2012 IRC Wall Bracing Provisions

INTERMITTENT BRACING METHODS Module 5

2012 IRC Wall Bracing 2

Objectives

Upon completion of this module, you will be better able to:

• Discuss intermittent panel methods

• Explain method wood structural panel, method structural fiberboard sheathing, and method gypsum board.

• Describe alternate braced wall panels, portal frames with hold-downs, and portal frames at the garage.

2012 IRC Wall Bracing 3

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 4

Method WSP – Wood Structural Panel 3/8" min. thickness

Wood structural panel defined in R604

8' to 12'

4' min.

Table R602.3(3)

5

Bracing: Panel Material - Intermittent

Method WSP – Wood Structural Panel

48" 48" 48"

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 6

Method SFB – Structural Fiberboard Sheathing 1/2" or 25/32" thick

Studs spaced 16" o.c. max.

Must conform to ASTM C 208

Nailing 3" o.c. edge, 6" o.c. field

8' to 12'

4' min. Table R602.10.4

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 7

Method SFB – Structural Fiberboard Sheathing

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 8

4' min.

Method GB – Gypsum Board

1/2" min. thick for studs

spaced 24" o.c. max.

4' minimum length

Nailing at 7" o.c.

Bracing length:

Single sided =

0.5 x actual length

Double sided =

1x actual length

No floating corners!

8' to 12'

Table R602.10.4

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 9

Method GB – Gypsum Board

2012 IBC Wall Bracing 10

Bracing: Panel Material - Intermittent

Table R602.10.5 Minimum length for braced wall panels

48″ to 58″

BWP

BWP

Height

BWP Length Minimum Length of BWPs

Table R602.10.5

Method (See Table R602.10.4)

Minimum Lengtha (inches) Contributing

Length (inches) Wall Height

8 ft. 9 ft. 10 ft. 11 ft. 12 ft.

DWB, WSP, SFB, PBS, PCP, HPS, BV-WSP

48 48 48 53 58 Actualb

GB 48 48 48 53 58

Double sided = Actual

Single sided = 0.5 × Actual

LIB 55 62 69 NP NP Actualb

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 11

Table R602.10.5.2 Effective length of braced panels less than 48"

For Methods

DWB, WSP, SFB, PBS, PCP, HPS

Actual

Length

Effective Length of BWP

8' 9' 10'

48" 48" 48" 48"

42" 36" 36" N/A

36" 27" N/A N/A

27" to 48"

BWP

BWP

Height

BWP Length Partial Credit for Narrow BWPs

R602.10.5.2

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 12

Method ABW - Alternate Braced Wall Equivalent to 48" panel

For use on bottom story only

Minimum length varies with SDC and height

Nailing:

Single story – 6" o.c. max

Bottom of two story – 4" o.c. max

Minimum hold-down capacity changes with SDC and height

R602.10.6.1, Table R602.10.4

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 13

Length

Height

Method ABW - Alternate Braced Wall

Table R602.10.5

Minimum ABW Length

Wall Height (ft.)

8 9 10 11 12

SDC A-C 28 32 34 38 42

SDC D0-D2 32 32 34 NP NP

Table R602.10.5 Minimum length for braced wall panels (excerpt)

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 14

Min. 3/8" thick wood structural panel sheathing

#4 bars top and bottom for bracing 12" x 12" min. footing

Anchor bolts 1/2" (2) with round washer

Hold-down capacity per Table R602.10.6.1

Wind

8' to 12'

SDC C, D0, D1

and D2

8' to 10'

Figure R602.10.6.1

Method ABW - Alternate Braced Wall

2012 IRC Wall Bracing 15

Design Category

and Wind Speed

Supporting

/Story

Hold Down Force (pounds)

Height of Braced Wall Panel

8 feet 9 feet 10 feet 11 feet 12 feet

SDC A, B

and C

Wind speed

< 110 mph

One story 1,800 1,800 1,800 2,000 2,200

First of two

stories 3,000 3,000 3,000 3,300 3,600

SDC D0, D1 and D2

Wind speed

< 110 mph

One story 1,800 1,800 1,800 NP NP

First of two

stories 3,000 3,000 3,000 NP NP

Bracing: Panel Material - Intermittent

Method ABW - Alternate Braced Wall

Table R602.10.6.1 Minimum Hold-down Forces For Method ABW Panels

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 16

Method PFH – Intermittent Portal Frame 16" min panel length for 1-story, 24" min for 2-story

Header 2' min. to 18' max.

