

MEDIUM

Carry out a pressure test, identify and treat identified airleakage. Enter result in EPC calculation.

MEDIUM

Some glazing is poorly insulated. Replace/improve glazingand/or frames.

MEDIUM

Consider installing solar water heating. LOW

Consider installing PV. LOW

d) Other RecommendationsThis section lists other recommendations selected by the energy assessor,based on an understanding of the building, and / or based on a valid existingenergy report.

No recommendations defined by the energy assessor have been identified.

Page 10: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 7 of 10

4. Next Steps

a) Your Recommendation ReportAs the building occupier, regulation 10(1) of SI 2007:991 requires that an EnergyPerformance Certificate "must be accompanied by a recommendation report".

You must be able to produce a copy of this Recommendation Report withinseven days if requested by an Enforcement Authority under regulation 39 of SI2007:991.

This Recommendation Report has also been lodged on the Government'scentral register. Access to the report, to the data used to compile the report, andto previous similar documents relating to the same building can be obtained byrequest through the Non-Dwellings Register (www.epcregister.com) using thereport reference number of this document.

b) Implementing recommendationsThe recommendations are provided as an indication of opportunities thatappear to exist to improve the building's energy efficiency.

The calculation tool has automatically produced a set of recommendations,which the Energy Assessor has reviewed in the light of his / her knowledgeof the building and its use. The Energy Assessor may have comments on therecommendations base on his / her knowledge of the building and its use. TheEnergy Assessor may have inserted additional recommendations in section 3d(Other Recommendations). He / she may have removed some automaticallygenerated recommendations or added additional recommendations.

These recommendations do not include matters relating to operation andmaintenance which cannot be identified from the calculation procedure.

c) Legal disclaimerThe advice provided in this Recommendation Report is intended to be forinformation only. Recipients of this Recommendation Report are advised toseek further detailed professional advice before reaching any decision on howto improve the energy performance of the building.

Page 11: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 8 of 10

d) ComplaintsDetails of the assessor and the relevant accreditation scheme are on thisreport and the energy performance certificate. You can get contact detailsof the accreditation scheme from our website at www.communities.gov.uk/epbd, together with details of their procedures for confirming authenticity of acertificate and for making a complaint.

Page 12: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 9 of 10

5. Glossary

a) PaybackThe payback periods are based on data provided by Good Practice Guides andCarbon Trust energy survey reports and are average figures calculated usinga simple payback method. It is assumed that the source data is correct andaccurate using up to date information.

The figures have been calculated as an average across a range of buildingsand may differ from the actual payback period for the building being assessed.Therefore, it is recommended that each suggested measure be furtherinvestigated before reaching any decision on how to improve the energyefficiency of the building.

b) Carbon impactThe High / Medium / Low carbon impact indicators against eachrecommendation are provided to distinguish, between the suggestedrecommendations, those that would most effectively reduce carbon emissionsfrom the building. For automatically generated recommendations, the carbonimpact indicators are determined by software, but may have been adjusted bythe Energy Assessor based on his / her knowledge of the building. The impactof other recommendations are determined by the assessor.

c) Valid reportA valid report is a report that has been:

• Produced within the past 10 years• Produced by an Energy Assessor who is accredited to

produce Recommendation Reports through a Government ApprovedAccreditation Scheme.

• Lodged on the Register operated by or on behalf of the Secretary ofState.

Page 13: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

0970-0646-4899-7593-7002

Page 10 of 10

6. Green Deal InformationWhen the Green Deal launches, it may enable you to improve the property tomake it more energy efficient and cheaper to run, without having to pay for thework upfront.

Page 14: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

SBEM Main Calculation Output DocumentTue Jul 12 10:22:45 2016 v5.2.g.3

Building Energy Performance and CO2 emissions

Annual Energy Consumption

Building name

Building type:

SBEM is an energy calculation tool for the purpose of assessing and demonstrating compliance with Building Regulations (Part L for England and Wales, Section 6 for Scotland, Part F for Northern Ireland, Part L for Republic of Ireland and Building Bye-laws Jersey Part 11) and to produce Energy Performance Certificates and Building Energy Ratings. Although the data produced by the tool may be of use in the design process, SBEM is not intended as abuilding design tool.

(Pie chart excluding Equipment end-use)

(Pie chart including Equipment end-use)

(*) Although energy consumption by equipment is shown in the graphs,the CO2 emissions associated with this end-use have not been takeninto account when producing the rating.

D1 Non-residential Institutions - Primary Health Care Building

15 George Rd, Edgbaston, B15 1

Heating

Cooling

Auxiliary

Hot Water

Lighting

Equipment*

Total

kWh/m2 2402101801501209060300

H 67%A 2%

L 22%

E 8%

H 73%

A 2%

L 24%

Equipment*

Lighting

Hot Water

Auxiliary

Cooling

Heating

kWh/m2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

30

24

18

12

6

0

Elec

Fuel

kgCO2/m232241680

0 kgCO2/m2 displaced by the use of renewable sources.

Building area is 215.63 m2

Page 1 of 2

Page 15: 6 George Road Edgbaston Birmingham B15 1NP July … (*) Unless superseded by a later recommendation report Page 1 of 10 Recommendation Report Report Reference Number: 0970-0646-4899-7593-7002

Annual Heating Demand

Notional

Actual

kWh/m2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

25

20

15

10

5

0

Annual Cooling Demand

Notional

Actual

kWh/m2

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

7.5

6

4.5

3

1.5

0

Notional

Actual

kWh/m216012080400

Notional

Actual

kWh/m228211470