Each vertical panel replaces a 48" braced wall panel

Extended header 16" or

24" min.

8' to 10'

R602.10.6.2, Table R602.10.5

PF

H

PF

H

PF

H

Opening Opening

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 17

Min. 3/8" thick wood structural panel

(1) 5/8" anchor bolt with 2x2 washer

10' Max.

Extended header

3" o.c. nailing

4,200 lb strap type hold-down

1,000 lb strap capacity (opposite side from sheathing)

Method PFH – Intermittent Portal Frame

Figure R602.10.6.2

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 18

Method PFH with taller walls – Wall height up to 12 ft. tall – Portal height limited to 10 ft. (top of header) – Pony wall built above portal header – 4 ft. max pony wall height – Pony walls require tension straps (Table

R60210.6.4) – Number of jack studs required for single portal post

in Table R502.5(1)

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 19

For use in SDC A-C only

Bracing length = 1.5 x length of panel

Minimum 24" length

Header 2' min. to 18' max.

R602.10.6.3, Table R602.10.5

Method PFG – Intermittent Portal Frame at Garage

Min. 1,000 lb strap (opposite side from

sheathing)

No hold-downs required

Extended header

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 20

Method PFG – Intermittent Portal Frame at Garage

Min. 7/16" thick wood structural panel

(2) 1/2" anchor bolts with 2x2 washers

10' Max.

Extended header

3" o.c. nailing

No hold-downs required

1,000 lb strap capacity (opposite side)

Figure R602.10.6.3

2012 IBC Wall Bracing 21

2012 IBC Wall Bracing 22

Method PFG with taller walls – Wall height up to 12 ft. tall – Portal height limited to 10 ft. (top of header) – Pony wall built above portal header – 4 ft. max pony wall height – Pony walls require tension straps (Table

R602.10.6.4) – Number of jack studs required for single portal

post in Table R502.5(1)

Bracing: Panel Material - Intermittent

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 23

Table R602.10.5 Minimum length for braced wall panels (excerpt)

Minimum Length of BWPs

Method (See Table R602.10.4)

Minimum Lengtha (inches) Contributing

Length (inches) Wall Height

8 ft. 9 ft. 10 ft. 11 ft. 12 ft.

DWB, WSP, SFB, PBS, PCP, HPS, BV-WSP 48 48 48 53 58 Actualb

ABW SDC A, B and C 28 32 34 38 42

48 SDC Do, D1 and D2 32 32 34 NP NP

PFH

Supporting roof only 16 16 16 18c 20c 48

Supporting one story and roof

24 24 24 27c 29c 48

PFG SDC A, B and C 24 27 30 33d 36d 1.5 × Actualb

Bracing: Panel Material - Intermittent

2012 IBC Wall Bracing 24

Table R602.10.5 Minimum length for braced wall panels (excerpt)

Minimum Length of BWPs

Method (See Table R602.10.4)

Minimum Lengtha (inches) Contributing

Length (inches) Wall Height

8 ft. 9 ft. 10 ft. 11 ft. 12 ft.

DWB, WSP, SFB, PBS, PCP, HPS, BV-WSP 48 48 48 53 58 Actualb

ABW SDC A, B and C 28 32 34 38 42

48 SDC Do, D1 and D2 32 32 34 NP NP

PFH

Supporting roof only 16 16 16 18c 20c 48

Supporting one story and roof

24 24 24 27c 29c 48

PFG SDC A, B and C 24 27 30 33d 36d 1.5 × Actualb

Summary

This module covered: • Intermittent bracing methods

– Wood structural panel and structural fiberboard.

• Method wood structural panel, method structural fiberboard sheathing, and method gypsum board – Three most common bracing methods in the U.S. – Method gypsum board in nearly all houses in the country

• Alternate Braced Wall panel – oldest of methods

• Portal Frames with Hold-downs, and Portal Frames at the Garage. – Used at the garage or at openings along a wall line in the

dwelling.

2012 IBC Wall Bracing 25